Loading...
HomeMy WebLinkAboutProject InformationJob: 1300 Air Calcs, LLC Load Short Form Date: Aug 06, 2020 House By. Vicki Lynne Nisa Air Calcs, LLC i550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email:vicldlynne@aircalcs.com For: Shockley Residence, Air Conditioning Unlimited 5912 Sunset Blvd, Fort Pierce, FL 34982 Design Information Htg Cig Infiltration Outside db (°F) 41 90 Method Simplified Inside db (°F) 70 75 Construction quality Average Design TD (°F) 29 15 Fireplaces 0 Daily range - L Inside humidity (%) 30 50 Moisture difference (grAb) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Goodman Mfg. Trade Trade GOODMAN Model Cond GSX16S301A AHRI ref Coil ASPT39C14A AHRI ref 201785799 Efficiency 100 EFF Efficiency 13.0 EER,15.5 SEER Heating input 5.6 kW Sensible cooling 19600 Btuh Heating output 19097 Btuh Latent cooling 8400 Btuh Temperature rise 19 OF Total cooling 28000 Btuh Actual airflow 933 cfm Actual airflow 933 cfm Airflowfactor 0.051 cfm/Btuh Airflowfactor 0.051 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.78 ROOM NAME Area (ft2) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) CigAVF (cfm) WIC 29 708 275 36 14 M Bath 44 1410 523 72 27 Master Bedroom 179 2212 2212 114 113 Foyer 42 0 0 0 0 Pantry 14 0 0 0 0 Great Room 258 3581 4739 184 242 Bath 47 596 284 31 14 Lin 6 0 0 0 0 Bed 3 167 2937 2083 151 106 Bed 2 151 2977 2117 153 108 Hall 40 0 0 0 0 �MIA, Orla fa7ra Fnga 1 Q� mR Ur'JrV l cvv -. -1 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. wrightsoft® /akRight-Sute®Universal 2019 19.020 RSU27054 —Ss W rlghtsoft HVAM5912 Scrset Blvd PSL Prop.rup Calc= MJ8 Front Door faces: N 2020-Aug-0712:24:53 Pagel House d 1232 18177 18265 933 933 Other equip loads 1349 716 Equip. @ 0.95 RSM 18108 Latent cooling 5434 -/ Al 11 lay,)r. 1 �'IFd) 1 933 1 V I f"LL ' •-"•- Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft® Rig ht-Sute®UrNersal201919.0.20 RSU27054 / p..slWrightsoftWAC15912SInsetBlvd PSLProp.rLp Caic=MJ8 Frort Door faces: N 2020-ALg-07 12:24:53 Page 2 Building Analysis Job: Air Calcs, LLC g Y Date: Aug Aug 06, 2020 House By. Vicki Lynne Nisa Air Calm, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: violdlynne@aircalcs.com ENRijis-,ject inTormation For: Shockley Residence, Air Conditioning Unlimited 5912 Sunset Blvd, Fort Pierce, FL 34982 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (OF) 70 75 Elevation: 26 ft Latitude: 28°N Design TD (OF) Relative humidity (%) 29 30 15 50 Outdoor: Heating Cooling Moisture difference (grAb) 2.4 56.9 Dry bulb (OF) 41 90 Infiltration: Daily range (OF) - 15 (L ) Method Simplified Wet bulb (OF) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Heating 1 Component Btuh/ t2 Btuh % of load Walls 3.1 3958 20.3 Glazing 17.9 2331 11.9 Doors 3.7 77 0.4 Ceilings 1.0 1221 6.3 Floors 3.1 3807 19.5 Infiltration 2.3 2588 13.3 Ducts 4193 21.5 Piping 0 0 Humidification 0 0 Ventilation 1349 6.9 Adjustments 0 Total 195251 100.0 Cooling Component Btuh/ftz Btuh % of load Walls 1.8 2310 12.2 Glazing 28.2 3676 19.4 Doors 3.7 78 0.4 Ceilings 1.8 2224 11.7 Floors 0 0 0 Infiltration 0.6 702 3.7 Ducts 4754 25.0 Ventilation 716 3.8 Internal gains 4520 23.8 Blower 0 0 Adjustments 0 Total 18982 100.0 Latent Cooling Load = 5434 Btuh Overall U-value = 0.101 BtuhV °F Data entries checked. Glazi Floors Infiltration nternal Gains -r- wrightsoft- - 2020-Aug-0712:24:53 Right-Stite® universal 2019 19.020 RSU27054 Page 1 ...sUr ghtsoft HVAM5912 Sunset Blvd PSL Prop.nQ Calc= MA Front Door faces: N ' Air Calcs, LLC Component Constructions p Job: 1300 Date: Aug 06, 2020 House By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email:viddlyrm@aircalcs.com Project• . • ` For: Shockley Residence, Air Conditioning Unlimited 5912 Sunset Blvd, Fort Pierce, FL 34982 Design . • .. Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (OF) 70 75 Elevation: 26 ft Design TD (OF) 29 15 Latitude: 28ON Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (grAb) 2A 56.9 Dry bulb (OF) 41 90 Infiltration: Daily range (OF) - 15 (L ) Method Simplified Wet bulb (OF) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions or Area U value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ft?°F ft' F/Btuh Btuh/ft' Btuh BtuhRN Btuh Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd Ins, 8" Thk, 1/2" Gyp Bd Int Fnsh n 105 0.109 5.1 3.15 330 2.02 211 e 410 0.109 5.1 3.15 1292 2.02 826 s 217 0.109 5.1 3.15 685 2.02 438 w 262 0.109 5.1 3.15 824 2.02 527 all 994 0.109 5.1 3.15 3130 2.02 2002 Partitions Frm Wall, 1/2" Gyp.Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud Windows Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2 ft \Mndow ht, 1 ft sep.); 6.89 ft head ht Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (3 ft window ht, 1 ft sep.); 6.89 ft head ht Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.89 ft head ht Impact, Clear Lowe, TEMP: Impact, Clear Lowe, TEMP; NFRC rated (SHGC=0.21); foreground = green grass (0.23); 1 ft overhang (6.6 ft window ht, 1 ft sep.); 6.89 ft head ht Impact, Clear Lowe: Impact, Clear Lcwe; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.89 ft head ht Doors Fbrgls Door 282 0.101 11.0 2.94 827 1.09 308 n 4 0.580 0 16.8 67 11.4 45 e 9 0.580 0 16.8 151 27.6 248 e 31 0.580 0 16.8 525 27.6 860 e 40 0.650 0 18.9 746 32.2 1275 w 16 0.620 0 18.0 280 26.7 416 w 31 0.620 0 18.0 561 26.7 832 all 47 0.620 0 18.0 841 26.7 1248 w 21 0.127 7.0 3.69 77 3.73 78 C � wrightsoft® 2020-Aug-0712:24:53 ,e.,•�•��,.•".­.-' RlghtSite®Universal 201919.020RSU27054 Page AM...MrightsoftHVAC15912St�etBlvdPSLProp.rtp Calc=MJ8 Frond Door faces: N Ceilings Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh Floors On Grade Depth, Tile Flr Fnsh -1i1- wrightsoft® ,.,�� �•".,�,.."... �, Right-Stite@)UNversal201919.0.20RSU27054 ..s\WdghlsoftHVAC\5912SurretBlvd PSLProp.rLQ Calc=MJ8 FrordDoorfaces: N 1232 0.034 30.0 0.99 1221 1.80 2224 133 0.989 0 28.7 3807 0 0 2020-Aug-07 12:24:53 Page 2 Pro ect Summary Job: 1300 Air Calcs, LLC 1 ry Date: Aug 06, 2020 House By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Emali:vicldlyrm@aircalcs.com Project• • For: Shockley Residence, Air Conditioning Unlimited 5912 Sunset Blvd, Fort Pierce, FL 34982 Notes: Design Information Weather: St Lucie Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 13984 Btuh Structure 13511 Btuh Ducts 4193 Btuh Ducts 4754 Btuh Central vent (42 cfm) 1349 Btuh Central vent (42 cfm) 716 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 19525 Btuh Use manufacturer's data n Rate/swing multiplier Equipment sensible load 0.95 18108 Btuh Infiltration Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2404 Btuh Ducts 1395 Btuh Central vent (42 cfm) 1635 Btuh Heating Cooling Outside air Area (f?) 1232 1232 Equipment latent load 5434 Btuh Volume.(fN) 10828 10828 Airchanges/hour 0.45 0.23 Equipment Total Load (Sen+Lat) 23542 Btuh Equiv. AVF (cfm) 81 42 Req. total capacity at 0.70 SHR 2.2 ton Heating Equipment Summary Cooling Equipment Summary Make Make Goodman Mfg. Trade Trade GOODMAN Model Cond GSX16S301A AHRI ref Coil ASPT39C14A AHRI ref 201785799 Efficiency 100 EFF Efficiency 13.0 EER,15.5 SEER Heating Input 5.6 kW Sensible cooling 19600 Btuh Heating output 19097 Btuh Latentcooling 8400 Btuh Temperature rise 19 OF Total cooling 28000 Btuh Actual airflow 933 cfm Actual airflow 933 cfrn Airflowfactor 0.051 cfm/Btuh Airflowfactor 0.051 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.78 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wr7ghtsoft"' 2020-Aug-0712:24:53 "-"�� " a� a • RightSute®Universal 201919.020 RSU27054 Page 1 s\WrightsoftHVAC15912SumetBlvd PSLProp.np Calc=MJ8 Front Door faces: N Air Caics, LLC Ri ht-J® Worksheet Job: 1300 g Date: Aug 06, 2020 House By. Vicki Lynne Nisa Air Caics, LLC 7551) Hidden Hammock Ln. Vero Beach, FL32966 Phone:772.800.8413 Email: vicldlyrre@aircalcs.com 1 2 3 4 5 Room name E)posed wall Room height Room dimensions Room area House 132.8 ft 8.8 ft d 1232.3 ftz WIC 5.3 ft 8.2 ft heaUwol 5.5 x 5.3 ft 28.9 ft' Ty Construdion number U-value (Btuh/t2 - °F) Or HTM (Btuhlftz) Area (ft2) or perimeter (ft) Load (Btuh) Area W) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross NIPS Heat Cool 6 11 T L--(' Bik Wail, Stucco F)d Impact, Clear Lower Blk Wall, Stucco Fed Clear Lowe Impact, Clear Low-e impact, Impact, Clear Lowe, Bilk Wall, Stucoo F)d Bilk Wall, Sluoco 6d Impact, Clear Lowe Impact, Clear Lowe Fbrqls Door Frm Wall, 1C1" Gyp.B Attic, Shngl Roof, R On Grade Depth, Tile 0.109 0.580 0.109 0.580 0.580 0.650 0.109 0.109 0.620 0.620 0.127 0.101 0.034 0.989 n n e a a a s w w w w - - 3.15 16.82 3.15 16.82 16.82 18.85 3.15 3.15 17.98 17.98 3.69 2.94 0.99 28.68 2.02 11.37 2.02 27.57 27.57 32.19 2.02 2.02 26.67 26.67 3.73 1.09 1.80 0.60 109 4 490 9 31 40 217 329 16 31 21 282 1232 1232 105 0 410 0 0 0 217 262 0 0 21 282 1232 133 330 67 1292 151 525 746 685 824 280 561 77 827 1221 3807 211 45 826 248 860 1275 438 527 416 832 78 308 2224 0 43 0 0 0 0 0 0 0 0 0 0 45 29 29 43 0 0 0 0 0 0 0 0 0 0 45 29 5 136 0 0 0 0 0 0 0 0 0 0 132 29 151 87 0 0 0 0 0 0 0 0 0 0 49 52 0 W V�1 �G L_pG P C F 6 c) AED excursion 0 -11 Envelope loss/gain 11396 8289 447 177 12 a) Infiltration b) Room ventilation 2588 0 702 0 97 0 26 0 13 Internal gains: Occupants@ 230 Applianoesrother 4 920 3600 0 0 0 Subtotal (lines 6 to 13) 13984 13511 545 204 14 15 Less external load Less transfer Redistribution Subtotal Dud loads 30% 35% 0 0 0 13984 4193 0 0 0 13511 4754 30% 35% 0 0 0 545 163 0 0 0 204 72 Total room load Air required (dm) 181771 9331 18265 9331 708 1 36 275 14 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -i+i wrightsoR 2020-Aug-0712:24:53 Right-Suite®Universal 2019 19.0.20 RSU27054 Page 1 ..s\Wrightsoft HVAC15912 Suset Blvd PSL Prop.np Cale= W8 Front Door faces: N • Air Calm LLC Right-J® Worksheet House Air Caics, LLC 7F.rn HiriMn Hammock Ln- Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilynne@aircelcs.com Job: 1300 Date: Aug 06, 2020 By. Vicki Lynne Nisa 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area M Bath 13.5 ft 82 ft heaU000l 5.5 x 8.0 ft 44.0 tt2 Master Bedroom 13.5 ft 82 ft heattcool 13.5 x 13.3 ft 178.9 ft2 Ty Conshvction number U-value (Btuh/ft2 °F) Or HTM (Btuh/ft2) Area (fiz) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat , Cool Gross N/P/S Heat Cool 6 11 VN L--G Blk Wall, Stucco Ext Impact; Clear Low-e Blk Wall, Stucco Ext Impact, Clear Lowe Impact, ClearLow2 Impad,Clear Lowe, Blk Wall, Stucco Ext Wall, Stucco Ext Impact, Clear Lowe Impact, Clear Lowe FbrQIs Door Frm Wall,1/2" Gyp.B Atfic, Shngl Roof, R On Grade Depth, Tile 0.109 0.580 0.109 0.580 0.580 0.650 0.109 0.109 0.620 0.620 0.127 0.101 0.034 0.989 n n a a a a s w w w w - - - 3.15 16.82 3.15 16.82 16.82 18.85 3.15 3.15 17.98 17.98 3.69 2.94 0.99 28.68 2.02 11.37 2.02 27.57 27.57 32.19 2.02 2.02 26.67 26.67 3.73 1.09 1.80 O.do 66 4 45 0 0 0 0 0 0 0 0 0 44 44 62 0 45 0 0 0 0 0 0 0 0 0 44 14 194 67 142 0 0 0 0 0 0 0 0 0 44 387 124 45 91 0 0 0 0 0 0 0 0 0 79 0 0 0 111 0 16 0 0 0 0 0 0 111 179 179 0 0 95 0 0 0 0 0 0 0 0 111 179 14 0 0 300 0 262 0 0 0 0 0 0 325 177 387 0 0 192 0 430 0 0 0 0 0 0 121 323 0 W vbBlk P C F 6 c) AED excursion -21 3 Envelopeloss/gain 834 319 1452 1069 12 a) Infiltration b) Room ventilation 250 0 68 0 250 0 68 0 13 Internal gains: Occupants @ 230 Applianoeslother 0 0 0 0 0 500 Subtotal (lines 6 to 13) 1084 387 1702 1636 14 15 Less external load Less transfer Redistribution Subtotal Dud loads 30% 35% 0 0 0 1084 325 0 0 0 387 136 30% 35% 0 0 0 1702 510 0 0 0 1636 576 Total room load Air required (cfm) 1410 1 72 523 271 2212 1 114 2212 113 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. C-I'I.F- wrightsoR 2020-Aug-0712:24:53 Right-Sute®Universal 201919.020RSU27064 Paget ..s\W rightsoft HVAC\5912 Su set Blvd PSL Prop.r p Calc= MJ6 Front Door faces: N Air Calcs, LLC Right-J® Worksheet Job: 1300 House Date: Aug 06, 2020 By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: Vicldlym@aircalcs.com 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Foyer 6.0 ft 9.5 ft heaUcool 6.0 x 7.0 ft 42.0 ft= Pantry 0 It 82 ft headcool 4.0 x 3.5 it 14.0 ft Ty Construction number U-value (BtuIA2 °F) Or HTM (Btuh/ft2) Area (its) or perimeter (ft) Load (Btuh) Area (ft-) or perimeter (ft) Load (Btuh) Heat Cool Gross I N/P/S Heat Cool Gross N/P/S Heat I Cool 6 11 G Blk Wall, Stucco Ext Impact, Clear Lowe Blk Wall, Stucco Fed Impact, Clear Lowe Impact, Clear Lowe Impact, Clear Lowe, Blk Wall, Stucco Ext Blk Wall, Stu000 Ed ImpaaClear Lowe Impact, Clear Lowe Fbrals Door Frm Wall,10" Gyp.B Attic, Shngl Roof, R On Grade Depth, Tile 0.109 0.580 0.109 0.580 0.580 0.650 0.109 0.109 0,620 0.620 0.127 0.101 0.034 0.989 n n a a a a s w w w w 3.15 16.82 3.15 16.82 16.82 18.85 3.15 3.15 17.98 17.98 3.69 2.94 0.99 28.68 2.02 11.37 2.02 27.57 27.57 32.19 2.02 2.02 26.67 26.67 3.73 1.09 1.80 t].00 0 0 0 0 0 0 0 57 0 0 21 67 42 42 0 0 0 0 0 0 0 36 0 0 21 67 42 6 0 0 0 0 0 0 0 113 0 0 77 195 42 172 0 0 0 0 0 0 0 73 0 0 78 73 76 0 0 0 0 0 0 0 0 0 0 0 0 0 14 14 0 0 0 0 0 0 0 0 0 0 0 0 14 0 0 0 0 0 0 0 0 0 0 0 0 0 14 0 0 0 0 0 0 0 0 0 0 0 0 0 25 0 F-G \f �--CGI W Vjl LI--pG P C F 6 c) AED excursion -17 -1 Envelopeloss/gain 600 282 14 24 12 a) Infiltration b) Room ventilation 129 0 35 0 1 0 0 0 0 13 Internal gains: Occupants@ 230 Applianoesrother 0 0 0 0 0 0 Subtotal (lines 6 to 13) 729 317 14 24 14 15 Less eudernalload Less transfer Redistribution Subtotal Ductloads 1 30% 35% 0 0 -729 0 01 0 0 -317 0 0 30% 35% 0 0 -14 0 0 0 0 -24 0 0 Total room load Air required (dm) 0 0 0 01 0 0 0 0 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -lily wrY9htsoit 2020-Aug-0712:24:53 AZZ t1 Right-Sute@Udversal201919.020RSU27054 Page ...Mrightsoft HVAQ5912 Sunset Blvd PSL Prop.rup Calc= MJ8 Front Door faces: N Air Calm, LLC Ri hW@ Worksheet Job: 1300 g Date: Aug 06, 2020 House By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone:772.800.8413 Email:,Acld"@aircaics.com 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Great Room 14.0 ft 9.5 It heaV000l 1.0 x 258.0 It 258.0 ft2 Bath 5.5 It 8.2 ft heat/000l 5.5 x 8.5 it 46.8 ft2 Ty Construction number U-value (Btuh/ft2-°F) Or HTM (Btuh/112) Area (ft) or perimeter (ft) Load (Bfuh) Area (ft) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 L--C Blk Wall, Stucco Ext Impact Clear Low-e Blk Wall, Stucco Ext Impact Clear Lowe Impact, Clear Lowe Impact Clear Lowe, Blk Wall, Stucco E)d Blk Wall, Slucoo Ext impact, Clear Lowe mpact, Clear Lowe Fbrgls Door Frm Wall,19' Gyp.B At c, Shngl Roof, R On Grade Depth, Tile 0.109 0.580 0.109 .0.580 0.580 0.650 0.109 0.109 0.620 0.620 0.127 0.101 0.0.34 0.989 n n a a a a s w w w w 3.15 16.82 3.15 16.82 16.82 18.85 3.15 3.15 17.98 17.98 3.69 2.94 0.99 28.68 2.02 11.37 2.02 27.57 27,57 32.19 2.02 2.02 26.67 26.67 3.73 1.09 1.80 0.00 0 0 0 0 0 0 0 133 0 31 0 59 258 258 0 0 0 0 0 0 0 102 0 0 0 59 258 14 0 0 0 0 0 0 0 321 0 561 0 174 256 402 0 0 0 0 0 0 0 205 0 832 0 65 466 0 0 0 0 0 0 0 0 45 0 0 0 0 47 47 0 0 0 0 0 0 0 45 0 0 0 0 47 6 0 0 0 0 0 0 0 142 0 0 0 0 46 158 0 0 0 0 0 0 0 91 0 0 0 0 84 0 W P C F 6 c) AED excursion 159 -11 Envelope loss/gain 1713 1726 346 165 12 a) Infiltration b) Roomventilation 301 0 82 0 102 0 28 0 13 Internal gains: Occupants @ 230 Appliances/other 2 460 900 0 0 0 Subtotal (lines6 to 13) 2014 3168 448 192 14 15 Less external load Less transfer Redistribution Subtotal Ducloads 30% 35% 0 0 741 2755 826 0 0 337 3505 1233 30% 35% 0 0 10 458 137 0 0 17 210 74 Total room load Air required (cm) 1 3581 1 184 4739 242 596 1 31 284 14 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -rw 2020-Aug-0712:24:53 Right-Sute®Universal2019 19.020 RSU27054 Page 4 MrightsoftHVACZ912Sunset Blvd PSLProp.n.p Calc=MJ8 FrontDoorfaces: N Air Caics, LLC Right-J® Worksheet Job: 1300 House Date: Aug 06, 2020 By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone:772.800.8413 Email:,Acldlynne@aircaics.com 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Lin 0 ft 82 ft heaNcool 2.0 x 3.0 ft 6.0 ftz Bed 3 25.5 ft 82 ft heaUmol 1.0 x 167.1 ft 167.1 ft2 Ty Construction number U-value (Btuhlft2---F) Or HTM (Btuh/ft2) Area (ft-) or perimeter (ft) Load (BWh) Area (f 2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 yJ t--G Blk Wall, Stucco Ext Ifpad,Clear Lowe Blk Wall, Stucco Ext Impact, Clear Lowe Impact Clear Lowe Impact, Clear Lowe, Blk Wall; Stucco IRA Blk Wall, Stucco Ext Impact, Clear Lowe Impact,ClearLowe Fbrqls Door Frm Wall. I)Z'Gyp.B Atfiq Shngl Roof, R On Grade Depth, Tile 0.109 0.580 0.109 0.580 0,580 0.650 0.109 0.109 0.620 0.620 0.127 0.101 0.034 0.989 n n a a a a s w w w w 3.15 16.82 3.15 16.82 16.82 18.85 3.15 3.15 17.98 17.98 3.69 2.94 0.99 28.68 2.02 11.37 2.02 27.57 27.57 32.19 2.02 2.02 26.67 26.67 3.73 1.09 1.80 0.00 0 0 0 0 0 0 0 0 0 0 0 0 6 6 0 0 0 0 0 0 0 0 0 0 0 0 6 0 0 0 0 0 0 0 0 0 0 0 0 0 6 0 0 0 0 0 0 0 0 0 0 0 0 0 11 0 0 0 111 0 16 0 98 0 0 0 0 0 167 167 0 0 95 0 0 0 98 0 0 0 0 0 167 26 0 0 300 0 262 0 310 0 0 0 0 0 166 731 0 0 192 0 430 0 198 0 0 0 0 0 302 0 Val �--( W P C F 6 c) AED exaars on -1 10 Envelope losslgain 6 10 1769 1132 12 a) Infiltration b) Room ventilation 0 0 0 0 473 0 128 0 13 Internal gains: Occupants @ 230 Applianceskther 0 0 0 0 0 250 Subtotal (lines 6 to 13) 6 10 2242 1510 14 15 Less external load Lesstransfbr Redistribution Subtotal Ductloads 1 30% 35% 0 0 -6 0 0 0 0 -10 0 0 30% 35% 0 0 18 2260 678 0 0 31 1541 542 Total room load Air required (dm) 0 0 0 0 2937 151 2083 106 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -1'i.F- wrlgF�tsoft 2020-Aug-0712:24:53 Right-SuteOUniversal 2019 19.0.20 RSU27054 Page 5 ..s\WrightsoftHVACl5912Sunset Blvd PSLProp.np Cale =MJ8 Front Door faces: N Air Calcs, LLC Right-J® Worksheet Job: 1300 House By. Aug 06, 2020 By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Emaii:vlcldlynne@aircalcs.com 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Bed 2 26.0 ft 82 ft heaUmol 1.0 x 150.9 ft 150.9 ft� Hall 0 it 82 ft heaV000l 1.0 x 39.5 ft 39.5 ft Ty Construction number U-value (Btuh/ft' °F) Or HTM (Btuhlft=) Area (f-) or perimeter (ft) Load (Btuh) Area (fP) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 Vi/ L-G Blk Wall, Stucco Ext Impac,Clear Lowe Blk Wall, Stucco Ext Impact, Clear Lowe Impact, Clear Lowe Impad Clear Lowe, Blk Wall, Stuoco Ext Blk Wall, Stucco Ext Impact, Clear Lowe Impact, Clear Lowe Fbrals Door Frm Wall, 1l2" Gyp.B Attic, Shngl Roof, R On Grade Depth, Tile 0.109 0.580 0.109 0.580 0.580 0.650 0.109 0.109 0.620 0.620 0.127 0.101 0.034 0.989 n n a a e a s w w w w - - - 3.15 16.82 3.15 16.82 16.82 18.85 3.15 3.15 17.98 17.98 3.69 2.94 0.99 28.68 2.02 11.37 2.02 27.57 27.57 32.19 2.02 2.02 26.67 26.67 3.73 1.09 1.80 0.00 0 0 0 0 0 0 119 94 16 0 0 0 151 151 0 0 0 0 0 0 119 79 0 0 0 0 151 26 0 0 0 0 0 0 375 248 280 0 0 0 150 746 0 0 0 0 0 0 240 159 416 0 0 0 272 0 0 0 0 0 0 0 0 0 0 0 0 0 40 40 0 0 0 0 0 0 0 0 0 0 0 0 40 0 0 0 0 0 0 0 0 0 0 0 0 0 39 0 0 0 0 0 0 0 0 0 0 0 0 0 71 0 W IL-_G D P C F 6 c) AED excursion 81 -4 Envelopeloss/gain 1798 1168 39 68 12 a) Infiltration b) Room venfilation 482 0 131 0 0 0 0 0 13 Intemalgains: Ocaipants@ 230 Appliances/other 0 0 250 0 0 0 Subtotal (lines 6 to 13) 2280 1549 14 15 Less external load Less transfer Redistribution Subtotal Ductloads 30% 35% 0 0 10 2290 687 0 0 17 1566 551 30% 35%0 43968 0 0 -68 0 Tatal room load A rtmg, fired (dm) 2977 153 2117 108 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. 1�.F- wrig�F�tsoTt^ 2020-Aug-0712:24:53 ^� RlghtSute@UrNersal 2019 19.020 RSU27054 Page 6 sMrightsoftHVAC15912Sunset Blvd PSLProp.rup CaIc=MJ8 FrontDoorfaces: N Air Calcs, LLC Ri ht-JO Worksheet Job: 1300 House Date: Aug 06, 2020 By. Vicki Lynne Nisa Air Calm, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: \4cldlynr)e@aircales.com 1 Room name DR/IGt 2 3 4 5 E)posed wall Room height Room dimensions Room area 23.5 ft 9.5 ft heatl000l 1.0 x 256.3 ft 256.3 ft= Ty Construction number U-value (Btuh/!?°F) Or HTM (Btuh/t2) Area (ft=) or perimeter (ft) Load (Btuh) Area or perimeter Load Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 y/ l-G Blk Wall, Stucco Ext Impact, Clear Lowe Blk Wall, Stu000 EA Impact, Clear Lowe Impac,Clear Lowe Impact Clear Lowe, Blk Wall, Stuob Ext Blk Wall, Stucco Ext Impac , Clear Lowe Impact, Clear Lowe Fbrals Door Frm Wall, 1/2" Gyp.B Attic,, Shngl Roof, R On Grade Depth, Tile 0.109 0.580 0.109 0.580 0.580 0.650 0.109 0.109 0.620 0.620 0.127 0.101 0.034 0.989 n n a a a a s w w w w - - - 3.15 16.82 3.15 16.82 16.82 18.85 3.15 3.15 17.98 17.98 3.69 2.94 0.99 28.68 2.02 11.37 2.02 27.57 27.57 32.19 2.02 2.02 26.67 26.67 3.73 1.09 1.80 0.00 0 0 223 9 0 40 0 0 0 0 0 0 256 256 0 0 175 0 0 0 0 0 0 0 0 0 256 24 0 0 550 151 0 746 0 0 0 0 0 0 254 674 0 0 352 248 0 1275 0 0 0 0 0 0 462 0 1N W �G P C F 6 c) AED excursion -187 Envelopeloss/gain 2376 2150 12 a) Infiltration b) Room ventilation 505 0 137 0 13 Internal gains: Occupants @ 230 Appliancestother 2 460 1700 Subtotal (lines 6 to 13) 2881 4447 Less external load 0 0 14 15 Less transfer Redistibution Subtotal Ductloads 30% 35% 0 9 2890 867 0 16 4463 1570 Total room load Airrequired(dm) 3756 193 6033 308 Calculations approved bVACCAto meet all requirements of Manual J 8th Ed. -rP- wrYghtsoR^' 2020-Aug-0712:24:53 . P. Right -Sate® Universal 2019 19.020 RSU27054 Page 7 ..slWrightsoftWAC15912SursetBlvd PSLProp.rup Calc=MJB FrontDoorfaces: N Air Calcs, LLC Duct System Summary House Air Calcs, LLC •7550 Hidden Hammock LR Vero Beach, FL32966 Phone:772.800.8413 Emall:,,icldlynne@alrcalcs.com For: Shockley Residence, Air Conditioning Unlimited 5912 Sunset Blvd, Fort Pierce, FL 34982 External static pressure Pressure losses Available static pressure Supply/ return available pressure Lowest fricti on rate Actual airflow Total effective length (TEL) Heating 0.70 in H2O 0 in H2O 0.70 in H2O 0.574 / 0.126 in H2O 0.167 1n/100ft 933 cfm 420 ft Supply Branch Detail Table Job: 1300 Date: Aug 06, 2020 By. Vicki Lynne Nisa Cooling 0.70 in H2O 0 in H2O 0.70 in H2O 0.574 / 0.126 in H2O 0.167 in/100ft 933 cfm Name Design (Btuh) Htg (cfrn) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Bath h 596 37 17 0.168 4.0 Ox0 VIFx 41.6 300.0 st3 Bed 2 h 2977 183 130 0.169 8.0 Ox 0 VI Fx 40.0 300.0 st3 Bed 3 h 2937 181 128 0.167 8.0 Ox 0 VIFx 44.7 300.0 st3 DR/Kit c 3016 116 185 0.254 7.0 Ox0 VIFx 26.4 200.0 st1 DRXit A c 3016 116 185 0.253 7.0 Ox 0 VI Fx 27.1 200.0 st1 Great Room c 2369 110 145 0.252 7.0 Ox0 VIFx 28.3 200.0 st1 Great Room -A c 2369 110 145 0.255 7.0 Ox 0 VI Fx 25.1 200.0 st1 M Bath h 1410 87 32 0.271 6.0 Ox 0 VI Fx 12.2 200.0 st2 Master Bedroom h 2212 136 136 0.265 7.0 Ox 0 VI Fx 16.9 200.0 st2 wic h 708 44 17 0.269 4.0 Ox 0 VIFx 13.4 200.0 st2 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st3 PeakAVF 401 275 0.167 511 12.0 0 x 0 VinlFlx st1 st1 PeakAVF 853 935 0.167 875 14.0 0 x 0 VinIFIX st2 PeakAVF 267 185 0.265 764 8.0 0 x 0 VinIFIX wrightsoft, 2020-Aug-0712:24:54 ati�Ia. .-ow.- Right -Sate® Universal 2019 19.020 RSU27054 Page 1 ...s\WrightsoftHVAc15912SusetBlvd PSLProp.rup Galc=MJ8 FrontDoorfaces: N Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening (in) Mat Trunk rb5 Ox0 183 130 75.4 0.167 526 8.0 Ox 0 VIFx rt1 rb6 Ox 0 181 128 74.5 0.168 518 8.0 Ox 0 VI Fx rt1 rb7 Ox 0 180 153 39.7 0.316 515 8.0 Ox 0 VIFx rb4 Ox 0 576 710 72.0 0.174 508 1 16.0 Ox 0 VIFx I rt1 Name Trunk Type Htg (cfm) Clg (cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk rt1 PeakAVF 940 967 0.167 547 18.0 0 x 0 VInIFIX -!}F wrightsoft, ^� .M,.k•ia,�wwu. �...wM Right-Sute®Universal 201919.020RSU27054 / A ...Mrightsoft WAC15912 Sunset Blvd PSL Prop.rLp Calc= MJ8 Front Door faces: N 2020-Aug-07 12:24:54 Page 2 Manual S Compliance Report Job: 1300 Air Calcs, LL'C p p Date: Aug 06, 2020 House By. Vicki Lynne Nisa Air Calcs, LLC -7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800,8413 Email:,Addlynne@alrcaics.com Project• • For. Shockley Residence, Air Conditioning Unlimited 5912 Sunset Blvd, Fort Pierce, FL 34982 Cooling Equipment Design Conditions Outdoor design DB: 90.4°F Sensible gain: 18982 Btuh Entering coil DB: 76.7°F Outdoor design WB: 77.4°F Latentgain: 5434 Btuh Entering coil WB: 63.9°F Indoor design DB: 75.0°F Total gain: 24416 Btuh Indoor RH: 50% Estimated airflow: 933 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Goodman Mfg. Actual airflow: 933 cfm Sensible capacity: 19600 Btuh Latent capacity: 8400 Btuh Total capacity: 28000 Btuh Model: GSX16S301A+ASPT39C14A 103% of load 155% of load 115% of load SHR: 70% Heating Equipment Design Conditions design DB: 41.0 °F Heat loss: 19525 Btuh Indoor design DB: 70.0'F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Manufacturer Actual airflow: Output capacity: Elec strip Model: 933 cfm 5.6 kW 98% of load Meets all requirements ofACCA Manual S. Entering coil DB: 68.2°F Temp. rise: 50 OF 2020-A 071224:54 - wrigf�tsoft� Pjgk_Sute®Universal 2019 19.020 RSU27054 Page 1 / +A..s\WrIghtsoltHVAC15912SunsetBlvdPSLProp.rup Calc=MJ8 Front Door faces: N M. FLOOR PLAN Job #: 1300 Performed by Vicki Lynne Nisa for: Shockley Residence 5912 Sunset Blvd Fort Pierce, FL 34982 L-11 Air Calcs, LLC 7550 Hidden Hammock Ln Vero Beach, FL 32966 Phone: 772.800.8413 vickilynne@aircalcs.com r Scale: 1 : 229 Page 1 Right -Suite® Universal 2019 19.0.20 RSU27054 2020-Aug-0712:25.48 ...AC\5912 Sunset Blvd PSL Prop.rup -�- wrightsoft® Duct System Summary House Job: 1372 Date: Nov11, 2020 By. Chris Bateman Air Calm, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: vicldlyrne@aircalcs.com e-roject intormation For. Delmadrid Residence,A[rConditioning Unlimited 6572 NW Chugwater Cir., Port St. Lucie, FL 34983 External static pressure Pressure losses Available static pressure Supply/ return available pressure Lowestfr[ction rate Actual airflow Total effective length (TEL) Heating 0.70 in H2O 0 in H2O 0.70 in H2O 0.445 / 0.255 in H2O 0.269 in/100ft 933 cfm 260 ft Supply Branch Detail Table Cooling 0.70 in H2O 0 in H2O 0.70 in H2O 0.445 / 0.255 in H2O 0.269 in/100ft 933 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Mat[ Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Bath h 578 34 16 0.305 4.0 Ox0 VIFx 31.2 115.0 st3 Bed 2 h 2900 170 119 0.269 7.0 Ox 0 M Fx 40.4 125.0 st3 Bed 3 h 2841 166 97 0.293 7.0 Ox 0 M FX 37.3 115.0 st3 Dining c 2482 128 150 0.400 6.0 Ox 0 VIFx 16.4 95.0 st1 Foyer h 2071 121 51 0.412 6.0 Ox0 VIFx 13.1 95.0 st1 Great Room C 3664 117 222 0.307 8.0 Ox0 MR 29.9 115.0 st3 Kitchen c 3868 95 234 0.302 8.0 Ox0 VIFx 32.7 115.0 st3 Laundry c 692 2 42 0.309 4.0 OXO VIFx 29.1 115.0 st3 M. Bath h 1432 84 32 0.380 5.0 Ox 0 VI Fx 17.3 100.0 st2 Master Bed h 2557 150 139 0.386 6.0 Ox 0 VI Fx 15.3 100.0 st2 Wic h 901 53 17 0.385 4.0 Ox0 VIFx 15.7 100.0 st2 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (dim) (Cfm) FIR (fpm) (in) (in) Material Trunk st3 PeakAVF 584 730 0.269 683 14.0 0 x 0 VinIFIX st1 st1 PeakAVF 833 931 0.269 871 14.0 0 x 0 VinIFIX st2 PeakAVF 287 189 0.380 821 8.0 0 x 0 VinIFIX -*- wrightsoft- �� RighdSuite®Universal201919.021 RSU29066 ACCK ...ghtsoft HVAQ6572 NW Chugwater Cir Psi Prop.rkp Cale= W8 Front Door faces: E 2020-Nov-1213:09:14 Page 1 r Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (dim) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Mat Trunk rb2 Ox 0 320 258 94.4 0.270 724 9.0 0x 0 VIFx rt1 rb3 Ox 0 169 139 94.5 0.269 382 9.0 Ox 0 VIFx rt1 rb4 Ox 0 53 17 50.0 0.509 151 8.0 Ox 0 VIFx rb1 Ox 0 579 706 92.2 0.276 505 16.0 Ox 0 VIFx rt1 Name Trunk Type Htg (Cfm) Clg (cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk rt1 PeakAVF 1067 1103 0.269 624 18.0 0 x 0 VinIFIX BoWitalic values have been manually overridden -i' wrightsoTt® �� A+rt.t• w�.wa-.��., Right-Sute®Udversa1201919.021 RSU29066 ACC& ...ghlsoftHVAQ6572NW ChigwaterCirPsi Prop.rp Calc=MJ8 Frord Door faces: E 2020-Nov-12 13:09:14 Page 2 -�- wrightsoft® Manual S Compliance Report p p Job: Date: 1372 Nov 11,2020 House By. Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicld1Ynne@aircalks.eom Project• • For: Delmadrid Residence, Air Conditioning Unlimited 6572 NW Chugwater Cir., Port St. Lucie, FL 34983 Design Conditions Outdoor design DB: 90.4°F Sensible gain: 19216 Btuh Entering coil DB: 76.7°F Outdoor design WB: 77.4°F Latent gain: 5431 Btuh Entering coil WB: 63.9°F Indoor design DB: 75.0°F Total gain: 24648 Btuh Indoor RH: 50% Estimated airflow: 933 ch Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Goodman Mfg. Model: GSX16S301A+ASPT39C14A Actual airflow: 933 ch Sensible capacity: 19600 Btuh 102%of load Latent capacity: 8400 Btuh 155% of load Total capacity: 28000 Btuh 114%ofload SHR: 70% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 20466 Btuh Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Manufacturer: Actual airflow: Output capacity: Elec strip Model: 933 cfm 5.8 kW 96% of load Meets all requirements ofACCA Manual S. Entering coil DB: 68.2°F Temp. rise: 50 °F wrightsoft® 2020-Nov-1213:09:14 M� RigftStite®Universal 201919.021RSU29066 Pagel ...ghlsoft HVAC16572 NW Chgwater Cir Psi Prop.rrtp Calc= W8 Front Door faces: E Level 1 E6% 21" ,z% 1P-8• SLAB ONLY a T II)EL0.EE5 o )anu• ,zn,•r. a i�;. P 166dm a q Kdchen 10'8 s y 1OX6 dm 1- �eM 5�A�,B,4�11v 6 O q �DINING1, Bed 3 $g t � w Wing r� H � Master Bed' < 3 e � weuc,�wrrrs MASTER HEDROO�� 12x1 ixsu,arEwsil :jIL s•n.n roenr . NAC r xu x Laund cau a 6 4" e � I I I _w-vrXx�wiu t• j bmonsnEfr aorioaHu r-,ns• ,r-r:v. qfm- g vx I I ; o ,I —T.U706 718 117 Ctffl --,-�-• I 18. Bed2j y12x1 I a M0 X _1- Ckeat Room : Gara ge 4 a s <aiven ruwEcss000x ._ wvnnrewnuvrcnrrosv ._---, . --------- ---_.Ir_..- _'__ram -----• ENS .I[ Eu4.CAl pr$KzsrCnl +I •--_——m� -�rsp—---__._..._.. ._� R�o`ur a GARAGE � EE99 A. ryrA nEran. A1GEa) ■ ■ 63 S1' 1'd% 3.5:5• 1'-,p 16% i•-lx' • P% 1P% Job M 1372 Performed by Chris Bateman for: Delmadrid Residence 6572 NW Chugwater Cir. Port St. Lucie, FL 34983 Air Calcs, LLC 7550 Hidden Hammock Ln Vero Beach, FL 32966 Phone: 772.800.8413 vickilynne@aircalcs.com Scale: 1 : 131 Page 1 Right -Suite® Universal 2019 19.021 RSU29066 2020-Nov-1213:09:47 72 NW Chugwater Cir Psl Prop.rup - wrightsoft, Right-J® Worksheet .lob: 1372 House Date: Nov11, 2020 By. Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email:,Ac44lynrL-@aircaics.com 1 Room name Laundry Bed 3 2 E)posed wall 0 ft 25.5 ft 3 Room height 8.0 ft heatIcool 8.0 ft heaV000l 4 5 Room dimensions Room area 6.0 x 3.0 ft 18.0 f 2 1.0 x 161.1 ft 161.1 ftz Ty Construction U-value Or HTM Area (ft2) Load Area (ft') Load number (Btuh/F °F) (BtuhV) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross NIPS Heat Cool 6 BIk Wall Stu000 EA - 0.109 n.- 3.15 2.02 --- 0 0 - p - _0-0.._.0 0 0 Impact Clear Lowe-- _ BIk Wall, Stuao E)d -- _ 0.580 0.109 _ n _' a _ _ 16.82 3.15 11,48 2.02 . _ _ _ . _0 0 _ _ 0 0 _ -. _ _ • Q 0 _-- _ 0 0 --- _ ._ 9 0 _ --.. _...0 0 0 0 11 Impact, Clear Lowe Impact, Clear Lowe 0.620 0.620 a a 17.98 17.98 27.18 27.18 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Ebmis-Door --- BIk Wall, Stucco E)d - - 0.127 0.109 e_ s 3:69 3.15 3.73 2.02 -- -Q 0 --- - 0 0 - - 0 0 -. 0 0 . - - 0 96 - - - 0 80 -- -0 253 0. 162 --- V�/ � Impact_ClearLowe - - -- ---_0.580_s_ 168.2._.13.64.----,--0----._...0 -------0 _-.---0.----- 16 _ 13------262_----_213 Bilk Wall, Stucco E)d Impact, Clear Lowe 0.109 0.580 w w 3.15 16.82 2.02 28.13 0 0 0 0 0 0 0 0 108 0 108 0 340 0 218 0 Impact, Clear Lowe _Lnna4 ClearLo-w-e -- Frmwgiljg2 Q --- 0.580 _ __-- 0.650 -- ---_ 0.101, w w .. _. 16.82 18.85 __2.94. 28.13 _i 26_.8_4 - 1.46._ 0 _-- -_ 9 --0 0 .-.._--- 0 --- - 0 0 -- ._.. _-- 0 -- --- 0 0 -- __-- - -0 _�. - . 0 - --------_0 -- -0 0 -- - . --9 - - ---0 0 -.---_ 0 -- - -0 0 0 P - - AttiGShnpl Roof, R.,_ - - -_18 _ 18 18 - 32 161, - .161 160 _-291_ F _-- -- ., On GradeDepth,Tile--- _0.034 -. 0.989 .__ .9.99 _._.28.68 ._.._..1$0 '.-:--0.00 - . --- -- - 18 _. -. _ -- _-.0 - _ _ _0 - -_ --- 0 --- _ 161 -- __ -. 26 _ .__ . 731. --- 6 c) AED excursion -35 -82 Envelope losslgain 18 -2 1747 801 12 a) Infiltration 0 0 463 126 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 500 250 Subtotal (lines 6 to 13) 18 498 2210 1177 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 10 17 8 13 14 Subtotal 28 514 2218 1190 15 Dud loads 28% 35% 8 178 28% 35% 623 411 Total room load T35 692 2841 1601 Air required (cfm) 2 35 139 81 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -rw wr7gFftsoTt- 2020-Nov 12 13:09:14 Rigid-Sute®Universal 201919.021RSU29066 Page ghtsoft HVACt6572 NW Chugwater Cir Psl Prop.rp Calc= W8 Front Door faces: E + wrightsoft9 RighW@ Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickiIynne@aircalcs.com Job: 1372 Date: Novll, 2020 By. Chris Bateman 1 Room name Bed 2 Bath 2 E)posed wall 26.0 It 5.5 ft 3 Room height 8.0 ft heaUmol 8.0 ft heaVcool 4 5 Room dimensions Room area 1.0 x 151.6 ft 151.6 ft' 5.5 x 8.5 ft 46.8 ft' Ty Construction number U-value (Btuh/ftz--°F) Or HTM (Btu Area (ftz) or perimeter (ft) Load (Btuh) Area (ft') or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 11rr�)// Blk Wall Stu000 ESQ Jmpaci,ClearLowe-- -. Blk Wall, Stucco-E# Impact, Clear Lowe Impact, Clear Lowe _ - 0.109 _ -- 0.580 0.109 0.620 0.620 n .; n,.'._ a a a 3.15 _16,82 3.15 17.98 17.98 - 2.02 -„ 11AQ 2.02 27.18 27.18 - - - 0 _ _ _.0 92 16 0 - - -0 -- ___-q 76 0 0 --`- 0 _-- _ 241 280 0 --- - 0 _-- _ -- 0 154 424 0 - -- 0 0 44 0 0 - ' 0 _ 0 44 0 0 -0 _0 139 0 0 0 ._ _ . -0 89 0 0 Fbrgls Dcor __ Blk Wall, SWom Ei Impact Clear Lowe -- _ _ _ 0.127 J 0309 --- 0.580 ___e s - .. S _ 3_.69 3.15 - 16.87 3.73 2:02 _ ._. _ ._._0 116 ...-.. - -- 0 116 -- - 365 -- - --0 234 -- 0 6 -0 - - - 0 0 -.__._ _0 - - - -0 i . - - 0.. - -0 0 ._ .._.. 0 W _ ! G ,_. VVV���lll BIk Wall, Stucco E)d Impact Clear Lowe 0.109 0.580 w w 3.15 16.82 2.02 28.13 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear Lowe -Impact ClearLow_e Fnn WaII j) T Gyp B - 0.580 _ _-0.650-'!v_.. 0.101 w . _ 16.82 18.85 2.94 28.13 _ 2684 , - 146 0 ---__-0 -0 0 0 _. 0.-__.___0 - - -0 0 -- 0 -- __0_ - - - 0 0 ---0 - 0 _____0 0 _ ----0 - - 0 _._ P _ -_---0 - 0 C Shngi Roof R- 0.99 152 -- _ _ _ 152 .. - . _ 150 _-_ -- _ .274 _._ ... 47 - - .47 -_ . 46 .. _-- . 84 _-- _ F __.__ .Attie - On Grade 0ePth,Tile__ ._----0.034 _- . - 0,989 _ 28.68. _...1:80 _ _.. 0.00 -- _-- 152 ---- - 26 _ -- -- _ 746 _ - -- _- - 0 - - -- - 47 _ - .. _ -. _6 ._ ... 158 _ ._ 6 6 c) AED excursion -22 -13 Envelope loss/gain 1783 1063 343 160 12 a) Infiltration 472 128 100 27 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianceslother 250 0 Subtotal (lines 6 to 13) 2255 1442 443 187 Less eMernalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 8 14 9 15 14 Subtotal 2264 1456 451 202 15 Duct loads 28% 35% 636 504 28% 35%1 127 70 Total room load 2900 1960 578 272 Air required (dm) 142 991 28 14 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -F�F =2 1.ts4 ft- 2020-Nov-1213:09:14 I&K RightSute®Universal 201919.021 RSU29066 Page ghtsoft HVAC16572 NW Clugwater Cir Psi Prop.rup Calc= MJ8 Front Door faces: E * wrightsoft' Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicldlyme@alrcalcs.00m Job: 1372 Date: Nov 11, 2020 By. Chris Bateman 1 Room name Hall Lin 2 Exposed wall O ft O ft 3 Room height 8.0 ft heaV000l 8.0 ft heaV000l 4 5 Room dimensions Room area 1.0 x 38B ft 38.8 ft' 2.0 x 3.0 ft 6.0 ft' Ty Construction U-value Or HTM Area (ft') Load Area (ft2) Load number (BtuhfiF--°F) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/PiS Heat Cool 6 V11 - Bilk Wall, Swan E)d Impact ear Lowe _ . Blk Wall, Stucco E)d 0.109 _ -. _ 0.580 0.109 n _. n.. a 315 1682 3.15 2 �2 ._ ...11-48 2.02 - -..._ _9 0 - 0 ._-- _ __0 0 - - -- _ — 0 - 0 . ..- _4 0 - -� - - -... Q 0 ,0 __. - 0. 0 - -0 _..._ _ 0 0 - -0 .. 0 0 _. _- 11 Impact, Clear Lowe Impact, Clear Lowe 0.620 0.620 a a 17.98 17.98 27.18 27.18 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 FbrAISDoor - BIKWaII,SW0006Q - -0.127 0.109 .._e s - _--3.69 3.15 _16.82 ---3.73 2.62 "13.64 -- 0 0 -_ -.--- b 0 0 - --0 --- -- 0 0 0 --- - 0.. 0 - -0 0 0 -- -0 - ---- 0 0 -- 0 - - --0 0 - ---0 - __ o 0 ---0 --- V� VVV���111 Elk Wall, Stucco Ext Impact Clear Lowe 0.109 0.580 w w 3.15 16.82 2.02 28.13 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear Lowe Impac Clear Low-e.- -- Firm -Wall, 1/?"Gyp B- 0.580 — 0.650 - -0.101 w . - w r 16.82 1.8.85 _ _._2.94 28.13 V_26.84 - ' 1:46 0 .---- ---- - - —0 0 - -- 0 --- -- 0 - -- --0 0 -- 0 0 -- --- 0 0 - --- .-0 0 - 0- P- - C - E__ -- Attica Sbq-QL aof, R. - On Grade Depth, Tile_.- _DAM - __-0- . .. _-0.99 --_- 28.68' _ _ 1.80 _ , _000 39 , _ __ 39 .- -_39 _- - 38 -- - 70 6 - ' 6 _ .._ .,..-6 - -11 6 c) AED excursion -5 -1 Envelope losstgain 38 65 6 10 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Applianoesrother 0 0 Subtotal (lines 6 to 13) 38 65 6 10 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution S8 -65 -6 -10 14 Subtotal 0 0 0 0 15 Dud loads 28% 35% 0 0 28% 35% 0 0 Total room load 0 0 0 0 Air required (dm) 0 0 0 0 Calculations aooroved bvACCA to meet all reouirements of Manual J 8th Ed. -r- wr7ghtsoft® 2020-Nov-1213:09:14 ""'' RightSuteOUniversal201919.021 RSU29066 Page 6 ghtsoft HVAC16572 NW Chugwater Cir Psi Prop.r p Cale= MA Front Door faces: E wrightsoft° Right-J® Worksheet Job: 1372 House Date: Nov11, 2020 By. Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vicldlynne@aircalcs.com 1 2 3 4 5 Room name E)posed wall Room height Room dimensions Room area Foyer 22.5 ft 9.5 ft heat/cool 9.0 x 13.5 It 121.5 ft2 Great Room 11.5 ft 9.5 ft heag000l 1.0 x 168.8 ft 168.8 1112 Ty Construction number U-value (BtuhA?--'F) Or HTM (Btuhlit2) Area (ft) or perimeter (ft) Load (Btuh) Area (ft) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P!S Heat Cool Gross N/P/S Heat Cool 6 11 -L--•-(' - y/ C Blk Wall SW000Ext - Im_.pac Clear Lowe. __... Blk Wall, Stucco Ext Impact, Clear Lowe Impact, Clear Lowe Fbrgls Door _,- Blk Wall; Stu000 I # Impact ClearLow-e .^ Blk Wall, Stucco Ext Impact, Clear Lowe Impac,Clear Lowe Imoad,ClearLowe _ Frrrf,Wall1r2'Gyp6- Atfic,ShnglRoof R . On Grade Depth, Tile_ _ , 0109 _ 0.580 0.109 0.620 0.620 012 017 _ _ _ 0;580 0.109 0.580 0.580 0650 _,0101 0034 _ _ _0.989 h ` w n_ a e e _ e_ s, s=_ w w w w__ - _r _ - 315 _ .1682 3.15 17.98 17.98 _ 3 69 315 -16.82 3.15 16.82 16.82 _ 1885 - -294 _ 099. _ -28 68_ - 202 __-2.01148 2 27.18 27.18 .. 3 73 2.02 13.64 2.02 28.13 28.13 26.84 1,46 _ 1.80, _ - . 0.00 -0 -0 86 0 0 ._ - _.?9 0 - -- ---0 0 0 0 0 _- ___.. 128.- _ _�22 _ -122 .___ _ 0 __. �'____.__ 65 0 0 _ -- _.._20 0 - --- 0 0 0 -__ ___ 0 128_. . _-.._.__ 122 - _ _ 23 0 0 206 0 0 74 _- -_-�0 __. _0 132 0 0 _ 75 0 0 0 0 0 __ -- 187 _ _ 219 -- -- _ _ _ 0 �_._--O 109 0 31 _-, 0 0 0 0 0 0 -- --0- _ • ,_. ,16-9 -- - ,_ 169 . - -. _- o 78 0 0 _ _ _-- 0 0 0 0 0 _ - 0 - _ __ _ 169 _ _ _ 12 ------------ -- 0 246 0 561 0 0 0 0 _ 0 .__ - 0 _ 167 _ -_ - 330 -- - _- -. •p 157 0 848 .-• _ -- -- Q 0 0 0 0 _ _ _ 0 -'-0 _305 _ _ -_0 -, 0 --- -- -_0 0 0 0 _ ___ 0 - .._.- 120 _ -- _645 6 c) AED excursion - 4 -32 Envelope lossIgain 1423 570 1304 1278 12 a) Infiltration b) Room ventilation 194 0 53 0 248 0 67 0 13 Internal gains. Oocupants@ 230 Appliances/other 0 0 0 2 460 900 Subtotal (lines 6 to 13) 1617 622 1552 2706 14 15 Less external load Less transfer Redistribution Subtotal Ductloads 28% 35% 0 0 0 1617 454 0 0 0 622 215 28% 359/6 0 0 10 1562 439 0 0 17 2722 942 I-TAjr Total room load required (dm) 2071 1 101 837 42 2001 98 3664 185 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -li.F 2020-Nov1213:09:14 i9CC�A '" "" ^� ^ f�ghtSdte®Universal 201919.021 RSU29066 Page ...ghtsoftHVAC\6572NWChugwaterair Psi Prop.np Cale =MJ8 Front Door faces: E