NEW Manual J Updated
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 09:12:47 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N 1402Job:Load Short Form Dec 29, 2020Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Spec Home, NisAir Air ConditioningFor: 4801 Sunset Blvd, Fort Pierce, FL 34982 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S030-230A** AHRI ref Coil CBA27UHE-030-230*++TDR AHRI ref 10259437 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW6.9 Sensible cooling Btuh20300 Heating output Btuh23456 Latent cooling Btuh8700 Temperature rise °F22 Total cooling Btuh29000 Actual air flow cfm967 Actual air flow cfm967 Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.048 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.78 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) M Hall 26 0 0 0 0 Laundry 68 908 988 39 47 Master Bath 90 1992 750 86 36 WIC 63 1610 580 70 28 Master Bed 247 2013 2230 87 107 Pantry 15 0 0 0 0 Kitchen/Nook 275 3644 4795 157 230 Great Room 377 4795 5987 207 287 Bed 3 173 2937 2067 127 99 Hall 30 0 0 0 0 Lin 8 0 0 0 0 Bath 50 738 380 32 18 Bed 2 182 3737 2392 161 115 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 09:12:47 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N House 1602 22373 20169 967 967 Other equip loads 1467 779 Equip. @ 0.95 RSM 19984 Latent cooling 6029 TOTALS 1602 23840 26014 967 967 2021-Nov-12 09:12:47 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N 1402Job:Building Analysis Dec 29, 2020Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Spec Home, NisAir Air ConditioningFor: 4801 Sunset Blvd, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 18.343713.1Walls 13.6325318.2Glazing 000Doors 6.715881.0Ceilings 22.653923.43.4Floors 11.727822.0Infiltration 20.94987Ducts 00Piping 00Humidification 6.21467Ventilation0Adjustments 100.023840Total Cooling Walls Glazing Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 13.027151.9Walls 17.7370020.6Glazing 000Doors 11.223431.5Ceilings 000Floors 3.77780.6Infiltration 26.85613Ducts 3.7779Ventilation 24.05020Internal gains 00Blower 0Adjustments 100.020948Total Latent Cooling Load = 6029 Btuh Overall U-value = 0.105 Btuh/ft²-°F Data entries checked. 2021-Nov-12 09:12:47 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N 1402Job:Component Constructions Dec 29, 2020Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Spec Home, NisAir Air ConditioningFor: 4801 Sunset Blvd, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 8143.155.10.109259n 5212.02 8922.0213953.155.10.109443e 4832.027553.155.10.109239s 5402.028443.155.10.109268w 24352.0238073.155.10.1091208all Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud 2801.465642.9411.00.101192 Windows Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (3.17 ft window ht, 1 ft sep.); 8 ft head ht 10911.516016.800.58010n Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 8 ft head ht 87828.152516.800.58031e Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); foreground = green grass (0.23); 10 ft overhang (8 ft window ht, 1 ft sep.); 8 ft head ht 62713.190518.800.65048e Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2.08 ft window ht, 1 ft sep.); 8 ft head ht 6113.57616.800.5805s Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 6 ft overhang (5.17 ft window ht, 1 ft sep.); 8 ft head ht 37716.840318.000.62022w Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 8 ft head ht 42427.228018.000.62016w 2021-Nov-12 09:12:47 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); foreground = green grass (0.23); 9.1 ft overhang (8 ft window ht, 1 ft sep.); 8 ft head ht 71114.890518.800.65048w Doors (none) Ceilings Attic, Shngls, R-30 Roof Ins, 1/2" Gyp Bd Int Fnsh 0.0341602 23431.4615880.9930.0 Floors On Grade Depth, Tile Flr Fnsh 00539228.700.989188 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 09:12:47 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N 1402Job:Project Summary Dec 29, 2020Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Spec Home, NisAir Air ConditioningFor:4801 Sunset Blvd, Fort Pierce, FL 34982 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh17386 Structure Btuh14556 Ducts Btuh4987 Ducts Btuh5613Central vent (46 cfm) 1467 Btuh Central vent (46 cfm) Btuh779 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh23840 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh19984 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh2576 Ducts Btuh1676Central vent (46 cfm) Btuh1778 CoolingHeating Outside air16021602Area (ft²) Equipment latent load Btuh6029 1378413784Volume (ft³)Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh26014 Equiv. AVF (cfm) 4687 Req. total capacity at 0.70 SHR ton2.4 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond ML14XC1S030-230A**AHRI ref Coil CBA27UHE-030-230*++TDR AHRI ref 10259437Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW6.9 Sensible cooling Btuh20300Heating output Btuh23456 Latent cooling Btuh8700 Temperature rise °F22 Total cooling Btuh29000Actual air flow cfm967 Actual air flow cfm967 Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.048Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.78 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 09:12:47Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N 1402Job:Right-J® Worksheet Dec 29, 2020Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House M Hall 2 Exposed wall 188.0 ft 4.0 ft 3 Room height 8.6 ft 8.0 heat/coolft 4 Room dimensions ft6.5x4.0 5 Room area 1601.8 ft²26.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 268 259 814 521 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 10 0 160 109 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 522 443 1395 892 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 31 0 525 878 0 0 0 0 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 13.0613.06 48 44 905 627 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 244 239 755 483 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 5 5 76 61 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 354 268 844 540 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 22 17 403 377 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 16 0 280 424 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 14.8114.81 48 39 905 711 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 192 192 564 280 32 32 94 47 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 1602 1602 1588 2343 26 26 26 38 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1602 188 5392 0 26 4 115 0 6 c) AED excursion 514 -5 Envelope loss/gain 14604 8758 235 80 12 a) Infiltration 2782 778 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 4 920 0 0 Appliances/other 4100 0 Subtotal (lines 6 to 13)17386 14556 235 80 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 -235 -80 14 Subtotal 17386 14556 0 0 15 Duct loads 29%39%4987 5613 29%39%0 0 Total room load 22373 20169 0 0 Air required (cfm)Air required (cfm)967 967 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 09:12:47Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N 1402Job:Right-J® Worksheet Dec 29, 2020Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Laundry Master Bath 2 Exposed wall 10.5 ft 21.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.5x10.5 ft12.0x7.5 5 Room area 68.3 ft²90.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 16 16 50 32 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 13.0613.06 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 96 91 288 184 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 5 5 76 61 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 12 12 38 24 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 14.8114.81 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 84 84 247 123 48 48 141 70 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 68 68 68 100 90 90 89 132 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 68 11 301 0 90 22 617 0 6 c) AED excursion -40 -32 Envelope loss/gain 616 183 1299 472 12 a) Infiltration 0 0 249 69 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)616 683 1548 541 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 90 31 0 0 14 Subtotal 705 713 1548 541 15 Duct loads 29%39%202 275 29%39%444 209 Total room load 908 988 1992 750 Air required (cfm)Air required (cfm)39 47 86 36 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 09:12:47Right-Suite® Universal 2021 21.0.10 RSU29066 Page 3...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N 1402Job:Right-J® Worksheet Dec 29, 2020Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name WIC Master Bed 2 Exposed wall 17.0 ft 14.5 ft 3 Room height 8.0 heat/coolft 8.5 heat/coolft 4 Room dimensions ft11.5x5.5 ft17.0x14.5 5 Room area 63.3 ft²246.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 44 44 139 89 123 108 339 217 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 16 0 262 439 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 13.0613.06 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 92 92 290 185 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 14.8114.81 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 63 63 63 93 247 247 244 361 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 63 17 488 0 247 15 416 0 6 c) AED excursion -24 5 Envelope loss/gain 979 342 1262 1021 12 a) Infiltration 273 76 247 69 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)1251 418 1509 1590 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 55 19 14 Subtotal 1251 418 1564 1609 15 Duct loads 29%39%359 161 29%39%449 621 Total room load 1610 580 2013 2230 Air required (cfm)Air required (cfm)70 28 87 107 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 09:12:47Right-Suite® Universal 2021 21.0.10 RSU29066 Page 4...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N 1402Job:Right-J® Worksheet Dec 29, 2020Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Pantry Kitchen/Nook 2 Exposed wall 0 ft 23.5 ft 3 Room height 8.0 heat/coolft 9.3 heat/coolft 4 Room dimensions ft3.0x5.0 ft274.5x1.0 5 Room area 15.0 ft²274.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 219 171 537 344 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 13.0613.06 0 0 0 0 48 44 905 627 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 14.8114.81 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 15 15 15 22 275 275 272 402 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 15 0 0 0 275 24 674 0 6 c) AED excursion -1 -201 Envelope loss/gain 15 21 2388 1171 12 a) Infiltration 0 0 438 122 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 2 460 Appliances/other 0 1700 Subtotal (lines 6 to 13)15 21 2826 3453 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -15 -21 5 7 14 Subtotal 0 0 2832 3460 15 Duct loads 29%39%0 0 29%39%812 1334 Total room load 0 0 3644 4795 Air required (cfm)Air required (cfm)0 0 157 230 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 09:12:47Right-Suite® Universal 2021 21.0.10 RSU29066 Page 5...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N 1402Job:Right-J® Worksheet Dec 29, 2020Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Great Room Bed 3 2 Exposed wall 29.0 ft 27.0 ft 3 Room height 9.3 heat/coolft 8.0 heat/coolft 4 Room dimensions ft14.5x26.0 ft172.5x1.0 5 Room area 377.0 ft²172.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 96 96 302 193 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 120 104 329 210 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 16 0 262 439 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 13.0613.06 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 242 171 540 345 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 22 17 403 377 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 14.8114.81 48 39 905 711 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 28 28 82 41 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 377 377 374 552 173 173 171 252 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 377 29 832 0 173 27 774 0 6 c) AED excursion 746 11 Envelope loss/gain 3135 2771 1839 1107 12 a) Infiltration 485 136 433 121 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 900 250 Subtotal (lines 6 to 13)3620 4267 2272 1478 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 106 54 10 14 14 Subtotal 3726 4321 2282 1492 15 Duct loads 29%39%1069 1666 29%39%655 575 Total room load 4795 5987 2937 2067 Air required (cfm)Air required (cfm)207 287 127 99 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 09:12:47Right-Suite® Universal 2021 21.0.10 RSU29066 Page 6...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N 1402Job:Right-J® Worksheet Dec 29, 2020Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Hall Lin 2 Exposed wall 0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft8.5x3.5 ft3.0x2.5 5 Room area 29.8 ft²7.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 13.0613.06 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 14.8114.81 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 30 30 29 44 8 8 7 11 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 30 0 0 0 8 0 0 0 6 c) AED excursion -2 -1 Envelope loss/gain 29 41 7 10 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)29 41 7 10 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -29 -41 -7 -10 14 Subtotal 0 0 0 0 15 Duct loads 29%39%0 0 29%39%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 09:12:47Right-Suite® Universal 2021 21.0.10 RSU29066 Page 7...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N 1402Job:Right-J® Worksheet Dec 29, 2020Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bath Bed 2 2 Exposed wall 5.5 ft 35.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft5.5x9.0 ft182.0x1.0 5 Room area 49.5 ft²182.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 44 35 109 70 128 128 403 258 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 10 0 160 109 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ee 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ee 18.8518.85 13.0613.06 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 56 56 176 113 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ss 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 100 84 266 170 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 16.8316.83 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ww 17.9817.98 27.1827.18 0 0 0 0 16 0 280 424 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 14.8114.81 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngls, R-30 0.034Attic, Shngls, R-30 0.034 --0.990.99 1.461.46 50 50 49 72 182 182 180 266 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 50 6 158 0 182 36 1018 0 6 c) AED excursion -15 72 Envelope loss/gain 475 236 2325 1303 12 a) Infiltration 88 25 569 159 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 250 Subtotal (lines 6 to 13)564 260 2894 1713 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 10 14 10 14 14 Subtotal 574 274 2904 1727 15 Duct loads 29%39%165 106 29%39%833 666 Total room load 738 380 3737 2392 Air required (cfm)Air required (cfm)32 18 161 115 2021-Nov-12 09:12:48 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N 1402Job:Duct System Summary Dec 29, 2020Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Spec Home, NisAir Air ConditioningFor: 4801 Sunset Blvd, Fort Pierce, FL 34982 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.559 / 0.141 in H2O in H2O0.559 / 0.141 Lowest friction rate in/100ft0.291in/100ft0.291 Actual air flow cfm967cfm967 Total effective length (TEL) ft240 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st3135.044.8VlFx0x04.00.3112238738hBath st3140.051.8VlFx0x07.00.2911381943737hBed 2 st3140.049.9VlFx0x07.00.2941191522937hBed 3 st2110.036.0VlFx0x07.00.3831721242993cGreat Room st2110.036.8VlFx0x07.00.3811721242993cGreat Room-A st2110.037.0VlFx0x06.00.380138942397cKitchen/Nook st2110.036.0VlFx0x06.00.383138942397cKitchen/Nook-A 80.05.2VlFx0x04.00.6565747988cLaundry st1100.020.3VlFx0x05.00.464431031992hMaster Bath st195.022.6VlFx0x05.00.47564521115cMaster Bed st195.019.8VlFx0x05.00.48764521115cMaster Bed-A st195.020.0VlFx0x05.00.48633831610hWIC Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 291 205 0.464 834 8.0 0x0 VinlFlx st3 Peak AVF 384 278 0.291 870 9.0 0x0 VinlFlx st2 st2 Peak AVF 822 898 0.291 840 14.0 0x0 VinlFlx Bold/italic values have been manually overridden 2021-Nov-12 09:12:48 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb5 0x 1880 162 48.5 0.291 538 8.0 x0 0 VlFx rb6 0x 6260 742 0 0 0 0 x0 0 VlFx rb4 0x 1940 138 0 0 0 0 x0 0 VlFx rb3 0x 1520 119 0 0 0 0 x0 0 VlFx 2021-Nov-12 09:12:48 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\4801 Sunset Blvd PSL Prop.rup Calc = MJ8 Front Door faces: N 1402Job:Manual S Compliance Report Dec 29, 2020Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Spec Home, NisAir Air ConditioningFor: 4801 Sunset Blvd, Fort Pierce, FL 34982 Cooling Equipment Design Conditions °F76.9Entering coil DB:Btuh20948Sensible gain:°F90.4Outdoor design DB: °F64.0Entering coil WB:Btuh6029Latent gain:°F77.4Outdoor design WB: Btuh26977Total gain:°F75.0Indoor design DB: cfm967Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: ML14XC1S030-230A**+CBA27UHE-030-230*++TDRModel:LennoxManufacturer: cfm967Actual airflow: % of load97Btuh20300Sensible capacity: % of load144Btuh8700Latent capacity: %70SHR:% of load107Btuh29000Total capacity: Heating Equipment Design Conditions °F68.1Entering coil DB:Btuh23840Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm967Actual airflow: °F50Temp. rise:% of load98kW6.9Output capacity: Meets all requirements of ACCA Manual S.