HomeMy WebLinkAboutNew Signed Energy CodeFORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the
Residential Simulated Performance Alternative shall include:
❑ This checklist
❑ Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/maybe greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 -one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ If Form R405 duct leakage type indicates anything other than "default leakage" then a completed
2020 Duct Leakage Test Report -Performance Method (usually one page)
11/12/2021 1:18:34 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 1 of 1
FORM R405-2020
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: 1916 Lynx Dr PSL Prop
Street: 1916 Lynx Dr
City, Stale, Zip: Fort Pierce , FL , 34949
Owner: Zeros Residence
Design Location: FL, ST_LUCIE_CO_INTL
1. New construction or existing
2. Single family or multiple family
3. Number of units, if multiple family
4. Number of Bedrooms
5. Is this a worst case?
6.
Conditioned floor area above grade (ft2)
Conditioned floor area below grade (ft2)
7.
Windows(425.8 sgft.)
Description
a. U-Factor:
Ohl, U=0.65
SHGC:
SHGC=0.21
b. U-Factor:
Dbl, U=0.58
SHGC:
SHGC=0.24
c. U-Factor:
Dbl, U=0.31
SHGC:
SHGC=0.19
Area Weighted Average
Overhang Depth:
Area Weighted Average
SHGC:
8.
Skylights
c. U-Factor:(AVG)
N/A
SHGC(AVG):
N/A
9.
Floor Types (2469.0 sgft.)
a. Slab -On -Grade Edge
Insulation
b. N/A
c. N/A
Glass/Floor Area: 0.172
New (From Plans)
Detached
1
3
Yes
2469
0
Area
136.00 ft2
Builder Name: PSL Prop
Permit Office:
Permit Number:
Jurisdiction: St. Lucie
County: St. Lucie (Florida Climate Zone 2 )
10. Wall Type>i2376.4 sgft.)
a. Concrete Block - Ext Insul, Exterior
b. Frame - Wood, Adjacent
c. N/A
d. N/A
11. Ceiling Types (2469.0 sgft.)
a. Roof Deck (Unvented)
b. N/A
c. N/A
12. Ducts
a. Sup: Attic, Ret: Attic, AH: Attic
Insulation
Area
R=4.1
1996.70 ft2
R=11.0
379.67 ft2
R=
ft2
R=
ft2
In
Area
R=20.0
2469.00 ft2
R=
ft2
R=
ft2
R ft2
6 985
121.01
ft2
13. Cooling systems
kBtu/hr
Efficiency
a. Central Unit
42.0 SEER:16.00
106.67
ft2
14. Heating systems
kBtu/hr
Efficiency
5.216
ft.
a. Electric Strip Heat
32.6
COP:1.00
0.211
Area
ft2
15. Hot water systems
a. Electric
Cap:
50 gallons
Insulation
Area
EF: 0.960
R=0.0
2469.00
f12
b. Conservation features
R=
ft2
None
R=
ft2
16. Credits
Patel
Total Proposed Modified Loads: 75.52
Total Baseline Loads: 76.83
I hereby certify that the plans and specifications covered by
this calculation are in compliance with the Florida Energy
Code. /Az" �
PREPARED BY: (2a
DATE: 11 /1212021
I hereby certify that this building, a esi ed, is in
with the Florida Energy Code. A �
DATE:
Review of the plans and
specifications covered by this
calculation indicates compliance
with the Florida Energy Code.
Before construction is completed
this building will be inspected for
compliance with Section 553.908
Florida Statutes.
BUILDING OFFICIAL:
DATE:
PASS
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 6.00 ACH50 (R402.4.1.2).
11/12/2021 1:18 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 6
anon IAIWKWEDI IT RI IMMARV RHFCKI 1ST RFPnRT
PROJECT
Title:
1916 Lynx Dr PSL
Prop
Bedrooms:
3
Address Type: Street Address
Building Type:
User
Conditioned Area:
2469
Lot #
Owner Name:
Zeros Residence
Total Stories:
1
Block/Subdivision:
# of Units:
1
Worst Case:
Yes
PlalBook:
Builder Name:
PSL Prop
Rotate Angle:
90
Street:
1916 Lynx Or
Permit Office:
Cross Ventilation:
No
County:
St. Lucie
Jurisdiction:
St. Lucie
Whole House Fan:
No
City, State,
Zip: Fort
Pierce ,
Family Type:
Detached
FL
34949
New/Existing:
New (From Plans)
Comment:
CLIMATE
Design
Temp
Int Design Temp
Heating
Design Daily Temp
Design Location
TMY Site
97.5 %
2.5 %
Winter
Summer Degree Days
Moisture
Range
FL, ST_LUCIE_CO_INTL
FL_VERO_BEACH_MUNI
39
90
70
75
299
58
Medium
BLOCKS
Number
Name
Area
Volume
1
Entire House
2469
25325.6
SPACES
Number
Name
Area
Volume Kitchen
Occupants
Bedrooms
Infil lD
Finished
Cooled
Heated
1
Master Bed
287
2870 No
0
1
1
Yes
Yes
Yes
2
WIC
78
780 No
0
1
Yes
Yes
Yes
3
Bed
193
1930 No
0
1
1
Yes
Yes
Yes
4
Bath
52
520 No
0
1
Yes
Yes
Yes
Bed 3
209
2090 No
0
1
1
Yes
Yes
Yes
6
Foyer
126
1562.4 No
0
1
Yee
Yes
Yes
7
Hall
34
340 No
0
1
Yes
Yes
Yes
8
Lin
5
50 No
0
1
Yes
Yes
Yes
9
Laundry
81
810 No
0
1
Yes
Yes
Yes
10
Dining
288
2995.2 No
0
1
Yes
Yes
Yes
11
Pantry
48
480 No
0
1
Yes
Yes
Yes
12
Bath 2
36
360 No
0
1
Yes
Yes
Yes
13
Living
545
5668 No
2
1
Yes
Yes
Yes
14
Kit Nook
291
2910 Yes
2
1
Yes
Yes
Yes
15
Master Bath
148
1480 No
0
1
Yes
Yes
Yes
16
Wtr Clst
24
240 No
0
1
Yes
Yes
Yes
17
Hall
24
240 No
0
1
Yes
Yes
Yes
11l12/2021 1:18 PM EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 6
FLOORS
# Floor Type
Space
Perimeter
Perimeter R-Value
Area
Joist R-Value
Tile
Wood
Carpet
1 Slab -On -Grade Edge Insulatio
Master Bed
31 ft
0
287.5 ft'
____
1
0
0
2 Slab -On -Grade Edge Insulatio
WIC
13 ft
0
78 ft'
____
1
0
0
3 Slab -On -Grade Edge Insulatio
Bed 2
15.6 ft
0
192.8 ft'
____
1
0
0
4 Slab -On -Grade Edge Insulatio
Bath
5.5 ft
0
52.3 ft'
----
1
0
0
5 Slab -On -Grade Edge Insulatio
Bed 3
38.5 ft
0
209.3 tt'
6 Slab -On -Grade Edge Insulatio
Foyer
18.5 it
0
126 W
____
1
0
0
7 Slab -On -Grade Edge Insulatio
Hall 2
1 it
0
34 112
--__
1
0
0
8Slab-On-Grade Edge Insulatio
Lin
i it
0
4.5 ft'
____
1
0
0
9Slab-On-Grade Edge Insulatio
Laundry
19 it
0
81.3 ft'
____
1
0
0
1061ab-On-Grade Edge Insulatio
Dining
16.5 ft
0
288 fl'
____
1
0
0
11Slab-On-Grade Edge Insulatio
Pantry
10.5 ft
0
48 ft'
----
1
0
0
12SIab-On-Grade Edge Insulatio
Bath 2
1 It
0
36 ft2
----
1
0
0
13SIab-On-Grade Edge Insulatio
Living
19.5 ft
0
545.3 fl'
____
1
0
0
14SIab-On-Grade Edge Insulatio
Kit Nook
34.1 ft
0
290.5 ft'
1
0
0
15SIab-On-Grade Edge Insulatio
Master Bath
loft
0
147.5 W
----
1
0
0
16SIab-On-Grade Edge Insulatio
Wtr Clst
1 ft
0
24 ft'
____
1
0
0
17SIab-On-Grade Edge Insulatio
Hall
1 it
0
24 ft'
1
0
0
ZiZ�lia
Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch
# Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg)
1 Hip Composition shingles 2761 ft' 0 W Medium N 0.3 No 0.9 No 20 26.57
V # Type
1 Full attic
ATTIC
Ventilation
Vent
Ratio
(1
in)
Area
RBS
IRCC
Unvenled
0
2469 fl'
N
N
11/12/2021 1:18 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 6
DRM R405-2020 INPUT SUMMARY CHECKLIST KtNUK I
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
1 Under Attic (Unvented) Master Bed 0 Blown 287W 0.1 Wood
2 Under Attic (Unvented) WIC 0 Blown 78 ft' 0.1 Wood
3 Under Attic (Unvented) Bed 0 Blown 193 ft2 0.1 Wood
4 Under Attic (Unvented) Bath 0 Blown 52 ft2 0.1 Wood
5 Under Attic (Unvented) Bed 0 Blown 209 ft2 0.1 Wood
6 Under Attic (Unvented) Foyer 0 Blown 126 ft2 0.1 Wood
7 Under Attic (Unvented) Hall 2 0 Blown 34 ft2 0.1 Wood
8 Under Attic (Unvented) Lin 0 Blown 5W 0.1 Wood
9 Under Attic (Unvented) Laundry 0 Blown 81 ft2 0.1 Wood
10 Under Attic (Unvented) Dining 0 Blown 288 ft2 0.1 Wood
11 Under Attic (Unvented) Pantry 0 Blown 48 ft2 0.1 Wood
12 Under Attic (Unvented) Bath 2 0 Blown 36 ft2 0.1 Wood
13 Under Attic (Unvented) Living 0 Blown 545 ft' 0.1 Wood
14 Under Attic (Unvented) Kit Nook 0 Blown 291 ft2 0.1 Wood
15 Under Attic (Unvented) Master Bath 0 Blown 148 ft2 0.1 Wood
16 Under Attic (Unvented) Wtr Clst 0 Blown 24 ft2 0.1 Wood
17 Under Attic (Unvented) Hall 0 Blown 24 ft2 0.1 Wood
WALLS
Adjacent Cavity Width Height Sheathing Framing Solar Below
Ornt To WaU T Space R-value E In Rt In Ama R-Value-Fraction Absor-Grade"k
_ 1 N=>E Exterior Concrete Block - Ext Insilllaster Bed 4.1 17 6 10 0 175.0 ft2 0 0 0.3 0
2 W=>N Exterior Concrete Block - Ext InsMaster Bed 4.1 13 6 10 0 135.0 ft2 0 0 0.3 0
_ 3 N=>E Exterior Concrete Block- Ext Insul WIC 4.1 13 0 10 0 130.0 ft2 0 0 0.3 0
4 N=>E Exterior Concrete Block - Ext Insul Bed 2 4.1 15 6 10 0 155.0 W 0 0 0.3 0
_ 5 N=>E Exterior Concrete Block - Ext Insul Bath 4.1 5 6 10 0 55.0 ft2 0 0 0.3 0
_ 6 N=>E Exterior Concrete Block - Ext Insul Bed 3 4A 15 6 10 0 155.0 ft2 0 0 0.3 0
_ 7 E=>S Exterior Concrete Block - Ext Insul Bed 3 4.1 13 6 10 0 135.0 ft2 0 0 0.3 0
_ 8 S=>W Exterior Concrete Block - Ext Insul Bed 3 4.1 9 6 10 0 95.0 ft2 0 0 0.3 0
_ 9 E=>S Exterior Concrete Block - Ext Insul Foyer 4.1 7 0 12 5 86.9 fl' 0 0 0.3 0
_ 10 S=>W Garage Frame - Wood Foyer 11 11 6 12 5 142.8 W 0 0.25 0.8 0
11 S=>W Garage Frame - Wood Laundry 11 6 6 10 0 65.0 ft2 0 0.25 0.8 0
12 E=>S Garage Frame - Wood Laundry 11 12 6 10 0 125.0 W 0 0.25 0.8 0
13 S=>W Exterior Concrete Block - Ext Insul Dining 4.1 12 0 10 5 125.0 ft2 0 0 0.3 0
14 E=>S Garage Frame - Wood Dining 11 4 6 10 5 46.9 ft2 0 0.25 0.8 0
15 E=>S Exterior Concrete Block - Ext Insul Pantry 4.1 2 6 10 0 25.0 ft2 0 0 0.3 0
16 S=>W Exterior Concrete Block - Ext Insul Pantry 4.1 8 0 10 0 80.0 ft2 0 0 0.3 0
_ 17 S=>W Exterior Concrete Block - Ext Insul Living 4.1 4 6 10 5 46.9 ft2 0 0 0.3 0
_ 18 W=>N Exterior Concrete Block - Ext Insul Living 4A 15 0 10 5 156.3 W 0 0 0.3 0
_ 19 S=>W Exterior Concrete Block - Ext InsulKit Nook 4.1 21 0 10 0 210.0 ft2 0 0 0.3 0
20 SW=>N Exterior Concrete Block - Ext InsulKit Nook 4.1 5 8 10 0 56.7 ft2 0 0 0.3 0
21 W=>N Exterior Concrete Block - Ext InsulKit Nook 4.1 7 6 10 0 75.0 ft' 0 0 0.3 0
22 N=>E Exterior Concrete Block - Ext InsMaster Bath 4.1 10 0 10 0 100.0 W 0 0 0.3 0
11/12/2021 1:18 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 6
UT SUMMARY CHECKLIST REPORT
FUKM
K4U5-2020
INP
WINDOWS
Orientation
shown is the entered orientation
=> changed
to Worst Case.
Wall
Overhang
#
Ornt ID
Frame
Panes
NFRC
U-Factor SHGC
Imp
Area
Depth
Separation
[nt Shade
Screening
1
N=>E 1
Vinyl
Low-E Double
Yes
0.58 0.24
Y
22.4 ft'
1 ft 0 in
1 ft 0 in
Drapes/blinds
Exterior 5
2
W=>N 2
Vinyl
Low-E Double
Yes
0.65 0.21
Y
64.0 ft'
10 ft 0 in
1 ft 0 in
Drapes/blinds
Exterior 5
3
N=>E 4
Vinyl
low-E Double
Yes
0.58 0.24
Y
22.4 ft°
1 ft 0 in
1 ft 0 in
Drapes/blinds
Exterior 5
4
N=>E 5
Vinyl
Low-E Double
Yes
0.58 0.24
Y
9.5 ft'
1 ft 0 in
1 It 0 in
Drapes/blinds
Exterior 5
5
N=>E 6
Vinyl
Low-E Double
Yes
0.45 0.18
Y
16.0 ft'
1 ft 0 in
1 ft 0 in
Drapes/blinds
Exterior 5
6
E=>S 7
Vinyl
Low-E Double
Yes
0.62 0.22
Y
22.4 ft'
1 ft 0 in
1 it 0 in
Drapes/blinds
Exterior 5
7
E=>S 9
Vinyl
Low-E Double
Yes
0.31 0.19
Y
10.3 ft'
10 ft 6 in
1 ft 0 in
Drapes/blinds
Exterior 5
8
E=>S 9
Vinyl
Low-E Double
Yes
0.31 0.19
Y
25.8 ft'
10 ft 6 in
1 it 0 in
Drapes/blinds
Exterior 5
9
E=>S 9
Vinyl
Low-E Double
Yes
0.31 0.19
Y
24.0 ft'
10 ft 6 in
1 ft 0 in
Drapes/blinds
Exterior 5
10
S=>W 13
Vinyl
Low-E Double
Yes
0.31 0.19
Y
46.5 fl'
1 ft 0 in
1 it 0 in
Drapes/blinds
Exterior 5
11
W=>N 18
Vinyl
Low-E Double
Yes
0.65 0.21
Y
72.0 ft'
10 It 0 in
1 ft 0 in
Drapes/blinds
Exterior 5
12
S=>W 19
Vinyl
Low-E Double
Yes
0.45 0.18
Y
17.1 ft'
1 ft 0 in
1 it 0 in
Drapes/blinds
Exterior 5
13
S=>W 19
Vinyl
Low-E Double
Yes
0.58 0.24
Y
22A ft'
1 it 0 in
1 ft 0 in
Drapes/blinds
Exterior 5
14
SW=>NW20
Vinyl
Low-E Double
Yes
0.58 0.24
Y
22.0 W
1 ft 0 in
1 it 0 in
Drapes/blinds
Exterior 5
15
W=>N 21
Vinyl
Low-E Double
Yes
0.58 0.24
Y
22.4 ft'
1 It 0 in
1 ft 0 in
Drapes/blinds
Exterior 5
16
N=>E 22
Vinyl
Low-E Double
Yes
0.45 0.18
Y
6.7 ft'
1 ft 0 in
1 ft 0 in
Drapes/blinds
Exterior 5
GARAGE
# Floor Area
Ceiling Area
Exposed Wall Perimeter
Avg. Wall Height
Exposed Wall Insulation
1 382.8 112
382.8 ft'
64 it
8 it
1
INFILTRATION
#
Scope
Method
SLA
CFM 50 ELA
EgLA
ACH
ACH 50
1
Wholehouse Proposed ACH(50) .000391
2532.6 138.94
260.85
.1'196
6
HEATING SYSTEM
# System
Type
Subtype
Speed
Efficiency
Capacity
Block
Ducts
1 Electric
Strip Heal/
None
COP:1
32.6 kBtu/hr
1
sys#1
COOLING SYSTEM
# System
Type
Subtype
Subtype
Efficiency
Capacity
Air Flow
SHR Block
Ducts
1 Central
Unit/
Split
Sing]
SEER: 16
42 kBlu/hr 1260 cfm
0.85 1
sys#1
HOT WATER SYSTEM
# System Type
SubType
Location
EF Cap
Use
SetPnt
Conservation
1 Electric
None
Attic
0.96 50
gal
62.3 gal
120 deg
None
11/12/2021 1:18 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 6
SOLAR HOT WATER SYSTEM
FSEC
Cart #
A May
Company Name
System Model # Collector Model
Collector
# Area
Storage
Volume
FEF
None
None
ft'
DUCTS
J #
Supply ----
ion R-Value Area
Location
---- Return ---- Air
Location Area Leakage Type Handler
CFM 25 CFM25
TOT OUT
QN RLF
HVAC #
Heat Cool
1
Attic 6 985 ft'
Attic 985 ft' Default Leakage Attic
(Default) (Default)
1 1
TEMPERATURES
Programable Thermostat: Y
Ceiling Fans:
Heating [X] Jan [X] Feb [X] Mar Apr [ ]May lX� Jun fX] Jul lXl Aug lXl Sep € Oct [ Nov [ ] Dec
Venting [[ 11 Jan [[ 11 Feb [[[[X1I Mar Jun [[ 11 Jul ll 1I Aug l[ J1 Sep
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling (WD) AM PM 80 80 78 78 78 78 78 78 76 78 78 78
Cooling (WEH) 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78
Healing (WD) PM 66 68 66 68 68 68 68 68 68 68 8 68 68 68 66 66
Heating (WEH) PM 68 68 68 68 68 68 68 68 68 68 66 66
MASS
Mass Type
Area
Thickness
Furniture Fraction
Space
Default(8 Ibs/sq.ft.
0 ft'
0 ft
0.3
Master Bed
Default(B lbs/sq.ft.
ft'
it
0.3
WIC
Default(8 lbs/sq.ft.
ft'
ft
0.3
Bed 2
Default(8 lbs/sq.ft.
ft'
ft
0.3
Bath
Default(8 Ibs/sq.ft.
ft'
ft
0.3
Bed 3
Default(8 lbs/sq.ft.
ft'
ft
0.3
Foyer
Default(8 lbs/sq.ft.
ft'
It
0.3
Hall
Default(8 lbs/sq.ft.
ft'
ft
0.3
Lin
Default(8 lbs/sq.ft.
ft2
ft
0.3
Laundry
Default(8 lbs/sq.ft.
ft'
It
0.3
Dining
Default(8 lbs/sq.ft.
ft'
it
0.3
Pantry
Default(8 Ibs/sq.ft.
ft'
ft
0.3
Bath 2
Default(8 lbs/sq.ft.
ft'
ft
0.3
Living
Default(8 Ibs/sq.ft.
ft'
ft
0.3
Kit Nook
Default(8 Ibs/sq.ft.
ft'
ft
0.3
Master Bath
Default(8 Ibs/sq.ft.
ft'
ft
0.3
Wtr Clst
. _.__ PLIA "
e=
ft
0.3
Hall
11/12/2021 1:18 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 6 of 6
FORM R405-2020
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 98
The lower the EnergyPerformance Index, the more efficient the home.
1916 Lynx Dr, Fort Pierce, FL, 34949
1. New construction or existing New (From Plans) 10. Wall Type and Insulation Insulation Area
Detached a. Concrete Block - Exl Insul, Exterior R=4.1 1996.70 ft2
2. Single family or multiple family b. Frame - Wood, Adjacent R=11.0 379.67 ft2
3. Number of units, if multiple family 1 c. N/A R= ft2
4. Number of Bedrooms 3 d. N/A R= ft2
11. Ceiling Type and insulation level Insulation Area
5. Is this a worst case? Yes a. Roof Deck (Unvented) R=20.0 2469.00 ft2
6. Conditioned Floor area (ft2) 2469 b. N/A R= ft2
c. N/A R= ft2
7. Windows** Description Area 12. Ducts, location & insulation level R ft2
a. U-Factor: Dbl, U=0.65 136.00 ft2 a. Sup: Attic, Ret: Attic, AH: Attic 6 986
SHGC: SHGC=0.21
b. U-Factor: Dbl, U=0.58 121.01 ft2
SHGC: SHGC=0.24 13, Cooling systems kBtu/hr Efficiency
c. U-Factor: Dbl, U=0.31 106.67 ft2 a. Central Unit 42.0 SEER:16.00
SHGC: SHGC=0.19
d. U-Factor: other (see details) 62.17 ft2 14. Heating systems kBtu/hr Efficiency
SHGC: other (see details) a. Electric Strip Heat 32.6 COPA.00
Area Weighted Average Overhang Depth: 5.216 ft.
Area Weighted Average SHGC: 0.211
8. Skylights Description Area 15. Hot water systems Cap: 50 gallons
a. U-Factor(AVG): N/A ft2 a. Electric EF: 0.96
SHGC(AVG): N/A b. Conservation features
9. Floor Types Insulation Area None
a. Slab -On -Grade Edge Insulation R=0.0 2469.00 fie Credits (Performance method) Pstat
b. N/A R= ft2
c. N/A R= ft2
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
n this home before final in"erwo
isplay Card will be completed
based on installed Code cBuilder Signature:Date: � / /zAddress of New Home:,City/FL Zip: rf ?;df el
3g9qe(
"Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code,
Energy Conservation, contact the Florida Building Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
11/12/2021 1:18 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
afnry Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: 1916 Lynx or Permit Number:
Fort Pierce , FL, 34949
MANDATORY REQUIREMENTS = See individual code sections for full details.
SECTION MCI I GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official she require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
(Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresoid residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
❑ R402A Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
R402.4.1
Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1
and
❑ R402.4.1.2.
The sealing methods between dissimilar materials shall allow for differential expansion and
contraction.
R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
❑ with the manufacturers instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3lhrough 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and Flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, If installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑ R402.4.2 Fireplaces. New wood -burning (replaces shall have light -filling Flue dampers or doors, and outdoor combustion air. Where
using tight -filling doors on factory -built fireplaces listed and labeled In accordance with ILL 127, the doors shall be tested and listed for the
fireplace. Where using tight -filling doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cm
per square fool (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
11/12/2021 1:18 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7fh Edition (2020) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
❑R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
R403.1.1 Thermostat provision (Mandatory). Al least one thermostat shall be provided for each separate heating and cooling system.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heal shall have controls
that, except during defrost, prevent supplemental heal operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (1), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough -in lest: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturers air handler enclosure if installed at the time of the lest. All registers shall be taped or otherwise
sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct air leakage lest shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing Is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where on =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
ElR403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying Fluids above 105°F (41°C)
or below 55"F (130C) shall be Insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for
circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The
controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no
demand for hot water.
❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
11/12/2027 1:18 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 71h Edition (2020) Compliant Software Page 2 of 6
MANDATORY REQUIREMENTS AS (Continued)
❑ R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
❑ R403.5.6.1.1 Automatic controls. Service water -healing systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 1000F to 140*F (380C to 600C).
❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided topermitthe power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water -heating systems to be turned off.
❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal: and
2. Be installed at an orientation within 45 degrees of true south.
R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s)I then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
❑ R403.7A Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based
on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design
conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other
factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems. New or replacement healing and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed. TABLE R403.6A
nnCruAMlrel VFNTILATION SYSTEM FAN EFFICACY
Vvn
FAN LOCATION
VLAIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMU
(CFM)
HRV or ERV
Any
1.2 cfm/wall
Any
Range hoods
In -line fan
Any
Any
2.8 cfm/watt
2.8 cfm/waft
JAny
Any
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90 2.8 cfm/watf
For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916
11/12/2021 118 PM EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7fh Edition (2020) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
❑R403.7A.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 limes greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
i. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by aFlorida-registered engineer, in attached single- and multiple -family units, the capacity o
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heal pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
ElR403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and Ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50OF (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40OF (4.80C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the selling of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
11/12/2021 1:18 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5
R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
❑ the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
❑ R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa healers shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
healers fired by natural or LP gas shall not have continuously burning pilot lights.
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
❑ with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
❑R403.11 Portable spas (Mandatory). The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
❑ R403A3 Dehumidifiers (Mandatory If installed, a dehumidifer shall conform to the following requirements:
1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house
is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2. The dehumidifier shall be controlled by a sensor that is installed In a location where it is exposed to mixed house air.
3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
❑ R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403A3,
conform to the following requirements:
i. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct.
3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
11/12/2021 1:18 PM EnergyGauge� USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5
2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: 1916 Lynx Dr PSL Prop Builder Name: PSL Prop
Street: 1916 Lynx Dr Permit Office:
City, State, Zip: Fort Pierce FL Permit Number:
, 34949
0
ul
w
Owner: Zeros Residence Jurisdiction: St. Lucie
U
Design Location: FL, ST_LUCIE_CO_INTL
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
requirements
Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
Ceiling/attic
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
Walls
The junction of the lop plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
with a material having a thermal resistance of R-3
sealed.
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
skylights and framing shall be sealed.
and doors
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
maintain permanent contact with the underside of
(including
insulation.
subfloor decking, or floor framing cavity insulation
above -garage
shall be permitted to be in contact with the top side
and cantilevered
of sheathing, or continuous insulation installed on
floors)
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
Crawl space walls
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace wall
.
Duct shafts, utility penetrations, and flue shafts opening to
Shafts, penetrations
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
cavities shall be filled by insulation that on
Narrow cavities
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spa
s.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the finished surface.
thermal envelope shall be air tight and IC rated.
Batt insulation shall be cut neatly to fit around wiring
Plumbing and wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box of
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sealed in a manner that is recommended by the manufacturer.
sprinklers
Caulking or other adhesive sealants shall not be used to fill voids
between fire sodnj�lpg gover plates and )Uall Or -Ann
a. In addition, inspecuon or tog wars scan uc III a�uvl6a„moo wi.p, u ;� r.�..-.-..- -.." '
11/12/2021 1:18 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2111112o Flnrida Building Code. Enerqv Conservation, 7th Edition
Jurisdiction: St. Lucie
Permit #:
Job Information
Builder: PSL Prop Community: Lot: NA
Address: 1916 Lynx Dr
City: Fort Pierce State: FL Zip: 34949
Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ERI Method
OPRESCRIPTIVE METHOD•The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air
changes per hour at a pressure of 0.2 inch w.g. (50 Pascals) in Climate Zones 1 and 2.
O PERFORMANCE or ERI METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding
the selected ACH(50) value, as shown on Form R405-2020 (Performance) or R406-2020 (ERI), section labeled as infiltration, sub -section ACH50.
ACH(50) specified on Form R405-2020-Energy Calc (Performance) or R406-2020 (ERI): 6.000
x 60 =-3.9039E12 — Method for calculating building volume:
CFM(50) Building Volume ACH(50) O Retrieved from architectural plans
PASS • Code software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSIIRESNETIICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(01 (9), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers Including exhaust, intake, makeup air, back draft and Flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
11/12/2021 1:18:49 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1