Date: 10-28-2021
To: Advanced Hurricane Protection
Project: Schuster Residence
9600 S Ocean Dr, Unit 1109, Jensen Beach, FL
Subject: Glazed openings protection.
Glazed openings Marks 1 thru 7 in Unit 1109 have been protected with the system
described below.
Bertha HV Accordion Shutter, Schedule 3.
Florida Approval: FL# 1850.2
System meets:
Impact requirements.
Site Wind Pressures
Refer to the following pages for structural analysis, product approval and wind loads.
Respectfully submitted,
AHP 21008
Structural Analysis
System: Bertha HV Accordion Shutter LMI/SMI
Governing Code: Florida Building Code 2020 (7th Edition)
Section 1609.1.2 Protection of Openings
Comparison Table
POSITIVE NEGATIVE
1 61.06 61.34 61" 65 10'-9" 65 11'-11"GOOD
2 61.04 61.33 95" 65 10'-9" 65 11'-11"GOOD
3 61.04 61.33 95" 65 10'-9" 65 11'-11"GOOD
4 61.04 61.33 95" 65 10'-9" 65 11'-11"GOOD
5 61.04 111.18 95" 65 10'-9" 115 8'-11"GOOD
6 59.65 107.46 95" 65 10'-9" 115 8'-11"GOOD
7 59.66 60.41 95" 65 10'-9" 115 11'-11"GOOD
MAX.
SHUTTER
SPAN FOR
NEGATIVE
WIND
ACTUAL VS FPA
REQUIREMENTS
Bertha
HV
Accordion
Shutter -
Schedule
#3
1850.2
Please refer to Table shown below for a comparison between the marks on the project and the limitations of the
Florida Approval.
MARK SYS. FL#
SITE WIND PRESSURE
IN PSF FRAME
HEIGHT
ALLOWABLE
DESIGN
POSITIVE
PRESSURE IN
PSF
MAX.
SHUTTER
SPAN FOR
POSITIVE
WIND
ALLOWABLE
DESIGN
NEGATIVE
PRESSURE IN
PSF
1
2
2
3
4
5
6
7
66 West Flagler Street Suite 900 - #4395 Miami, FL 33130 l 754.701.7126
admin@Jbdteam.com l www.Jbdteam.com
Date: 09/07/21
Project: Schuster Residence / 9600 S Ocean Dr, Unit 1109, Jensen Beach, FL
Re: Wind Loads
MecaWind v2351
Software Developer: Meca Enterprises Inc., www.meca.biz, Copyright © 2020
Calculations Prepared by: Calculations Prepared For:
Client: Schuster Residence
Date: Sep 07, 2021 Project #: 21008
Designer: Julio Gonzalez, P.E. Location: 9600 S Ocean Dr, Unit 1109, Jensen Beach, FL 34957
Description:
Windows and Door Retrofit
File Location : D:\AHP 21008 Schuster WL\Wind Loads\Schuster Residence mecawind.wnd
Basic Wind Parameters
Wind Load Standard = ASCE 7-16 Exposure Category = D
Wind Design Speed = 170.0 mph Risk Category = II
Structure Type = Building Building Type = Enclosed
Building Inputs
RoofType: Building Roof Type = Flat : Flat Roof =
RfHt : Roof Height = 140.000 ft W : Building Width = 78.000 ft
L : Building Length = 258.000 ft OH : Type of Overhang = None
Parapet : Type of Parapet = Parapet Par : Is there a Parapet = True
PHt : Height of Parapet = 3.000 ft Por : Parapet Porosity = Solid
P_GCPi : Parapet Int Press = +/-0.00 OH_ALL : None = 0.000 ft
Main Wind Force Resisting System (MWFRS) Calculations per Ch 27 Part 1:
h = Mean Roof Height above grade = 140.000 ft
Kh = 15 ft [4.572 m]< Z <Zg -->(2.01*(Z/zg)^(2/Alpha) {Table 26.10-1}= 1.519
Kzt = Topographic Factor is 1 since no Topographic feature specified = 1.000
Kd = Wind Directionality Factor per Table 26.6-1 = 0.85
Zg = Elevation above Sea Level = 0.000 ft
Ke = Ground Elevation Factor: Ke = e^-(0.0000362*Zg) {Table 26.9-1} = 1.000
GCPi = Ref Table 26.13-1 for Enclosed Building = +/-0.18
RA = Roof Area = 20124.00 sq ft
LF = Load Factor based upon ASD Design = 0.60
qh = (0.00256 * Kh * Kzt * Kd * Ke * V^2) * LF = 57.32 psf
qin = For Negative Internal Pressure of Enclosed Building use qh*LF = 57.32 psf
qip = For Positive Internal Pressure of Enclosed Building use qh*LF = 57.32 psf
Gust Factor Calculation:
Gust Factor Category I Rigid Structures - Simplified Method
G1 = For Rigid Structures (Nat. Freq.>1 Hz) use 0.85 = 0.85
Gust Factor Category II Rigid Structures - Complete Analysis
Zm = 0.6 * Ht = 84.000 ft
Izm = Cc * (33 / Zm) ^ 0.167 = 0.128
Lzm = L * (Zm / 33) ^ Epsilon = 730.523
Q = (1 / (1 + 0.63 * ((B + Ht) / Lzm)^0.63))^0.5 = 0.879
G2 = 0.925*((1+1.7*lzm*3.4*Q)/(1+1.7*3.4*lzm)) = 0.877
Gust Factor Used in Analysis
G = Lessor Of G1 Or G2 = 0.850
Components and Cladding (C&C) Calculations per Ch 30 Part 3:
Theta = Slope of Roof = 0.0 Deg
h = Mean Roof Height above grade = 140.000 ft
Kh = 15 ft [4.572 m]< Z <Zg -->(2.01*(Z/zg)^(2/Alpha) {Table 26.10-1}= 1.519
Kzt = Topographic Factor is 1 since no Topographic feature specified = 1.000
Kd = Wind Directionality Factor per Table 26.6-1 = 0.85
GCPi = Ref Table 26.13-1 for Enclosed Building = +/-0.18
LF = Load Factor based upon ASD Design = 0.60
qh = (0.00256 * Kh * Kzt * Kd * Ke * V^2) * LF = 57.32 psf
LHD = Least Horizontal Dimension: Min(B, L) = 78.000 ft
a1 = Min(0.1 * LHD, 0.4 * h = 7.800 ft
a = Max(a1, 0.04 * LHD, 3 ft [0.9 m]) = 7.800 ft
Effective Wind Area for C&C per Ch 30 Part 3
Description Zone Elev Width Span 1/3 Area Ref GCp GCp
Length Rule Fig Max Min
ft ft ft ft sq ft
------------------------------------------------------------
Mark 1 4 110.00 4.406 5.323 No 23.45 30.6-1 0.885 -0.890
Mark 2, 3 & 4 4 110.00 2.958 7.958 No 23.54 30.6-1 0.885 -0.890
Mark 5 5 110.00 2.958 7.958 No 23.54 30.6-1 0.885 -1.759
Mark 6 5 110.00 3.840 7.958 No 30.56 30.6-1 0.860 -1.695
Mark 7 4 110.00 3.833 7.958 No 30.50 30.6-1 0.861 -0.874
Wind Pressures for C&C per Ch 30 Part 3
All wind pressures include a load factor of 0.6
Description Zone qi q_ww q_oth P_WW P_WW P_Oth P_Oth P_Max P_Min
Max Min Max Min
ft psf psf psf psf psf psf psf psf psf
--------------------------------------------------------------------
Mark 1 4 57.32 54.97 57.32 58.98 -59.25 61.06 -61.34 61.06 -61.34
Mark 2, 3 & 4 4 57.32 54.97 57.32 58.96 -59.24 61.04 -61.33 61.04 -61.33
Mark 5 5 57.32 54.97 57.32 58.96 -107.04 61.04 -111.18 61.04 -111.18
Mark 6 5 57.32 54.97 57.32 57.62 -103.47 59.65 -107.46 59.65 -107.46
Mark 7 4 57.32 54.97 57.32 57.63 -58.35 59.66 -60.41 59.66 -60.41
GCp = Walls and Flat Roofs (Slope < 10 Deg) use Fig 30.56-1
= Per Fig 30.5-1 Note 6 Roof Slopes >= 10 Deg use Fig 30.3-2A, B and C
qi = qh for Enclosed buildings
q_ww = qz for Windward walls
q_oth = qh for Leeward walls, Side walls and Roofs
P_WW = Press on Windward Walls: q_ww * GCp - qi * (+/-GCpi) [Eqn 30.5-1]
P_Oth = Press on Leeward/Side/Roof: q_oth * GCp - qi * (+/-GCpi) [Eqn 30.5-1]
P_Max = Max Positive Pressure on C&C component: Max(P_WW, P_Oth)
P_Min = Max negative pressure on C&C component: Min(P_WW, P_Oth)
* Per Para 30.2.2 the Minimum Pressure for C&C is 9.60 psf [0.460 kPa] {Includes LF}