Loading...
HomeMy WebLinkAboutProject InformationJob: -�- wrightsoft® Manual S Compliance Report Date: Mar 15, 2021 Entire House R�IV�`�Y AUG 2 _ ryC�l ST. Lucie n- Project Information For: OVERTON RESIDENCE 0 N. DIXIE HIGHWAY Parcel ID: 1408-703-0050-000-8, FORT PIERCE, FL 34946 Design Conditions Outdoor design DB: 90.4°F Outdoor design WB: 77.40F Indoor design DB: 72:0°F_ Indoor RH: 50 % Sensible gain: 25087 Btuh Latentgain: 8903 Btuh Total gain:. 33991 Btuh Estimated airflow: 1075 cfm Entering coil DB: 72.3°F Entering coil WB: 60.8°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIItAC Manufacturer: Trane Model: 4TTR6042J1+4TXCD008DS3+S9X2D120U5PSB Actual airflow: 107.5 cfm Sensible capacity: 28813 Btuh 115% of load Latent capacity: 9378 Btuh 105% of load Total capacity: 38191 Btuh 112%ofload SHR: 75% Design Conditions Outdoor design DB: 41.0°F Heat loss: 30200 Btuh Entering coil DB: 69.7°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elecstrip Manufacturer: Model: Actual airflow: 1075 cfm Output capacity: 8.1 kW 92% of load Temp. rise: 50 °F oQ, 1110 ov Meets all requirements ofACCA Manual S. wrightsofto 2021-Apr-1316:46:56 �� •r+rt.�•ie.n.nirowm..•vc•mwmi Rigtt-Stite® Uriversal 2021 21.0.05 RSU29964 Page 1 ...DoamertsUrigNsoftWAC\OVERTONRESIDENCE.rup Calc=MA Frort Door faces: E -�- wrightsoft® Load Short Form Entire House Job: Date: Mar 15, 2021 By. For: OVERTON RESIDENCE 0 N. DIXIE HIGHWAY Parcel ID: 1408-703-0050-000-8, FORT PIERCE, FL 34946 Htg Cig Infiltration Outside db (°F) 41 90 Method Simplified Inside db (OF) 70 72 Construction quality Average Design TD (°F) 29 18 Fireplaces 0 Daily range - L Inside humidity (%) 30 50 Moisture difference (grAb) 2 63 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Trane Trade Trade TRANE Model Cond 4TTR6042J1 AHRI ref Coil 4TXCD008DS3+S9X2D120U5PSB AHRI ref 204378552 Efficiency 100 EFF Efficiency 14.0 EER, 16.5 SEER Heating input 8.1 kW Sensible cooling 31234 Btuh Heating output 27637 Btuh Latent cooling 9766 Btuh Temperature rise 23 OF Total cooling 41000 Btuh Actual airflow 1075 cfm Actual airflow 1075 cfm Airflowfactor 0.036 cfm/Btuh Airflowfactor 0.043 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.74 ROOM NAME Area (ftz) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) CIgAVF (cfm) M WIC 1 58 1659 708 59 30 M WIC2 53 997 487 35 21 MASTER BEDROOM 300 2670 2826 95 121 MASTER BATH 155 2409 1065 86 46 LAUNDRY 76 660 767 24 33 DINING 278 3572 4439 127 190 KITCHEN 213 2013 2540 72 109 BED 2 215 3716 2192 132 94 BED 3 220 2124 1837 76 79 GREAT ROOM 495 4450 3883 158 166 DEN 228 5067 3759 180 161 RATt4 0 Qr or-0 I r;Qr, 1 12.1 1)r^ Calculations approved byACCAto meet all requirements of Manual J 8th Ed. - wrightsoft 2021-Apr-1316:46:56 •Mrtok•/o. 6w•wue.•��m>.y Right -Sate® Urrversal 202121.0.05 RSU29964 Page ACM...DocunerlsUrigMsoftHVAC10VERTONRESIDENCE.rup Calc=MJ8 Frort Door faces: E Entire House 2377 30200 25087 1075 1075 Other equip loads 0 0 Equip. @ 0.95 RSM 23933 Latent cool i ng 8903 -M-rAl c r»nn 1100,27 -4m1Z -imG Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -*- wrightsoft® 2021-Apr-1316:46:56 ^'�^ •Mn•veo.�ueww.,Y p.m Riglt-Site®Uriversal202121.0.05RSU29964 Page 2 ...DoamerdslWriglIsoftHVAC\OVERTONRESIDENCE.np Cale =MJB Frort Door faces: E - wrightsoft® Project Summary Entire House Job: Date: Mar 15, 2021 By. Project Information For: OVERTON RESIDENCE 0 N. DIXIE HIGHWAY Parcel ID:1408-703-0050-000-8, FORT PIERCE, FL 34946 Notes: Weather: St Lucie Co IntI,.FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 72 OF Design TD 29 OF Design TD 18 OF Daily range L Relative humidity 50 % Moisture difference 63 gr/Ib Heating Summary . Sensible Cooling Equipment Load Sizing Structure 26921 Btuh Structure 23036 Btuh Ducts 3279 Btuh Ducts 2052 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 30200 Btuh Use manufacturer's data n Rate/swingg multipplier Equipmentsensibleload 0.95 Infiltration 23933 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 6671 Btuh Ducts 2232 Btuh Central vent (0 cfm) 0 Btuh Heatingg� cooling (none) Area (ftz) 2377 2377 Equipment latent load 8903 Btuh Volume (fP) 24170 24170 Air changes/hour 0.32 0.16 Equipment Total Load (Sen+Lat) 32837 Btuh Equiv AVF (cfm) 129 64 Req. total capacity at 0.76 SHR 2.6 ton Heating Equipment Summary Cooling Equipment Summary Make Make Trane Trade Trade TRANE Model Cond 4TTR6042J1 AHRI ref Coil 4TXCD008DS3+S9X2D120U5PSB AHRI ref 204378552 Efficiency 100 EFF Efficiency 14.0 EER,16.5 SEER Heating input 8.1 kW Sensible cooling 31234 Btuh Heating output 27637 Btuh Latent cooling 9766 Btuh Temperature rise 23 OF Total cooling 41000 Btuh Actual airflow 1075 cfm Actual airflow 1075 cfm Airflowfactor 0.036 cfm/Btuh Airflowfactor 0.043 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.74 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. ti. -Pp- =ightsoft- 2021-Apr-1316:46:56 11 •^*•+• ^� �^-+� P RigU-SJte®UNversal2021 21.0.05 RSU29964 Page 1 ACCDoameris0rigNsaftHVAC\OVERTONRESIDENCE.rup Calc=MA Frort Door faces: E FORM R405-2020 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: OVERTON RESIDENCE Builder Name: Street: 0 N Old Dixie Highway Fort Pierce 34946 Parcel ID: 1 Permit Office: ST. LUCIE COUNTY City, State, Zip: FORT PIERCE, FL, 34946 Permit Number: Owner: Jurisdiction: Design Location: FL, VERO_BEACH_MUNICIPAL_ARPT County: St. Lucie (Florida Climate Zone 2 ) 1. New construction or existing New (From Plans) 10. Wall Type�2294.0 sqft.) Insulation Area 2. Single family or multiple family Detached a. Concrete Block - Ext Insul, Exterior R=5.0 1972.80 ft2 b. Frame - Wood, Adjacent R=11.0 321.22 ft2 3. Number of units, if multiple family 1 c. N/A R= 2 ft 4. Number of Bedrooms 3 d. N/A R= ft2 5. Is this a worst case? No 11. Ceiling Types (2378.0 sgft.) Insulation Area a. Roof Deck (Unvented) R=30.0 2378.00 ft2 6. Conditioned floor area above grade (ft2) 2378 b. N/A R= ft2 Conditioned floor area below grade (ft2) 0 c. N/A R= ft2 7. Windows(229.7 sqft.) Description Area 12. Ducts a. Sup: Main, Ret: Main, AH: Main R ft2 6 646 a. U-Factor: Dbl, U=0.65 229.70 ft2 SHGC: SHGC=0.35 b. U-Factor: N/A ft2 13. Cooling systems kBtu/hr Efficiency SHGC: a. Central Unit 41.0 SEER:16.50 c. U-Factor: N/A ft2 SHGC: Area Weighted Average Overhang Depth: 4.821 ft. 14. Heating systems kBtu/hr Efficiency Area Weighted Average SHGC: 0.350 a. Electric Strip Heat 27.6 COP:1.00 8. Skylights Area c. U-Factor:(AVG) N/A ft2 15. Hot water systems SHGC(AVG): N/A a. Electric Cap: 80 gallons 9. Floor Types (2378.0 sqft.) Insulation Area EF: 0.900 a. Slab -On -Grade Edge Insulation R=0.0 2378.00 ft2 b. Conservation features b. N/A R= ft2 None c. N/A R= ft2 16. Credits Pstat Glass/Floor Area: 0.097 Total Proposed Modified Loads: 68.32 PASS Total Baseline Loads: 69.12 I hereby certify that the plans and specifications covered by Review of the plans and011) '"flu S?. ?� this calculation are in compliance with the Florida Energy specifications covered by this � _ p Code. calculation indicates compliance the Florida Energy Code. , with q�u,:'�., •.;; :_",•.•, ,� .O PREPARED BY: Before construction is completed DATE: 04/12/2021 this building will be inspected for compliance with Section 553.908 a I hereby certify that this building, as designed, is in compliance Florida Statutes. with the Florida Energy Code. G'OD WE. OWNER/AGENT: BUILDING OFFICIAL: DATE: DATE: - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory -sealed in accordance with R403.3.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 7.00 ACH50 (R402.4.1.2). 4/13/2021 4:50 PM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 4 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT PROJECT Title: Building Type: Owner Name: # of Units: Builder Name: Permit Office: Jurisdiction: Family Type: New/Existing: Comment: OVERTON RESIDENCE Bedrooms: 3 User Conditioned Area: 2378 Total Stories: 1 1 Worst Case: No Rotate Angle: 0 ST. LUCIE COUNTY Cross Ventilation: No Whole House Fan: No Detached New (From Plans) Address Type: Street Address Lot # Block/Subdivision: PlatBook: Street: 0 N Old Dixie Highway County: St. Lucie City, State, Zip: FORT PIERCE, FL, _ 34946 CLIMATE / V Design Location Design Temp TMY Site 97.5 % 2.5 % Int Design Temp Heating Design Daily Temp Winter Summer Degree Days Moisture Range FL, VERO_BEACH. MUN FL_VERO_BEACH_MUNI 45 90 70 75 299 64 Medium BLOCKS Number Name Area Volume 1 Blocki 2378 24255.6 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated 1 Main 2378 24255.6 Yes 4 3 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter R-Value Area Tile Wood Carpet 1 Slab -On -Grade Edge Insulatio Main 232.7 ft 2378 ft2 ---- 0 0 1 ROOF / # Roof Gable Roof Type Materials Area Area Color Rad Solar SA Emitt Emitt Deck Pitch Barr Absor. Tested Tested Insul. (deg) 1 Hip Composition shingles 2659 ft2 0 ft2 Medium N 0.4 N 0.9 No. 30 26.57 ATTIC V # Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 Full attic Unvented 0 2378 ft2 N N CEILING # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic (Unvented) Main 0 Blown 2378 ft2 0.1 Wood 4/13/2021 4:50 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 4 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT WALLS # C)rnt Adjacent To Wall TypeQ Space Cavity Width Height Sheathing Framing Solar Below 1 N Exterior Concrete Block - Ext Insul Main 5 42 5 12 0 509.0 ft2 0 0 0.3 0 2 E Exterior Concrete Block - Ext Insul Main 5 34 5 12 0 413.0 ft2 0 0 0.3 0 3 S Exterior Concrete Block - Ext Insul Main 5 45 4 9 4 423.1 ft2 0 0 0.3 0 4 W Exterior Concrete Block - Ext Insul Main 5 67 3 9 4 627.7 ft2 0 0 0.3 0 5 - Garage Frame - Wood Main 11 34 5 9 4 321.2 ft2 0 0.25 0.3 0 WINDOWS Orientation shown is the entered, Proposed orientation. / Wall Overhang V # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening 1 n 1 Vinyl Double (Clear) Yes 0.65 0.35 N 8.0 ft2 2 ft 0 in 1 ft 0 in None None 2 n 1 Vinyl Double (Clear) Yes 0.65 0.35 N 30.0 ft2 2 ft 0 in 1 ft 0 in None None 3 N 1 Vinyl Double (Clear) Yes 0:65 0.35 N 20.0 ft2 14 ft 0 in 0 ft 6 in None None 4 e 2 Vinyl Double (Clear) Yes 0.65 0.35 N 7.0 ft2 _ 8 ft 0 in 1 ft 0 in None None 5 e 2 Vinyl Double (Clear) Yes 0.65 0.35 N 30.0 ft2 2 ft 0 in 1 ft 0 in None None 6 e 2 Vinyl Double (Clear) Yes 0.65 0.35 N 40.0 ft2 8 ft 0 in 1 ft 0 in None None 7 s 3 Vinyl Double (Clear) Yes 0.65 0.35 N 8.0 ft2 2 ft 0 in 1 ft 0 in None None 8 s 3 Vinyl Double (Clear) Yes 0.65 0.35 N 40.2 ft2 2 ft 0 in 1 ft 0 in None None 9 w 4 Vinyl Double (Clear) Yes 0:65 0.35 N 10.5 ft2 14 ft 0 in 0 ft 6 in None None 10 W 4 Vinyl Double (Clear) Yes 0.65 0.35 N 36.0 ft2 2 ft 0 in 1 ft 0 in None None GARAGE # Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation 1 670 ft2 670 ft2 64 ft 9.3 ft 1 INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000453 2829.8 155.25 291.47 .1512 7 HEATING SYSTEM # System Type Subtype Speed Efficiency Capacity Block Ducts 1 Electric Strip Heat/ None COP:1 27.64 kBtu/hr 1 sys#1 COOLING SYSTEM # System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit/ Split Sing[ SEER: 16.5 41 kBtu/hr cfm 0.76 1 sys#1 4/13/2021 4:50 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 4 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Electric None Garage 0.9 80 gal 62.3 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Cert # Company Name System Model # Collector Model # Area Volume FEF None None ft2 DUCTS ---- Supply ---- =- Return ---- Air . CFM 25 CFM25 HVAC # # Location R-Value` Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 Main 6 646 ft2 Main 304 ft2. Default Leakage Main (Default) (Default) 1 1 TEMPERATURES Programable Thermostat: Y Ceiling Fans: Cool in Jan Feb rr ll Mar Heating Jan HFeb [X] Mar E A r APr f Ma j Jun Jul May Jun Jul X Au 4 � Aug Se SeP ri r [ Oct Oct Nov f X} Nov Dec HDec LX} Ventin [ 11 Jan Feb [[[[[[X]]]]]] Mar lX1 A r l Ma Jun Jul E [ Au Se [[[XXX]]] Oct [Xl Nov Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9. 10 11 12 Cooling (WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling (WEH) AM 78 78 78 78 78 78 78 78. 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating (WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating (WEH) AM 66 66 . 66 . 66 66 .68 68 68 68 68 68 68 PM 68 68 68 68 68 68—.--68 68 68 68 66 66 MASS Mass Type Area Thickness Furniture Fraction Space Default 8 Ibs/s .ft. 0 ft2 0 ft 0.3 Main 4/13/2021 4:50 PM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 4 FORM R405-2020 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 99 The lower the EnergyPerformance Index, the more efficient the home. 0 N Old Dixie Highway Fort Pierce 34946 Parcel ID: 1408-703-0050-000-8, FORT PIERCE, FL, 34946 1. New construction or existing New (From Plans) 10. Wall Type and Insulation Insulation Area 2. Single family or multiple family Detached a. Concrete Block - Ext Insul, Exterior R=5.0 1972.80 ft2 b. Frame - Wood, Adjacent R=11.0 321.22 ft2 3. Number of units, if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 3 d. N/A R= ft2 5. Is this a worst case? No 11. Ceiling Type and insulation level Insulation Area a. Roof Deck (Unvented) R=30.0 2378.00 ft2 6. Conditioned floor area (ft2) 2378 b. N/A R= ft2 7. Windows- Description Area c' _ z a. U-Factor: Dbl, U=0.65 229.70 ft2 12. Ducts, location & insulation level R ft2 a. Sup: Main, Ret: Main, AH: Main 6 646 SHGC: SHGC=0.35 b. U-Factor: N/A ft2 SHGC: 13. Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a. Central Unit 41.0 SEER:16.50 SHGC: d. U-Factor: N/A ft2 SHGC: 14. Heating systems kBtu/hr Efficiency a. Electric Strip Heat 27.6 COP:1.00 Area Weighted Average Overhang Depth: 4.821 ft. Area Weighted Average SHGC: 0.350 8. Skylights Description Area 15. Hot water systems Cap: 80 gallons a. U-Factor(AVG): N/A ft2 a. Electric EF: 0.9 SHGC(AVG): N/A b. Conservation features 9. Floor Types Insulation Area None a. Slab -On -Grade Edge Insulation R=0.0 2378.00 ft2 Credits (Performance method) Pstat b. N/A R= ft2 c. N/A R= ft2 I certify that this home has complied with the Florida Energy Efficiency Code for Building Construction through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL Display Card will be completed based on installed Code compliant features. Builder Signature: Address of New Home: Date: City/FL Zip: *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 4/13/2021 4:50 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 0 N Old Dixie Highway Fort Pierce 34946 Parcel ID: 1 Permit Number: FORT PIERCE, FL, 34946 MANDATORY REQUIREMENTS - See individual code sections for full details. V/ SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third parry shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL.127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 4/13/2021 4:50 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. ❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75• Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403:1 Controls. SECTION R403 SYSTEMS ❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. ❑ R403.3.2.1 Sealed air. handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. ❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage On to the outside of less than 0.080 (where On = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. ❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below 55°F (13°C) shall be insulated to a minimum of R-3. ❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. ❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall ❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. ❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 4/13/2021 4:50 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have ❑ heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 31/2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). ❑ R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60oC). ❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. ❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. ❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. ❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. ❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. ❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a.positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based ❑ on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMUIV (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 Umin. a. When tested in accordance with HVI Standard 916 4/13/2021 4:50 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the -capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections ❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. - ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40QF (4.M). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. ❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 4/13/2021 4:50 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5 F-1R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. ❑ R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. 0 R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. ❑ R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and -greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. ❑ R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 4/13/2021 4:50 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: OVERTON RESIDENCE Builder Name: Street: 0 N Old Dixie Highway Fort Pierce 34946 Parcel ID: 1 Permit Office: ST. LUCIE COUNTY City, State, Zip: FORT PIERCE, FL, 34946 Permit Number: Y U Owner: Jurisdiction: w Design Location: FL, VERO_BEACH_MUNICIPAL ARPT v COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in an dropped ceiling/soffit y pp g /soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/door jambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace wall . Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac 3s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring . and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind popmno and wiring. Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire snrunkler cover i2latp.,; and walls or cplfinos. a. In addition, inspection of log walls shall be in accordance with the provisions -of [CC-400. 4/13/2021 4:51 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: Permit #: Job Information, Builder: Community: Lot: NA Address: 0 N Old Dixie Highway Fort Pierce 34946 Parcel ID: 1408-703-0050-000-8 City: FORT PIERCE State: FL Zip: 34946 Air Leakage Ust ReSUIf$. Passing results must meet either the Performance, Prescriptive, or ERI Method O PRESCMPTIVE'METHOD-The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes per hour at a pressure, of 0.2 inch w.g. {50 Pascals) in Climate Zones 1 and 2. O PERFORMANCE or ERI METHOD -The building,(* dwelling unit shall be tested and:verified as having. an air leakage Cate of not exceeding the'selbeted ACH(50) value, as showrion Form R405-2020 (Performance) or'R406-2020 (ERI); section labeled as infiltration, sub -section ACH50:, ACH(50) specified on Form R405=2020-Energy Calc;(Performance) or R406-2020'(ERI) 7.000 x 60 24256 = Method for calculatinq building volume: CFM(50) Building Volume. ACH(50) O Retrieved from architectural plans ❑ PASS Code 40 software calculated When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(0, (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall. be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for -continuous ventilation systems and heat recovery ventilators shall be closed and sealed: 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 4/13/2021 4:51:09 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 -�- wrightsoft® Manual S Compliance Report.. Entire House Project Information Job: Date: Mar 15, 2621 By. For: OVERTON RESIDENCE 0 N. DIXIE HIGHWAY Parcel ID: 1408-703-0050-000-8, FORT PIERCE, FL 34946 Design Conditions Outdoor design DB: 90.4°F Sensible gain: 25087 Btuh Entering coil DB: . 72:3°F Outdoor design WB: 77.40F Latentgain: 8903 Btuh Entering coil WB: 60.8°F Indoor design DB: 72.0°F Total gain: 33991 Btuh IndoorRH: 50% Estimated airflow: 1075 ch Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Trane Model: 4TTR6042J1+4TXCD008DS3+S9X2D120U5PSB Actual airflow: 1075 cfm Sensible capacity: 28813 Btuh 115%of load Latent capacity: 9378 Btuh 105% of load Total capacity: 38191 Btuh 112%ofload SHR: 75% Heating Equipment Design: Conditions Outdoor design DB: 41.0°F Heat loss: 30200 Btuh Entering coil DB: 69.7°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Manufacturer: Actual airflow: Output capacity: Elec strip Model: 1075 cfm 8.1 kW 92% of load Meets all requirements ofACCA Manual S. Temp. rise: 50 OF -*- wrightsoft°' 2021-Apr-1316:46:56 nr+neN�e.�m2ww,.mcmmw�r IZgtt-Sute®Uriversal202121.0.05RSU29964 A Page 1 ...DoamerdslWrigFAsoftHVAC\OVERTONRESIDENCE.rup Ca1c=MJ8 FrontDoorfaces: E Load Short Form Job: wrightsoft® Date: Mar 15, 2021 Entire House By. Project Information For: OVERTON RESIDENCE 0 N. DIXIE HIGHWAY Parcel ID:1408-703-0050-000-8, FORT PIERCE, FL 34946 Design Information Htg Clg Infiltration Outside db (°F) 41 90 Method Simplified Inside db (°F) 70 72 Construction quality Average Design TD (°F) 29 18 Fireplaces 0 Dailyrange - L Inside humidity (%) 30 50 Moisture difference (grAb) 2 63 HEATING EQUIPMENT Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat 100 EFF 8.1 kW 27637 Btuh 23 °F 1075 cfrn 0.036 cfm/Btuh 0 in H2O COOLING EQUIPMENT Make Trane Trade TRANE Cond 4TTR6042J1 Coil 4TXCD008DS3+S9X2D120U5PSB AHRI ref 204378552 Efficiency 14.0 EER, 16.5 SEER Sensible cooling Latent cooling Total cooling Actual airflow Air flow factor Static pressure Load sensible heat ratio 31234 Btuh 9766 Btuh 41000 Btuh 1075 cfm 0.043 cfm/Btuh 0 in H2O 0.74 ROOM NAME Area (ftz) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) CIgAVF (cfm) M WIC 1 58 1659 708 59 30 M WIC 2 53 997 487 35 21 MASTER BEDROOM 300 2670 2826 95 121 MASTER BATH 155 2409 1065 86 46 LAUNDRY 76 660 767 24 33 DINING 278 3572 4439 127 190 KITCHEN 213 2013 2540 72 109 BED 2 215 3716 2192 182 94 BED 3 220 2124 1837 76 79 GREAT ROOM 495 4450 3883 158 166 DEN 228 5067 3759 180 161 RA-rW 7 oa Or,) raG 1�1 7r, Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -*- wrightsoft® 2021 -Apr-1 3 16:46:56 ti •NRokyMhshiroWNa+ryCanpM Right-Sate®Urrversal202121.0.05RSU29964 Page 1 +�...Doamerts\WrigtdsoftHVAC10VERTONRESIDENCE.np Calc=MJ8 Frort Door fares: E Entire House 2377 30200 25087 1075 1075 Other equip loads 0 0 Equip. @ 0.95 RSM 23933 Latent cool i ng 8903 TnTAI C 01:= 2n7nn 1 7001)7 4 n71Z 4 rn-7c Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wlrightsoft® 2021-Apr-1316:46:56 j, urt•[vo.mnwwm: ycomwro Right-SUte®Uriversal2021 21.0.05 RSU29964 Page 2 Doamer6s\Wrightmft,WAC\OVERTONRESIDENCE.rup Calc=MJ8 FrortDoorfaces: E £LT8LSTHS 895L69T8H y•T•T A £ 3o T gibed ova '£00.9-Hb9 :Pegvaodsooul (pasn aq qou Aam goTgm suoi,4ipa snoieasd Tta 8949TosgO) 60/80 '9T04 Ha EZOZ/60/ZO ::amva Holsvulaxs 6ZOZ/60/80 :asnssl ssva ZGtm4u0X a OOTH aHo elonl -is so�ossquoo a®� II 4siTeio9dS Te4u6mu0aTAu3 :HZSIS :IS allAOU8aV sagseyz : H'IZIS s?Ava ue-rae : xg SHOIZKoIaloadS u H H •pd6 0017 S jo Mog pejewi;sa je}o} a jo} '(woapaq jad Z) suosled 9 jo Aouedn000 wnwixew a gjinn swoojpeq g jo; pezis si walsAs a41 O SHHOxI [ ] : aaamftu NOISKAKoxa SHHOMI [ 00"0 ] : aHUInbza 'IZIa a z xxiod HONHUH3Hu/?I2iFiNIIiONHS MOZHS HAOeV ] [ S3 SHHONI ] 100'ZI? ] as oS aZHI3NIKUa ao NoSSoH H SNIOa ZAOSK ] [ Z3 SHHONI ] 100'Z6 ] HSIs DIHSSxs aasoaoua LEO NOISKAH'IH I •auil Apedad ]sane aqj @n •jQ jagnH 10 8uilJa]u90 :?lUKDI ORMI ao NolsKoo'I a N [ ] aHfi [x] HONHus [ ] :NOISKuwIaNO0 I MMOR [ ] aaarma [ ] mmaNKSS [xl :LZHSSIS Haxs K LIHSSIS V/N lzaa HUKnaS [ ] u DlHssxs MaN p189weIp ZHH3 HUKnaS [ L99 ] a [ ] sdmnd# saK bZ UHa SHSOQ[ 10 SNOZT39[ ] ISIOKaKo ?INKS emsoa maiwo [ ] x [SNouave om:?INKS Harms xsIoKaKo xmixvKl xSIoKHKo uoxaHouHSNI HSKHUJ moua u [ ] N ISIoKdKo V/N aas / SNOTIKJ [ ] K ISIoKdKo MaN al;aaS aaJ / SNOTIKJ [ 050' 4 ] S sNOISKoiai0Has a" miss LlHssxs xsuHdoud SIHS do SNHFIaozHAHa uoa aauInftu JNIiimaaa mmoz uo ' HSKZS l avuaaaa UZHso HIM RONV17CIKOO KOUd SNKOI'IaaK HHS idKaxa Sox SHOa SIxam sIHs ao HoNKnssl •aloA aNK ir= Havx 9NIHH mmaaa sim Ni S'Insau xvx SNOISKDiaiao➢I HonS NOISKOIZddK XiKaHa HHS x3Iaox Os SNKOI'IddK HHS Hulnftu 'SIDIUHa sIHs 3o Homissi uoa SISKfi K SK aHAuHS HOIHM ' SSova rivi'damVK NI H9NKH0 INK HGIIZ ao aondaa oI noH3S xNK doa HoNFimoadad xuoxoKasmvs HHSNKUKn9 SON SHOa N:amsxs ao TdnouddK mmmuKdaa •0•K•,3 '9-Hb9 aamcwHo aNK '•s•a 'S900'T8£ NOISoas ao SauKaNKSS aNK SNOISKoIai0Hds HIM H0NKau000K NI aHSonuSSNOo as ISM KSISIS [,chap= ai xvi do] [UZM,MN 'IHOUKa 'H9NKu 'dIHSNMOI 'NOISOHS] W?V M 4Md :# sNHranooa :# sa=HOHu :alKa HH3 :alKa HSKa 8-000-0900-EOL-80v6 :# ax IsuHaoua JoueWMMAMIij :NOISIAIaSns 8 :xooZs 6Z`OZ'66'86 :so'I 9b6K 1d 'aoJaid hod ftH aixia pl0 (181 :ssaaaaK IsuHaoua UuiJdnU NIeUUU : SNKOI'MdK MaN SalSO :Uoa slrauad HoIsonHISNoo 6u':Plwaa,4 ',A4uno:) aion� •1S 14 snd C�3/11�3O3�1 SIMSCI X01100MISN00 KHssas 'IKSOdSIa amv LxzKL%YztiL zemm HZISNO 999L691 dV : # NOISKoI'Iadv HsMMH 3o SNMHVCTHa 19L LSSZ-=IS-99 :# slmzcl vandoz3 ao HSKss NOTICE OF RIGHTS A party whose substantial interest is affected by this order may petition for an administrative hearing pursuant to sections 120.569 and 120.57, Florida Statutes. Such proceedings are governed by Rule 28-106, Florida Administrative Code. A petition for administrative hearing must be in writing and must be received by the Agency Clerk for the Department, within twenty-one (21) days from the receipt of this order. The address of the Agency Clerk is 4052 Bald Cypress Way, BIN A-02, Tallahassee, Florida 32399. The Agency Clerk's facsimile number is 850-413-8743. Mediation is not available as an alternative remedy. Your failure to submit a petition for hearing within 21 days from receipt of this order will constitute a waiver of your right to an administrative hearing, and this order shall become a 'final order'. Should this order become a final order, a party who is adversely affected by it is entitled to judicial review pursuant to Section 120.68, Florida Statutes. Review proceedings are governed by the Florida Rules of Appellate Procedure. Such proceedings may be commenced by filing one copy of a Notice of Appeal with the Agency Clerk of the Department of Health and a second copy, accompanied by the filing fees required by law, with the Court of Appeal in the appropriate District Court. The notice must be filed within 30 days of rendition of the final order. St. Lucie County Health Department Yf d 5150 NW Milner Dr Port Saint Lucie, FL 34983 HEALTH PAYING ON: #: 56-SF-2331767 BILL oOc #:56-BID-5414416 CONSTRUCTION APPLICATION #: AP1697568 RECEIVED FROM: Donald Overton AMOUNT PAID: $ 430.00 PAYMENT FORM: CREDIT CARD 00544 PAYMENT DATE: 07/15/2021 MAIL TO: Donald Overton FACILITY NAME: PROPERTY LOCATION: TBD Old Dixie Hwy Fort Pierce, FL 34946 Lot: 18,19,20,21 Block: B Property ID: 1408-703-0050-000-8 EXPLANATION or DESCRIPTION: 128 - OSTDS Construction System Inspection Research Fee -1 - Surcharge (All) -1 - OSTDS New Permit Surcharge -1 - OSTDS Construction Application and Plan Review,New 126 - OSTDS Construction Permit (New or Mod, Amendment) 127 - OSTDS Construction System Inspection 133 - OSTDS Construction Reinspection QUANTITY FEE 1 $ 5.00 1 $ 45.00 1 $ 100.00 1 $ 100.00 1 $ 55.00 1 $ 75.00 1 $ 50.00 RECEIVED BY: VanceMH AUDIT CONTROL NO. 66-PID-6089948 STATE : OF--, -D PERMIT19? TME Pr" AEALTFI PAT*PAID FS: 0 - fti-TE SEWAGE xTREATMENT AND DISPOSAL FEE PAID STEM."_ APPLICATION FOR C q9T]WbCk 'PRO: P.$1.4 TI& CREATED, "OR BE tOkStRi3j: 4viarvi-eW M I anor: kgoPoRTX ID .7 633 47M iolk'x PROPERTY SIZE ::8 ACRE$: -WATER -SUPPLY // :PRIVAT <c�20. QpD E, '3 >2 o',o v PF A Ir TEA * " ol.� ' T 60 DISTANCE PROPERTY N' '01d. DiXj�o. ,FL � 34.,94-6 MDO• btEq#1 Turn;TQ PPRkR No 37 `etea previous '6at-tp S.whidh .may .#qt be used)' Inoorp -04� pi;�L qd�'g Pip ..,Page 1 at, .4 STATE OF FLORIDA DEPARTMENT OF HEALTH ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEM APPLICATION FOR CONSTRUCTION PERMIT APPLICATION FOR: [X] New System [ ] Repair APPLICANT: Donald Overton AGENT: nnnald nvAOnn APP DOC # AP 1697568 PERMIT #: 56-SF-2331767 DATE PAID O7/15/2021 FEE PAID: 430.00 RECEIPT #:56-PID=508994 [ ] Existing System [ ] Holding Tank [ ] Innovative [ ] Abandonment [ ] Temporary I ] MAILING ADDRESS: 3406 SW Catskill Dr Port Saint Lucie, FL 34953 TELEPHONE: 1 (772) 261-1330 TO BE COMPLETED BY APPLICANT OR APPLICANT'S AUTHORIZED AGENT. SYSTEMS MUST BE CONSTRUCTED BY A PERSON LICENSED PURSUANT TO 489.105(3)(m) OR 489.552, FLORIDA STATUTES. IT IS THE APPLICANT'S REPONSIBILITY TO PROVIDE DOCUMENTATION OF THE DATE THE LOT WAS CREATED OR PLATTED (MM/DD/YY) IF REQUESTING CONSIDERATION OF STATUTORY GRANDFATHER PROVISIONS. LOT: 18,19,20,21 BLOCK: B SUBDIVISION: Riverview Manor PROPERTY ID # : 1408-703-0050-000-8 PLATTED: 09/01 /1955 ZONING: I/M OR EQUIVALENT: [ y 'I El PROPERTY SIZE: 0.80 ACRES WATER SUPPLY: [XI PRIVATE [ ]<=2000GPD [ 1>2000GPD IS SEWER AVAILABLE AS PER 381.0065, FS? [ Y ED DISTANCE TO SEWER: FT PROPERTY ADDRESS: TBD Old Dixie Hwy Fort Pierce, FL 34946 r DIRECTIONS TO PROPERTY: BUILDING INFORMATION: Type of Establishment [X] RESIDENTIAL No. of Bedrooms 3 [ ] COMMERCIAL Building # Persons Area Ft Served 2378 3 [ ] Floor/Equipment Drains [ ] Other (Specify) SIGNATURE: DH 4015, 08/09 (Obsoletes previous editions which may not be used) Incorporated 64E-6.001, FAC Total Design Flow For This Unit 400 DATE: 07/15/2021 Page 1 of 4 v 1.0.0 AP1697568 EID2331767 APP DOC #: AP1697568 STATE OF FLORIDA PERMIT NO. 56-SF-2331767 DEPARTMENT OF HEALTH ONSITE SEWAGE TREATMENT AND DISPOSAL DATE PAID: 07/15/2021 SYSTEM FEE PAID: 430.00 RECEIPT #: 56-PID-5089948 Additional Notes and Comments: County Notes Fields: Package Deal: Square Mile: General Comments: v 1.0.0 AP1697569 EID2331767 op4j- peow, eq uu-- 912- T xoxti-iaav, i T7 7 (UIDWS al rrysas-doa KZ-Z-TS; - .SRI RX". -6k` *�l I saw otussixx ONI-11 0 IM q (I" �011 M f MIS `Ma MLIVAT-12, docru- sm 'o r -*itit -6,T, Ims Ao 0ou 13 CAL., :tlav;toit -14. & a 4--a 44 '• s�Z%sIIQ:. y3Ycat32ills, ss PWIMOT1194" Pms1z" 14 77R 'ail �M" - am-noaa. V-du "a2monuissom'. Ila, S, Rio iia' i::?9 ,7 iqorxz I .rr isr OIL -smomm,'121-fi, 'SZX-, ymm"ziWes .3:' aoux lea. A-�(j ge 18 T; Od;-Md I VMU: . ;t' bra TiLTZ-1, M." AG '-MAAtim vallm%�Ill 30, 1 AUTHORIZED SEWAGE FLOW: UNOBSTRUCTED AREA AVAILABLE: STATE OF FLORIDA DEPARTMENT OF HEALTH ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEM SITE EVALUATION AND SYSTEM SPECIFICATION APPLICANT: Donald Overton CONTRACTOR / AGENT: Donald Overton LOT: 18,19,20.21 BLOCK: B APPLICATION # AP1697568 PERMIT # 56-SF-2331767 DOCUMENT # SF1578173 SUBDIVISION: Riverview Manor ID#: 1408-703-0050-000-8 TO BE COMPLETED BY ENGINEER, HEALTH DEPARTMENT EMPLOYEE, OR OTHER QUALIFIED PERSON. . ENGINEERS MUST PROVIDE REGISTRATION NUMBER AND SIGN AND SEAL EACH PAGE OF SUBMITTAL. COMPLETE ALL ITEMS. PROPERTY SIZE CONFORMS TO SITE PLAN: EX ]YES [ ]NO NET USABLE AREA AVAILABLE: 0.80 ACRES TOTAL ESTIMATED SEWAGE FLOW: 400 GALLONS PER DAY [ RESIDENCES -TABLET / OTHER -TABLE 2 ] 1200.00 GALLONS PER DAY [ 1500 GPD/ACRE OR 2500 GPD/ACRE ] 1500.00 SQFT UNOBSTRUCTED AREA REQUIRED: 1000.00 SQFT BENCHMARK/REFERENCE POINT LOCATION: Centerline of Huber Dr. @ the west property line. ELEVATION OF PROPOSED SYSTEM SITE 12.00 [ INCHES / FT ] [ ABOVE / BEL01 BENCHMARK/REFERENCE POINT THE MINIMUM SETBACK WHICH CAN BE MAINTAINED FROM THE PROPOSED SYSTEM TO THE FOLLOWING FEATURES SURFACE WATER: FT DITCHES/SWALES: FT NORMALLY WET: [ ]YES [X]NO WELLS: PUBLIC: FT LIMITED USE: FT PRIVATE: 96 FT NON -POTABLE: FT BUILDING FOUNDATIONS: 5 FT PROPERTY LINES: 29 FT POTABLE WATER LINES: 70 FT SITE SUBJECT TO FREQUENT FLOODING? [ ]YES [X]NO 10 YEAR FLOODING? [ ]YES [X]NO] 10 YEAR FLOOD ELEVATION FOR SITE: FT[ MSL / NGVD ] SITE ELEVATION: FT [ MSL / NGVD SOIL PROFILE INFORMATTON STTF. 1 ROTT. ARr17TT.R TNWARMATTAN CTTW. 9 USDA SOIL SERIES: Munsell #/Color Texture Depth 10YR 4/1 Sand 0 To 10 10YR 6/1 Sand 10 To 19 10YR 7/1 Sand 19 To 72 USDA SOIL SERIES: Munsell #/Color Texture Depth 10YR 4/1 Sand 0 To 5 10YR 6/1 Sand 5 To 22 10YR 7/1 Sand 22 To 57 10YR 5/3 Sand 57 To 72 OBSERVED WATER TABLE: 72.00 INCHES [ ABOVE / BELOW ] EXISTING GRADE TYPE: [ PERCHED / APPARENT ] ESTIMATED WET SEASON WATER TABLE ELEVATION: 72 INCHES [ ABOVE / BELOW ] EXISTING GRADE HIGH WATER TABLE VEGETATION: [ ]YES [X]NO MOTTLING: [ ]YES [X]NO DEPTH: INCHES SOIL TEXTURE/LOADING RATE FOR SYSTEM SIZING: Sand/0.60 DEPTH OF EXCAVATION: INCHES DRAINFIELD CONFIGURATION: [ ] TRENCH [XI BED [ ] OTHER (SPECIFY) r- REMARKS/ADDITIONAL CRITERIA No SHS indicators present. SITE EVALUATED BY: Davis, Brian (Title: Master Septic Tank Contractor) (Brian Davis Septic and Backhoe Se DR 4015, 08/09 (Obsoletes previous editions which may not be used) Incorporated: 64E-6.001, FAC DATE: 07/29/2021 Page 3 of 4 AP1697568 EID2331767 v 1.0.2