HomeMy WebLinkAboutProject InformationJob:
-�- wrightsoft® Manual S Compliance Report Date: Mar 15, 2021
Entire House R�IV�`�Y
AUG 2 _ ryC�l
ST. Lucie
n-
Project Information
For: OVERTON RESIDENCE
0 N. DIXIE HIGHWAY Parcel ID: 1408-703-0050-000-8, FORT PIERCE, FL 34946
Design Conditions
Outdoor design DB:
90.4°F
Outdoor design WB:
77.40F
Indoor design DB:
72:0°F_
Indoor RH:
50 %
Sensible gain:
25087
Btuh
Latentgain:
8903
Btuh
Total gain:.
33991
Btuh
Estimated airflow:
1075
cfm
Entering coil DB: 72.3°F
Entering coil WB: 60.8°F
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype:
SpIItAC
Manufacturer:
Trane
Model: 4TTR6042J1+4TXCD008DS3+S9X2D120U5PSB
Actual airflow:
107.5
cfm
Sensible capacity:
28813
Btuh
115% of load
Latent capacity:
9378
Btuh
105% of load
Total capacity:
38191
Btuh
112%ofload SHR: 75%
Design Conditions
Outdoor design DB: 41.0°F Heat loss: 30200 Btuh Entering coil DB: 69.7°F
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype: Elecstrip
Manufacturer: Model:
Actual airflow: 1075 cfm
Output capacity: 8.1 kW 92% of load Temp. rise: 50 °F
oQ,
1110 ov
Meets all requirements ofACCA Manual S.
wrightsofto 2021-Apr-1316:46:56
�� •r+rt.�•ie.n.nirowm..•vc•mwmi Rigtt-Stite® Uriversal 2021 21.0.05 RSU29964 Page 1
...DoamertsUrigNsoftWAC\OVERTONRESIDENCE.rup Calc=MA Frort Door faces: E
-�- wrightsoft® Load Short Form
Entire House
Job:
Date: Mar 15, 2021
By.
For: OVERTON RESIDENCE
0 N. DIXIE HIGHWAY Parcel ID: 1408-703-0050-000-8, FORT PIERCE, FL 34946
Htg
Cig
Infiltration
Outside db (°F)
41
90
Method
Simplified
Inside db (OF)
70
72
Construction quality
Average
Design TD (°F)
29
18
Fireplaces
0
Daily range
-
L
Inside humidity (%)
30
50
Moisture difference (grAb)
2
63
HEATING EQUIPMENT
COOLING EQUIPMENT
Make
Make Trane
Trade
Trade TRANE
Model
Cond 4TTR6042J1
AHRI ref
Coil 4TXCD008DS3+S9X2D120U5PSB
AHRI ref 204378552
Efficiency
100 EFF
Efficiency 14.0 EER, 16.5 SEER
Heating input
8.1
kW
Sensible cooling 31234
Btuh
Heating output
27637
Btuh
Latent cooling 9766
Btuh
Temperature rise
23
OF
Total cooling 41000
Btuh
Actual airflow
1075
cfm
Actual airflow 1075
cfm
Airflowfactor
0.036
cfm/Btuh
Airflowfactor 0.043
cfm/Btuh
Static pressure
0
in H2O
Static pressure 0
in H2O
Space thermostat
Load sensible heat ratio 0.74
ROOM NAME
Area
(ftz)
Htg load
(Btuh)
Clg load
(Btuh)
Htg AVF
(cfm)
CIgAVF
(cfm)
M WIC 1
58
1659
708
59
30
M WIC2
53
997
487
35
21
MASTER BEDROOM
300
2670
2826
95
121
MASTER BATH
155
2409
1065
86
46
LAUNDRY
76
660
767
24
33
DINING
278
3572
4439
127
190
KITCHEN
213
2013
2540
72
109
BED 2
215
3716
2192
132
94
BED 3
220
2124
1837
76
79
GREAT ROOM
495
4450
3883
158
166
DEN
228
5067
3759
180
161
RATt4 0
Qr
or-0
I r;Qr,
1 12.1
1)r^
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
- wrightsoft 2021-Apr-1316:46:56
•Mrtok•/o. 6w•wue.•��m>.y Right -Sate® Urrversal 202121.0.05 RSU29964 Page
ACM...DocunerlsUrigMsoftHVAC10VERTONRESIDENCE.rup Calc=MJ8 Frort Door faces: E
Entire House
2377
30200
25087
1075
1075
Other equip loads
0
0
Equip. @ 0.95 RSM
23933
Latent cool i ng
8903
-M-rAl c
r»nn
1100,27
-4m1Z
-imG
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
-*- wrightsoft® 2021-Apr-1316:46:56
^'�^ •Mn•veo.�ueww.,Y p.m Riglt-Site®Uriversal202121.0.05RSU29964
Page 2
...DoamerdslWriglIsoftHVAC\OVERTONRESIDENCE.np Cale =MJB Frort Door faces: E
- wrightsoft® Project Summary
Entire House
Job:
Date: Mar 15, 2021
By.
Project Information
For: OVERTON RESIDENCE
0 N. DIXIE HIGHWAY Parcel ID:1408-703-0050-000-8, FORT PIERCE, FL 34946
Notes:
Weather: St Lucie Co IntI,.FL, US
Winter
Design Conditions
Summer Design Conditions
Outside db
41 OF
Outside db
90
OF
Inside db
70 OF
Inside db
72
OF
Design TD
29 OF
Design TD
18
OF
Daily range
L
Relative humidity
50
%
Moisture difference
63
gr/Ib
Heating Summary
. Sensible Cooling Equipment Load Sizing
Structure
26921 Btuh
Structure
23036
Btuh
Ducts
3279 Btuh
Ducts
2052
Btuh
Central vent (0 cfm)
0 Btuh
Central vent (0 cfm)
0
Btuh
(none)
(none)
Humidification
0 Btuh
Blower
0
Btuh
Piping
0 Btuh
Equipment load
30200 Btuh
Use manufacturer's data
n
Rate/swingg multipplier
Equipmentsensibleload
0.95
Infiltration
23933
Btuh
Method
Simplified
Latent Cooling Equipment Load Sizing
Construction quality
Average
Fireplaces
0
Structure
6671
Btuh
Ducts
2232
Btuh
Central vent (0 cfm)
0
Btuh
Heatingg� cooling
(none)
Area (ftz)
2377 2377
Equipment latent load
8903
Btuh
Volume (fP)
24170 24170
Air changes/hour
0.32 0.16
Equipment Total Load (Sen+Lat)
32837
Btuh
Equiv AVF (cfm)
129 64
Req. total capacity at 0.76 SHR
2.6
ton
Heating Equipment Summary
Cooling Equipment Summary
Make
Make Trane
Trade
Trade TRANE
Model
Cond 4TTR6042J1
AHRI ref
Coil 4TXCD008DS3+S9X2D120U5PSB
AHRI ref 204378552
Efficiency
100 EFF
Efficiency 14.0 EER,16.5
SEER
Heating input
8.1 kW
Sensible cooling
31234
Btuh
Heating output
27637 Btuh
Latent cooling
9766
Btuh
Temperature rise
23 OF
Total cooling
41000
Btuh
Actual airflow
1075 cfm
Actual airflow
1075
cfm
Airflowfactor
0.036 cfm/Btuh
Airflowfactor
0.043
cfm/Btuh
Static pressure
0 in H2O
Static pressure
0
in H2O
Space thermostat
Load sensible heat ratio
0.74
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
ti. -Pp- =ightsoft- 2021-Apr-1316:46:56
11 •^*•+• ^� �^-+� P RigU-SJte®UNversal2021 21.0.05 RSU29964 Page 1
ACCDoameris0rigNsaftHVAC\OVERTONRESIDENCE.rup Calc=MA Frort Door faces: E
FORM R405-2020
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: OVERTON RESIDENCE
Builder Name:
Street: 0 N Old Dixie Highway Fort Pierce 34946 Parcel ID: 1
Permit Office: ST. LUCIE COUNTY
City, State, Zip: FORT PIERCE, FL, 34946
Permit Number:
Owner:
Jurisdiction:
Design Location: FL, VERO_BEACH_MUNICIPAL_ARPT
County: St. Lucie (Florida Climate Zone 2 )
1. New construction or existing New (From Plans)
10. Wall Type�2294.0 sqft.)
Insulation Area
2. Single family or multiple family Detached
a. Concrete Block - Ext Insul, Exterior
R=5.0 1972.80 ft2
b. Frame - Wood, Adjacent
R=11.0 321.22 ft2
3. Number of units, if multiple family 1
c. N/A
R= 2 ft
4. Number of Bedrooms 3
d. N/A
R= ft2
5. Is this a worst case? No
11. Ceiling Types (2378.0 sgft.)
Insulation Area
a. Roof Deck (Unvented)
R=30.0 2378.00 ft2
6. Conditioned floor area above grade (ft2) 2378
b. N/A
R= ft2
Conditioned floor area below grade (ft2) 0
c. N/A
R= ft2
7. Windows(229.7 sqft.) Description Area
12. Ducts
a. Sup: Main, Ret: Main, AH: Main
R ft2
6 646
a. U-Factor: Dbl, U=0.65 229.70 ft2
SHGC: SHGC=0.35
b. U-Factor: N/A ft2
13. Cooling systems
kBtu/hr Efficiency
SHGC:
a. Central Unit
41.0 SEER:16.50
c. U-Factor: N/A ft2
SHGC:
Area Weighted Average Overhang Depth: 4.821 ft.
14. Heating systems
kBtu/hr Efficiency
Area Weighted Average SHGC: 0.350
a. Electric Strip Heat
27.6 COP:1.00
8. Skylights Area
c. U-Factor:(AVG) N/A ft2
15. Hot water systems
SHGC(AVG): N/A
a. Electric
Cap: 80 gallons
9. Floor Types (2378.0 sqft.) Insulation Area
EF: 0.900
a. Slab -On -Grade Edge Insulation R=0.0 2378.00 ft2
b. Conservation features
b. N/A R= ft2
None
c. N/A R= ft2
16. Credits
Pstat
Glass/Floor Area: 0.097 Total Proposed Modified Loads: 68.32
PASS
Total Baseline Loads: 69.12
I hereby certify that the plans and specifications covered by
Review of the plans and011)
'"flu S?. ?�
this calculation are in compliance with the Florida Energy
specifications covered by this
� _ p
Code.
calculation indicates compliance
the Florida Energy Code.
,
with
q�u,:'�., •.;; :_",•.•, ,� .O
PREPARED BY:
Before construction is completed
DATE: 04/12/2021
this building will be inspected for
compliance with Section 553.908
a
I hereby certify that this building, as designed, is in compliance
Florida Statutes.
with the Florida Energy Code.
G'OD WE.
OWNER/AGENT:
BUILDING OFFICIAL:
DATE:
DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 7.00 ACH50 (R402.4.1.2).
4/13/2021 4:50 PM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 4
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title:
Building Type:
Owner Name:
# of Units:
Builder Name:
Permit Office:
Jurisdiction:
Family Type:
New/Existing:
Comment:
OVERTON RESIDENCE Bedrooms: 3
User Conditioned Area: 2378
Total Stories: 1
1 Worst Case: No
Rotate Angle: 0
ST. LUCIE COUNTY Cross Ventilation: No
Whole House Fan: No
Detached
New (From Plans)
Address Type: Street Address
Lot #
Block/Subdivision:
PlatBook:
Street: 0 N Old Dixie Highway
County: St. Lucie
City, State, Zip: FORT PIERCE,
FL, _ 34946
CLIMATE
/
V Design Location
Design Temp
TMY Site 97.5 % 2.5 %
Int Design Temp Heating Design Daily Temp
Winter Summer Degree Days Moisture Range
FL, VERO_BEACH. MUN FL_VERO_BEACH_MUNI 45 90
70 75 299 64 Medium
BLOCKS
Number
Name
Area Volume
1
Blocki
2378 24255.6
SPACES
Number
Name
Area Volume Kitchen Occupants
Bedrooms InfilID Finished Cooled Heated
1
Main
2378 24255.6 Yes 4
3 1 Yes Yes Yes
FLOORS
#
Floor Type
Space Perimeter R-Value
Area Tile Wood Carpet
1 Slab -On -Grade Edge Insulatio
Main 232.7 ft
2378 ft2 ---- 0 0 1
ROOF
/
#
Roof Gable Roof
Type Materials Area Area Color
Rad Solar SA Emitt Emitt Deck Pitch
Barr Absor. Tested Tested Insul. (deg)
1
Hip Composition shingles 2659 ft2 0 ft2 Medium
N 0.4 N 0.9 No. 30 26.57
ATTIC
V #
Type
Ventilation Vent Ratio (1 in)
Area RBS IRCC
1
Full attic
Unvented 0 2378 ft2 N N
CEILING
#
Ceiling Type
Space R-Value Ins Type Area Framing Frac Truss Type
1
Under Attic (Unvented)
Main 0 Blown
2378 ft2 0.1 Wood
4/13/2021 4:50 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 4
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
WALLS
#
C)rnt
Adjacent
To Wall TypeQ
Space Cavity Width Height
Sheathing Framing Solar
Below
1
N
Exterior Concrete Block - Ext Insul
Main
5 42 5 12
0 509.0 ft2
0
0 0.3
0
2
E
Exterior Concrete Block - Ext Insul
Main
5 34 5 12
0 413.0 ft2
0
0 0.3
0
3
S
Exterior Concrete Block - Ext Insul
Main
5 45 4 9
4 423.1 ft2
0
0 0.3
0
4
W
Exterior Concrete Block - Ext Insul
Main
5 67 3 9
4 627.7 ft2
0
0 0.3
0
5
-
Garage Frame - Wood
Main
11 34 5 9
4 321.2 ft2
0 0.25 0.3
0
WINDOWS
Orientation shown is the entered, Proposed orientation.
/
Wall
Overhang
V
#
Ornt ID Frame Panes NFRC
U-Factor SHGC Imp
Area Depth
Separation Int
Shade
Screening
1
n 1 Vinyl Double (Clear)
Yes
0.65 0.35 N
8.0 ft2 2 ft 0 in
1 ft 0 in
None
None
2
n 1 Vinyl Double (Clear)
Yes
0.65 0.35 N
30.0 ft2 2 ft 0 in
1 ft 0 in
None
None
3
N 1 Vinyl Double (Clear)
Yes
0:65 0.35 N
20.0 ft2 14 ft 0 in
0 ft 6 in
None
None
4
e 2 Vinyl Double (Clear)
Yes
0.65 0.35 N
7.0 ft2 _ 8 ft 0 in
1 ft 0 in
None
None
5
e 2 Vinyl Double (Clear)
Yes
0.65 0.35 N
30.0 ft2 2 ft 0 in
1 ft 0 in
None
None
6
e 2 Vinyl Double (Clear)
Yes
0.65 0.35 N
40.0 ft2 8 ft 0 in
1 ft 0 in
None
None
7
s 3 Vinyl Double (Clear)
Yes
0.65 0.35 N
8.0 ft2 2 ft 0 in
1 ft 0 in
None
None
8
s 3 Vinyl Double (Clear)
Yes
0.65 0.35 N
40.2 ft2 2 ft 0 in
1 ft 0 in
None
None
9
w 4 Vinyl Double (Clear)
Yes
0:65 0.35 N
10.5 ft2 14 ft 0 in
0 ft 6 in
None
None
10
W 4 Vinyl Double (Clear)
Yes
0.65 0.35 N
36.0 ft2 2 ft 0 in
1 ft 0 in
None
None
GARAGE
#
Floor Area Ceiling Area
Exposed Wall Perimeter
Avg. Wall Height
Exposed Wall Insulation
1
670 ft2 670 ft2
64 ft
9.3 ft
1
INFILTRATION
#
Scope
Method SLA
CFM 50 ELA EgLA ACH
ACH 50
1 Wholehouse Proposed ACH(50) .000453
2829.8 155.25 291.47 .1512
7
HEATING SYSTEM
#
System Type Subtype
Speed Efficiency
Capacity
Block
Ducts
1
Electric Strip Heat/ None
COP:1
27.64 kBtu/hr
1
sys#1
COOLING SYSTEM
#
System Type Subtype
Subtype Efficiency
Capacity Air Flow SHR
Block
Ducts
1
Central Unit/ Split
Sing[ SEER: 16.5 41 kBtu/hr
cfm 0.76
1
sys#1
4/13/2021 4:50 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 4
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
HOT WATER SYSTEM
# System Type SubType
Location
EF Cap
Use
SetPnt
Conservation
1 Electric None
Garage
0.9 80 gal
62.3 gal
120 deg
None
SOLAR HOT WATER SYSTEM
FSEC
Collector
Storage
Cert # Company Name
System Model # Collector Model
# Area
Volume
FEF
None None
ft2
DUCTS
---- Supply ----
=- Return ----
Air .
CFM 25
CFM25
HVAC #
# Location R-Value` Area
Location
Area Leakage Type
Handler
TOT
OUT
QN
RLF
Heat Cool
1 Main 6 646 ft2
Main
304 ft2. Default Leakage
Main
(Default)
(Default)
1 1
TEMPERATURES
Programable Thermostat: Y
Ceiling Fans:
Cool in Jan Feb rr ll Mar
Heating Jan HFeb [X] Mar
E
A r
APr f
Ma j Jun Jul
May Jun Jul
X Au
4 � Aug
Se
SeP
ri
r
[
Oct
Oct
Nov
f X} Nov
Dec
HDec
LX}
Ventin [ 11 Jan Feb [[[[[[X]]]]]] Mar
lX1
A r l
Ma Jun Jul
E
[ Au
Se
[[[XXX]]]
Oct
[Xl Nov
Dec
Thermostat Schedule: HERS 2006 Reference
Hours
Schedule Type 1
2
3
4 5 6
7
8
9.
10
11
12
Cooling (WD) AM 78
78
78
78 78 78
78
78
80
80
80
80
PM 80
80
78
78 78 78
78
78
78
78
78
78
Cooling (WEH) AM 78
78
78
78 78 78
78
78.
78
78
78
78
PM 78
78
78
78 78 78
78
78
78
78
78
78
Heating (WD) AM 66
66
66
66 66 68
68
68
68
68
68
68
PM 68
68
68
68 68 68
68
68
68
68
66
66
Heating (WEH) AM 66
66
. 66 .
66 66 .68
68
68
68
68
68
68
PM 68
68
68
68 68 68—.--68
68
68
68
66
66
MASS
Mass Type
Area
Thickness
Furniture Fraction
Space
Default 8 Ibs/s .ft.
0 ft2
0 ft
0.3
Main
4/13/2021 4:50 PM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 4
FORM R405-2020
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 99
The lower the EnergyPerformance Index, the more efficient the home.
0 N Old Dixie Highway Fort Pierce 34946 Parcel ID: 1408-703-0050-000-8, FORT PIERCE, FL, 34946
1. New construction or existing
New (From Plans)
10. Wall Type and Insulation
Insulation
Area
2. Single family or multiple family
Detached
a. Concrete Block - Ext Insul, Exterior
R=5.0
1972.80 ft2
b. Frame - Wood, Adjacent
R=11.0
321.22 ft2
3. Number of units, if multiple family
1
c. N/A
R=
ft2
4. Number of Bedrooms
3
d. N/A
R=
ft2
5. Is this a worst case?
No
11. Ceiling Type and insulation level
Insulation
Area
a. Roof Deck (Unvented)
R=30.0
2378.00 ft2
6. Conditioned floor area (ft2)
2378
b. N/A
R=
ft2
7. Windows- Description
Area
c'
_
z
a. U-Factor: Dbl, U=0.65
229.70 ft2
12. Ducts, location & insulation level
R ft2
a. Sup: Main, Ret: Main, AH: Main
6 646
SHGC: SHGC=0.35
b. U-Factor: N/A
ft2
SHGC:
13. Cooling systems
kBtu/hr
Efficiency
c. U-Factor: N/A
ft2
a. Central Unit
41.0 SEER:16.50
SHGC:
d. U-Factor: N/A
ft2
SHGC:
14. Heating systems
kBtu/hr
Efficiency
a. Electric Strip Heat
27.6
COP:1.00
Area Weighted Average Overhang Depth:
4.821 ft.
Area Weighted Average SHGC:
0.350
8. Skylights Description
Area
15. Hot water systems
Cap:
80 gallons
a. U-Factor(AVG): N/A
ft2
a. Electric
EF: 0.9
SHGC(AVG): N/A
b. Conservation features
9. Floor Types
Insulation
Area
None
a. Slab -On -Grade Edge Insulation
R=0.0
2378.00 ft2
Credits (Performance method)
Pstat
b. N/A
R=
ft2
c. N/A
R=
ft2
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code compliant features.
Builder Signature:
Address of New Home:
Date:
City/FL Zip:
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code,
Energy Conservation, contact the Florida Building Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
4/13/2021 4:50 PM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: 0 N Old Dixie Highway Fort Pierce 34946 Parcel ID: 1 Permit Number:
FORT PIERCE, FL, 34946
MANDATORY REQUIREMENTS - See individual code sections for full details.
V/
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and
R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third parry shall inspect all components and verify compliance.
❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL.127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
4/13/2021 4:50 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75• Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
R403:1 Controls. SECTION R403 SYSTEMS
❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
❑ R403.3.2.1 Sealed air. handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise
sealed during the test.
Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage On to the outside of less than 0.080 (where On =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
❑ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for
circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The
controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no
demand for hot water.
❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
4/13/2021 4:50 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
❑
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 31/2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
❑ R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 60oC).
❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water -heating systems to be turned off.
❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a.positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based
❑ on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design
conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other
factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMUIV
(CFM)
HRV or ERV
Any
1.2 cfm/watt
Any
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 Umin. a. When tested in accordance with HVI Standard 916
4/13/2021 4:50 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the -capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. -
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40QF (4.M).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
4/13/2021 4:50 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5
F-1R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
❑ R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
0 R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
❑ R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements:
1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house
is less than 75 pints/day and -greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
❑ R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13,
conform to the following requirements:
1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct.
3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
4/13/2021 4:50 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5
2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: OVERTON RESIDENCE Builder Name:
Street: 0 N Old Dixie Highway Fort Pierce 34946 Parcel ID: 1 Permit Office: ST. LUCIE COUNTY
City, State, Zip: FORT PIERCE, FL, 34946 Permit Number:
Y
U
Owner: Jurisdiction:
w
Design Location: FL, VERO_BEACH_MUNICIPAL ARPT
v
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
Breaks or joints in the air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in an dropped ceiling/soffit
y pp g /soffit
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/door jambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
above -garage
subfloor decking, or floor framing cavity insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace wall
.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
3s.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the finished surface.
thermal envelope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
.
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
extend behind popmno and wiring.
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire snrunkler cover i2latp.,; and walls or cplfinos.
a. In addition, inspection of log walls shall be in accordance with the provisions -of [CC-400.
4/13/2021 4:51 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction:
Permit #:
Job Information,
Builder: Community: Lot: NA
Address: 0 N Old Dixie Highway Fort Pierce 34946 Parcel ID: 1408-703-0050-000-8
City: FORT PIERCE State: FL Zip: 34946
Air Leakage Ust ReSUIf$. Passing results must meet either the Performance, Prescriptive, or ERI Method
O PRESCMPTIVE'METHOD-The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air
changes per hour at a pressure, of 0.2 inch w.g. {50 Pascals) in Climate Zones 1 and 2.
O PERFORMANCE or ERI METHOD -The building,(* dwelling unit shall be tested and:verified as having. an air leakage Cate of not exceeding
the'selbeted ACH(50) value, as showrion Form R405-2020 (Performance) or'R406-2020 (ERI); section labeled as infiltration, sub -section ACH50:,
ACH(50) specified on Form R405=2020-Energy Calc;(Performance) or R406-2020'(ERI) 7.000
x 60 24256 = Method for calculatinq building volume:
CFM(50) Building Volume. ACH(50) O Retrieved from architectural plans
❑ PASS Code
40 software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals).
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(0, (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall. be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for -continuous ventilation systems and heat recovery ventilators shall be closed and sealed:
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
4/13/2021 4:51:09 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
-�- wrightsoft® Manual S Compliance Report..
Entire House
Project Information
Job:
Date: Mar 15, 2621
By.
For: OVERTON RESIDENCE
0 N. DIXIE HIGHWAY Parcel ID: 1408-703-0050-000-8, FORT PIERCE, FL 34946
Design Conditions
Outdoor design DB:
90.4°F
Sensible gain:
25087
Btuh Entering coil DB: . 72:3°F
Outdoor design WB:
77.40F
Latentgain:
8903
Btuh Entering coil WB: 60.8°F
Indoor design DB:
72.0°F
Total gain:
33991
Btuh
IndoorRH:
50%
Estimated airflow:
1075
ch
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype:
SplitAC
Manufacturer:
Trane
Model: 4TTR6042J1+4TXCD008DS3+S9X2D120U5PSB
Actual airflow:
1075
cfm
Sensible capacity:
28813
Btuh
115%of load
Latent capacity:
9378
Btuh
105% of load
Total capacity:
38191
Btuh
112%ofload SHR: 75%
Heating Equipment
Design: Conditions
Outdoor design DB:
41.0°F
Heat loss: 30200 Btuh Entering coil DB: 69.7°F
Indoor design DB:
70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type:
Manufacturer:
Actual airflow:
Output capacity:
Elec strip
Model:
1075 cfm
8.1 kW 92% of load
Meets all requirements ofACCA Manual S.
Temp. rise: 50 OF
-*- wrightsoft°' 2021-Apr-1316:46:56
nr+neN�e.�m2ww,.mcmmw�r IZgtt-Sute®Uriversal202121.0.05RSU29964
A Page 1
...DoamerdslWrigFAsoftHVAC\OVERTONRESIDENCE.rup Ca1c=MJ8 FrontDoorfaces: E
Load Short Form Job:
wrightsoft® Date: Mar 15, 2021
Entire House By.
Project Information
For: OVERTON RESIDENCE
0 N. DIXIE HIGHWAY Parcel ID:1408-703-0050-000-8, FORT PIERCE, FL 34946
Design Information
Htg Clg Infiltration
Outside db (°F) 41 90 Method Simplified
Inside db (°F) 70 72 Construction quality Average
Design TD (°F) 29 18 Fireplaces 0
Dailyrange - L
Inside humidity (%) 30 50
Moisture difference (grAb) 2 63
HEATING EQUIPMENT
Make
Trade
Model
AHRI ref
Efficiency
Heating input
Heating output
Temperature rise
Actual airflow
Air flow factor
Static pressure
Space thermostat
100 EFF
8.1
kW
27637
Btuh
23
°F
1075
cfrn
0.036
cfm/Btuh
0
in H2O
COOLING EQUIPMENT
Make
Trane
Trade
TRANE
Cond
4TTR6042J1
Coil
4TXCD008DS3+S9X2D120U5PSB
AHRI ref
204378552
Efficiency
14.0 EER, 16.5 SEER
Sensible cooling
Latent cooling
Total cooling
Actual airflow
Air flow factor
Static pressure
Load sensible heat ratio
31234
Btuh
9766
Btuh
41000
Btuh
1075
cfm
0.043
cfm/Btuh
0
in H2O
0.74
ROOM NAME
Area
(ftz)
Htg load
(Btuh)
Clg load
(Btuh)
Htg AVF
(cfm)
CIgAVF
(cfm)
M WIC 1
58
1659
708
59
30
M WIC 2
53
997
487
35
21
MASTER BEDROOM
300
2670
2826
95
121
MASTER BATH
155
2409
1065
86
46
LAUNDRY
76
660
767
24
33
DINING
278
3572
4439
127
190
KITCHEN
213
2013
2540
72
109
BED 2
215
3716
2192
182
94
BED 3
220
2124
1837
76
79
GREAT ROOM
495
4450
3883
158
166
DEN
228
5067
3759
180
161
RA-rW 7
oa
Or,)
raG
1�1
7r,
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
-*- wrightsoft® 2021 -Apr-1 3 16:46:56
ti •NRokyMhshiroWNa+ryCanpM Right-Sate®Urrversal202121.0.05RSU29964
Page 1
+�...Doamerts\WrigtdsoftHVAC10VERTONRESIDENCE.np Calc=MJ8 Frort Door fares: E
Entire House
2377
30200
25087
1075
1075
Other equip loads
0
0
Equip. @ 0.95 RSM
23933
Latent cool i ng
8903
TnTAI C
01:=
2n7nn
1 7001)7
4 n71Z
4 rn-7c
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
wlrightsoft®
2021-Apr-1316:46:56
j, urt•[vo.mnwwm: ycomwro Right-SUte®Uriversal2021 21.0.05 RSU29964 Page 2
Doamer6s\Wrightmft,WAC\OVERTONRESIDENCE.rup Calc=MJ8 FrortDoorfaces: E
£LT8LSTHS 895L69T8H y•T•T A
£ 3o T gibed ova '£00.9-Hb9 :Pegvaodsooul
(pasn aq qou Aam goTgm suoi,4ipa snoieasd Tta 8949TosgO) 60/80 '9T04 Ha
EZOZ/60/ZO ::amva Holsvulaxs 6ZOZ/60/80 :asnssl ssva
ZGtm4u0X a OOTH
aHo elonl -is
so�ossquoo
a®�
II 4siTeio9dS Te4u6mu0aTAu3 :HZSIS :IS allAOU8aV
sagseyz : H'IZIS s?Ava ue-rae : xg SHOIZKoIaloadS
u
H
H
•pd6 0017
S
jo Mog pejewi;sa je}o} a jo} '(woapaq jad Z) suosled 9 jo Aouedn000 wnwixew
a gjinn swoojpeq g jo; pezis si walsAs a41
O
SHHOxI [
] : aaamftu NOISKAKoxa
SHHOMI [ 00"0 ] : aHUInbza 'IZIa a
z
xxiod HONHUH3Hu/?I2iFiNIIiONHS MOZHS
HAOeV ] [ S3 SHHONI ] 100'ZI? ]
as oS aZHI3NIKUa ao NoSSoH H
SNIOa
ZAOSK ] [ Z3
SHHONI ] 100'Z6 ]
HSIs DIHSSxs aasoaoua LEO NOISKAH'IH I
•auil Apedad ]sane aqj @n •jQ jagnH 10 8uilJa]u90 :?lUKDI ORMI ao NolsKoo'I a
N
[ ] aHfi [x] HONHus [ ] :NOISKuwIaNO0 I
MMOR [ ] aaarma [ ] mmaNKSS [xl :LZHSSIS Haxs K
LIHSSIS V/N lzaa HUKnaS [ ] u
DlHssxs MaN p189weIp ZHH3 HUKnaS [ L99 ] a
[ ] sdmnd# saK bZ UHa SHSOQ[ 10 SNOZT39[ ] ISIOKaKo ?INKS emsoa maiwo [ ] x
[SNouave om:?INKS Harms xsIoKaKo xmixvKl xSIoKHKo uoxaHouHSNI HSKHUJ moua u [ ] N
ISIoKdKo V/N aas / SNOTIKJ [ ] K
ISIoKdKo MaN al;aaS aaJ / SNOTIKJ [ 050' 4 ] S
sNOISKoiai0Has a" miss LlHssxs
xsuHdoud SIHS do SNHFIaozHAHa uoa aauInftu JNIiimaaa mmoz uo ' HSKZS
l avuaaaa UZHso HIM RONV17CIKOO KOUd SNKOI'IaaK HHS idKaxa Sox SHOa SIxam sIHs ao HoNKnssl
•aloA aNK ir= Havx 9NIHH mmaaa sim Ni S'Insau xvx SNOISKDiaiao➢I HonS NOISKOIZddK XiKaHa
HHS x3Iaox Os SNKOI'IddK HHS Hulnftu 'SIDIUHa sIHs 3o Homissi uoa SISKfi K SK aHAuHS HOIHM
' SSova rivi'damVK NI H9NKH0 INK HGIIZ ao aondaa oI noH3S xNK doa HoNFimoadad xuoxoKasmvs
HHSNKUKn9 SON SHOa N:amsxs ao TdnouddK mmmuKdaa •0•K•,3 '9-Hb9 aamcwHo aNK '•s•a 'S900'T8£
NOISoas ao SauKaNKSS aNK SNOISKoIai0Hds HIM H0NKau000K NI aHSonuSSNOo as ISM KSISIS
[,chap= ai xvi do]
[UZM,MN 'IHOUKa 'H9NKu 'dIHSNMOI 'NOISOHS]
W?V M 4Md :# sNHranooa
:# sa=HOHu
:alKa HH3
:alKa HSKa
8-000-0900-EOL-80v6 :# ax IsuHaoua
JoueWMMAMIij :NOISIAIaSns 8 :xooZs 6Z`OZ'66'86 :so'I
9b6K 1d 'aoJaid hod ftH aixia pl0 (181 :ssaaaaK IsuHaoua
UuiJdnU NIeUUU : SNKOI'MdK
MaN SalSO :Uoa slrauad HoIsonHISNoo
6u':Plwaa,4 ',A4uno:) aion� •1S
14 snd
C�3/11�3O3�1 SIMSCI X01100MISN00
KHssas
'IKSOdSIa amv LxzKL%YztiL zemm HZISNO
999L691 dV : # NOISKoI'Iadv HsMMH 3o SNMHVCTHa
19L LSSZ-=IS-99 :# slmzcl vandoz3 ao HSKss
NOTICE OF RIGHTS
A party whose substantial interest is affected by this order may petition for an
administrative hearing pursuant to sections 120.569 and 120.57, Florida Statutes. Such
proceedings are governed by Rule 28-106, Florida Administrative Code. A petition for
administrative hearing must be in writing and must be received by the Agency Clerk for the
Department, within twenty-one (21) days from the receipt of this order. The address of the
Agency Clerk is 4052 Bald Cypress Way, BIN A-02, Tallahassee, Florida 32399. The Agency
Clerk's facsimile number is 850-413-8743.
Mediation is not available as an alternative remedy.
Your failure to submit a petition for hearing within 21 days from receipt of this order will
constitute a waiver of your right to an administrative hearing, and this order shall become a 'final
order'.
Should this order become a final order, a party who is adversely affected by it is entitled
to judicial review pursuant to Section 120.68, Florida Statutes. Review proceedings are
governed by the Florida Rules of Appellate Procedure. Such proceedings may be commenced
by filing one copy of a Notice of Appeal with the Agency Clerk of the Department of Health and a
second copy, accompanied by the filing fees required by law, with the Court of Appeal in the
appropriate District Court. The notice must be filed within 30 days of rendition of the final order.
St. Lucie County Health Department
Yf d 5150 NW Milner Dr Port Saint Lucie, FL 34983
HEALTH
PAYING ON: #: 56-SF-2331767 BILL oOc #:56-BID-5414416 CONSTRUCTION APPLICATION #: AP1697568
RECEIVED FROM: Donald Overton AMOUNT PAID: $ 430.00
PAYMENT FORM: CREDIT CARD 00544 PAYMENT DATE: 07/15/2021
MAIL TO: Donald Overton
FACILITY NAME:
PROPERTY LOCATION:
TBD Old Dixie Hwy
Fort Pierce, FL 34946
Lot:
18,19,20,21 Block: B
Property ID: 1408-703-0050-000-8
EXPLANATION or DESCRIPTION:
128 - OSTDS Construction System Inspection Research Fee
-1 - Surcharge (All)
-1 - OSTDS New Permit Surcharge
-1 - OSTDS Construction Application and Plan Review,New
126 - OSTDS Construction Permit (New or Mod, Amendment)
127 - OSTDS Construction System Inspection
133 - OSTDS Construction Reinspection
QUANTITY
FEE
1
$
5.00
1
$
45.00
1
$
100.00
1
$
100.00
1
$
55.00
1
$
75.00
1
$
50.00
RECEIVED BY: VanceMH AUDIT CONTROL NO. 66-PID-6089948
STATE : OF--, -D PERMIT19? TME Pr" AEALTFI PAT*PAID
FS:
0 - fti-TE SEWAGE xTREATMENT AND DISPOSAL FEE PAID
STEM."_
APPLICATION FOR C q9T]WbCk
'PRO: P.$1.4 TI&
CREATED, "OR
BE tOkStRi3j:
4viarvi-eW M I anor:
kgoPoRTX ID .7 633
47M iolk'x
PROPERTY SIZE ::8 ACRE$: -WATER -SUPPLY // :PRIVAT <c�20. QpD E, '3 >2 o',o
v PF
A Ir TEA * " ol.� ' T
60 DISTANCE
PROPERTY N' '01d. DiXj�o. ,FL � 34.,94-6
MDO•
btEq#1 Turn;TQ PPRkR
No
37
`etea previous '6at-tp S.whidh .may .#qt be used)'
Inoorp -04� pi;�L qd�'g
Pip
..,Page 1 at, .4
STATE OF FLORIDA
DEPARTMENT OF HEALTH
ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEM
APPLICATION FOR CONSTRUCTION PERMIT
APPLICATION FOR:
[X] New System
[ ] Repair
APPLICANT: Donald Overton
AGENT: nnnald nvAOnn
APP DOC # AP 1697568
PERMIT #: 56-SF-2331767
DATE PAID O7/15/2021
FEE PAID: 430.00
RECEIPT #:56-PID=508994
[ ] Existing System [ ] Holding Tank [ ] Innovative
[ ] Abandonment [ ] Temporary I ]
MAILING ADDRESS: 3406 SW Catskill Dr Port Saint Lucie, FL 34953
TELEPHONE: 1 (772) 261-1330
TO BE COMPLETED BY APPLICANT OR APPLICANT'S AUTHORIZED AGENT. SYSTEMS MUST BE CONSTRUCTED BY
A PERSON LICENSED PURSUANT TO 489.105(3)(m) OR 489.552, FLORIDA STATUTES. IT IS THE
APPLICANT'S REPONSIBILITY TO PROVIDE DOCUMENTATION OF THE DATE THE LOT WAS CREATED OR PLATTED
(MM/DD/YY) IF REQUESTING CONSIDERATION OF STATUTORY GRANDFATHER PROVISIONS.
LOT: 18,19,20,21 BLOCK: B
SUBDIVISION: Riverview Manor
PROPERTY ID # : 1408-703-0050-000-8
PLATTED: 09/01 /1955
ZONING: I/M OR EQUIVALENT: [ y 'I El
PROPERTY SIZE: 0.80 ACRES WATER SUPPLY: [XI PRIVATE [ ]<=2000GPD [ 1>2000GPD
IS SEWER AVAILABLE AS PER 381.0065, FS? [ Y ED DISTANCE TO SEWER: FT
PROPERTY ADDRESS: TBD Old Dixie Hwy Fort Pierce, FL 34946
r DIRECTIONS TO PROPERTY:
BUILDING INFORMATION:
Type of
Establishment
[X] RESIDENTIAL
No. of
Bedrooms
3
[ ] COMMERCIAL
Building # Persons
Area Ft Served
2378 3
[ ] Floor/Equipment Drains [ ] Other (Specify)
SIGNATURE:
DH 4015, 08/09 (Obsoletes previous editions which may not be used)
Incorporated 64E-6.001, FAC
Total Design Flow
For This Unit
400
DATE: 07/15/2021
Page 1 of 4
v 1.0.0 AP1697568
EID2331767
APP DOC #: AP1697568
STATE OF FLORIDA PERMIT NO. 56-SF-2331767
DEPARTMENT OF HEALTH
ONSITE SEWAGE TREATMENT AND DISPOSAL DATE PAID: 07/15/2021
SYSTEM FEE PAID: 430.00
RECEIPT #: 56-PID-5089948
Additional Notes and Comments:
County Notes Fields:
Package Deal:
Square Mile:
General Comments:
v 1.0.0 AP1697569 EID2331767
op4j- peow, eq uu--
912-
T xoxti-iaav, i
T7 7
(UIDWS al
rrysas-doa KZ-Z-TS; -
.SRI RX".
-6k` *�l I
saw otussixx
ONI-11 0 IM q
(I" �011
M
f MIS `Ma MLIVAT-12, docru- sm 'o r
-*itit -6,T, Ims
Ao 0ou
13 CAL., :tlav;toit -14. &
a
4--a
44
'• s�Z%sIIQ:. y3Ycat32ills,
ss PWIMOT1194" Pms1z"
14
77R 'ail �M" -
am-noaa. V-du "a2monuissom'. Ila, S,
Rio
iia'
i::?9 ,7
iqorxz I
.rr
isr OIL -smomm,'121-fi,
'SZX-, ymm"ziWes
.3:' aoux lea.
A-�(j ge 18
T;
Od;-Md I VMU: . ;t'
bra
TiLTZ-1, M." AG '-MAAtim
vallm%�Ill 30, 1
AUTHORIZED SEWAGE FLOW:
UNOBSTRUCTED AREA AVAILABLE:
STATE OF FLORIDA
DEPARTMENT OF HEALTH
ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEM
SITE EVALUATION AND SYSTEM SPECIFICATION
APPLICANT: Donald Overton
CONTRACTOR / AGENT: Donald Overton
LOT: 18,19,20.21 BLOCK: B
APPLICATION # AP1697568
PERMIT # 56-SF-2331767
DOCUMENT # SF1578173
SUBDIVISION: Riverview Manor ID#: 1408-703-0050-000-8
TO BE COMPLETED BY ENGINEER, HEALTH DEPARTMENT EMPLOYEE, OR OTHER QUALIFIED PERSON. . ENGINEERS MUST PROVIDE
REGISTRATION NUMBER AND SIGN AND SEAL EACH PAGE OF SUBMITTAL. COMPLETE ALL ITEMS.
PROPERTY SIZE CONFORMS TO SITE PLAN: EX ]YES [ ]NO NET USABLE AREA AVAILABLE: 0.80 ACRES
TOTAL ESTIMATED SEWAGE FLOW: 400 GALLONS PER DAY [ RESIDENCES -TABLET / OTHER -TABLE 2 ]
1200.00 GALLONS PER DAY [ 1500 GPD/ACRE OR 2500 GPD/ACRE ]
1500.00 SQFT UNOBSTRUCTED AREA REQUIRED: 1000.00 SQFT
BENCHMARK/REFERENCE POINT LOCATION: Centerline of Huber Dr. @ the west property line.
ELEVATION OF PROPOSED SYSTEM SITE 12.00 [ INCHES / FT ] [ ABOVE / BEL01
BENCHMARK/REFERENCE POINT
THE MINIMUM SETBACK WHICH CAN BE MAINTAINED FROM THE PROPOSED SYSTEM TO THE FOLLOWING FEATURES
SURFACE WATER: FT DITCHES/SWALES: FT NORMALLY WET: [ ]YES [X]NO
WELLS: PUBLIC: FT LIMITED USE: FT PRIVATE: 96 FT NON -POTABLE: FT
BUILDING FOUNDATIONS: 5 FT PROPERTY LINES: 29 FT POTABLE WATER LINES: 70 FT
SITE SUBJECT TO FREQUENT FLOODING? [ ]YES [X]NO 10 YEAR FLOODING? [ ]YES [X]NO]
10 YEAR FLOOD ELEVATION FOR SITE: FT[ MSL / NGVD ] SITE ELEVATION: FT [ MSL / NGVD
SOIL PROFILE INFORMATTON STTF. 1 ROTT. ARr17TT.R TNWARMATTAN CTTW. 9
USDA SOIL SERIES:
Munsell #/Color
Texture
Depth
10YR 4/1
Sand
0 To 10
10YR 6/1
Sand
10 To 19
10YR 7/1
Sand
19 To 72
USDA SOIL SERIES:
Munsell #/Color
Texture
Depth
10YR 4/1
Sand
0 To 5
10YR 6/1
Sand
5 To 22
10YR 7/1
Sand
22 To 57
10YR 5/3
Sand
57 To 72
OBSERVED WATER TABLE: 72.00 INCHES [ ABOVE / BELOW ] EXISTING GRADE TYPE: [ PERCHED / APPARENT ]
ESTIMATED WET SEASON WATER TABLE ELEVATION: 72 INCHES [ ABOVE / BELOW ] EXISTING GRADE
HIGH WATER TABLE VEGETATION: [ ]YES [X]NO MOTTLING: [ ]YES [X]NO DEPTH: INCHES
SOIL TEXTURE/LOADING RATE FOR SYSTEM SIZING: Sand/0.60 DEPTH OF EXCAVATION: INCHES
DRAINFIELD CONFIGURATION: [ ] TRENCH [XI BED [ ] OTHER (SPECIFY)
r- REMARKS/ADDITIONAL CRITERIA
No SHS indicators present.
SITE EVALUATED BY:
Davis, Brian (Title: Master Septic Tank Contractor) (Brian Davis Septic and Backhoe Se
DR 4015, 08/09 (Obsoletes previous editions which may not be used) Incorporated: 64E-6.001, FAC
DATE: 07/29/2021
Page 3 of 4
AP1697568 EID2331767 v 1.0.2