11345 U.S. Highway 1
Sebastian, FL. 32958
Orlando
723 Progress Way
Sanford, FL. 32771
Mailing
PO Box 78-1377
Sebastian, FL. 32978
Phone: 772-589-0712
C.A.# 5693
KSMengineering.net
KSM JOB #:219529-1d/JM/ah
NUC #215
Nuc Model:MC-1DR-P
Nuc Serial #:MD80404215
4801 Sunset Boulevard
Indian River Estates
Fort Pierce, Florida
Compacted Foundation Fill - 1st & 2nd Lifts
DEPTH PEN
READ
DRY
DENSITY
MAX. DRY
PROCTOR VALUE (P.C.F)
PERCENT
COMPACTION
1 S.E.12" - 24"14D 109.5 111.6 98.1%
2 Center "15D 111.2 "99.6%
3 N.W."15D 109.8 "98.4%
4 S.W.0" - 12"14D 109.0 "97.7%
5 N.E."15D 110.3 "98.8%
6 Center "15D 109.9 "98.5%
Proctor Optimum Moisture:
Proctor Max. Dry Density: P.C.F.
@ Test Locations the Density &
Penetrometer readings indicate the
Degree of Compaction Meets
11/18/2021
Email: St. Lucie County Building Department; mcarthuresther@bellsouth.net
PE # 68366
11.7%
12.0%
Respectfully Submitted:
Disclaimer:Contractor is responsible to maintain the tested area
in the condition that KSM completed the indicated passed
compaction test.KSM is not responsible if the tested area has
been altered from the approved inspected condition.
Proudly Serving Florida since 1990
Certified Women Owned Business - WBE
Minimum Requirement
Soil Description:
ITEM TESTED:
111.6
TEST LOCATION
OF SAMPLE
SOIL COMPACTION REPORT
ASTM D 1557 and ASTM D 6938
November 17, 2021DATE TESTED:
PERMIT #:
CONTRACTOR:R & E Loader
21050779
Julie E. Keller, P.E. President
Traces of Clay
for Staked Foundation
JOB LOCATION:
Test report shall not be reproduced, except in full, without the written approval of KSM Engineering & Testing