HomeMy WebLinkAboutAPPROVED TARPON FLATS- MANUAL JCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-30 15:40:24 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Job:Project Summary Sep 30, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information TARPON FLATSFor: 3937 SHORE SIDE DRIVE, FORT PIERCE, FL Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh35170 Struc ture Btuh27195 Ducts Btuh7383 Ducts Btuh4079 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh42553 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh29710 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh3521 Ducts Btuh2882 Central vent (0 cfm)Btuh0 CoolingHeating (none) 24332433Area (ft²)Equipment latent load Btuh6403 2262722627Volume (ft³) Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh36113 Equiv. AVF (cfm)60121 Req. total capacity at 0.70 SHR ton3.5 Heating Equipment Summary Cooling Equipment Summary Make Make Trane Trade Trade TRANE Model Cond 4TTR6042J1 AHRI ref Coil TEM4A0C42S41++TDR AHRI ref 8703699 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW12.8 Sensible cooling Btuh28700 Heating output Btuh43835 Latent cooling Btuh12300 Temperature rise °F29 Total cooling Btuh41000 Actual air flow cfm1367 Actual air flow cfm1367 Air flow factor cfm/Btuh0.032 Air flow factor cfm/Btuh0.044 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.83 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-30 15:40:24 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 30, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House MASTER BEDROOM 1 2 Exposed wall 258.5 ft 51.0 ft 3 Room height 9.3 ft 9.3 heat/coolft 4 Room dimensions ft316.0x1.0 5 Room area 2433.0 ft²316.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 586 494 1978 1081 186 186 745 407 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 20 0 364 300 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 72 0 1310 1079 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 80 70 281 154 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 10 0 182 269 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 177 99 395 216 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 20.3620.36 54 3 983 1099 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 9.509.50 24 24 437 228 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 369 333 1335 729 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 22.0722.07 36 15 655 794 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 400 363 1452 793 140 118 473 259 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 4 4 73 60 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 12 12 218 180 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 21 21 388 255 21 21 388 255 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 138 74 295 161 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 18 7 318 228 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 18 7 328 234 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 29 12 528 377 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 419 201 803 439 149 83 332 181 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.6532.65 24 1 437 784 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 27.5527.55 128 6 2330 3527 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 36 2 655 885 36 2 655 885 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 30 2 546 738 30 2 546 738 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 237 200 800 437 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 19 0 352 520 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 15.1415.14 18 0 328 273 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 2433 2433 3858 3329 316 316 501 432 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 2433 259 9829 0 316 51 1939 0 6 c) AED excursion 2533 579 Envelope loss/gain 31457 21700 5579 3736 12 a) Infiltration 3713 995 732 196 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 4500 0 Subtotal (lines 6 to 13)35170 27195 6311 3932 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 35170 27195 6311 3932 15 Duct loads 21%15%7383 4079 21%15%1325 590 Total room load 42553 31274 7636 4522 Air required (cfm)Air required (cfm)1367 1367 245 198 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-30 15:40:24 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 30, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC 1 M BATH 1 2 Exposed wall 6.0 ft 10.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft7.0x6.0 ft110.0x1.0 5 Room area 42.0 ft²110.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 56 56 223 122 93 57 228 125 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 36 0 655 540 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 20.3620.36 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 9.509.50 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 22.0722.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.6532.65 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 27.5527.55 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 15.1415.14 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 42 42 67 57 110 110 174 150 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 42 6 228 0 110 10 380 0 6 c) AED excursion -12 -61 Envelope loss/gain 518 168 1438 754 12 a) Infiltration 86 23 144 38 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 200 Subtotal (lines 6 to 13)604 191 1582 993 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 6 5 14 Subtotal 604 191 1588 998 15 Duct loads 21%15%127 29 21%15%333 150 Total room load 731 220 1921 1147 Air required (cfm)Air required (cfm)23 10 62 50 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-30 15:40:24 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 3 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 30, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M TOILET 1 CLST 4 2 Exposed wall 6.0 ft 0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft4.0x6.0 ft8.0x2.0 5 Room area 24.0 ft²16.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 56 46 183 100 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 10 0 182 150 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 20.3620.36 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 9.509.50 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 22.0722.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.6532.65 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 27.5527.55 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 15.1415.14 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 24 24 38 33 16 16 25 22 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 24 6 228 0 16 0 0 0 6 c) AED excursion -18 -1 Envelope loss/gain 632 265 25 21 12 a) Infiltration 86 23 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)718 288 25 21 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 3 2 -25 -21 14 Subtotal 720 290 0 0 15 Duct loads 21%15%151 44 21%15%0 0 Total room load 871 334 0 0 Air required (cfm)Air required (cfm)28 15 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-30 15:40:24 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 4 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 30, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 4 UTILITY RM 2 Exposed wall 13.0 ft 7.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft12.0x13.0 ft12.0x7.0 5 Room area 156.0 ft²84.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 121 85 340 186 65 55 221 121 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 10 0 182 150 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 36 0 655 540 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 20.3620.36 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 9.509.50 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 22.0722.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.6532.65 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 27.5527.55 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 15.1415.14 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 156 156 247 213 84 84 133 115 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 156 13 494 0 84 7 266 0 6 c) AED excursion -115 -58 Envelope loss/gain 1737 824 802 327 12 a) Infiltration 187 50 100 27 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1000 600 Subtotal (lines 6 to 13)1923 1874 902 954 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 39 31 10 8 14 Subtotal 1962 1906 912 962 15 Duct loads 21%15%412 286 21%15%191 144 Total room load 2374 2192 1103 1106 Air required (cfm)Air required (cfm)76 96 35 48 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-30 15:40:24 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 5 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 30, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name ENTRY HALL BATH 4 2 Exposed wall 0 ft 0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft72.0x1.0 ft10.0x6.0 5 Room area 72.0 ft²60.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 20.3620.36 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 9.509.50 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 22.0722.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.6532.65 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 27.5527.55 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 15.1415.14 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 72 72 114 99 60 60 95 82 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 72 0 0 0 60 0 0 0 6 c) AED excursion -6 -22 Envelope loss/gain 114 93 95 60 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 300 Subtotal (lines 6 to 13)114 93 95 360 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -114 -93 263 119 14 Subtotal 0 0 358 479 15 Duct loads 21%15%0 0 21%15%75 72 Total room load 0 0 434 551 Air required (cfm)Air required (cfm)0 0 14 24 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-30 15:40:24 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 6 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 30, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 3 KITCHEN/DINING 2 Exposed wall 7.0 ft 11.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft6.0x9.0 ft303.0x1.0 5 Room area 54.0 ft²303.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 20.3620.36 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 9.509.50 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 22.0722.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 65 61 245 134 47 35 138 75 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 4 4 73 60 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 12 12 218 180 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 56 32 127 70 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.6532.65 0 0 0 0 24 1 437 784 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 27.5527.55 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 15.1415.14 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 54 54 86 74 303 303 480 415 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 54 7 266 0 303 11 418 0 6 c) AED excursion -28 96 Envelope loss/gain 669 239 1819 1619 12 a) Infiltration 100 27 158 42 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 200 2200 Subtotal (lines 6 to 13)770 466 1977 3862 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 121 66 4 3 14 Subtotal 890 532 1981 3865 15 Duct loads 21%15%187 80 21%15%416 580 Total room load 1077 612 2397 4444 Air required (cfm)Air required (cfm)35 27 77 194 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-30 15:40:24 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 7 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 30, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name GREAT RM FOYER 2 Exposed wall 22.0 ft 6.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft19.0x20.0 ft6.0x12.0 5 Room area 380.0 ft²72.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 56 32 127 70 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 20.3620.36 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 9.509.50 0 0 0 0 24 24 437 228 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 22.0722.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 28 28 112 61 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 177 49 195 107 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.6532.65 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 27.5527.55 128 6 2330 3527 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 15.1415.14 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 380 380 603 520 72 72 114 99 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 380 22 837 0 72 6 228 0 6 c) AED excursion 1490 -24 Envelope loss/gain 4075 5704 906 372 12 a) Infiltration 316 85 86 23 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)4391 5789 993 395 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 462 164 -993 -395 14 Subtotal 4853 5952 0 0 15 Duct loads 21%15%1019 893 21%15%0 0 Total room load 5872 6845 0 0 Air required (cfm)Air required (cfm)189 299 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-30 15:40:24 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 8 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 30, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 3 CLST 3 2 Exposed wall 25.0 ft 2.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft151.0x1.0 ft9.0x2.0 5 Room area 151.0 ft²18.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 9 9 37 20 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 121 67 268 146 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 20.3620.36 54 3 983 1099 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 9.509.50 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 22.0722.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 102 102 410 224 19 19 74 41 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.6532.65 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 27.5527.55 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 15.1415.14 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 151 151 239 207 18 18 29 25 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 151 25 951 0 18 2 76 0 6 c) AED excursion 172 -4 Envelope loss/gain 2888 1869 179 61 12 a) Infiltration 359 96 29 8 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3246 1965 208 69 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 572 220 -208 -69 14 Subtotal 3819 2185 0 0 15 Duct loads 21%15%802 328 21%15%0 0 Total room load 4620 2513 0 0 Air required (cfm)Air required (cfm)148 110 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-30 15:40:24 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 9 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 30, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M HALL 2 MBATH 2 2 Exposed wall 4.0 ft 14.2 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft4.0x5.0 ft172.0x1.0 5 Room area 20.0 ft²172.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 20.3620.36 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 9.509.50 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 132 96 385 210 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 22.0722.07 0 0 0 0 36 15 655 794 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 37 37 149 81 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.6532.65 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 27.5527.55 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 15.1415.14 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 20 20 32 27 172 172 273 235 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 20 4 152 0 172 14 539 0 6 c) AED excursion -7 140 Envelope loss/gain 333 102 1852 1381 12 a) Infiltration 57 15 204 55 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)390 117 2056 1435 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -390 -117 111 33 14 Subtotal 0 0 2167 1469 15 Duct loads 21%15%0 0 21%15%455 220 Total room load 0 0 2622 1689 Air required (cfm)Air required (cfm)0 0 84 74 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-30 15:40:24 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 10 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 30, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M TOILET 2 MASTER BEDROOM 2 2 Exposed wall 10.0 ft 53.8 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft29.5x1.0 ft263.0x1.0 5 Room area 29.5 ft²263.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 nene 4.004.00 2.192.19 67 57 228 125 13 13 53 29 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nene 18.2018.20 26.8826.88 10 0 182 269 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 20.3620.36 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 9.509.50 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 26 26 105 58 112 112 448 245 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 22.0722.07 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 11.9311.93 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 swsw 4.004.00 2.192.19 0 0 0 0 138 74 295 161 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 18 7 318 228 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 18 7 328 234 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 swsw 18.2018.20 13.0113.01 0 0 0 0 29 12 528 377 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.6532.65 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 27.5527.55 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 24.5924.59 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 237 200 800 437 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 19 0 352 520 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 15.1415.14 0 0 0 0 18 0 328 273 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 30 30 47 40 263 263 417 360 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 30 10 380 0 263 54 2044 0 6 c) AED excursion -31 463 Envelope loss/gain 943 461 5910 3327 12 a) Infiltration 144 39 773 207 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1087 500 6683 3534 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 139 42 14 Subtotal 1087 500 6822 3575 15 Duct loads 21%15%228 75 21%15%1432 536 Total room load 1315 575 8254 4112 Air required (cfm)Air required (cfm)42 25 265 180 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-30 15:40:24 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 11 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Sep 30, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC 2 2 Exposed wall 10.6 ft 3 Room height 9.3 heat/coolft 4 Room dimensions ft90.5x1.0 5 Room area 90.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 .G 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 .G 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 .W 13A-4ocs 0.143 ne 4.00 2.19 0 0 0 0 11 G 2 glazing, clr low-e 0.650 ne 18.20 26.88 0 0 0 0 W 13A-4ocs 0.143 e 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 e 18.20 20.36 0 0 0 0 G 2 glazing, clr low-e 0.650 e 18.20 9.50 0 0 0 0 W 13A-4ocs 0.143 se 4.00 2.19 99 99 396 216 G 2 glazing, clr low-e 0.650 se 18.20 22.07 0 0 0 0 W 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 G 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 G 2 glazing, clr low-e 0.650 s 18.20 11.93 0 0 0 0 W 13A-4ocs 0.143 sw 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 sw 18.20 13.01 0 0 0 0 G 2 glazing, clr low-e 0.650 sw 18.20 13.01 0 0 0 0 G 2 glazing, clr low-e 0.650 sw 18.20 13.01 0 0 0 0 W 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 w 18.20 32.65 0 0 0 0 G 2 glazing, clr low-e 0.650 w 18.20 27.55 0 0 0 0 G 2 glazing, clr low-e 0.650 w 18.20 24.59 0 0 0 0 G 2 glazing, clr low-e 0.650 w 18.20 24.59 0 0 0 0 W 13A-4ocs 0.143 nw 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 nw 18.20 26.88 0 0 0 0 G 2 glazing, clr low-e 0.650 nw 18.20 15.14 0 0 0 0 C 16X19-0md 0.408 -1.59 1.37 91 91 143 124 F 22A-tph 1.358 -38.02 0.00 91 11 402 0 6 c) AED excursion -22 Envelope loss/gain 942 318 12 a) Infiltration 153 41 b) Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)1094 359 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 1094 359 15 Duct loads 21%15%230 54 Total room load 1324 413 Air required (cfm)43 18 2021-Sep-30 15:40:32 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Job:Duct System Summary Sep 30, 2021Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information TARPON FLATSFor: 3937 SHORE SIDE DRIVE, FORT PIERCE, FL CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm1367cfm1367 Total effective length (TEL)ft204 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st2115.012.1VlFx0x05.01.00027351077hBATH 3 st2115.016.7VlFx0x05.01.0002414551cBATH 4 st1115.048.0VlFx0x07.01.0001101484620hBEDROOM 3 st2115.012.4VlFx0x07.01.00096762192cBEDROOM 4 st1115.042.7VlFx0x08.01.000150943423cGREAT RM st1115.037.7VlFx0x08.01.000150943423cGREAT RM-A st4135.034.2VlFx0x07.01.00097382222cKITCHEN/DINING st4135.037.0VlFx0x07.01.00097382222cKITCHEN/DINING-A st4135.034.9VlFx0x06.01.00050621921hM BATH 1 st4135.036.0VlFx0x04.01.0001528871hM TOILET 1 st1115.040.5VlFx0x05.01.00025421315hM TOILET 2 st6155.045.1VlFx0x04.01.0001023731hM WIC 1 st3135.063.1VlFx0x04.01.00018431324hM WIC 2 st6155.049.2VlFx0x07.01.000991233818hMASTER BEDROOM 1 st6155.048.5VlFx0x07.01.000991233818hMASTER BEDROOM 1-A st3135.063.1VlFx0x08.01.0001802658254hMASTER BEDROOM 2 st1115.043.1VlFx0x06.01.00074842622hMBATH 2 st2115.013.9VlFx0x06.01.00048351106cUTILITY RM 2021-Sep-30 15:40:32 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 ...Wrightsoft HVAC\TARPON FLATS- SHORE SIDE DR.rup Calc = MJ8 Front Door faces: E Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st3 Peak AVF 308 198 1.000 881 8.0 0x0 VinlFlx st1 st1 Peak AVF 771 706 1.000 721 14.0 0x0 VinlFlx st6 Peak AVF 269 207 1.000 770 8.0 0x0 VinlFlx st4 st4 Peak AVF 435 466 1.000 594 12.0 0x0 VinlFlx st2 st2 Peak AVF 596 661 1.000 618 14.0 0x0 VinlFlx Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 13670 1367 0 0 0 0 x0 0 VlFx