HomeMy WebLinkAboutDuct LeakageDuct Leakage Test Report
Prescriptive or Performance Method
Permit #
Job Information
Builder: DR HORTON
Community: CREEKSIDE Lot: 107
Address: 9308 POTOMAC DRIVE Unit:
City: FORT PIERCE
State; FL Z7'P- 34945
Duct Leakage Test Results
0 Presciptive Method 0 Performance Method
System I cFM25 0 Prescriptive Method cfm25 (total)
System 2 To qualify as "substantially leak free" Qn must be less than or equal to 0.04
0fm2s if air handier unit is installed. If air handler unit is not installed, Qn Total
System 3 must be less than or equal to 0.03. This testing method meets the
Lfrn25 requirements in accordance with Section R403-2-2
Sum of any additional
systems
Total of all systems C) Performance Method dm25 (Out or Total)
cfm25 To qualify as "substantially leak free" Qn must not be greater than the
proposed duct leakage Qn specified on Form P,405-2014
40 1828 0.02 Qn
in
T Leakage Total of all systems Total Conditioned -q e Type selected On specified an Form
Square Footage on Form R4052014 R405-2014 (Energy Ca1c)
(Energy COW
PASS FAIL F— —__
Testing Company
Company Name: SUN SEAL LLC Phone: 321-412-0035
11 hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected
I
j compliance path as stated above, either the Prescriptive Method or Performance Method -
Date of Test: 11/15/2021
Signature of Tester:: 71-�
Printed Name of Tester:
License/Certification # —5066440—issuing AuthQrlty...B.PI...
1 � _Envelope Leakage Test Repo6l
FPermit 4
Job Information
Builder: DR HORTON Community:
CREEKSIDE Lot: 107
Address: 9308 POTOMAC DRIVE
Unit:
city: FORT PIERCE
State: EL zip: 34945
Air Leakage Test Results Passing results must be 7RCH(50) or less
1258 x fit} = 15720 = 4 Method for calculating building volume:
CEM(50) Building Volume ACH(50) 0 Retrieved from architectural plans
(Code software calculated
PASS jaf FAIL 0 Field measured and calculated
When ACH(50) is less than 3, Mechanical Ventilation installation must be verified by building department.
Certification of Test Results
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes
per hour in Climate Zones 1 and 2, 3 air changes per hour in Climate zones 3 through 8. Testing shall be conducted with a blower door at a
pressure of 0.2 inches w.g. (SO pascals). Testing shall be conducted by wither individuals as defined in Section 553.993(5) or (7), F.S. or
individuals licensed as set forth in Section 489.105(3)(f), (g), or (1) or an approved third party. A written report of the results of the test
shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of
of the pull
Testing Company
;Company Name: SUN SEAS_ LLC Phone: 321-412-0035
1I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected
compliance path as stated above, either the Prescriptive Method or Performance Method.
Date of Test: 11 /15/2021
Signature of Fester: 1
Printed Name of Tester: DA'IEL MURPHY
Lice nselcertif!cation 4 5055440 Issuing authority BPI