Loading...
HomeMy WebLinkAboutEnergy CodeFORM R405-2017 'a RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2017 Florida Building Code, Energy Conservation 'via the residential Simulated Performance Method shall include: ❑ This checklist ❑ A Form R405 report that documents that the Proposed Design complies with Section R405.3 of the Florida Energy Code. This form shall include a summary page indicating home address, a -ratio and the pass or fail status along with summary areas anblypes of components, whether the home was simulated as a worst -case orientation, name and version of the compliance software tool, name of individual completing the compliance report (one page) and an input summary checklist that can be used for field verification (usually four pages/may be greater). t_ ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO for the Performance Method: Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed Envelope Leakage Test Report (usually one page) ❑ If Form R405 duct leakage type indicates anything other than "default leakage" then a completed Form R405 Duct Leakage Test Report (usually one page) 8/13/2018 2:24.48 PM EnergyGauge® USA 6.0.02 (Rev. 1) - RaRes2017 FBC 6th Edition (2017) CompliayAre op Pa -gel - of 1 2017 EPL DISPLAY CARD ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 97 The lower the Energy Performance Index, the more efficient the home. 1. New home or, addition 1. New (From Plans) 12. Duds, location & insulation level a) Supply duds R 6.0 2. Single-family or multiple -family 2. Single-family b) Return duds R 6.0 c) AHU location 2nd Floor 3. No. of units (if multiple -family) 3. 1 4. Number of bedrooms 4. 2 13. Cooling system: Capacity 58.5 a) Split system SEER 16.0 5. Is this a worst case? (yes/no) 5. No b) Single package SEER c) Ground/watersource SEER/COP 6. Conditioned floor area (sq. ft.) 6. 2479 d) Room un'rt/PTAC EER 11.0 e) Other 7. Windows, type and area a) U-fador.(weighted average) 7a. 0.575 b) Solar Heat Gain Coefficient (SHGC) 7b. 0.300 14. Heating system: Capacity 58.0 c) Area 7c. 395.8 a) Split system heat pump HSPF 9.0 b) Single package heat pump HSPF 8. Skylights c) Electric resistance COP a) U-fador.(weighted average) 8a. NA d) Gas furnace, natural gas AFUE b) Solar Heat Gain Coefficient (SHGC) 8b. NA e) Gas furnace, LPG AFUE f) Other 5.80 9. Floor type, insulation level: a) Slab -on -grade (R-value) 9a. 0.0 b) Wood, raised (R value) 9b. 15. Water heating system c) Concrete, raised (R-value) Sr- a) Electric resistance EF 0.95 b) Gas fired, natural gas EF 10. Wall type and insulation: c) Gas fined, LPG EF A. Exterior. d) Solar system with tank EF 1. Wood frame (Insulation R-value) 10A1. e) Dedicated heat pump with tank EF 2. Masonry (Insulation R value) 10A2. 4.1 f) Heat recovery unit HeatRec% B. Adjacent: g) Other 1. Wood frame (Insulation R value) 10131. 2. Masonry (Insulation R-value) 1062. 16. HVAC credits claimed (PerformanceMethod) 11. Ceiling type and insulation level a) Ceiling fans Yes a) Under attic 11a. 30.0 b) Cross ventilation No b) Single assembly 11b. c) Whole house fan No c) Knee wallstskylight walls 11 c. d) Multizone cooling credit d) Radiant barrier installed 11d. No e) Multizone heating credit f) Programmable thermostat Yes *Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. I certify that this home has complied with the Florida Building Code, Energy Conservation, through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL display card will be completed based on installed code compliant features. Builder Signature: Date: Address of New Home: 581 Beach Avenue City/FL Zip: Port St Lucie, FL 34952 8/13/2018 2:25:28 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) t' oC"51ge 1 of 1 FORM R405-2017 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Yancy Residence EG Builder Name: Street: 581 Beach Avenue Permit Office: City, State, Zip: Port St. Lucie, FL , 34952 Permit Number Owner. Yancy Residence Jurisdiction: St. Lucie County Design Location: FL, ST LUCIE CO INTL County: St Lucie (Florida Climate Zone 2 ) 1. New construction or existing New (From Plans) 9. Wall Types (2426.0 sgfL) Insulation Area 2. Single family or multiple family Single-family a. Concrete Block - Int Insul, Exterior R=4.1 2262.00 ft2 b. Interior Frame - Wood, Interior R=11.0 164.00 ft2 3. Number of units, if multiple family 1 G WA R= ft2 4. Number of Bedrooms 2 d. WA R= ftz 10. Ceiling Types (2479.0 sgfL) Insulation. Area 5. Is this a worst case? No a. Under Attic (Vented) R=30.0 2479.00 ft2 6. Conditioned floor area above grade (ftz) 2479 b. WA R= ftz Conditioned floor area below grade (ft2) 0 c. N/A R= ft2 11. Duds R ftz 7. Windows(395.8 sqft.) Description Area a. Sup: Attic, Ret: Attic, AH: 2nd Floor 6 739 a. U-Factor: Dbl, U=0.45 235.33 ftz SHGC: SHGC=0.30 b. U-Factor. Dbl, U=0.76 120.94 ft2 12. Cooling systems kBtu/hr Efficiency SHGC: SHGC=0.30 a. Central Unit 46.5 SEER:16.00 b.'PTAC and Room Unit 12.0 EERA 1.00 c. U-Factor. Dbl, U=0.75 39.54 ftz SHGC: SHGC=0.30 13. Heating systems kBtuRv Efficiency d. U-Factor. WA f a. Electric Heat Pump 46.5 HSPF:9.00 SHGC: b. PTHP 11.5 COP:5.80 Area Weighted Average Overhang Depth: 3.639 ft. Area Weighted Average SHGC: 0.300 14. Hot water systems a. Electric Cap: 40gallonsEF: 8. Floor Types (2479.0 sgft.) Insulation Area 0.950 a. Slab -On -Grade Edge Insulation R=0.0 2479.00 ft2 b. Conservation features b. N/A R= ftz None c. N/A R= ft2 15. Credits CF, Pstat Total Proposed Modified Loads: 74.35 Glass/Floor Area: 0.160 PASS Total Baseline Loads: 76.26 �7�7 I hereby certify that the plans and specifications covered by Review of the plans and aF'TiBE S7,grF this calculation are in ce Florida Energy specifications covered by this__ _ , O ��, Code. calculation indicates compliance �',',.o�.��\ with the Florida Energy Code. � F lrrer,''y;'.•;;.�. „ O� PREPARED BY: DATE: Before construction is completed this building will be inspected for v� a compliance with Section 553.908 I hereby certify that this building, as designed, is in compliance Florida Statutes. with the Florida Energy CttL'-� OWNER/AG BUILDING OFFICIAL: DATE: 2�v DATE: - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory -sealed in accordance with R403.3.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402A.1.2). - Compliance with a proposed duct leakage Qn requires a Duct Leakage Test Report confirming duct leakage to outdoors, tested in accordance with ANSI1RESNETACC 380, is not greater than 0.030 Qn for whole house. 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 6 File Copy FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT PROJECT Title: Yancy Residence EG Bedrooms: 2 Address Type: Street Address Building Type: User Conditioned Area: 2479 Lot # Owner Name: Yancy Residence Total Stories: 1 Block/Subdivision: ' # of Units: 1 Worst Case: No PlatBook: Builder Name: Rotate Angle: 270 Street: 581 Beach Avenue Permit Office: Cross Ventilation: No County: St. Lucie Jurisdiction: St Lucie County Whole House Fan: No City, State, Zip: Port St. Lucie , Family Type: Single-family FL, 34952 New/Existing: New (From Plans) Comment: CLIMATE Design Temp Int Design Temp Heating Design Daily Temp Design Location TMY Site 97.5 °% 2.5 °% Winter Summer Degree Days Moisture Range FL, ST LUCIE_CO INTL FL VERO BEACH_MUNI 39 90 70 75 299 58 Medium BLOCKS Number Name Area Volume 1 AHU1 1852 14816 2 AHU2 627 5016 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated 1 2nd Floor 130 1040 No 0 1 Yes Yes Yes 2 RR KITCHEN 162 1296 Yes 1 1 Yes Yes Yes 3 OFFICE 78 624 No 0 1 Yes Yes Yes 4 ENTRY 117 936 No 0 1 Yes Yes Yes 5 CMD 23 184 No 0 1 Yes Yes Yes 6 M BATH 93 744 No 0 1 Yes Yes Yes 7 M BED 243 1944 No 0 1 1 Yes Yes Yes 8 DINING 206 1648 No 0 1 Yes Yes Yes 9. FR KITCHEN 141 1128 Yes 0 1 Yes Yes Yes 10 BED 2 192 1536 No 0 1 1 Yes Yes Yes 11 BATH 2 59 472 No 0 1 Yes Yes Yes 12 M WIC 92 736 No 0 1 Yes Yes Yes 13 LIVING 316 2528 No 2 1 Yes Yes Yes 14 COND GARAGE 627 5016 No 0 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab -On -Grade Edge Insulatio 2nd Floor 23 ft 130 ftz _ 1 0 0 2 Slab -On -Grade Edge Insulatio RR KITCHEN 14.5 ft 162 ftz 1 0 0 3 Slab -On -Grade Edge Insulatio OFFICE 11.3 ft 78 ft2 _ 1 0 0 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 6 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT FLOORS # Floor Type Space Perimeter Perimeter R Value Area Joist R-Value Tile Wood Carpet 4 Slab -On -Grade Edge Insulatio ENTRY 6.9 It 117 ft2 — 1 0 0 5 Slab -On -Grade Edge Insulatio CMD 1 It 23 ft2 _ 1 0 0 6 Slab -On -Grade Edge Insulatio M BATH 16.1 It 93 ft2 �e 1 0 0 7 Slab -On -Grade Edge Insulatio M BED 35.2 ft 243 fie _ 1 0 0 8 Slab -On -Grade Edge Insulatio DINING 23.8 ft 206 f12 — 1 0 0 9 Slab -On -Grade Edge Insulatio FR KITCHEN 14.5 It 141 f12 — 1 0 0 10SIab-On-Grade Edge Insulatio BED 2 30.5 ft 192 fl? — 1 0 0 11SIab-On-Grade Edge Insulatio BATH 2 1 It 59 fie e 1 0 0 12SIab-On-Grade Edge Insulatio M WIC 1 ft 92 W _ 1 0 0 13SIab-On-Grade Edge Insulatio LIVING 22 ft 316 ft2 _ 1 0 0 14SIab-On-GradeEdge Insulatio COND GARAGE 84.7 It 627 ft2 _ 1 0 0 ROOF Roof Gable Roof Rad Solar SA Emitt Emiti Deck Pitch # Type Materials Area Area Color Ban- Absor. Tested Tested Insul. (deg) 1 Hip Composition shingles 2613 ft2 0 ft2 Light N 0.5 No 0.9 No 0 18.4 ATTIC # Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 Full attic Vented 300 2479 ft2 N N CEILING # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic (Vented) 2nd Floor 30 Blown 130 ft2 0.11 Wood 2 Under Attic (Vented) RR KITCHEN 30 Blown 162 ft2 0.11 Wood 3 Under Attic (Vented) OFFICE 30 Blown 78 ft2 0.11 Wood 4 Under Attic (Vented) ENTRY 30 Blown 117 ft2 0.11 Wood 5 Under Attic (Vented) CMD 30 Blown 23 ft2 0.11 Wood 6 Under Attic (Vented) M BATH 30 Blown 93 ft2 0.11 Wood 7 Under Attic (Vented) M BED 30 Blown 243 ft2 0.11 Wood 8 Under Attic (Vented) DINING 30 Blown 206 fF 0.11 Wood 9 Under Attic (Vented) FR KITCHEN 30 Blown 141 ft2 0.11 Wood 10 Under Attic (Vented) BED 2 30 Blown 192 ft2 0.11 Wood 11 Under Attic (Vented) BATH 2 30 Blown 59 W 0.11 Wood 12 Under Attic (Vented) M WIC 30 Blown 92 ft2 0.11 Wood 13 UnderAttic (Vented) LIVING 30 Blown 316 ft2 0.11 Wood 14 Under Attic (Vented) COND GARAGE 30 Blown 627 ft2 0.11 Wood 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 6 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT WALLS Adjacent Cavity Width Height Sheathing Framing Solar Below Space 1 NE=>NW Exterior Concrete Block - Int lnsul2nd Floor 4.1 10 0 8 0 80.0 ftz 0 0 0.6 0 2 SE=>NE Exterior Concrete Block - Int Insul2nd Floor 4.1 13 0 8 0 104.0 ft2 0 0 0.6 0 3 SE=>NE Exterior Concrete Block - Int InsM KITCHEN 4.1 12 6 8 0 100.0 ftZ 0 0 0.6 0 4 SW=>SE Exterior Concrete Block - Int InsBR KITCHEN 4.1 2 0 8 0 16.0 ft2 0 0 0.6 0 5 E=>N Exterior Concrete Block - Int Insul OFFICE 4.1 11 5 8 ' 0 91.3 ft2 0 0 0.6 0 6 SW=>SE COND G Interior Frame - Wood OFFICE 11 5 0 8 0 40.0 112 0 0.25 0.6 0 7 S=>E COND G Interior Frame - Wood OFFICE 11 5 2 8 0 41.3 ft2 0 0.25 0.6 0 8 W=>S Exterior Concrete Block - Int Insul ENTRY 4.1 6 11 8 0 55.3 f12 0 0 0.6 0 9 S=>E COND G Interior Frame - Wood ENTRY 11 10 4 8 0 82.7 ft2 0 0.25 0.6 0 10 S=>E Exterior Concrete Block - Int Insul M BATH 4.1 8 1 8 0 64.7 f12 0 0 0.6 0 11 W=>S Exterior Concrete Block - Int Insul M BATH 4.1 8 1 8 0 64.7 f12 0 0 0.6 0 12 N=>W Exterior Concrete Block - Int Insul M BED 4.1 15 5 8 0 123.3 ft2 0 0 0.6 0 13 E=>N Exterior Concrete Block -1nt Insul M BED 4.1 1 10 8 0 14.7 ft2 0 0 0.6 0 14 S=>E Exterior Concrete Block - Int Insul M BED 4.1 2 3 8 0 18.0 ft2 0 0 0.6 0 15 W=>S Exterior Concrete Block-fntInsul M BED 4.1 15 8 8 0 125.3 f12 0 0 0.6 0 16 N=>W Exterior Concrete Block - Int Insul DINING 4.1 1 10 8 0 14.7 ft2 0 0 0.6 0 17 NW=>S Exterior Concrete Block - Int Insul DINING 4.1 22 0 8 0 176.0 ft2 0 0 0.6 0 18 NW=>S Exterior Concrete Block - Int lns9R KITCHEN 4.1 14 6 8 0 116.0 ft' 0 0 0.6 0 19 NE=>NW Exterior Concrete Block - Int Insul BED 2 4.1 16 0 8 0 128.0 ft 0 0 0.6 0 20 SE=>NE Exterior Concrete Block - Int Insul BEDZ 4.1 2 6 8 0 20.0 ft2 0 0 0.6 0 21 NW-S Exterior Concrete Block - Int Insul BED 2 4.1 12 0 8 0 96.0 ft2 0 0 0.6 0 22 SE=>NE Exterior Concrete Block - Int Insul LIVING 4.1 22 0 8 0 176.0 ft2 0 0 0.6 0 23 N=>W Exterior Concrete Block - Int InsGOND GARA 4.1 10 7 8 0 84.7 ft2 0 0 0.6 0 24 E=>N Exterior Concrete Block - lnt'Ins(DOND GARA 4.1 20 10 8 0 166.7 ft2 0 0 0.6 0 25 S=>E Exterior Concrete Block - Int lnS010ND GARA 4.1 28 6 8 0 228.0 IF 0 0 0.6 0 26 W=>S Exterior Concrete Block - Int InsQOND GARA 4.1 24 10 8 0 198.7 ft2 0 0 0.6 0 DOORS # Omt Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 W=>S Insulated ENTRY None .4 3 8 24 ft2 2 E=>N Insulated COND GARA None .4 3 8 24 ft2 3 W=>S Insulated COND GARA None .4 16 8 128 ft2 WINDOWS Orientation shown is the entered orientation => changed to As Built rotated 270 degrees). V Wall Overhang # Omt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening 1 NE=>NW 1 TIM Low-E Double Yes 0.45 0.3 Y 24.0 ft2 6 ft 7 in 0 ft 0 in None None 2 E=>N 5 TIM Low-E Double Yes 0.76 0.3 Y 4.5 ft2 3 f111 in 0 ft0 in None None 3 E=>N 5 TIM Low-E Double Yes 0.76 0.3 Y 4.7 f12 ft 11 in 0 ft 0 in None None 4 E=>N 5 TIM Low-E Double Yes 0.76 0.3 Y 4.9 ft2 3 ft 11 in Oft 0 in None None 5 W=>S 8 TIM Low-E Double Yes 0.45 0.3 Y 9.3 ft2 12 ft 0 in 0 ft 0 in None None 6 W=>S 8 TIM Low-E Double Yes 0.45 0.3 Y 10.7 ft2 12 ft 0 in 0 ft 0 in None None 8113/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 6 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT WINDOWS Orientation shown is the entered orientation => changed to As Bunt rotated 270 degrees). Wall Overhang Omt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening 7 S=>E 10 TIM Low-E Double Yes 0.75 0.3 Y 4.7 ft2 7 ft 7 in 0 ft 0 in None None 8 W=>S 11 TIM Low-E Double Yes 0.75 0.3 Y 9A f12 4 ft 0 in 0 ft 0 in None None 9 W==>S 11 TIM Low-E Double Yes 0.75 0.3 Y 4.9 ft2 4,ft 0 in 0 It 0 in None None 10 N=>W 12 TIM Low-E Double Yes 0.45 0.3 Y 47.3 ft2 3 ft 5 in 0 ft 0 in None None 11 NW=>SW17 TIM Low-E Double Yes 0.76 0.3 Y 38.0 ft2 1 ft 6 in 0 ft 0 in None None 12 NW=>SW17 TIM Low-E Double Yes 0.76 0.3 Y 19.5 ft2 1;ft 6 in 0 ft 0 in None None 13 NW=>SWt7 TIM Low-E Double Yes 0.45 0.3 Y 72.0 fig 3 ft 5 in 0 ft 0 in None None 14 NW=>SW18 TIM Low-E Double Yes 0.45 0.3 Y 72.0 ft2 3 It 5 in 0 It 0 in None None 15 NE=>NW19 TIM Low-E Double Yes 0.76 0.3 Y 49.3 ft' 1 ft 6 in 0 It 0 in None None 16 NE=>NW 1 TIM Low-E Double Yes 0.75 0.3 Y 20.6 ft' 3 ft 11 in 0 ft 0 in None None INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000254 1652.7 90.73 170.63 .0881 5 HEATING SYSTEM # System Type Subtype Efficiency Capacity Block Duds 1 Electric Heat Pump/ Split HSPF.9 46.5 kBtu/hr 1 sys#1 2 PTHP/ None COP:5.8 11.5 kBtu/hr 2 Ductless COOLING SYSTEM # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit/ Split SEER:16 46.5 kBtu/hr 1550 cfm 0.8 1 sys#1 2 PTAC and Room Unit/ Through the Wall(Single) SEER: 11 12 kBtulhr 370 cfm 0.8 2 Ductless HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Electric None 2nd Floor 0.95 40 gal 60.9 gat 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Cart # Company Name System Model # Collector Model # Area Volume FEF None None ft2 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 6 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT DUCTS — Supply — V - Return — Air CFM 25 CFM25 HVAC # # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 Attic 6 739 ft Attic 73911E Prop_ Leak Free 2nd Floor — cfm 55.6 cfm 0.03 0.50 1 1 TEMPERATURES Programable Thermostat: Y Ceiling Fans: Cooling[ j Jan j Feb Heatin[X] Jan [X] Feb (j Mar [Xj Mar [ j Apr [ ] pr [ j May may Jun Jun Jul Jul Au rl Aug Se Sep j j Oct [ ] Oct MNov Nov Dec HDec Ventin [ j Jan [[ ]] Feb [Xj Mar [X] A r [) Ma Jun Jul Aug Se [X] Oct Nov Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling (WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling (WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating (VVD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating (WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 MASS Mass Type Area Thickness Furniture Fraction Space Default(8 lbs/sq.ft. O'fiz 0 ft 0.3 2nd Floor Defautt(8 Ibs/sq.ft_ ftZ ft 0.3 RR KITCHEN Default(8 Ibs/sq.ft. ftZ ft 0.3 OFFICE Default(8 lbs/sq.ft_ ftZ ft 0.3 ENTRY Defau@(8 Ibs/sq.ft. ftZ ft 0.3 CMD Default(8 lbs/sq.ft. ftZ It 0.3 M BATH Default(8 lbs/sq.f . ftZ ft 0.3 M BED Default(8 Ibs/sq.ft. ttZ It 0.3 DINING Default(8 Ibs/sq.ft. ftZ It 0.3 FR KITCHEN Default(8 lbs/sq.fL ftZ ft 0.3 BED 2 Default(8 Ibs/sq.ft. ftZ ft 0.3 BATH 2 Default(8 Ibs/sq.ft. ftZ ft 0.3 M WIC Default(8 Ibs/sq.ft. ftZ ft 0.3 LIVING Default(8 lbs/s .ft. ftZ ft 0.3 COND GARAGE 8/1312018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 6 of 6 Florida Building Code, Energy Conservation, 6th Edition (2017) 'Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 581 Beach Avenue Permit Number Port St. Lucie, FL , 34952 MANDATORY REQUIREMENTS See individual code sections for full details. IFA SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402A.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. R402.4.1 Building thermal enveldpe building thermal envelope shag comply with Sections R402A.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shag allow for differential expansion and contraction. R402A.1.1 InstallationThe components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate hot exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 02 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be dosed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be dosed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shag be dosed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shag be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. R402.4.2 Fireplaces. New woad -burning fireplaces shall have tight fitting flue dampers or doors, and outdoor combustion air. Where using fight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. 0 R402A.3 Fenestration air,leakagdtUndows, skylights -arid sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101fl.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 8/13/2018 2:25 PM EnergyGauge@ USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402A.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shaft meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and duds in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.42 and Section R1006 of the Florida Building Code, Residential. R402A.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2:0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 controls. SECTION R403 SYSTEMS R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.3.2 Sealing (Mandatory) All duds, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered duds or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet dud tightness criteria below. Duct tightness shall be verified by testing !in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. 0 r7 R403.3.2.1 Sealed air handier. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. Ej R403.3.3 Duct testing (Mandatory). Duds shall be pressure tested to determine air leakage by one of the following methods: Rough -in test Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handier enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. Postconstruction test Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handier enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the duds and air handlers are located entirely within the building thermal envelope. 2. Duct testing,is not mandatory for buildings complying by Section 405 of this code. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. ❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41 °C) or below 55°F (13"C) shall be insulated to a minimum of R-3. ❑ 'R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory)Heated water circulation systems shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return 0 pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance With the times when heated water is used in the occupancy. 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have ' heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'/ inches (89mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory]. R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100'F to 140"F (38"C to 60"C). a R403.5.6.1.2 Shutdown. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Wager -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as.applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. Ei R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where whole -house mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment (Mandatory). R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, ublityroom 90 2.8 cim/watt Any For SI: 1 cfiri = 28.3 Umin. a. When tested in accordance with HVI Standard 916 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 6 MANDATORY REQUIREMENTS - (Continued) ,❑R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment The capacity of fossl fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. ❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections ❑ C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50"F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40'F (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. ❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at ❑ the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5 R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. �O R403.11 Portable spas (Mandatofy6e energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be high -efficacy lamps or not less than 75 percent of the permanently installed fighting fixtures shall contain only high -efficacy lamps. Exception: Low -voltage lighting. R404.1.1 Lighting equipment (Mandatory)Fuel gas lighting systems shall not have continuously burning pilot lights. 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 5