REPORT OF FOUNDATION PAD COMPACTION
Client: G.W.Purucker Homes Report Date: August*1%4,'-2 '; _4 0"
5608 PGA Boulevard,Suite 208 Project No: 337
Palm Beach Gardens,Florida 33410 Lab No: 304
Site: Lot 70,5024 Watersong Way Permit No: 0703-0148
Fort Pierce,St.Lucie County,Florida
Foundation Pad
Density tests and Hand Cone Penetrometer (HCP) readings were made at a minimum of three locations in
the building pad. Density tests were performed in the upper one foot of fill. HCP readings were taken in
hand auger boreholes at one foot intervals from slab grade through the depth of fill. The density tests were
performed in general compliance with ASTM D 2922. The HCP test, in conjunction with information about
the soil type, is empirically correlated to the relative density of subsurface soils.
Density Date Elevation Dry Density( sf) Percent
Test No. Tested Location (feet) In Place Proctor Compaction
1 8/13/07 Southwest Corner 0- 1 115.7 117.1 98.8
2 Center Area 0- 1 116.3 117.1 99.3
3 1 8/14/07 lNortheast Comer 1 0- 1 1 115.5 1 117.1 1 98.6
* All elevations are below slab grade.
The depth of the-fill was approximately two to three feet. The fill should extend at least five feet beyond the
building perimeter. At the time of our testing no information was available regarding the foundation pad
setbacks.
In the locations and depths that were tested, the fill has been compacted to a minimum of 95 percent of the
modified Proctor maximum dry density (ASTM D 1557). No soil borings were performed below the
recently placed fill.
Distribution: Submitted by:
Client(PSL Office) - 3 A.M.,E GTiVE1RIG AND TESTING,INC.
SLC Bldg. Dept. - 1
P ul C.Martin,P.E.,
PCM/ah Florid'a.-Registration No. 65051