HomeMy WebLinkAboutPhillips, Brent port gen infoINSTALLATION INSTRUCTIONS - ENGLISH
Manual Transfer Interlock Kit
No. LITLK
IMPORTANT SAFETY INSTRUCTIONS - READ ALL INSTRUCTIONS BEFORE USING.
U WARNING
• TO AVOID FIRE, SHOCK OR DEATH: TURN OFF POWER SUPPLYING THIS EQUIPMENT, AND CONFIRM POWER IS OFF,
before installing, removing or servicing this equipment.
• This equipment MUST BE installed and serviced by an electrician.
• Replace all doors and covers before connecting power to this equipment.
• To be installed and/or used in accordance with electrical codes and regulations.
• To be used in permanently installed and listed enclosures only.
TRADEMARK DISCLAIMER
LEVIi6W
DI-000-LITLK-05A
Use herein of third party trademarks, service marks, trade names, brand names and/or product names are for informational purposes only, are/may be the
trademarks of their respective owners, such use is not meant to imply affiliation, sponsorship, or endorsement.
LIMITED PRODUCT WARRANTY
For Leviton's limited product warranty, go to www.leviton.com. For a printed copy of the warranty you may call 1-800-323-8920.
INTRODUCTION
This Instruction sheet provides steps for installing the Manual
Transfer Interlock Kit. The kit includes a hold down breaker bracket,
generator mechanical interlock bracket along with mounting screws
and a hole pattern drill template.
The hold down breaker bracket is used to secure a generator supply
branch breaker onto the interior assembly. The generator mechanical
interlock bracket slides between the handle of the utility main breaker
and the handle of generator supply breaker to prevent both from
being switched ON at the same time.
The hole pattern drill template will be used to drill mounting holes for
the generator mechanical interlock bracket.
INSTALLATION
WARNING: TO AVOID FIRE, SHOCK OR DEATH: TURN OFF
POWER SUPPLYING THIS EQUIPMENT, AND CONFIRM
POWER IS OFF, before installing, removing or servicing this
equipment.
NOTE: Installation with indoor load center shown.
1. Remove the six (x6) cover screws (A) from the panelboard and lift
off cover assembly (fig. 1).
NOTE: Keep screws to re -attach the cover after installation.
2. Separate the dead front (B) from the cover by backing out the
two (x2) captive adjustment screws (C) (fig. 2).
3. Install the hold down bracket (D) and secure to the interior base
with a #10 thread cutting screw (E) (provided).
Tighten to 20 in-lbf (2.2 N-m) (fig. 3).
4, Lay the dead front (B) flat with the back facing down. Place the
hole pattern drill template (F) on the dead front (B) between the
top of the main breaker knockout (G) and the top of the branch
breaker twistouts (H) and secure in place with tape (fig. 4).
Fig. 1
Fig. 2
Dead front
Cover screws
(B)
(A) (A)
°
•' 0
00
00
•oo
00
0
0
0
0
®-'
0
Adjustment
0
screws
(x2) (C)
00
00
00
00
L
0
®
°
NOTE: Installation
with indoor load center shown.
(> 2017 Leviton Mfg. Co., Inc.
For Technical Assistance Call: 1-BOG-824-3005 (U.S.A. Only)
1 800 405-5320 (Canada Only) w Jeviton.com
DI-000-LITLK-05A
5. Drill two mounting holes (1) (oO.203 in. or No. 6) for the generator mechanical
interlock bracket in the dead front (B) as marked on the hole pattern drill template.
OPERATION
Clean any burs from other side (fig. 5).
Switching from utility power to generator power (Fig. 7):
6. Secure the generator mechanical interlock bracket (J) to the dead front (B) with
two #8-32 x 1/4 screws (K) (provided). Screws must from
1. Move the handle of the main breaker (L) to the OFF position.
2. Slide
enter the back, through
the dead front (B) and into the generator mechanical interlock bracket (J) (fig. 6).
the top of the generator mechanical interlock bracket (J) down.
3. Move the handle of the generator breaker (M) to the ON position.
7. Re -attach the dead front (B) to the cover and then the cover to the panelboard.
Switching from generator power to utility power (Fig 8):
1. Move the handle of the generator breaker (M) to the OFF position.
SAVE THESE INSTRUCTIONS
2. Slide the top of the generator mechanical interlock bracket (J) up.
3. Move the handle of the main breaker (L) to the ON position.
Fig. 3 V
0
L Fl
�`—_ _'L
111_= �_��
o UD
Fig.
7
®
#10 Thread --- _
cutting screw — —
®, O
(E)
00
®
®
Mechanical
®
B
interlock
Handle of main
E—
0
bracket (J)
breaker OFF
®
in dawn
(L)
®
position
Op
Hold down —
0 18
bracket
Handle of
generator
Fig. 4
Tap of main
breaker
breaON
Hole pattern
breaker knockout Top of branch
(L)
drill template
(G) breaker twistouts
(F'
(H)
Dead front
Q
(8)
00
Tape
oc
00
Fig.5
Fig.
8
Mounting holes
(00.203 in. or No.
6)
(x2) (1)
Dead front
Handle of main
breaker ON
Mechanical
(L)
interlock
bracket
in up up
Fig. 6
position
Mechanical interlock
bracket
#8-32 x 1/4
Handle of
W
screws
generator
(x2)(K)
breaker
((���
g�10
OFF
(L'
��
o 0
Dead front
Q
(B)
o❑
0 p
00
0 2017 Leviton Mfg. Co., Inc.
For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only)
1 800 405-5320 (Canada Only) www.leviton.com
DI-000-LITLK-05A
HOLE PATTERN DRILL TEMPLATE
GABARIT DE PERQAGE
PLANTILLA DE PERFORAC16N CON PATRON DE ORIFICIOS
For use with catalog number LITLK / Pour le no de catalogue LITLK
Para utilizarse con el catalogo nOmero LITLK
Cut along dotted line / Couper le long de la ligne pointillee / Cortar a to largo de la linea punteada
Mounting Holes
Trous de fixation
Onficros de Montag
(00.203 in. or No. 6)
I I
I I
1 I
I® ®I
I I
i I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
LEVITY
DG-000-LITLK-25A
For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only)