HomeMy WebLinkAboutAPPROVED GONZALEZ- MANUAL JCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-23 11:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...mnets\Wrightsoft HVAC\GONZALEZ- 151 NETTLES.rup Calc = M J8 Front Door faces: S Job:Project Summary Sep 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information GONZALEZ RESIDENCEFor: LOT 151 NETTLES, JENSEN BEACH, FL Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh24429 Struc ture Btuh15779 Ducts Btuh4658 Ducts Btuh6564 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh29087 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh21226 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh2059 Ducts Btuh1771 Central vent (0 cfm)Btuh0 CoolingHeating (none) 18121812Area (ft²)Equipment latent load Btuh3829 1478414784Volume (ft³) Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh25055 Equiv. AVF (cfm)4994 Req. total capacity at 0.70 SHR ton2.5 Heating Equipment Summary Cooling Equipment Summary Make Make Trane Trade Trade TRANE Model Cond 4TTR4031L1 AHRI ref Coil TEM6A0C36H31++TDR AHRI ref 7567544 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW8.1 Sensible cooling Btuh20580 Heating output Btuh27714 Latent cooling Btuh8820 Temperature rise °F26 Total cooling Btuh29400 Actual air flow cfm980 Actual air flow cfm980 Air flow factor cfm/Btuh0.034 Air flow factor cfm/Btuh0.044 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.85 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-23 11:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...mnets\Wrightsoft HVAC\GONZALEZ- 151 NETTLES.rup Calc = M J8 Front Door faces: S Job:Right-J® Worksheet Sep 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House LIVING 2 Exposed wall 264.8 ft 52.2 ft 3 Room height 8.2 ft 8.0 heat/coolft 4 Room dimensions ft294.0x1.0 5 Room area 1812.0 ft²294.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 784 712 2849 1557 160 120 479 262 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 12 0 218 180 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 30 0 546 450 10 0 182 150 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 10 0 190 156 10 0 190 156 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 20 0 364 300 20 0 364 300 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 387 259 1037 567 193 125 499 273 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 29 5 523 750 10 1 174 250 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 10 2 190 272 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 89 14 1615 2315 59 5 1077 1543 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 664 594 2378 1300 64 64 256 140 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 4 8 73 60 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 6 12 109 90 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 10 20 182 150 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 30 60 546 450 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 20 40 364 300 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 168 168 673 368 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 190 171 683 373 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 4 0 73 108 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 15 0 273 403 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 1112 1112 1762 1521 86 86 136 117 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 1123 181 6899 0 294 52 1984 0 6 c) AED excursion 0 38 Envelope loss/gain 21548 11667 5341 3228 12 a) Infiltration 2881 812 549 155 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 3300 0 Subtotal (lines 6 to 13)24429 15779 5889 3383 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 24429 15779 5889 3383 15 Duct loads 19%42%4658 6564 19%42%1123 1407 Total room load 29087 22343 7012 4790 Air required (cfm)Air required (cfm)980 980 236 210 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-23 11:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 ...mnets\Wrightsoft HVAC\GONZALEZ- 151 NETTLES.rup Calc = M J8 Front Door faces: S Job:Right-J® Worksheet Sep 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name KITCHEN BATH 2 2 Exposed wall 25.0 ft 18.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft293.0x1.0 ft12.0x6.0 5 Room area 293.0 ft²72.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 72 72 288 158 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 128 102 408 223 48 44 176 96 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 4 4 73 60 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 6 6 109 90 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 20 20 364 300 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 96 96 384 210 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 0 0 0 0 0 0 0 0 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 293 25 951 0 72 18 684 0 6 c) AED excursion -45 -18 Envelope loss/gain 2120 726 1318 349 12 a) Infiltration 263 74 189 53 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1400 200 Subtotal (lines 6 to 13)2383 2200 1507 602 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 674 166 367 91 14 Subtotal 3057 2366 1874 693 15 Duct loads 19%42%583 984 19%42%357 288 Total room load 3640 3350 2232 981 Air required (cfm)Air required (cfm)123 147 75 43 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-23 11:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 3 ...mnets\Wrightsoft HVAC\GONZALEZ- 151 NETTLES.rup Calc = M J8 Front Door faces: S Job:Right-J® Worksheet Sep 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name HALL STORAGE 2 Exposed wall 19.0 ft 6.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft103.0x1.0 ft4.0x6.0 5 Room area 103.0 ft²24.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 40 40 160 88 48 48 192 105 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 40 40 160 88 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 72 72 288 158 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 0 0 0 0 0 0 0 0 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 103 19 722 0 24 6 228 0 6 c) AED excursion -11 -3 Envelope loss/gain 1331 321 420 102 12 a) Infiltration 200 56 63 18 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1531 378 483 119 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -1531 -378 490 121 14 Subtotal 0 0 973 240 15 Duct loads 19%42%0 0 19%42%186 100 Total room load 0 0 1159 340 Air required (cfm)Air required (cfm)0 0 39 15 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-23 11:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 4 ...mnets\Wrightsoft HVAC\GONZALEZ- 151 NETTLES.rup Calc = M J8 Front Door faces: S Job:Right-J® Worksheet Sep 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M BATH M WIC 2 Exposed wall 31.8 ft 7.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft144.0x1.0 ft8.0x7.0 5 Room area 144.0 ft²56.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 144 132 529 289 56 56 224 123 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 12 0 218 180 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 111 91 365 199 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 10 1 174 250 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 10 1 190 272 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 144 144 228 197 56 56 89 77 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -5 -11 Envelope loss/gain 1704 1382 313 189 12 a) Infiltration 335 95 74 21 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 150 Subtotal (lines 6 to 13)2039 1476 387 359 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 18 15 14 Subtotal 2039 1476 405 375 15 Duct loads 19%42%389 614 19%42%77 156 Total room load 2428 2090 482 531 Air required (cfm)Air required (cfm)82 92 16 23 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-23 11:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 5 ...mnets\Wrightsoft HVAC\GONZALEZ- 151 NETTLES.rup Calc = M J8 Front Door faces: S Job:Right-J® Worksheet Sep 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name MASTER BEDROOM CLST 2 2 Exposed wall 29.3 ft 2.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft275.5x1.0 ft10.0x2.0 5 Room area 275.5 ft²20.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 82 43 173 95 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 10 1 174 250 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 30 2 538 772 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 152 137 549 300 16 16 64 35 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 15 15 273 225 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 276 276 437 377 20 20 32 27 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 51 -2 Envelope loss/gain 2144 2069 96 60 12 a) Infiltration 308 87 21 6 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 150 0 Subtotal (lines 6 to 13)2452 2306 117 66 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 94 63 -117 -66 14 Subtotal 2546 2369 0 0 15 Duct loads 19%42%485 985 19%42%0 0 Total room load 3031 3354 0 0 Air required (cfm)Air required (cfm)102 147 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-23 11:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 6 ...mnets\Wrightsoft HVAC\GONZALEZ- 151 NETTLES.rup Calc = M J8 Front Door faces: S Job:Right-J® Worksheet Sep 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name W/D HALLWAY 2 Exposed wall 0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft4.0x4.0 ft91.0x1.0 5 Room area 16.0 ft²91.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 16 16 25 22 91 91 144 125 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 0 0 0 0 3 0 0 0 6 c) AED excursion -1 -4 Envelope loss/gain 25 21 144 121 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)25 21 144 121 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -25 -21 -144 -121 14 Subtotal 0 0 0 0 15 Duct loads 19%42%0 0 19%42%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-23 11:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 7 ...mnets\Wrightsoft HVAC\GONZALEZ- 151 NETTLES.rup Calc = M J8 Front Door faces: S Job:Right-J® Worksheet Sep 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 2 WIC 3 2 Exposed wall 11.0 ft 15.3 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft128.0x1.0 ft22.5x1.0 5 Room area 128.0 ft²22.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 88 73 292 160 40 40 160 88 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 15 15 273 225 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 82 82 330 180 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 128 128 203 175 23 23 36 31 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 72 6 235 0 23 15 580 0 6 c) AED excursion -30 -10 Envelope loss/gain 1004 530 1105 289 12 a) Infiltration 116 33 161 45 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1000 0 Subtotal (lines 6 to 13)1119 1562 1266 334 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 101 68 0 0 14 Subtotal 1220 1631 1266 334 15 Duct loads 19%42%233 678 19%42%241 139 Total room load 1452 2309 1508 473 Air required (cfm)Air required (cfm)49 101 51 21 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-23 11:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 8 ...mnets\Wrightsoft HVAC\GONZALEZ- 151 NETTLES.rup Calc = M J8 Front Door faces: S Job:Right-J® Worksheet Sep 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM3 BATH 3 2 Exposed wall 17.7 ft 12.7 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft156.0x1.0 ft45.0x1.0 5 Room area 156.0 ft²45.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 48 48 192 105 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 26.0826.08 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 88 78 312 171 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 10 10 182 150 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 54 39 155 85 54 50 199 109 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 4 0 73 108 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 15 0 273 403 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 156 156 247 213 45 45 71 62 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 156 18 672 0 45 13 482 0 6 c) AED excursion 52 23 Envelope loss/gain 1841 1074 1017 405 12 a) Infiltration 186 52 134 38 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 400 0 Subtotal (lines 6 to 13)2027 1527 1150 443 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 9 8 9 8 14 Subtotal 2037 1534 1160 451 15 Duct loads 19%42%388 638 19%42%221 188 Total room load 2425 2173 1381 638 Air required (cfm)Air required (cfm)82 95 47 28 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-23 11:28:49 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 9 ...mnets\Wrightsoft HVAC\GONZALEZ- 151 NETTLES.rup Calc = M J8 Front Door faces: S Job:Right-J® Worksheet Sep 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name STAIRS 2 Exposed wall 18.0 ft 3 Room height 12.0 heat/coolft 4 Room dimensions ft4.0x18.0 5 Room area 72.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A-4ocs 0.143 n 4.00 2.19 216 196 785 429 .G 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 .G 2 glazing, clr low-e 0.650 n 18.20 14.99 20 0 364 300 .G 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 11 G 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 W 13A-4ocs 0.143 se 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 se 18.20 26.08 0 0 0 0 G 2 glazing, clr low-e 0.650 se 18.20 26.08 0 0 0 0 G 2 glazing, clr low-e 0.650 se 18.20 26.08 0 0 0 0 W 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 G 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 G 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 G 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 G 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 W 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 W 13A-4ocs 0.143 nw 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 nw 18.20 26.88 0 0 0 0 G 2 glazing, clr low-e 0.650 nw 18.20 26.88 0 0 0 0 C 16X19-0md 0.408 -1.59 1.37 72 72 114 99 F 22A-tph 1.358 -38.02 0.00 38 10 361 0 6 c) AED excursion -26 Envelope loss/gain 1624 801 12 a) Infiltration 284 80 b) Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)1908 881 Less external load 0 0 Less transfer 0 0 Redistribution 55 46 14 Subtotal 1963 928 15 Duct loads 19%42%374 386 Total room load 2338 1314 Air required (cfm)79 58 2021-Sep-23 11:28:55 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...mnets\Wrightsoft HVAC\GONZALEZ- 151 NETTLES.rup Calc = M J8 Front Door faces: S Job:Duct System Summary Sep 23, 2021Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information GONZALEZ RESIDENCEFor: LOT 151 NETTLES, JENSEN BEACH, FL CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm980cfm980 Total effective length (TEL)ft178 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st5150.013.9VlFx0x06.01.00043752232hBATH 2 st3115.011.3VlFx0x05.01.00028471381hBATH 3 st2115.09.9VlFx0x07.01.000101492309cBEDROOM 2 st3115.08.0VlFx0x07.01.00095822173cBEDROOM3 st4150.027.5VlFx0x08.01.0001471233350cKITCHEN st4150.026.6VlFx0x08.01.0002102367012hLIVING st6135.027.9VlFx0x07.01.00092822090cM BATH st6135.026.2VlFx0x05.01.0002316531cM WIC st2115.010.2VlFx0x08.01.0001471023354cMASTER BEDROOM 95.010.0VlFx0x06.01.00058792338hSTAIRS st5150.014.1VlFx0x04.01.00015391159hSTORAGE st3115.018.0VlFx0x05.01.00021511508hWIC 3 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 359 357 1.000 658 10.0 0x0 VinlFlx st1 st5 Peak AVF 114 58 1.000 582 6.0 0x0 VinlFlx st1 st1 Peak AVF 473 415 1.000 602 12.0 0x0 VinlFlx st3 Peak AVF 179 144 1.000 670 7.0 0x0 VinlFlx st6 Peak AVF 98 115 1.000 329 8.0 0x0 VinlFlx st2 st2 Peak AVF 249 363 1.000 822 9.0 0x0 VinlFlx 2021-Sep-23 11:28:55 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 ...mnets\Wrightsoft HVAC\GONZALEZ- 151 NETTLES.rup Calc = M J8 Front Door faces: S Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 9800 980 0 0 0 0 x0 0 VlFx