Loading...
HomeMy WebLinkAboutPROJECT INFORMATIONCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-May-26 08:47:48 Right-Suite® Universal 2021 21.0.07 RSU29066 Page 1 ...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1509Job:Load Short Form 5/25/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Jorgensen Residence, Air Conditioning UnlimitedFor: 4910 Myrtle Dr, Ft. Pierce, FL 34982 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Goodman Mfg. Trade Trade GOODMAN Model Cond GSX160301F AHRI ref Coil ASPT37C14A AHRI ref 201384656 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW6.3 Sensible cooling Btuh19600 Heating output Btuh21437 Latent cooling Btuh8400 Temperature rise °F21 Total cooling Btuh28000 Actual air flow cfm933 Actual air flow cfm933 Air flow factor cfm/Btuh0.047 Air flow factor cfm/Btuh0.050 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.75 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) WIC 30 925 290 44 14 Master Bath 50 1514 549 72 27 Master Bed 189 2607 2310 124 115 Great Room 306 3268 4536 155 226 Bed 3 154 3064 2476 145 124 Lin 5 0 0 0 0 Bath 47 590 257 28 13 Bed 2 173 3164 2276 150 114 Hall 24 0 0 0 0 Pantry 8 0 0 0 0 KitchenNook 217 2287 4548 109 227 Foyer 83 1829 649 87 32 Laundry 24 408 805 19 40 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-May-26 08:47:48 Right-Suite® Universal 2021 21.0.07 RSU29066 Page 2 ...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N House 1307 19656 18696 933 933 Other equip loads 2206 1171 Equip. @ 0.95 RSM 18954 Latent cooling 6577 TOTALS 1307 21862 25530 933 933 2021-May-26 08:47:48 Right-Suite® Universal 2021 21.0.07 RSU29066 Page 1 ...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1509Job:Building Analysis 5/25/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Jorgensen Residence, Air Conditioning UnlimitedFor: 4910 Myrtle Dr, Ft. Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 17.738723.1Walls 11.9260717.9Glazing 0.3743.7Doors 5.912961.0Ceilings 22.048063.73.7Floors 12.427022.5Infiltration 19.74298Ducts 00Piping 00Humidification 10.12206Ventilation0Adjustments 100.021862Total Cooling Walls Glazing Other Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 11.823401.9Walls 18.8374225.7Glazing 0.4753.7Doors 9.719211.5Ceilings 000Floors 3.77330.7Infiltration 24.54866Ducts 5.91171Ventilation 25.35020Internal gains 00Blower 0Adjustments 100.019868Total Latent Cooling Load = 6577 Btuh Overall U-value = 0.108 Btuh/ft²-°F Data entries checked. 2021-May-26 08:47:48 Right-Suite® Universal 2021 21.0.07 RSU29066 Page 1 ...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1509Job:Component Constructions 5/25/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Jorgensen Residence, Air Conditioning UnlimitedFor: 4910 Myrtle Dr, Ft. Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 3953.155.10.109125n 2532.02 382.02593.155.10.10919ne 642.021013.155.10.10932e 2412.023773.155.10.109120e 382.02593.155.10.10919se 5642.028823.155.10.109280s 6662.0210403.155.10.109330w 18632.0229133.155.10.109925all Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud 4761.469592.9411.00.101327 Windows Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (3.17 ft window ht, 1 ft sep.); 6.8 ft head ht 5511.58016.800.5805n Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 3 ft overhang (5.25 ft window ht, 1 ft sep.); 6.8 ft head ht 17422.114218.000.6208ne 54223.441718.000.62023e 12616.014218.000.6208se 84221.670018.000.62039all Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.25 ft window ht, 1 ft sep.); 6.8 ft head ht 63027.241718.000.62023e Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 43928.126216.800.58016w Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.25 ft window ht, 1 ft sep.); 6.8 ft head ht 65228.139016.800.58023w 2021-May-26 08:47:48 Right-Suite® Universal 2021 21.0.07 RSU29066 Page 2 ...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 8 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht 64516.075818.800.65040w Doors Fbrgls Door 753.73743.697.00.12720e Ceilings Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.03424 431.80240.9930.0 18771.4612720.9930.00.0341283 19211.4712960.9930.00.0341307all Floors On Grade Depth, Tile Flr Fnsh 00480628.700.989168 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-May-26 08:47:48 Right-Suite® Universal 2021 21.0.07 RSU29066 Page 1 ...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1509Job:Project Summary 5/25/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Jorgensen Residence, Air Conditioning UnlimitedFor:4910 Myrtle Dr, Ft. Pierce, FL 34982 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh15358 Structure Btuh13830 Ducts Btuh4298 Ducts Btuh4866Central vent (69 cfm) 2206 Btuh Central vent (69 cfm) Btuh1171 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh21862 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh18954 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh2475 Ducts Btuh1427Central vent (69 cfm) Btuh2675 CoolingHeating Outside air13071307Area (ft²) Equipment latent load Btuh6577 1130511305Volume (ft³)Air changes/hour 0.230.45 Equipment Total Load (Sen+Lat)Btuh25530 Equiv. AVF (cfm) 4385 Req. total capacity at 0.70 SHR ton2.3 Heating Equipment Summary Cooling Equipment Summary Make Make Goodman Mfg.Trade Trade GOODMAN Model Cond GSX160301FAHRI ref Coil ASPT37C14A AHRI ref 201384656Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW6.3 Sensible cooling Btuh19600Heating output Btuh21437 Latent cooling Btuh8400 Temperature rise °F21 Total cooling Btuh28000Actual air flow cfm933 Actual air flow cfm933 Air flow factor cfm/Btuh0.047 Air flow factor cfm/Btuh0.050Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.75 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-May-26 08:47:48Right-Suite® Universal 2021 21.0.07 RSU29066 Page 1...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House WIC 2 Exposed wall 167.6 ft 11.0 ft 3 Room height 8.6 ft 8.0 heat/coolft 4 Room dimensions ft5.5x5.5 5 Room area 1307.3 ft²30.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 130 125 395 253 44 44 139 89 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 5 0 80 55 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 27 19 59 38 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 8 0 142 174 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 32 32 101 64 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 186 120 377 241 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 23 0 417 630 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 23 7 417 542 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 20 20 74 75 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 27 19 59 38 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 8 6 142 126 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 280 280 882 564 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 409 330 1040 666 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 16 0 262 439 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 23 0 390 652 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 40 34 758 645 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 327 327 959 476 44 44 129 64 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 24 24 24 43 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 1283 1283 1272 1877 30 30 30 44 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1307 168 4806 0 30 11 315 0 6 c) AED excursion 479 -12 Envelope loss/gain 12656 8077 613 185 12 a) Infiltration 2702 733 109 30 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 4 920 0 0 Appliances/other 4100 0 Subtotal (lines 6 to 13)15358 13830 722 215 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 15358 13830 722 215 15 Duct loads 28%35%4298 4866 28%35%202 75 Total room load 19656 18696 925 290 Air required (cfm)Air required (cfm)933 933 44 14 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-May-26 08:47:48Right-Suite® Universal 2021 21.0.07 RSU29066 Page 2...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Master Bath Master Bed 2 Exposed wall 14.5 ft 26.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft9.0x5.5 ft14.5x13.0 5 Room area 49.5 ft²188.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 72 67 212 136 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 5 0 80 55 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 44 44 139 89 104 88 279 178 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 16 0 262 439 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 104 104 306 152 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 50 50 49 72 189 189 187 276 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 50 15 416 0 189 26 746 0 6 c) AED excursion -23 94 Envelope loss/gain 895 328 1779 1138 12 a) Infiltration 287 78 258 70 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)1183 406 2037 1708 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1183 406 2037 1708 15 Duct loads 28%35%331 143 28%35%570 601 Total room load 1514 549 2607 2310 Air required (cfm)Air required (cfm)72 27 124 115 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-May-26 08:47:48Right-Suite® Universal 2021 21.0.07 RSU29066 Page 3...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Great Room Bed 3 2 Exposed wall 20.5 ft 26.0 ft 3 Room height 9.4 heat/coolft 8.0 heat/coolft 4 Room dimensions ft17.0x18.0 ft154.3x1.0 5 Room area 306.0 ft²154.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 116 116 365 234 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 169 129 406 260 92 69 217 139 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 23 0 390 652 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 40 34 758 645 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 24 24 69 34 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 306 306 303 448 154 154 153 226 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 306 21 588 0 154 26 746 0 6 c) AED excursion 482 180 Envelope loss/gain 2125 1869 1871 1431 12 a) Infiltration 419 114 515 140 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 900 250 Subtotal (lines 6 to 13)2544 3342 2386 1821 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 10 13 8 11 14 Subtotal 2553 3356 2394 1832 15 Duct loads 28%35%715 1181 28%35%670 644 Total room load 3268 4536 3064 2476 Air required (cfm)Air required (cfm)155 226 145 124 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-May-26 08:47:48Right-Suite® Universal 2021 21.0.07 RSU29066 Page 4...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Lin Bath 2 Exposed wall 0 ft 5.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft2.5x2.0 ft5.5x8.5 5 Room area 5.0 ft²46.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 44 44 139 89 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 5 5 5 7 47 47 46 68 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 5 0 0 0 47 6 158 0 6 c) AED excursion 0 -10 Envelope loss/gain 5 7 343 147 12 a) Infiltration 0 0 109 30 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)5 7 452 177 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -5 -7 9 13 14 Subtotal 0 0 461 190 15 Duct loads 28%35%0 0 28%35%129 67 Total room load 0 0 590 257 Air required (cfm)Air required (cfm)0 0 28 13 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-May-26 08:47:48Right-Suite® Universal 2021 21.0.07 RSU29066 Page 5...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 2 Hall 2 Exposed wall 26.5 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft15.0x11.5 ft8.0x3.0 5 Room area 172.5 ft²24.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 92 69 217 139 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 23 0 417 630 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 120 120 378 242 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 173 173 171 252 24 24 24 35 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 173 27 760 0 24 0 0 0 6 c) AED excursion 22 -2 Envelope loss/gain 1943 1285 24 33 12 a) Infiltration 525 143 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)2468 1678 24 33 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 4 6 -24 -33 14 Subtotal 2473 1684 0 0 15 Duct loads 28%35%692 592 28%35%0 0 Total room load 3164 2276 0 0 Air required (cfm)Air required (cfm)150 114 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-May-26 08:47:48Right-Suite® Universal 2021 21.0.07 RSU29066 Page 6...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Pantry KitchenNook 2 Exposed wall 0 ft 12.1 ft 3 Room height 8.0 heat/coolft 9.4 heat/coolft 4 Room dimensions ft3.0x2.5 ft216.5x1.0 5 Room area 7.5 ft²216.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 14 14 44 28 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 27 19 59 38 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 8 0 142 174 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 47 24 75 48 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 0 0 0 0 23 7 417 542 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 27 19 59 38 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 0 0 0 0 8 6 142 126 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 8 8 7 11 217 217 215 317 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 8 0 0 0 217 12 347 0 6 c) AED excursion -1 -190 Envelope loss/gain 7 10 1499 1120 12 a) Infiltration 0 0 283 77 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 2 460 Appliances/other 0 1700 Subtotal (lines 6 to 13)7 10 1782 3357 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -7 -10 5 7 14 Subtotal 0 0 1787 3364 15 Duct loads 28%35%0 0 28%35%500 1184 Total room load 0 0 2287 4548 Air required (cfm)Air required (cfm)0 0 109 227 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-May-26 08:47:48Right-Suite® Universal 2021 21.0.07 RSU29066 Page 7...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Foyer Laundry 2 Exposed wall 21.5 ft 4.0 ft 3 Room height 9.4 heat/coolft 8.0 heat/coolft 4 Room dimensions ft16.5x5.0 ft6.0x4.0 5 Room area 82.5 ft²24.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 32 32 101 64 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 47 27 85 54 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 20 20 74 75 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 155 155 456 226 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 0 0 0 0 24 24 24 43 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 83 83 82 121 0 0 0 0 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 83 22 617 0 24 4 115 0 6 c) AED excursion -27 -34 Envelope loss/gain 1313 449 239 74 12 a) Infiltration 116 32 79 22 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)1429 480 319 596 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1429 480 319 596 15 Duct loads 28%35%400 169 28%35%89 210 Total room load 1829 649 408 805 Air required (cfm)Air required (cfm)87 32 19 40 2021-May-26 08:47:49 Right-Suite® Universal 2021 21.0.07 RSU29066 Page 1 ...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1509Job:Duct System Summary 5/25/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Jorgensen Residence, Air Conditioning UnlimitedFor: 4910 Myrtle Dr, Ft. Pierce, FL 34982 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.439 / 0.261 in H2O in H2O0.439 / 0.261 Lowest friction rate in/100ft0.268in/100ft0.268 Actual air flow cfm933cfm933 Total effective length (TEL) ft261 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st3125.031.5VlFx0x04.00.2801534590hBath st3125.038.4VlFx0x07.00.2681361803164hBed 2 st3125.038.7VlFx0x07.00.2681481753064hBed 3 st2100.024.9VlFx0x06.00.351391041829hFoyer st3125.038.1VlFx0x07.00.269136932268cGreat Room 75.010.0VlFx0x06.00.516136932268cGreat Room-A st2100.018.1VlFx0x06.00.371136652274cKitchenNook st2100.018.6VlFx0x06.00.370136652274cKitchenNook-A st2100.024.0VlFx0x04.00.3544823805cLaundry st1110.023.7VlFx0x05.00.32833861514hMaster Bath st1105.023.5VlFx0x07.00.3411381492607hMaster Bed-A st1105.022.2VlFx0x04.00.3451753925hWIC Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 287 189 0.328 824 8.0 0x0 VinlFlx st3 Peak AVF 482 436 0.268 883 10.0 0x0 VinlFlx st2 st2 Peak AVF 739 796 0.268 744 14.0 0x0 VinlFlx Bold/italic values have been manually overridden 2021-May-26 08:47:49 Right-Suite® Universal 2021 21.0.07 RSU29066 Page 2 ...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb3 0x 1800 136 97.5 0.268 517 8.0 x0 0 VlFx rt1 rb2 0x 1750 148 92.1 0.284 500 8.0 x0 0 VlFx rt1 rb4 0x 2010 156 41.5 0.629 576 8.0 x0 0 VlFx rb1 0x 5640 680 94.5 0.276 487 16.0 x0 0 VlFx rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 919 964 0.268 691 16.0 0x0 VinlFlx 2021-May-26 08:47:49 Right-Suite® Universal 2021 21.0.07 RSU29066 Page 1 ...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1509Job:Manual S Compliance Report 5/25/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Jorgensen Residence, Air Conditioning UnlimitedFor: 4910 Myrtle Dr, Ft. Pierce, FL 34982 Cooling Equipment Design Conditions °F77.2Entering coil DB:Btuh19868Sensible gain:°F90.4Outdoor design DB: °F64.4Entering coil WB:Btuh6577Latent gain:°F77.4Outdoor design WB: Btuh26444Total gain:°F75.0Indoor design DB: cfm933Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: GSX160301F+ASPT37C14AModel:Goodman Mfg.Manufacturer: cfm933Actual airflow: % of load99Btuh19600Sensible capacity: % of load128Btuh8400Latent capacity: %70SHR:% of load106Btuh28000Total capacity: Heating Equipment Design Conditions °F67.4Entering coil DB:Btuh21862Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm933Actual airflow: °F50Temp. rise:% of load98kW6.3Output capacity: Meets all requirements of ACCA Manual S.