HomeMy WebLinkAboutENERGY EFFICIENCY CODEFORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the
Residential Simulated Performance Alternative shall include:
❑ This checklist
❑ Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/may be greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1. 9 - one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ if Form R405 duct leakage type indicates anything other than "default leakage'; then a completed
2020 Duct Leakage Test Report - Performance Method (usually one page)
5/26/2021 8:53:21 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
FORM R405-2020
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: 4910 Myrtle Dr PSL Prop Builder Name: PSL Prop
Street: 4910 Myrtle Dr Permit Office:
City, State, Zip: Ft. Pierce , FL , 34982 Permit Number:
Owner: Jorgensen Residence Jurisdiction: St. Lucie
Design Location: FL, ST_LUCIE_CO_INTL County: St. Lucie (Florida Climate Zone 2 )
From Plans 10, Wall Type41418.1 sqft.) Insulation Area
1. New construction or existing New ( ) a. Concrete Block - Exl Insul, Exterior R=4A 1091.20 ft2
2. Single family or multiple family Detached b. Interior Frame - Wood, Interior R=11.0 326.92 ft2
3. Number of units, if multiple family 1 c. N/A R= ft2
d. N/A R= ft2
4. Number of Bedrooms 3 11. Ceiling Types (1307.0 sgft.) Insulation Area
5. Is this a worst case? Yes a. Under Attic (Vented) R=30.0 1307.00 ft2
b. N/A R= ft2
6. Conditioned floor area above grade (ft2) 1307 c. N/A R= ft2
Conditioned floor area below grade (ft2) 0 12Ducts R ft2
7. Windows(145.6 sgft.) Description Area a. Sup: Attic, Rat: Attic, AH: Attic 6 522
.
a. U-Factor: Dbl, U=0.62 62,13 ft2
SHGC: SHGC=0.22 kBtu/hr Efficiency
b. U-Factor: Dbl, U=0.58 43.44 ft2 13 aCCent al systems
Unit 28.0 SEER:16.00
SHGC: SHGC=0.24
c. U-Factor: Dbl, U=0.65 40.00 ft2
SHGC: SHGC=0.21 14. Heating systems kBtu/hr Efficiency
Area Weighted Average Overhang Depth: 3,459 ft. a. Electric Strip Heat 21.4 COP:1.00
Area Weighted Average SHGC: 0,223
8, Skylights Area
c. U-Factor.(AVG) N/A it2 15. Hot water systems
SHGC(AVG): N/A a. Electric Cap: 50 gallons
EF: 0.960
9, Floor Types (1307.4 sqft.) Insulation Area
a. Slab -On -Grade Edge Insulation R=0.0 1307,40 ft2 b. Conservation features
b. N/A R= ft2 None
c. N/A
R= ft2 16, Credits Pstat
Total Proposed Modified Loads: 43.15 PASS
Glass/Floor Area: 0.111 Total Baseline Loads: 43.82
TAGST
1 hereby certify that the plans and specifications covered by Review of the plans and 04 _ gTl0
this calculation are in compliance with the Florida Energy specifications covered by this S ,, _ _ c vt�
Code. calculation indicates compliance o �
�/ '' with the Florida Energy Code. tune "'-
PREPARED BY: g� Before construction is completed WWW �V p
,�29 this building will be inspected for t7 l
DATE: - compliance with Section 553.908
Florida Statutes.
I hereby certify that t>Codie.
g,/a"ne Is in co ance l�COp yy�K4�y
with the Florida Ener
OWNER/AGENT:-BUILDING OFFICIAL:
DATE: DATE:
Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with 11403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 6,00 ACH50 (R402.4.1.2).
5/26/2021 8:53 AM
7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 6
PROJECT
Address Type: Street Address
Bedrooms: 3
Title: 4910 Myrtle Dr PSL Prop Lot #
Building Type: User Conditioned Area: 1307
1 Block/Subdivision:
Total Stories:
Owner Name: Jorgensen Residence PlatBook:
# of Units: 1 Worst Case: Yes
Builder Name: PSL Prop Rotate Angle: 180 Street: 4910 Myrtle Dr
Permit on:
Cross Ventilation: No County: St. Lucie
Jurisdiction: St. Lucie Whole House Fan: No City, State, Zip: FPierce ,
FL,
, 34982
Family Type: Detached
New/Existing: New (From Plans)
Comment:
CLIMATE
Design Temp Int Design Temp Heating Design Daily Temp
Design Location TMY Site 97.5 % 2.5 % Winter Summer Degree Days Moisture Range
FL, ST_LUCIE_CO_INTL FL VERO_BEACH _MUNI 39 90 70 75 299 58 Medium
BLOCKS
Number Name Area Volume
1 Entire House 1307 11300.2
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated
1 WIG 30 240 No 0 1 Yes Yes Yes
2 Master Bath 50 400 No 0
1 Yes Yes Yes
3 Master Bed 189 1512 No 0
1 1 Yes Yes Yes
4 Great Room 303 2848.2 No 2
1 Yes Yes Yes
5 Bed 3 154 1232 No 0 1 1 Yes Yes Yes
6 Lin 5 40 No 0 1 Yes Yes Yes
7 Bath 47 376 No 0 1 Yes Yes Yes
8 Bed 173 1384 No 0 1 1 Yes Yes Yes
9 Hall 24 192 No 0 1 Yes Yes Yes
10 Pantry 8 64 No 0 1 Yes Yes Yes
11 KitchenNook 217 2039.8 Yes 2
1 Yes Yes Yes
12 Foyer 83 780.2 No 0 1 Yes Yes Yes
13 Laundry 24 192 No 0 1 Yes Yes Yes
FLOORS
# Floor Type Space Perimeter Perimeter R Value Area Joist R-Value Tile Wood Carpet
_ 1 Slab -On -Grade Edge Insulatio WIC 11 it 0 30.3 ft' ----
1 0 0
2 Slab -On -Grade Edge Insulatio Master Bath 14.5 It 0 49.5 ft' ----
1 0 0
_ 3 Slab -On -Grade Edge Insulatio Master Bed 26 ft 0 188.5 ft' ----
1 0 0
4 Slab -On -Grade Edge Insulatio Great Room 20.5 ft 0 306 ft' ----
1 0 0
5/26/2021 8:53 AM
7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 6
DRM R405-2020 INPUT SUMMARY GNtGKLIJ I mrrum t
FLOORS
# Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
5 Slab -On -Grade Edge Insulatio Bed 3 26 ft 0 154.3 ft' ____ 1 0 0
6 Slab -On -Grade Edge Insulatio Lin 1 ft 0 5 ft' ____ 1 0 0
_ 7 Slab -On -Grade Edge Insulatio Bath 5.5 ft 0 46.8 ft' ____ 1 0 0
_ 8 Slab -On -Grade Edge Insulatio Bed 2 26.5 it 0 172.5 ft' ---- 1 0 0
9 Slab -On -Grade Edge Insulatio Hall 1 ft 0 24 ft' ---- 1 0
10SIab-On-Grade Edge Insulatio Pantry 1 It 0 7.5 ft' ---- 1 0 0
_ 1lSlab-On-Grade Edge Insulatio KitchenNook 12.1 ft 0 216.5 ft' ---- 1 0 0
12SIab-On-Grade Edge Insulatio Foyer 21.5 ft 0 82.5 ft' ---- 1 0 0
13SIab-On-Grade Edge Insulatio Laundry 4 ft 0 24 ft' ____ 1 0 0
ROOF
Roof Gable Roof Red Solar SA Emitt Emitt Deck Pitch
# Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg)
1 Hip Composition shingles 1461 ft' 0 ft' Medium N 0.31 No 0.9 No 0 26.57
/ ATTIC
V # Type Ventilation Vent Ratio (1 in) Area RBS IRCC
1 Full attic Vented 300 1307 ft' N N
CEILING
# Ceiling Type Space R Value Ins Type Area Framing Free Truss Type
_ 1 Under Attic (Vented) WIC 30 Blown 30 ft' 0.1 Wood
2 Under Attic (Vented) Master Bath 30 Blown 50 ft' 0.1 Wood
_ 3 Under Attic (Vented) Master Bed 30 Blown 189 ft' 0.1 Wood
_ 4 Under Attic (Vented) Great Room 30 Blown 303 ft' 0.1 Wood
_ 5 Under Attic (Vented) Bed 3 30 Blown 154 ft' 0.1 Wood
_ 6 Under Attic (Vented) Lin 30 Blown 5 ft' 0.1 Wood
7 Under Attic (Vented) Bath 30 Blown 47 ft' 0.1 Wood
_ 8 Under Attic (Vented) Bed 2 30 Blown 173 ft2 0.1 Wood
_ 9 Under Attic (Vented) Hall 30 Blown 24 ft' 0.1 Wood
_ 10 Under Attic (Vented) Pantry 30 Blown 8 ft' 0.1 Wood
_ 11 Under Attic (Vented) KitchenNook 30 Blown 217 ft' 0.1 Wood
12 Under Attic (Vented) Foyer 30 Blown 83 ft' 0.1 Wood
13 Under Attic (Vented) Laundry 30 Blown 24 ft' 0.1 Wood
5/26/2021 8:53 AM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 6
DRM R405-2020 INPUT SUMMARY CHECKLIST REPUKI
WALLS
ATdjacent \AI II Space cavity Width Height Sheathing Framing Solar Below
T R\I Ft I Ft Ip AR \/ I F M' -AbeeC. Grad °
_ 1 N=>S Exterior Concrete Block - Ext Insul WIC 4.1 5 6 8 0 44,0 fV 0 0 0.3 0
_ 2 E=>W WIC Interior Frame - Wood WIC 11 5 6 8 0 44.0 ft2 0 0,25 0.8 0
_ 3 N=>S Exterior Concrete Block - Ext InsMaster Bath 4.1 9 0 8 0 72.0 W 0 0 0.3 0
_ 4 W=>E Exterior Concrete Block - Ext InsMaster Bath 4,1 5 6 8 0 44.0 ft2 0 0 0.3 0
_ 5 W=>E Exterior Concrete Block - Ext InstUaster Bed 4.1 13 0 8 0 104.0 ft2 0 0 0.3 0
_ 6 E=>W WIC Interior Frame - Wood Master Bed 11 13 0 8 0 104.0 ft2 0 0,25 0,8 0
_ 7 W=>E Exterior Concrete Block - Ext InsCdreat Room 4.1 18 0 9 5 169.5 ft2 0 0 0,3 0
_ 8 N=>S WIC Interior Frame - Wood Great Room 11 2 6 9 5 23.5 ft2 0 0.25 0.8 0
_ 9 S=>N Exterior Concrete Block - Ext Insul Bed 3 4,1 14 6 8 0 116.0 ft2 0 0 0.3 0
_ 10 W=>E Exterior Concrete Block - Ext Insul Bed 3 4.1 11 6 8 0 92.0 ft2 0 0 0.3 0
_ 11 S=>N Exterior Concrete Block - Ext Insul Bath 4,1 5 6 8 0 44.0 ft2 0 0 0.3 0
12 E=>W Exterior Concrete Block - Ext Insul Bed 2 4.1 11 6 8 0 92.0 ft2 0 0 0,3 0
_ 13 S=>N Exterior Concrete Block - Ext Insul Bed 2 4.1 15 0 8 0 120.0 ft2 0 0 0.3 0
14 N=>S Exterior Concrete Block - Ext InddltchenNook 4.1 1 6 9 5 14.1 ft2 0 0 0.3 0
15 NE=>SW Exterior Concrete Block - Ext ln9dltchenNook 4.1 2 10 9 5 26.7 ft2 0 0 0.3 0
16 E=>W Exterior Concrete Block - Ext InsdltchenNook 4.1 5 0 9 5 47.1 ft2 0 0 0.3 0
_ 17 SE=>NW Exterior Concrete Block - Ext InsWitchenNook 4.1 2 10 9 5 26.7 ft2 0 0 0,3 0
18 E=>W Exterior Concrete Block - Ext Insul Foyer 4.1 5 0 9 5 47.1 ft2 0 0 0,3 0
19 N=>S WIC Interior Frame - Wood Foyer 11 16 6 9 5 155.4 ft2 0 0.25 0,8 0
20 E=>W Exterior Concrete Block - Ext Insul Laundry 4.1 4 0 8 0 32.0 ft2 0 0 0,5 0
DOORS
Storms U-Value Width Height Area
# Ornt Door Type Space Ft In Ft In
1 E=>W Insulated Foyer
None .13 3 6 8 20 ft2
WINDOWS
Orientation shown is the entered orientation (=>I changed to Worst Case.
/ Wall Overhang
V # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening
1 N=>S 3 Metal Low-E Double Yes 0.58 0,24 Y 4.8 W 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
2 W=>E 5 Metal Law-E Double Yes 0,58 0,24 Y 15.5 ft2 1 ft 0 in 1 It 0 in Drapesiblinds Exterior 5
_ 3 W=>E 7 Metal Low-E Double Yes 0,65 0,21 Y 40.0 ft2 8 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
4 W=>E 10 Metal Low-E Double Yes 0.58 0.24 Y 23.2 ft2 1 ft o in 1 ft 0 in Drapes/blinds Exterior 5
5 E=>W 12 Metal Low-E Double Yes 0.62 0.22 Y 23.2 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
6 NE=>SW 15 Metal Low-E Double Yes 0.62 0,22 Y 7.9 ft2 3 It 0 in 1 ft 0 in Drapes/blinds Exterior 5
_ 7 E=>W 16 Metal Low-E Double Yes 0,62 0,22 Y 23,2 ft2 3 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
8 SE=>NW 17 Metal Low-E Double Yes 0,62 0,22 Y 7.9 ft2 3 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5
5/26/2021 8:53 AM
7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 6
FORM R405-2020 INPUT SUMMARY CHECKLIS I KtIJUK t
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation
1 382.8 ft' 382.8 ft'
64 ft 8 ft 1
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000329 1130 62 116.39 .11W 6
HEATING SYSTEM
Speed Efficiency Capacity
# System Type Subtype
Block Ducts
1 Electric Strip Heat/None
COP:1 21.44 kBtu/hr 1 sys#1
COOLING SYSTEM
# System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unil/ Split Singl SEER: 16 28 kBtu/hr cfm 0.85 1 sys#1
HOT WATER SYSTEM
# System Type SubType Location EF Cap
Use SetPnt Conservation _
_ 1 Electric None Garage 0.96 50 gal 60.9 gal 120 deg
None
SOLAR HOT WATER SYSTEM
FSEC
Collector Storage
Carl# Company Name System Model # Collector Model # Area Volume FE
ft'
None None
DUCTS
-- Supply ---- --- Return ----
Air CFM 25 CFM25 HVAC #
# Location R-Value Area Location Area Leakage Type Handler TOT OUT ON RLF Heat Cool
1 Attic 6 522 ft' Attic 522 ft' Default Leakage Attic (Default) (Default)
5/26/2021 8:53 AM
7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 6
u.mr IT et IRA KRAOV .^uGl`lll IBT RFPn;RT
l-UKlvl M4uo-LULU
-
- -
TEMPERATURES
Programabie Thermostajjt:jjY
Crreiling Fans:
Heating EX� Jan [X]
Feb
H Mar
f
]
Apr
May([j`
May
]J fr[
rl
]
ri Jul
f[[l ]J
ri Aug
frE ]
ri
Sep
rr
Q Oct
Nov
Nov
Dec
Dec
Venting l[ Jan ll 11
Feb
X Mar
lXl
[
Jun
[
Thermostat Schedule: HERS 2006
Reference
Hours
Schedule Type
1
2
3
4
5
6
7
8
9
10
11
12
Cooling (WD)
PM
80
78
78
78
78
78
78
78
78
78
78
80
Cooling (WEH)
PM
78
78
78
78
78
78
78
78
78
78
78
78
Heating (WD)
PM
68
68
68
68
68
68
68
68
68
68
66
66
Heating (WEH)
PM
68
68
68
68
68
68
68
68
68
68
66
66
MASS
Mass Type
Area
Thickness
Furniture Fraction
Space
Default(8 Ibs/sq.ft.
0 ft'
0 ft
0.3
WIC
Default(8 Ibs/sq.ft.
ft'
ft
0.3
Master Bath
Default(8 Ibs/sq.ft.
ft'
ft
0.3
Master Bed
Default(8 Ibs/sq.ft.
ft'
ft
0.3
Great Room
Default(8 Ibs/sq.ft.
ft'
ft
0.3
Bed 3
Default(8 lbs/sq.ft.
fl'
ft
0.3
Lin
Default(8 lbs/sq.ft.
ft'
ft
0.3
Bath
Default(8 Ibs/sq.ft,
ft'
ft
0.3
Bed 2
Default(8 lbs/sq.ft.
ft2
ft
0.3
Hall
Default(8 lbs/sq.ft.
ft'
ft
0.3
Pantry
Default(8 lbs/sq.ft.
ft'
ft
0.3
KitchenNook
Default(8 lbs/sq.ft.
fN
ft
0.3
Foyer
Default(8 Ibs/s .ft.
ft'
ft
0.3
Laund ry
5/26/2021 8:53 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 6 of 6
FORM R405-2020
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 98
The lower the EnergyPerformance Index, the more efficient the home.
4910 Myrtle Dr, Ft. Pierce, FL, 34982
From Plans 10. Wall Type and Insulation Insulation Area
1. New construction or existing New ( ) a. Concrete Block - Ext Insul, Exterior R=4.1 1091.20 ft'
2. Single family or multiple family Detached b. Interior Frame - Wood, Interior R=1 I o 326.92 ft'
R= ft'
3. Number of units, if multiple family 1 c. N/A
4. Number of Bedrooms 3
d. NIA R= ft'
11. Ceiling Type and insulation level Insulation Area
5. Is this a worst case? Yes a. Under Attic (Vented) R=30.0 1307000 ft'
1307 b. N/A R= ft'
6. Conditioned floor area (W) c. N/A R= ft'
7. Windows" Description Area 12. Ducts, location & insulation level R fP
a. U-Factor: Dbl, U=0.62 62.13 ft' a. Sup: Attic, Ret: Attic, AH: Attic 6 522
SHGC: SHGC=0.22
b. U-Factor: Dbl, U=0.58 43.44 ft' kBtu/hr Efficiency
SHGC: SHGC=0.24 13, Cooling systems
c. U-Factor: Dbl, U=0.65 40.00 ft'
a. Central Unit 28.0 SEER:16.00
SHGC: SHGC=0.21
d. U-Factor: N/A ft' 14, Heating systems kBtu/hr Efficiency
SHGC: a. Electric Strip Heat 21.4 COPA.00
Area Weighted Average overhang Depth: 3.459 ft.
Area Weighted Average SHGC: 0.223
8. Skylights Description Area
15, Hot water systems Cap: 50 gallons
a. Electric
a. U-Factor(AVG): N/A ft' EF: 0.96
SHGC(AVG): N/A b. Conservation features
9. Floor Types Insulation Area None
a. Slab -On -Grade Edge Insulation R=0.0 1307.40 ft' Credits (Performance method) Pstat
b. N/A R= ft'
c. NIA R= ft'
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection. Othe is new EP Display Card will be completed
based on installed Code compliant fe re
Builder Signature: Date: g z�
Address of New Home:City/FL Zip: IT7{ jjUCe,r l
3 y982
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code,
Energy Conservation, contact the Florida Building Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
5/26/2021 8:53 AM
7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: 4910 Myrtle Dr Permit Number: I
Ft Pierce FL 34982
MANDATORY REQUIREMENTS -See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory)She building official shall require that an energy performance level (EPL)
display card be completed and certifed by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifcations submitted to demonstrate code wmpliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
❑ R402.4.1 Building thermal envelope7he building thermal envelope shall comply with Sections R402.4.1.1 and
R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSIIRESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as def ned in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be pertormed a[ any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, freplace and stove doors shall be closed, but not sealed, beyond the Intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall he closed, but not sealed beyond intended
infltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and coaling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑R402.4.2 Fireplaces. New wood -burning freplaces shall have light -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
freplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot (1.5 Lis/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
5/26/2021 8:53 AM EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combusiion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Seciion R1006 of the Florida Building Code, Residential.
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 al a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided far each separate healing and ccoling system.
❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verifed by testing in accordance with ANSIIRESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturer s air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise
sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the lest shall be signed by the party conducting the test and provided to the code offcial.
R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for
circulating hot water system pumps shall star[ the pump based on the identification of a demand for hot water within the occupancy. The
controls shall automatically turn off the pump when the water in [he circulation loop is at the desired temperature and when there is no
demand for hot water.
❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when healed water is used in the occupancy.
5/26/2021 8:53 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
❑R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
❑ R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100OF to 140°F (38°C to 60'C).
❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be providtopermitthe power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energysupplied to the main burner(s) of
combustion types of service water -heating systems to be turned off.
❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1,
R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
❑ fan efficacy.When installed to function as a whole -house mechanical
R403.6.1 Whole -house mechanical ventilation system
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1,
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASH
RAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be Insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based
on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design
conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other
factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed. TABLE R403.6.1
.-..._. � . =rUAAOrAI 111=1uTll ATION SYSTEM FAN EFFICACY
wnul.c-nvwc
ry ,. -
-• - - -
FAN LOCATION
AIRFLO C RATE MINIMUM
MIN�CFM/WATT)EFFICACY a
AIRFLOW RATE MAXIMU
HRV opuffityroom
Any
1.2 cfm/watt
Any
Range
In -line
Any
Any
2.8 cfm/watt
2.8 cfm/watt
Any
Any
Bathro
10
1.4 cfm/watt
`90
Bathro
90
2.8 cfm/watI
Any
For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916
5/26/2021 8:53 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
❑R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer s product Ilnes. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall 6e for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return ducts) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by aFlorida-registered engineer, in attached single- and multiple -family units, the capacity o
equipment may 6e sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or mare of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.0 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall Include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
5/26/2021 8:53 AM EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5
❑R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with avapor-retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an opemlion season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
❑ R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
❑R403.11 Portable spas (Mandatory).The energy consumption of electrio-powered portable spas shall be controlled by the
requirements of APSP-14.
R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements:
1, The minimum rated efficiency of the dehumidifier shall he greater than 1.7 liters/ kWh if the total dehumidifer capacity far the house
is less than 75 pints/day and greater than 2.38 IiterslkWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3. Any dehumidifer unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
q, Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13,
conform to the following requirements:
1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air dud between the dehumidifer inlet and outlet duct.
2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct hetween the dehumidifier and central supply duct.
3, A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4, Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-0.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
efOcacy ofgattleast 45 lumens(pea watt oryshall utilizellamps with aneefficacyfof not ess thane651umens Ipera,INled luminaires shall have an
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
ananr»t R�Sa AM EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5
2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name:
Street:
City, State, Zip:
Owner:
Design Location:
COMPONENT
General
requirements
Ceilinglattic
Walls
Windows, skylights
and doors
Rim joists
Floors
(including
above -garage
and cantilevered
floors)
Crawl space walls
Shafts, penetrations
4910 Myrtle Dr PSL Prop
4g10 Myrtle Dr
I. Pierce , FL , 34982
Jorgensen Residence
FL, ST_LUCIE_CO_INTL
AIR BARRIER CRITERIA
Builder Name: PSL Prop
Permit Office:
Permit Number:
Jurisdiction: St, Lucie
A continuous air barrier shall be installed in the building envelope.
The exterior thermal envelope contains a continuous air barrier.
Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with
the insulation and any gaps in the air barrier shall be sealed.
Aocess openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
The junction of the foundation and sill plate shall be sealed.
The junction of the top plate and the top of exterior walls shall be
sealed.
Knee walls shall be sealed.
The space between window/door jambs and framing, and
skylights and framing shall be sealed.
Rim joists shall include the air barrier.
The air barrier shall be installed at any exposed edge of
insulation.
Exposed earth in unvented crawl spaces shall be covered with
a Class I vapor retarder with overlapping joints taped.
Duct shafts, utility penetrations, and, flue shafts opening to
Narrow cavities
Garage separation Air sealing shall b
Recessed lighting Recessed light fixture
shall be sealed to
Plumbing and wiring
b
The air barrier ins
r wall
tubs shall separatlphone
box o
The air barrier shalls
boxes or air-sealegister
boots
r
HVAC supply andthermal
enveloped
When required to
sealed in a manner
Caulking or other
INSULATION INSTALLATION CRITERIA
permeable insulation shall
not be used as a sealing material.
The insulation in any dropped ceiling/soffit
shalI be aligned with the air barrier.
e provided between the garage and conditioned spa
urea installed in the building thermal envelope
the finished surface.
tolled at exterior walls adjacent to showers and
e them from the showers and tubs.
all be installed behind electrical or communication
d boxes shall be installed.
return register boots that penetrate building
shall be sealed to the sub -floor, wall covering or
be sealed, concealed fire sprinklers shall only be
that is recommended by the manufacturer.
adhesive sealants shall not be used to fill voids
be in accordance with the provisions of ICC-400.
Cavities within corners and headers of frame walls
shall be insulated by completely filling the cavity
with a material having a thermal resistance of R-3
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
,...� inpinnm nlinnment with the air barrier.
Rim joists shall be insulated.
Floor framing cavity insulation she be installed fo
maintain permanent contact with the underside of
subFloor decking, or floor framing cavity insulation
shalI be permitted to be in contact with the top side
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Where provided instead of floor insulation, insulation
shall be permanently attached to the crawlspace wal
Batts in narrow cavities shall be cut to fit, or narrow
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
Recessed light fixtures installed in the building
thermal envelope shall be air tight and IC rated.
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
Exterior walls adjacent to showers and tubs shall
be insulated.
a. In addition, inspection of log walls shall
5/26/2021 8:53 AM EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software
Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction: St. Lucie
Permit #:
Job Information
Builder: PSL Prop Community: Lot: NA
Address: 4910 Myrtle Dr
City: Ft. Pierce State: FL Zip: 34982
Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ERI Method
O PRESCRIPTIVE METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air
changes per hour at a pressure of 0.2 inch w.g. (50 Pascals) in Climate Zones 1 and 2.
O PERFORMANCE or ERI METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding
the selected ACH(50) value, as shown on Form R405-2020 (Performance) or R406-2020 (ERI), section labeled as infiltration, sub -section ACH50.
ACH(50) specified on Form R405-2020-Energy Cale (Performance) or R406-2020 (ERI): 6.000
x 60 11300 — Method for calculating building volume:
CFM(50) Building Volume ACH(50) O Retrieved from architectural plans
PASS 0 Code software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if Installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
5/26/2021 8:53:39 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1