HomeMy WebLinkAboutREVISED PROJECT INFORMATIONCalculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Oct-11 13:36:05
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1509Job:Load Short Form 5/25/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Jorgensen Residence, NisAir Air ConditioningFor:
4910 Myrtle Dr, Ft. Pierce, FL 34982
Design Information
InfiltrationClgHtg
Blower doorMethod9041Outside db (°F)
3 (partial) / 1Shielding / stories7570Inside db (°F)
50 Pa / 0 cfmPressure / AVF1529Design TD (°F)
L-Daily range
5030Inside humidity (%)
572Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond ML14XC1S030-230A**
AHRI ref Coil CBA27UHE-030-230*++TDR
AHRI ref 10259437
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW6.3 Sensible cooling Btuh20300
Heating output Btuh21437 Latent cooling Btuh8700
Temperature rise °F20 Total cooling Btuh29000
Actual air flow cfm967 Actual air flow cfm967
Air flow factor cfm/Btuh0.046 Air flow factor cfm/Btuh0.051
Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.76
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
WIC 30 968 296 44 15
Master Bath 50 1610 572 74 29
Master Bed 189 2797 2313 128 119
Great Room 306 3589 4551 164 233
Bed 3 154 3292 2517 150 129
Lin 5 0 0 0 0
Bath 47 655 254 30 13
Bed 2 173 3405 2311 155 119
Hall 24 0 0 0 0
Pantry 8 0 0 0 0
KitchenNook 217 2510 4579 115 235
Foyer 83 1911 646 87 33
Laundry 24 442 808 20 41
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Oct-11 13:36:05
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2
...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
House 1307 21181 18847 967 967
Other equip loads 1420 754
Equip. @ 0.95 RSM 18699
Latent cooling 6163
TOTALS 1307 22601 24862 967 967
2021-Oct-11 13:36:05
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1509Job:Building Analysis 5/25/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Jorgensen Residence, NisAir Air ConditioningFor:
4910 Myrtle Dr, Ft. Pierce, FL 34982
Design Conditions
Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
Blower doorMethod)L(15-Daily range (°F)
3 (partial) / 1Shielding / stories77-Wet bulb (°F)
50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph)
Heating
Walls
Glazing
Other
Ceilings
Floors
Infiltration
Ducts
Ventilation
% of loadBtuhBtuh/ft²Component
17.138723.1Walls
11.5260717.9Glazing
0.3743.7Doors
9.220741.6Ceilings
21.348063.73.7Floors
14.131852.9Infiltration
20.24562Ducts
00Piping
00Humidification
6.31420Ventilation0Adjustments
100.022601Total
Cooling
Walls
Glazing
Other
Ceilings
Infiltration Ducts
Internal Gains
Ventilation
% of loadBtuhBtuh/ft²Component
11.923401.9Walls
19.1374225.7Glazing
0.4753.7Doors
8.215981.2Ceilings
000Floors
4.89480.9Infiltration
26.15124Ducts
3.8754Ventilation
25.65020Internal gains
00Blower
0Adjustments
100.019600Total
Latent Cooling Load = 6163 Btuh
Overall U-value = 0.228 Btuh/ft²-°F
Data entries checked.
2021-Oct-11 13:36:05
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1509Job:Component Constructions 5/25/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Jorgensen Residence, NisAir Air ConditioningFor:
4910 Myrtle Dr, Ft. Pierce, FL 34982
Design Conditions
Location: CoolingHeatingIndoor:
7570Indoor temperature (°F)St Lucie Co Intl, FL, US
1529Design TD (°F)ft26Elevation:
5030Relative humidity (%)°N28Latitude:
Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating
Infiltration:9041Dry bulb (°F)
Blower doorMethod)L(15-Daily range (°F)
3 (partial) / 1Shielding / stories77-Wet bulb (°F)
50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph)
Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr
BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft²
Walls
Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 3953.155.10.109125n 2532.02
382.02593.155.10.10919ne
3052.024773.155.10.109152e
382.02593.155.10.10919se
5642.028823.155.10.109280s
6662.0210403.155.10.109330w
18632.0229133.155.10.109925all
Partitions
Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16"
OC Stud
4761.469592.9411.00.101327
Windows
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (3.17 ft window ht, 1 ft sep.); 6.8 ft head ht
5511.58016.800.5805n
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 3 ft overhang (5.25 ft window ht, 1 ft sep.); 6.8 ft head ht
17422.114218.000.6208ne
54223.441718.000.62023e
12616.014218.000.6208se
84221.670018.000.62039all
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.25 ft window ht, 1 ft sep.); 6.8 ft head ht
63027.241718.000.62023e
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht
43928.126216.800.58016w
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (5.25 ft window ht, 1 ft sep.); 6.8 ft head ht
65228.139016.800.58023w
2021-Oct-11 13:36:05
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2
...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21);
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 8 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht
64516.075818.800.65040w
Doors
Fbrgls Door 753.73743.697.00.12720e
Ceilings
Attic, Shngls, R-20 Roof Deck Ins, 1/2" Gyp Bd Int Fnsh 21.00.4051307 15981.2220741.59
Floors
On Grade Depth, Tile Flr Fnsh 00480628.700.989168
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Oct-11 13:36:05
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1509Job:Project Summary 5/25/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Jorgensen Residence, NisAir Air ConditioningFor:4910 Myrtle Dr, Ft. Pierce, FL 34982
Notes:
Design Information
St Lucie Co Intl, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75
Design TD °F29 Design TD °F15Daily range L
Relative humidity %50Moisture difference gr/lb57
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh16619 Structure Btuh13722
Ducts Btuh4562 Ducts Btuh5124Central vent (45 cfm) 1420 Btuh Central vent (45 cfm) Btuh754
Outside air Outside airHumidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh22601 Use manufacturer's data n
Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh18699
Method Latent Cooling Equipment Load SizingBlower door
Shielding / stories 3 (partial) / 150 Pa / 0 cfmPressure / AVF Structure Btuh2965
Ducts Btuh1476Central vent (45 cfm) Btuh1721
CoolingHeating Outside air13071307Area (ft²) Equipment latent load Btuh6163
1130511305Volume (ft³)Air changes/hour 0.300.53 Equipment Total Load (Sen+Lat)Btuh24862
Equiv. AVF (cfm) 56100 Req. total capacity at 0.70 SHR ton2.2
Heating Equipment Summary Cooling Equipment Summary
Make Make LennoxTrade Trade LENNOX
Model Cond ML14XC1S030-230A**AHRI ref Coil CBA27UHE-030-230*++TDR
AHRI ref 10259437Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW6.3 Sensible cooling Btuh20300Heating output Btuh21437 Latent cooling Btuh8700
Temperature rise °F20 Total cooling Btuh29000Actual air flow cfm967 Actual air flow cfm967
Air flow factor cfm/Btuh0.046 Air flow factor cfm/Btuh0.051Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.76
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Oct-11 13:36:05Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name House WIC
2 Exposed wall 167.6 ft 11.0 ft
3 Room height 8.6 ft 8.0 heat/coolft
4 Room dimensions ft5.5x5.5
5 Room area 1307.3 ft²30.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 130 125 395 253 44 44 139 89
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 5 0 80 55 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 27 19 59 38 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 8 0 142 174 0 0 0 0
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 218 152 477 305 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 23 0 417 630 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 23 7 417 542 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 20 20 74 75 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 27 19 59 38 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 8 6 142 126 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 280 280 882 564 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 409 330 1040 666 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 16 0 262 439 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 23 0 390 652 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 40 34 758 645 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 327 327 959 476 44 44 129 64
CC Attic, Shngls, R-20 0.405Attic, Shngls, R-20 0.405 --1.591.59 1.221.22 1307 1307 2074 1598 30 30 48 37
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1307 168 4806 0 30 11 315 0
6 c) AED excursion 479 -12
Envelope loss/gain 13434 7754 631 177
12 a) Infiltration 3185 948 129 38
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 4 920 0 0
Appliances/other 4100 0
Subtotal (lines 6 to 13)16619 13722 760 216
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 16619 13722 760 216
15 Duct loads 27%37%4562 5124 27%37%209 81
Total room load 21181 18847 968 296
Air required (cfm)Air required (cfm)967 967 44 15
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Oct-11 13:36:05Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Master Bath Master Bed
2 Exposed wall 14.5 ft 26.0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft9.0x5.5 ft14.5x13.0
5 Room area 49.5 ft²188.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 72 67 212 136 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 5 0 80 55 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 44 44 139 89 104 88 279 178
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 16 0 262 439
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 104 104 306 152
CC Attic, Shngls, R-20 0.405Attic, Shngls, R-20 0.405 --1.591.59 1.221.22 50 50 79 60 189 189 299 230
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 50 15 416 0 189 26 746 0
6 c) AED excursion -24 95
Envelope loss/gain 925 315 1891 1094
12 a) Infiltration 339 101 304 90
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 500
Subtotal (lines 6 to 13)1264 416 2195 1684
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 1264 416 2195 1684
15 Duct loads 27%37%347 155 27%37%603 629
Total room load 1610 572 2797 2313
Air required (cfm)Air required (cfm)74 29 128 119
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Oct-11 13:36:05Right-Suite® Universal 2021 21.0.08 RSU29066 Page 3...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Great Room Bed 3
2 Exposed wall 20.5 ft 26.0 ft
3 Room height 9.4 heat/coolft 8.0 heat/coolft
4 Room dimensions ft17.0x18.0 ft154.3x1.0
5 Room area 306.0 ft²154.3 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 116 116 365 234
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 169 129 406 260 92 69 217 139
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 23 0 390 652
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 40 34 758 645 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 24 24 69 34 0 0 0 0
CC Attic, Shngls, R-20 0.405Attic, Shngls, R-20 0.405 --1.591.59 1.221.22 306 306 485 374 154 154 245 189
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 306 21 588 0 154 26 746 0
6 c) AED excursion 482 179
Envelope loss/gain 2307 1796 1963 1393
12 a) Infiltration 494 147 607 181
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 2 460 0 0
Appliances/other 900 250
Subtotal (lines 6 to 13)2801 3303 2570 1824
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 15 11 12 9
14 Subtotal 2816 3314 2583 1833
15 Duct loads 27%37%773 1237 27%37%709 684
Total room load 3589 4551 3292 2517
Air required (cfm)Air required (cfm)164 233 150 129
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Oct-11 13:36:05Right-Suite® Universal 2021 21.0.08 RSU29066 Page 4...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Lin Bath
2 Exposed wall 0 ft 5.5 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft2.5x2.0 ft5.5x8.5
5 Room area 5.0 ft²46.8 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 44 44 139 89
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-20 0.405Attic, Shngls, R-20 0.405 --1.591.59 1.221.22 5 5 8 6 47 47 74 57
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 5 0 0 0 47 6 158 0
6 c) AED excursion 0 -10
Envelope loss/gain 8 6 371 136
12 a) Infiltration 0 0 129 38
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)8 6 499 174
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -8 -6 15 11
14 Subtotal 0 0 514 185
15 Duct loads 27%37%0 0 27%37%141 69
Total room load 0 0 655 254
Air required (cfm)Air required (cfm)0 0 30 13
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Oct-11 13:36:05Right-Suite® Universal 2021 21.0.08 RSU29066 Page 5...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Bed 2 Hall
2 Exposed wall 26.5 ft 0 ft
3 Room height 8.0 heat/coolft 8.0 heat/coolft
4 Room dimensions ft15.0x11.5 ft8.0x3.0
5 Room area 172.5 ft²24.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 92 69 217 139 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 23 0 417 630 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 120 120 378 242 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-20 0.405Attic, Shngls, R-20 0.405 --1.591.59 1.221.22 173 173 274 211 24 24 38 29
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 173 27 760 0 24 0 0 0
6 c) AED excursion 21 -2
Envelope loss/gain 2046 1243 38 28
12 a) Infiltration 619 184 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 250 0
Subtotal (lines 6 to 13)2665 1677 38 28
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 7 5 -38 -28
14 Subtotal 2672 1682 0 0
15 Duct loads 27%37%733 628 27%37%0 0
Total room load 3405 2311 0 0
Air required (cfm)Air required (cfm)155 119 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Oct-11 13:36:05Right-Suite® Universal 2021 21.0.08 RSU29066 Page 6...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Pantry KitchenNook
2 Exposed wall 0 ft 12.1 ft
3 Room height 8.0 heat/coolft 9.4 heat/coolft
4 Room dimensions ft3.0x2.5 ft216.5x1.0
5 Room area 7.5 ft²216.5 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 14 14 44 28
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 27 19 59 38
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 8 0 142 174
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 47 24 75 48
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 0 0 0 0 23 7 417 542
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 27 19 59 38
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 0 0 0 0 8 6 142 126
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0
CC Attic, Shngls, R-20 0.405Attic, Shngls, R-20 0.405 --1.591.59 1.221.22 8 8 12 9 217 217 343 265
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 8 0 0 0 217 12 347 0
6 c) AED excursion 0 -190
Envelope loss/gain 12 9 1628 1068
12 a) Infiltration 0 0 334 99
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 2 460
Appliances/other 0 1700
Subtotal (lines 6 to 13)12 9 1961 3328
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -12 -9 8 6
14 Subtotal 0 0 1969 3334
15 Duct loads 27%37%0 0 27%37%541 1245
Total room load 0 0 2510 4579
Air required (cfm)Air required (cfm)0 0 115 235
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Oct-11 13:36:05Right-Suite® Universal 2021 21.0.08 RSU29066 Page 7...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1509Job:Right-J® Worksheet 5/25/2021Date:House Chris BatemanBy:Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
1 Room name Foyer Laundry
2 Exposed wall 21.5 ft 4.0 ft
3 Room height 9.4 heat/coolft 8.0 heat/coolft
4 Room dimensions ft16.5x5.0 ft6.0x4.0
5 Room area 82.5 ft²24.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nn 16.8216.82 11.4811.48 0 0 0 0 0 0 0 0
.WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0
.GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0
11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 47 27 85 54 32 32 101 64
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 27.1827.18 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 ee 17.9817.98 23.3723.37 0 0 0 0 0 0 0 0
DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 20 20 74 75 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 sese 17.9817.98 16.0016.00 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0
WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 ww 16.8216.82 28.1328.13 0 0 0 0 0 0 0 0
GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 ww 18.8518.85 16.0516.05 0 0 0 0 0 0 0 0
PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 155 155 456 226 0 0 0 0
CC Attic, Shngls, R-20 0.405Attic, Shngls, R-20 0.405 --1.591.59 1.221.22 83 83 131 101 24 24 38 29
FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 83 22 617 0 24 4 115 0
6 c) AED excursion -27 -34
Envelope loss/gain 1362 429 254 60
12 a) Infiltration 137 41 93 28
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230230 0 0 0 0
Appliances/other 0 500
Subtotal (lines 6 to 13)1499 470 347 588
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 1499 470 347 588
15 Duct loads 27%37%412 176 27%37%95 220
Total room load 1911 646 442 808
Air required (cfm)Air required (cfm)87 33 20 41
2021-Oct-11 13:36:06
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1509Job:Duct System Summary 5/25/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Jorgensen Residence, NisAir Air ConditioningFor:
4910 Myrtle Dr, Ft. Pierce, FL 34982
CoolingHeating
External static pressure in H2O0.70in H2O0.70
Pressure losses in H2O0in H2O0
Available static pressure in H2O0.70in H2O0.70
Supply / return available pressure 0.439 / 0.261 in H2O in H2O0.439 / 0.261
Lowest friction rate in/100ft0.268in/100ft0.268
Actual air flow cfm967cfm967
Total effective length (TEL) ft261
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st3125.031.5VlFx0x04.00.2801636655hBath
st3125.038.4VlFx0x07.00.2681421863405hBed 2
st3125.038.7VlFx0x07.00.2681551803292hBed 3
st2100.024.9VlFx0x06.00.351401051911hFoyer
st3125.038.1VlFx0x07.00.269140982276cGreat Room
75.010.0VlFx0x06.00.516140982276cGreat Room-A
st2100.018.1VlFx0x06.00.371141692289cKitchenNook
st2100.018.6VlFx0x06.00.370141692289cKitchenNook-A
st2100.024.0VlFx0x04.00.3545024808cLaundry
st1110.023.7VlFx0x06.00.32835881610hMaster Bath
st1105.023.5VlFx0x07.00.3411421532797hMaster Bed-A
st1105.022.2VlFx0x04.00.3451853968hWIC
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st1 Peak AVF 294 196 0.328 844 8.0 0x0 VinlFlx
st3 Peak AVF 501 453 0.268 638 12.0 0x0 VinlFlx st2
st2 Peak AVF 767 824 0.268 771 14.0 0x0 VinlFlx
Bold/italic values have been manually overridden
2021-Oct-11 13:36:06
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2
...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb3 0x 1860 142 97.5 0.268 534 8.0 x0 0 VlFx rt1
rb2 0x 1800 155 92.1 0.284 516 8.0 x0 0 VlFx rt1
rb4 0x 2060 161 41.5 0.629 591 8.0 x0 0 VlFx
rb1 0x 5870 702 94.5 0.276 503 16.0 x0 0 VlFx rt1
Return Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
rt1 Peak AVF 954 999 0.268 716 16.0 0x0 VinlFlx
2021-Oct-11 13:36:06
Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1
...nts\Wrightsoft HVAC\4910 Myrtle Dr PSL Prop.rup Calc = MJ8 Front Door faces: N
1509Job:Manual S Compliance Report 5/25/2021Date:House Chris BatemanBy:
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com
Project Information
Jorgensen Residence, NisAir Air ConditioningFor:
4910 Myrtle Dr, Ft. Pierce, FL 34982
Cooling Equipment
Design Conditions
°F76.7Entering coil DB:Btuh19600Sensible gain:°F90.4Outdoor design DB:
°F63.9Entering coil WB:Btuh6163Latent gain:°F77.4Outdoor design WB:
Btuh25764Total gain:°F75.0Indoor design DB:
cfm967Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
ML14XC1S030-230A**+CBA27UHE-030-230*++TDRModel:LennoxManufacturer:
cfm967Actual airflow:
% of load104Btuh20300Sensible capacity:
% of load141Btuh8700Latent capacity:
%70SHR:% of load113Btuh29000Total capacity:
Heating Equipment
Design Conditions
°F68.2Entering coil DB:Btuh22601Heat loss:°F41.0Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Elec stripEquipment type:
Model:Manufacturer:
cfm967Actual airflow:
°F50Temp. rise:% of load95kW6.3Output capacity:
Meets all requirements of ACCA Manual S.