HomeMy WebLinkAboutDrawingsSTRUCTURAL LUMBER & FRAMING NOTES A 1. TIME QUALITY OF LUMBER AND THE DESIGN FOR LOAD SUPPORTING MEMBERS SHALL CONFORM TO THE STANDARD. "NATIONAL DESIGN SPECIFICATION FOR STRESS GRADE LUMBER AND ITS FASTENINGS", LATEST EDITION. 2. MINIMUM LUBBER GRADE SHALL BE AS FOLLOWS: TIMBER GREATER THAN THAN 5" THICK SYP, 20% m.c., #1 WITH fb = 1500 psi LEDGERS, HEADERS, JOIST SYP, 19% m.c., #2 WITH fb = varies /size BEAMS, BLOCKING, PLATES, ETC. STUDS AND BRACING SYP, 19% mx,., #2 WITH fc = 975 TRUSSES: SYP, 19% M.C., 2400f�(CHORDS); i3s(,WEBS) 3. WOOD IN CONTACT WITH MASONRY, CONCRETE OR EXPOSED TO WEATHER TO BE PRESSURE TREATED. 4. PLYWOOD SHALL MEET THE REQUIREMENTS OF THE LATEST EDITION( OF U.S. PRODUCT STANDARD P.S.I., AMERICAN PLYWOOD ASSOCIATION. ROOF DIAPHRAGMS SHALL BE STRUCTURAL 1, C-D EXTERIOR GRADE, 6. NOT USED 7. NOT USED B,. NOT USED 9, NOT USED 10. WHERE ROOF DECK IS 6/8®s CDX PLYWOOD, PLYWOOD SHALL BE PLACED IN FULL 4'x68 PANELS AS MUCH AS POSSIBLE., WITH LONG DIMENSION (FACE GRAIN) ORIENTED TO SPAN ACROSS TRUSSES. PROVIDE PURLINS BETWEEN TRUSSES ALONG LONG EDGES OF PANELS, WHEN PANELS ARE ATTACKED DIRECTLY TO TRUSS,/ RATER, ATTACH WITH WITH 10d (DEFORMED SHANK NAILS AT " o.C-_ AT -ALL -PANEL EDGES AND AT 12" O.C. AT INTERMEDIATE SiUPPORTS. � f r 11. THE NUMBER AND SIZE OF NAILS CONNECTING WOOD MEMBERS SHALL NOT BE LESS THAN THOSE SET FORTH IN TABLE 2 06.3.1 OF FLORIDA BUILDING COME. ALL NAILS SHALL BE COMMON NAILS U.O.N. ALL NAILS USED FOR EXTERIOR WALL/ROOF FRAMING SHALL BE HOT -DIP GALVANIZED. 12, ALL BOLTS SHALL BE GALVANIZED STANDARD MACHINE BOLTS WITH MALLEABLE IRON OR GALVANIZED STEEL PL. WASHERS WHEN HEAD OR NUT BEARS ON WOOD. HOLES FOR BOLTS SMALL BE DRILED WITH A BIT 1 /32` LARGER THAN NOMINAL BOLT DIAMETER. TIGHTEN ALL BOLTS BEFORE PLASTERING. 13. LAG BOLTS AND SCREWS SMALL BE PREDRILLED. THE DIA. OF PREDRILLED HOLES SHALL BE 60OF SHANK DIAMETER. THE THREADED PORTION OF THE SCREW SHALL BE INSERTED BY TURNING WITH A WRENCH, NOT BY DRIVING WITH A HAMMER. PENETRATION OF THREADED PORTION SHALL BE 7 DIAMETERS MININUM. 14. NO STRUCTURAL MEMBER SHALL BE CUT WITHOUT THE APPROVAL OF OWNER & ARCHITECT OF RECORD. ANY CUTTING, NOTCHING OR BORING OF WOOD SHALL CONFORM TO THE LOCAL BUILDING CODE, 15. ALL HARDWARE CONNECTING WOOD MEMBERS SHALL BE RECESSED WHEN REQUIRED BY ARCHITECTURAL FINISH, VERIFY WITH ARCHITECTURAL DRAWINGS. 16. ALL WOOD CONNECTIONS INDICATED BY SIMPSON STRONG TIE UNLESS OTHERWISE NOTED, USP, SEMCO OR OTHER MANUFACTURERS MAY BE SUBMITTED IF THEY ARE EQUAL OR BETTER IN CAPACITIES, INCLUDING UPLIFT, �0 Ir 11 P ig e r c J SEC 19 20 TWNSHP 36S. RANGE 4; E® 157.76 FT OF N 251 FT OF S 1 2. OF SE 1/4 OF SEC` 19, LYC E OF FEC RR AND S 157.76 ET CE N 21 FT OF FRACTIONAL SEC 20 - LESS SR 707®66/1 08 AS RECORDED IN PUBLIC RECORDS OF ST LUCIE COUNTY, FLORIDA PROJECT DESCRIPTION: LATERAL AND GRAVITY LOAD. REMODEL OF EXISTING RESIDENCE, IN 17, ALL EXTERIOR FRAMED WALLS & SHEAR WALLS SHALL BE 2x6 AT 16" O.C. AND PHASES. REPLACE WINDOWS AND SHALL BE SHEATHED WITH MIN. 1,/2" PLYWOOD NAILED WITH 10d NAILS DOORS CONSTRUCT CABINETS AND AT 6" O,C. ALONG ALL EDGES & 12" O.C. AT INTERMEDIATE SUPPORTS TYP, m r % A c-1_ M 1 i � k. A n l k l � M r-,� -7M 1 f`, A � A K € n EXISTING SITErrm'6LANSCALE NTS DRAWING INDEX AO.1 COVER DRAWING INDEX, CODE ANALYSIS & NOTES A0.2 SCHEDULES & NOTES A1.1 EXISTING PLAN A1.2 REMODEL ENTIRE FLOOR PLAN A2'..1 PHASE 1-DEMOLITION PLAN, PROPOSED PLAN A2.2 PHASE 1- ELECTRICAL MECHANICAL A3.1 PHASE 2-DEMOLITION PLAN A3.2 PHASE 2-REMODEL FLOOR PLAN A4.1 BUILDING ELEVATION A4.2. BUILDING ELEVATION & SECTIONS M3.1 MECHANICAL PLAN, SCHEDULE & NOTES P3.1 PLUMBING PLAN & NOTES P3.2 PLUMBING RISER & NOTES E3.1 ELECTRICAL PLAN & NOTES E3.2 RISER DIAGRAM & SCHEDULES & LOAD CALC. CODE ANALYSIS: Building Typed EXISTING RESIDENCE Project Description: Phased Remodel Classification of Work: Level 3 Chpt 6 & 7 Classif.of Hazard of Contents: Ordinary Hazard Occupancy Classifications Residential: .--..- LIVING AREA (CONDITIONED) NET = 207 S.F. Unconditioned Attached Utility = 276 s.f. Carport & Porches = s.f. Existing under roof = 3309 s.f. Site Area = 86,104 s.f, (1.98 Acre) G 11 iD (DZ-0 7' FILE COPY I ............ . ............. .. .............................. ........ ......... ................. .......................................... 11_.­­.­­­ ................. %­­­­ . ........ .................................................... p­­,,.p . ........................................ I ....... . ...... PLAN NOTES: 1. WRITTEN DIMENSIONS SHALL. HAVE PRECEDENCE OVER SCALE DIMENSIONS. Contractors shall verify and be responsible for dimensions and field conditions of job. 2. Not Used 3. Dimensions (Exterior) from face of masonry or concrete, to face of wall sheathing on stud, and (Interior) face of wall finish (Masonry or gyp. bd) to stud wall finish unle�ss otherwise noted. Studs assumed to be norn. 4" interior & 6" exteiri.:)r wall UON 4. Door head heights shall be 6'-8" unless otherwise noted (UON). 5. Window unit designations are based on typical aluminum units. A 1/2" insulated glazing unit is recommended. A comparable size/ quality unit by various manufacturers may be used as long as the required wind load presures are ceritified in compliance. vts ® 10/22/21 Permit Comments ./////l/��.:,.F.C/f/fd//I9/.G.: ....r:.4�f�.�Y. ..:, .f, �l. /,...:./.i»,..!/:9/fib E•1H/!f%..::: GraphicARCHITECT Designer. - 0013444 •: Pierce, 349812 J 00, 6. �fi•;fffffffffffil.;%;:.::::%J/l/lfll/fl//l;Y/JJ/JSG:;�S:Sik.".D:/If.Ufff.+rY:`ffffffffff/ff.U/ f!'% / ::::. y • WNIvk AO.1 iK////lff ::...»MfiYfl?/10.•`:..:9H/L:5Y:3%f///1 :.,.6:Y/f?/: Y:;:e:..;: �iff:Nf:'ff?b/f/./f.`;::�iYf/f 1 /4" = 1'-0WOW ENA 10-13-21 f:s^ffiaff ::. :>rfr,.:sva�aff.:✓fffff,,:,�,,,,,,,,nr.�f�:earotrxt �h,::: �: ,: rea f/.C{Cf.......�/l„rf{f/.!{C.....:..../// ....:/.L/ff ........, //%,...........b.;.;.:,..if/..: , .."i:.;;;:::;;;:i:.:' .:..::.:.: ..:. .:.::.y.: «ff.,•............. .... ...r.»............., «...:.:::::::::::::::::,n ::.. , .......... .... :.......... :: ... f 1�/s>%i{If %%... ,J. STRUCTURAL NOTES GENERAL ALL MATERIALS AND WORKMANSHIP TO CONFORM TO THE LATEST EDITION OF THE FLORIDA BUILDING CODE (2020) 1. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO STARTING CONSTRUCTION AND THE OWNER SHALL BE NOTIFIED IMMEDIATELY OF ANY DISCREPANCIES OR INCONSISTENCIES. DO NOT SCALE DIMENSIONS WHERE NO DIMENSION IS PROVIDED. CONSULT WITH THE OWNER FOR CLARIFICATION BEFORE PROCEEDING WITH THE WORK. 2. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. 3. DESIGN LOADS: TRUSS DESIGN FIRST FLOOR LIVE LOAD 100 PSF above Grade (MIN. 40 PSF) TOP CHORD LIVE LOAD - 20 PSF ROOF LIVE LOAD 20 PSF TOP CHORD DEAD LOAD - 7 PSF (MIN.) ROOF DEAD LOAD 10 PSF BOTTOM CHORD LIVE LOAD- 0 PSF RISK CATEGORY II BOTTOM CHORD DEAD LOAD-10 PSF MIN. WIND LOAD 160 MPH (PLUS UP TO 100 LB CONCENTRATED LOAD) IMPORTANCE FACTOR 1.00 EXPOSURE CATEGORY B INTERNAL PRESSURE COEF. 0.18f (BASIC LOAD VELICITY PRESSURE _ _-- PSF for Roof & Wall END ZONE which is 15 Ft. or less Mean HQ PLUS CONCENTRATED LOADS DUE TO MECHANICAL EQUIPMENT & 100 LB. SUSPENDED OWNER ITEMS (SUCH AS CHANDLIERS, LIGHTS, ETC.) REFER TO ELECTRICAL PLAN FOR LIGHT & CHANDLIER LOCATIONS 4. THE CONTRACT ARCHITECTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED FACILITY. UNLESS OTHERWISE SHOWN THESE DOCUMENTS DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE BUT ARE NOT LIMITED TO BRACING, SHORING OR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. 5. THE FOUNDATION DESIGN SHOWN IN THESE DRAWINGS IS BASED ON THE ASSUMPTION THAT THE SOIL BENEATH THE BUILDING IS WELL COMPACTED SOIL WITH MINIMUM ALLOWABLE BEARING PRESSURE OF 2,000 PSF. THE CONTRACTOR SHALL HAVE ALL FILL TESTED FOR COMPACTION TO CONFORM TO 2000 psf ALLOWABLE BEARING PRESSURE OR TO OWNER FURNISHED SOIL REPORT RECOMMENDATIONS FOR COMPACTION AND SOIL BEARING CAPACITY. 6. TRUSS SHOP DRAWINGS (Where Applicable) SHALL BE SUBMITTED BY THE OWNER OR CONTRACTOR AS REQUIRED TO BUILDING DEPARTMENT FOR PERMITTING. SHOP DRAWINGS AND CALCULATIONS SHALL BE SIGNED AND SEALED BY A REGISTERED STRUCTURAL ENGINEER IN THE STATE OF FLORIDA. SHOP DRAWINGS SHALL SHOW SIZES, DESIGN VALUES, MATERIALS AND DIMENSIONAL RELATIONSHIP OF COMPONENTS AS WELL AS BEARING AND ANCHOR DETAILS FOR TRUSS TO TRUSS AND/OR TRUSS GIRDER CONNECTIONS. 7. MASONRY UNITS: STANDARD UNITS: ASTM C90, GRADE N-II, NORMAL WEIGHT 8 x 16 INCH FACE SIZE, 8" THICKNESS. TYPE II, MOISTURE CONTROLLED UNITS W/ DRY BLOCK HOLLOW LOADBEARING BLOCK: ASTM C 90 (FL MODIFIED C90) WEIGHT CLASSIFICTION: NORMAL WEIGHT. (125 pcf MIN.) COMPRESSIVE STRENGTH: fm = 1500 PSI MORTAR FOR UNIT MASONRY. COMPLY WITH ASTM C 270. CEMENTITOUS MATERIAL: PREMIXED MASONRY CEMENT OF FORMULATION REQUIRED. AGGREGATE: NATURAL OR MANUFACTURED SAND MORTAR MIX CONCRETE 1. ALL PHASES OF WORK PERTAINING TO THE CONCRETE CONSTRUCTION SHALL CONFORM TO THE BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE. ACI 318 AND STANDARD BUILDING CODE REQUIREMENTS. 2. ALL CONCRETE SHALL BE REGULAR WIGHT CONCRETE WITH A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI A 28 DAYS. 3. ALL CONCRETE MIXES SHALL BE DESIGNED BY A RECOGNIZED TESTING LABORATORY AND APPROVED BY THE OWNER, IF REQUIRED BY OWNER. 4. COMPRESSIVE STRENGTH TEST REPORTS SHALL BE SUBMITTED TO THE OWNER & AND AVAILABLE FOR THE BUILDING DEPARTMENT IF REQUIRED. 5. AGGREGATES IN REGULAR WEIGHT CONCRETE SHALL CONFORM TO ASTM C-33. 6. PORTLAND CEMENT: TYPE I OR II CONFORMING TO ASTM C-150. LOW ALKALI, MILL TESTED WITH CERTIFICATES OF COMPLIANCE REQUIRED. 7. CONCRETE MIXING OPERATIONS. ETC. SHALL CONFORM TO ASTM C-94. 8. UNLESS OTHERWISE SHOWN OR NOTED, CONCRETE COVER FOR REINFORCING BARS TO FACE OF CONCRETE SHALL BE AS FOLLOWS: A. CONCRETE IN CONTACT WITH EARTH, UNFORMED ------ 3" B. CONCRETE IN CONTACT WITH EARTH, FORMED ------- 2" C. WALL EXTERIOR FACE ------------------- 1 1 /2" D. WALL INTERIOR FACE ---------------------- 1 " 9. ALL REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS SHALL BE WELL SECURED IN POSITION PROIR TO PLACING CONCRETE. 10. REFER TO ARCHITECTURAL DRAWINGS FOR MOLDS, GROOVES, ORNAMENTS, CLIPS OR GROUNDS REQUIRED TO BE CAST INTO THE CONCRETE AND FOR EXTENT OF DEPRESSIONS, RAMPS, ETC. 11. PROJECTION CORNERS OF SLABS, BEAMS, WALLS, COLUMNS, ETC. SHALL BE FORMED SHALL BE FORMED WITH 3/4" CHAMFER, UNLESS SHOWN OR NOTED OTHERWISE. 12. ROUGHEN ALL CONSTRUCTION JOINTS TO A MINIMUM 1/4" AMPLITUDE. REINFORCING STEEL 1. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE WITH THE "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" (ACI-318) AND THE "MANUAL OF STANDARD PRACTICE FOR REINFORCED CONCRETE CONSTRUCTION" BY THE C.R.S.I. OR AS MODIFIED BY THE CONSTRUCTION DOCUMENTS. 2. MAIN REINFORCING STEEL - A615 GRADE 60 3. ALL REINFORCING BAR BENDS SHALL BE MADE COLD. 4. REINFORCING SPLICES, WHERE REQUIRED, SHALL LAP 40 BAR DIAMETERS OR 24 INCHES MINIMUM AT ALL SPLICES. 5. ALL BARS SHALL BE MARKED SO THEIR IDENTIFICATION CAN BE MADE WHEN THE FINAL IN -PLACE INSPECTION IS MADE. 6. MASONRY REINFORCEMENT: JOINT REINFORCEMENT -PROVIDE WELDED WIRE UNITS SPACED AT 16" O.C. VERTICALLY FOR RUNNING BOND, 8" O.C. VERTICALLY FOR STACKED BOND. PREFABRICATED WITH DEFORMED CONTINUOUS SIDE RODS (3/16" DIA.) AND PLAIN CROSS RODS (0.1483" DIA.) INTO STRAIGHT LENGTHS OF NOT LESS THEN 10" WITH PREFAB. CORNER AND TEE UNITS. TRUSS OR LADDER DESIGN. USE TYPE S MORTAR W/ DRY BLOCK IN TOP PL. SPLICE OVER STUD - FRAMING NOTES 1. INTERIOR NON -LOAD BEARING WALLS (2X4 STUDS U.O.N.) 2. FRAMING SIMILAR TO DETAIL WITH SINGLE PLATE TOP & BOTTOM, WITH 8d OR 16d NAIL CONNECTIONS, OR OPTION - SIMPSON CONNECTORS MAY BE USED. 3. FLOOR ANCHORS AS NOTED IN DETAIL. 2-2x PL. MIN. W/ 16d @ 16°g O.C. MAX, 2-8d PER STUD 1 x4 DIAG. LET -IN BRACE @ ANGLE BETWEEN 60 0& g. LINTEL 45" TO HOR. a (or SIMPSON RCWB € 2 0�' OR CS-WSD WALL BRACING) M 2-10d EA. END FIRE BLKG-2x I. I MIMIDHT. f8'O" MAX, OP fNI%IG SPACING) TYP, i TYP. CORNE MULTISTU[R a I 3 I I TYP. MULTI STUD ANCHORED W,/ SIMPSON HTT208 < U.O.N. TYP. STUD ANCHORED W/ SIMPSON RSP 4 TOP & BOTT. SIMPSON A35 (TYP. U.ON,) 2-16d EA. STUD D ABOVE LINTEL LI N TEL DATE- B. April 2021 ANCHOR/ CONNECTOR SCHEDULE **a. Refer to plans -- CONNECTORS NOT NECESSARILY USED. MARK , MANUFACTURER QTY, PART No. ATTACHMENT CONNECTED MAX. LATERAL REMARKS FL. PROD EA ELEMENTS ELEMENTS UPLIFT F1/ F2 NUMBER 1 SIMPSON **. H3 4-8d RAFTER TO PLATE 455 125 / 160 NAILED RAFTER TO EXIST. 4-8d ' WALL PLATE 3 SIMPSON (1 -SDS2.5 16-1/4 x 2.5"SDS 14-1/4 x 2.5'°SDS BM. TO POST 5680 LBS. - BM-1, & BM-2 to 1218.28 4x4 POST 1 & 2 4 � SIMPSON ( 1 H16 6-1/4 x 2-1/4 TITAN SCREWS � TRUSS TO BM or WALL 1300 LBS. - 1423.3 4A SIMPSON (1) HGAM 10 4-TITAN/SCREWS 2 TRUSS TO BM/WALL/ ROOF 850LBS. 870/815 1423.9 5 SIMPSON (1) AC4(MAX) 14-16d 14-16d BM-2 TO POST 25D0 LBS. 1070 CAP POST # AND BM-2 6 SIMPSON (1) GLTV, 1.59 1.5, 4-8d, 6-8d 8-8d Bm. BM-3/JOIST TO BM-2 1640 LBS. BM-3 to BM-2 POST #3 1218.73 x9 POST 3 &WALL PLATE BM-3 TO WALL 7 SIMPSON (1) E H10 g-10d BM/PLATE 10-10dx 1-1 2 JOIST TO BEAM 780 LBS. 505 450 / JOIST TO BM. 474.96 8 SIMPSON (4) LTS16 16_1od GABLE TRUSS TO BM 1260 LBS. 75/125 1423.14 0 SIMPSON (1) CBS 44 2-5/8" BOLTS POST TO CONC. 4200 LBS. 4X4 Pt ST to CONC. SLAB/ FOUNDATION 474.45 9.1 SIMPSON (1) ABU44 2-1 2"0 TO POSTPOST TO CONC. 2160 LBS. 4x4 POS T to CONC. - 5 8, BOLT BOLT 6" EMBED SLAB/ FOUNDATION 10 SIMPSON 1l � ! MBHA 3.56/ 16 18-" x 8 A.B. 2-3/4 ; BM. TO WALL 7250 LBS. - BM to CMU WALL 538.10 11 SIMPSON - A35 6-8d x 1 1 2" 6-8d MISC. FRAMING BRACING 450 LBS. OUTRIGGER TO JOIST 474.4 x 1 1%2" 12 SIMPSON - SIDS 1/4 x1.5' TITEN SCREWS MISC. FRAMING BRACING 200 LBS. 525 SHEAR 1463.46 12.1 SIMPSON - `SDS 1/4 x2.5 TITEN SCREWS MISC. FRAMING BRACING 240 LBS, 525 SHEAR 1463.47 12.2 SIMPSON - SIDS 1/4 x4.5 TITEN SCREWS MISC. FRAMING BRACING 445 LBS. 525 SHEAR 1463.50 13 SIMPSON (1) IHTT20B 5/8" AB 10-16d Sinkers COLUMN HOLD DOWN 1750 LBS. - 503.21 14 SIMPSON **a RSP 4 4=8d x 1 1/2„ d x 1 1 /2 STUD TO PLATE TOP & BOTT. 315 LBS. 210 / 305 - 474.30 6 15 SIMPSON - RCWB-12 2-16d Plate STUD BRACING DIAGONAL BRACING 1-8d stud s _ - - 16 SIMPSON - 'Framing Screws MISC. FRAMING7 BRACING 17 SIMPSON (2) HH6 18 SIMPSON - �SP2 19 SIMPSON - CS-16 SIMPSON STA.24 STRAP TIE EA. DE Wj' 16--10d, �lV2 ABOVE LOW" BM TO STU (UPLIFT AP.= 1465 MIN.) WNW TYP. DBL PT 2X PLATE 5" IMIN. D„ MAX. 1/2"Dic. x 8" LG (4" MIN. EMBED INTO SLAB) @ EA, END & @ 48" O,C. (TYP. U.O:N.) am RI A ARCHITECT Graphic Designer LIC. # AR 0013444 Orlando, • • : 32804 407-628-8982 # : :•: Remodel for M/M Mark Fick RESIDENCE EMTIRE RESIDENCE PHASE 1 + 2 20-008 BEARING ' A'_®, SCHEDULES, NOTES (0.177"-x 3" SHOT PINS 0 NON -BEARING WALLS CONNECTORS 32" O.C. ALT,) DETAILS NOTES: �� 1. FOR OPENING SIZES SEE PLANS, ELEVATIONS & SECTIONS >ff.L f.V.4 //////H.R'.. :: <%/,I,%Nf .::: ,i<i4F`ffff.:•f✓ 1.G .i.:%.Y.Y ::: ,ca FOR LINTEI" SIZES SEE FRAMING PLAN & LINTEL SCHEDULE, AO.2 2. DEFER TO FRAMING AND FOUNDATION PLANS FOR ., :ffff/ ...»..:: SPECIFIC ANCHORING REQUIREMENTS. AS NOTED ban DEW SCALD. N T S 8-31-21 rea Randal" Nm Date Deecx�tbn — — — — — —1 A ARCHITECT Graphic Designer LIC. # AR 0013444 Fort Pierce, FI 34982 407-304-0264 readesignl•gmail.com Remodel for M/M Mark Fick RESIDENCE No.- . . EXISTING PLAN Drawtq Na- A1.1 EXISTING FLOOR PLANBMW 1/4 99 = 1 9-099 Al. 1 SCALF 1/4'-1'-®' (1/81 HALF SIZE) Issas Data 8-31-21 Draw" W. re® Checked BY WIND PRESSURE CHART FXK-8.Tj__--OPENING AREA NEGATIVE WIND PRESSURE +oo POSITIVE WIND PRESSURE WALL —TYPE I EGEND EXISTING WALL— FRAME OR CMU 2x6 STUDS 0 16" O.C. EXTERIOR R-19 INSULATION w/ NEW INTERIOR PARTITION 2X4 STUDS ® 16" O.C. (--------------- NEW MASONRY WALL'fit aundny ONRY WALL W/ 1-1/2 FURRING, INSULATION & 1/2" GYP. BD. Sink , r I LAUNDRY SCREEN ENCLOSURE 14'-4" X 7'-6" +43.9 CONCRETE IN —FILL OR --- --Ii IIr It L aQ ouC,L oNEW yFOUNDATION &SLAB. II iI E 2 I I I I I in I N nio0 c,o BATH 5'-511 X 6'-0" • �1_bl, pocket Fut. REF. MUD ROOM 8'-1Oil X 6'-011 r— '-611tow tickku eUTILITY #rut14'-7 X 12'-1" 1 I RZL I EXIST. I I r-r-------- 3060 dbl r { I ------------------ ----- i ' 1 I T-------- - . J _--- -i Tut. , II I i L---J +4s.a j I Q N ! 1 oven II 3'-51' 8'-2" 3'-11 II II 11 II Kitchen/ Dining----- I I 161'-8" X 22'-31, 2 II II � II I j j 1 A3.2 3 I I s.. II +43.5 {I � I I {I NEW LINTELS II I I 11 I I II sh48 sh48 I�1­237--ij 0 - s.. s. III ! +41.9 C +43.5 C I � I III I I PORCH III I N.I I I I EXIST. LINTELS III I III I.! v 45'-0" EXIST -r------------------------------------------------------ -r--I -H I Carport I 1 8" r Q +45.2 4050 5L Z Q dY 4 Bed Room #2 3065 • Im 1 LIN. 3 -0"we pocket -- I v. r--- CAB. J 1 cAB 4,-8„ i2'-5„ II \ II '-6i' I I 30b8 2 HAUL - ---__ ___ ' S UB/SHOWER GAB. ; GAB. --------------, L-------------- I I r _ �' _ 5066/< ['5'-0 1 /2"f 1 I I I I I APPROXIMATE f ,�►�� BATH #1 "Pocket I � + LOCATION OF 4U_ `I — 8 E ATTIC ACCESS o LIN. MULTI-PURP05E RM. +45.5 Living Room r 1 I 4'_ " 9'-9" 3 GAS. 1 I I O I O T± step I pocket `� Entry I I I 3056 Fixed D 1 305Fixed b s. . ------------------------------------------------------ ------------------------------------------------------- I EXIST. EXIST. +43.9 LINTEL/BEAM LINTEL/BEAM I I I { I I ---- 58.4 s.f 1 I `- -------y...J -- /� 55.4 s.f �1--------------------------------- r— +40.9 LIVING AREA I Conditioned = 2051 SCE FT unconditioned Attached. Utility = 216 50 FT carport = 633150 FT porch a 24150 FT gross under roof = 3309 50 FT 1. REFER TO SHEET A3.2 FOR KEY NOTES FOR PROPOSED PLAN. No. Date Deacrlptlon 10/29/21 Permit comment ARCHITECT Graphic Designer LIC. # AR 0013444 Fort Pierce, FI 34932 407-304-0264 readesignl•gmail.com Remodel for M/M Mark Fick RESIDENCE 9309 INDIAN RIVER DRIVE FORT PIERCE, FL Project Nor 20-008 Craft 'title+ REMODEL FLOOR PLAN -- —.--------- — —� Dra, No: A1.2 REMODEL FLOOR PLAN tee` 1/499 = 19_099 A .2 SCALE 1/4'-1'-0' (1/8" HALF SIZE) h°"e Data 8 - 31- 21 Drawn BY rea Checked Br. REMOVE1. REMOVE PLUMBING FIXTURE, WATER PIPING, DEVICES AND SANITARY PIPING. 2. DEVICES,• PLUMBING DOOR,PIPES, DEVICES 3. REMOVE EXISTING WINDOW AND PREP FOR INSTALLATION OF NEW WINDOW OR GLASS BLOCK IN OPENING OR INFILL. 4. REMOVE EXISTING DOOR, OR REMOVE5. ♦POST ABOVE MASONRY WALL, SUPPORTSHORE EXISTING ROOF, PREP FOR INSTALLATION OF REPLACEMENT BEAM & ♦. SLOE TO ALIGN WITH NEW SOUTH r REMOVET. POST & SLAB IN PREP • INSTALLATION] OBEAM & F SUPPORT POST. REINFORCE7. REPAIR, ., 2nd AND 3rd RAFTER TO EVERY OTHER RAFTEIL (n 8. EXISTING BEAM TO BE REMOVED, SHORE AS REQUIRED IN 0 FOR INSTALLATION OF NEW BEAM. z 9. DOOR,PREP REMOVE INTERIOR , DISCARD. REMOVE BASE CABINET, COLUNTERS AND WALL CABINETS < IN EXISTING KITCHEN. 0-1 11. REMOVE10. DROPPED EXISTING KITCHEN. 12. REMOVE EXISTING APPLIANCES (RANGE, HOOD, OVEN, As • REMOVE13. ♦ , ADD LEVELING COMPOUND AS REQUIRED. 14. CUT NEW DOOR OR OPENING OPENING CONCRETE SHOREWILL SERVE AS A LINTEL. 15. ROOF, AND REMOVE POSTSEXISTING . PREP FOR • OF POSTSSUPPORT WINDOW16. REMOVE EXISTING HIGH ARCHED SURROUND FRAME, PREP FOR NEW GLASS BLOCK AT TOP AND HOOD VENT PIPE PENETRATIONBELOW. DEMOLITION WINDOWS, DOORS. COLUMNS/0 DEMOLITION 4 3 ®-- 3 r �\ ®EXISTING CONC. BEAM ilm 14 i 3 3 CDEMO PLAN 0 I00A21_ ; r EXISTING WALL— FRAME OR CMU 2x6 STUDS 0 • EXTERIOR • INSULATION 1iiii-imwi MASONRY WALL W1 1-1/2 FURRING, INSULATION & 1/2" P r SCREEN ENCLOSURE NEW CONCRETE IN —FILL OR `'•_ - `', FOUNDATION & SLAB. LO I N Wft; PROPOSED r 1. NEW WINDOW IN EXISTING OPENING. 2, INSTALL GLASS BLOCK INTO EXISTING OPENING. 3. FILL IN EXISTING DOOR OPENING. WITH PT 2X6 0 16"O.C. WITH 5/8" SHEATHING OR CMU WITH #4 REINFORCING BAR 024" RUNNING VERT & DOWELLED HORIZONTAL INTO EXIST. MASONRY WALL 24" 4. NEW MULTI —UNIT WINDOW. REWORK OPENING TO ORIGINAL LINTEL OVER LARGER OPENING AS REQUIRED. 5. INSTALL NEW SUPPORT POSTS, NEW BEAM (2--2X8 W/ 1/2" PLYWD) TO CHANGE THE SLOPE OF THE EXISTING ROOF TO MATCH SLOPE AND EAVE HT. OF THE NEW ROOF FROM 7HE CONCRETE UTILITY ROOM. 6. INSTALL NEW SUPPORT POSTS, WITH NEW SLAB/FOUNDATION, & NEW BEAM TO CHANGE THE SLOPE OF THE EXISTING ROOF TO MATCH SLOPE AND EAVE HT. OF THE NEW R':,OF FROM THE CONCRETE UTILITY ROOM. 7. TYPICAL WOOD HEADERS (3) 2X8 W/ 1/2" PLYWD BETWEEN TO MAKE 5-1/2" THICK S. EXISTING CONCRETE TIE BEAM TO SERVE AS LINTEL FOR NEW DOOR OPENING. IINISTALL NEW DOUBLE SWING DOOR WITH INSULATION/ SEALS. 9. EXISTING WOOD HEADERS 2X12 IN PATIO. 10 NEW COLUMNS— 4X4 (SEE ELEVATION FOR CONFIGURATION) 11 ACCESS PANEL— FOR PLUMBING ACCESS. 12 NOTE USED 13 EXISTING BEAM (OLD CARPORT ENTRY). 14 ONE COURSE OF GLASS BLOCK AT TOP OF EXISTING OPENING WHERE CURVE WINDOW REMOVED. HOOD VENT PIPE BELOW (NOT SHOWN) Revisions: .f Date Description 0 •rrri-* ARCHITECT Graphic Designer LIC. # AR 0013444 Fort Pierce,i •, .00 6 Remodel f ,,idi o M/M Mcrk Fick RESIDENCE 9309 INDIAN RIVER DRIVE FORT PIERCE, FIL Project No.: 20-008 Drawing PHASE 1 DEMO i PROPOSED PLANS Drawing No.: A2.1 Scale: 1 /4" 1.-0" Issue Date: —14-21 Drawn By. rea Checked By. Revisions: T ELECTRICAL LEGEND 1. ALL WORK DONE SHALL CONFORM TO ALL STATE OF FLORIDA CHIME CODES AND LOCAL ORDINANCES. REFER TO SHEET AO.1 CODE ANALYSIS. Y CEILING MOUNTED LIGHT (DSD SMOKE DETECTOR 2. ALL OUTLETS SHALL BE NEC REQUIRED ARCFAULT OUTLETS. (2} R RECESSED CAN OSDM SMOKE & CARBON MONOXIDE DETECTOR 3, OUTLETS IN KITCHEN AND BATHROOMS SHALL BE GF! PROTECTED. WALL MOUNT LIGHT DUPLEX RECEPTACLE 220V. OUTLET RECESSED WALL WASH LIGHT SPECIALTY J.B. 2 X 2 RECESSED LIGHT FIXTURE wP WATERPROOF RECEPT, FLOOR RECEPTACLE 2 X 4 RECESSED LIGHT FIXTURE Effl PRE —WIRED GARAGE DOOR OPENER 1 X 4 RECESSED LIGHT FIXTURE GROUND FAULT 1 X 4 WALL MOUNTED FIXTURE GFI INTERRUPT RECEPT. 14 TELEPHONE JACK 1 X 4 SURFACE MOUNTED < INTERCOM/ COMPUTER 130X %—� FLUORESCENT LIGHT W/ CONDUIT TO ABOVE CLG. PULL CHAIN LIGHT <TV CABLE JACK PC rfl DISCONNECT SWITCH —�-- WALL SCONCE Q ELECTRICAL METER FLOOD LIGHTS ® ELECTRICAL PANEL CHANDELIER CEILING FAN w/ LITE KIT WALL SWITCH JUNCTION BOX F FAN/LIGHT COMBINATION DOOR BELL/ FAN/MOTOR GARAGE DOOR SWITCH KEYNOTES K0# SWITCH " POT RACK LIGHTING. 3. JUNCTION BOX FOR MINI —SPLIT #1. 4. JUNCTION BOX FOR MINI —SPLIT #2 5. JUNCTION BOX FOR MINI —SPLIT 3. 0. JUNCTION BOX FOR MINI —SPLIT #4. 7. JUNCTION BOX FOR MINI —SPLIT #5. &JUNCTION BMINI—SPLI ON ON ROOF. BOX FOROPERATOR i 10-FEED TO GATE POST LIGHTS. 11. JUNCTION BOX FOR KITCHEN HOOD. `15.CONDUIT UNDER FLOOR WITH POWER TO ISLAND No. Date Description REFER TO E3.2 ELECTRICAL RISER DIAGRAM IDS TO POWER COMPANY — aundn� - GFI Sink , Shower ° LAUNDRY ° 1 '-4" X ° I I i 20V \\�J 4 +{ d 1`10I00 GFI BAT MUD OOM I (D 1f=000 'd ~ 3 Pi HAIRDEG loll 'T-I%l I V. / I;ATWOOD ° y f' � !L I° 5 -74 t-- _-,II ARCHITECT -TiLI �'; _ Graphic Designer 14 7 X 12_I �I1 ° LIC. # AR 0013444 Fort Pierce, FI 34982 12 3 4 407-304-0264 GFI--------- ---- �G I B i� GFI ° zQ . ...... 11 L"-------------- Location of New I ; I=U i ......ry;i Outlet boxes (40" 15 I 11REF. i I AFF-Y.I.F.) 01 a-,..-...,_..... GFI Remodel for + 3-5 -2 3-e-11 M/M Mark Fick ° RESIDENCE N -H Its 1 Dining ~ �� -I ' r, s -L 9309 INDIAN RIVER DRIVE 10 � J FORT PIERCE., FL GSDM FILE copy II I Wshy P wP ; _ II f I� Project No.: 20-008 I I Drawing Title: I I. PHASE 1 I® ELECTRICAL ®i it MCHAI(dAL PLANS I I® ®I I Drawing No.: ME ® 2.2 EXISTING WALL- FRAME OR GMU DEMOLITIONrO DOORS. 0 DEMOLITION COLUMNS/ POSTS I I I I I I I I I I I I I � I I � I I i I I I I r L_----------------------------- i I lul r iI I I f I I � I f � I I -------------------------------------------- I I I I I I I I I I Zi '" i • •:. ! ,. • ! • =r • � r �" r •` ii �- ;r 1 r'I k! • i i ��%�i� M ` r • Pierce, / • 407-304-02 FILE COPS' . ,od Na. r rr. PHASE 1 • DEMOLITION PLAN scalw DEMOLITION PLAN pia = , -o • Pierce, / • 407-304-02 FILE COPS' . ,od Na. r rr. PHASE 1 • DEMOLITION PLAN scalw DEMOLITION PLAN pia = , -o WIND PRESSURE CHART I­7T-5. PENING AREA r--EGATIVE WIND PRESSURE +oo3—POSITIVE WIND PRESSURE 2 A4.1 WALL —TYPE —LEGEND t'*VK EXISTING WALL- FRAME OR CMU 2x6 STUDS 0 16" O.C. EXTERIOR w/ R-19 INSULATION NEW INTERIOR PARTITION 2X4 STUDS @ 16" O.C. NEW MASONRY WALL MASONRY WALL W/ 1-1/2 FURRING, INSULATION & 1/2" GYP. BID. NEW CONCRETE IN -FILL OR FOUNDATION & SLAB. � m s m ® EXIST.OR NEW LINTEL/ BEAM z r7---- -- LIVINO AREA Conditioned = 2051 50 FT unconamonea ^rracnea. jilmity = 2ittPre carport b5l 50 FT porch 24� SO FT gross under roof 350q 2. INSTALL GLASS BLOCK INTO EXISTING OPENING. 3. FILL IN EXISTING DOOR OR WINDOW OPENING. WITH PT 2X6 @ SHEATHING OR CMU WITH #4 REINFORCING BAR @24" RUNNING DOWELLED HORIZONTAL INTO EXIST. MASONRY WALL 924" 4. NEW 1TVILTI-1111IT 1,11ADVT1. RETTORK OFnIRG TO ORIGINAL LINTEL OVER LARGER OPENING AS REQUIRED. 5. INSTALL NEW SUPPORT POSTS, NEW BEAM (2-2X8 W/ 1/2" PLYWD) TO CHAN THE SLOPE OF THE EXISTING ROOF TO MATCH SLOPE AND EAVE HT. OF THE NEW ROOF FROM THE CONCRETE UTILITY ROOM. I 6. INSTALL NEW SUPPORT POSTS, WITH NEW SLAB/FOLINDATION, & NEW BEAM TO CHANGE THE SLOPE OF THE EXISTING ROOF TO MATCH SLOPE AND EAVE HT. OF THE NEW ROOF FROM THE CONCRETE UTILITY ROOM. 7. TYPICAL WOOD HEADERS (3) 2X8 W/ 1/2" PLYWD BETWEEN TO OAKE 5-1/2" THICV1 8. EXISTING TIE BEAM TO SERVE AS LINTEL FOR NEW DOOR OPENI\IG. INSTALL A DOUBLE SWING DOOR WITH INSULATION/ SEALS. 9. EXISTING WOOD HEADERS 2X12 IN PATIO. 10 NEW COLUMNS- 04 (SEE ELEVATION FOR CONFIGURATION) 11 ACCESS PANEL- FOR PLUMB114G ACCESS. 12 REPAIR FLOOR AND JAMBS AS REQUIRED AT THE ENLARGED OFr-114ING 13 EXISTING BEAM (OLD CARPORT ENTRY). 14 ONE COURSE OF CLASS BLOCK IN THE TOP OF EXISTING OPENINl':P. 15 NOT USED 16 NEW WELL. EQUIPMENT AND REVERSE OSMOSIS SYSTEM LOCATION, 17 ADD ALPINE EXTENSION ROOF EDGE, TYPICAL ALL GABLES. Interior SCALE : 'KI.Achen Elevation 1/47-1'-Ow (1/8w HALF SUE.) 201, 321, 24" b:7j L7] 10/29/21 Permit comment writellm ARCHITECT Graphic Designer LIC. # AR 0013444 Fort Pierce, Fl 34982 407--304-0264 i S n-y_ Ll! kn, T I &. F In I-M Proled No.- 20-008 PHASE 1 & 2 PROPOSED FLOOR PLAN --- — — — — — — - — — — — — — — — — — - ----------- 15 K Z-e 1 31 =� ELEVATION 0 E pa, I01 FRONT Ea s t ELEVATION 9 0 ik KEYNOTES ELEVATION COURSE2. EXISTING SINGLE OF i COUNTER.THE KITCHEN POSTSSUPPORTS SHOREEXISTING BEAM. UP AS REQUIRED TO SUPPORI ROOF TO REMOVE EXISTING POSTS SUPPORTNEW • AE"'BEAM OWEST N SUPPORTED ON COLUMNS OVERHANG.HURRICANE CLIPLS & TO LEDGER BOLTED (1/2" EPDXY OR SIMPSON ANCHORS EMBED 6") INTO CONCRETE ROOv DIA. PIPE OR WOOD i c; PATIO.COLUMN SUPPORTING NEW BEAM FOR SHED IRIOOF OVER UTILITY • REPAIR AND PAINT STUCCO FINISH ON EXTERIOR 9. EXISTING SHINGLE OR ROLLED ROOFING. (to be replaced with NEW Roofing under Separate Permit) JAIlt"114• • 12. NEW AC CONDENOR UNIT ANCHORED WITH HURRICANE ANCHOREDSTRAPS TO CURB OR PIT 4X4 RAILS CONCRETEi DECK I CLOSE13. r OPENING WITH FRAMING AND STUCCO ON EXTERIOR • PATIO16. EXISTING WEE PIPE COLUMNS' TO BE REUSE TO SUPPORT EXISTING FOOTINGS AND NEW BUCKET WELD TO TOP TO BOLT TO NEW REAM, Revhiom to. Date DemxWm 1 1fl/22/21 Permit comment 1 /29/21 Permit comment GraphicARCHITECT • AR Orlando, Florida 32804 407-628-8982 FAX: 407-628-8982 rr- ELEVATIONS �TL� ip 131 "A& ELEVATION �E'CTION ct UTILITY RM. C2f'Al = - .4 io%w AV ^a to a a a a® ewa _ . I ­% SECTION ct CARPORT REFER TO NOTES ON SHEET A4.1 10 4A 1 1 /2"Al I ---------- ... ....... QV. C port 6 4 NEW BEAM BRG, 1 2"AFF 11,,e ABV E V B Am BRO. C FUTURE WINDOW 7 1 '7 1 __231L .. . ....... SAW -CUT EXIST SAB AS REQUIRED FORL PLIJMBING7 #3 BARS DOWEL AT 9" I.C. EPDXY 6" INTO SLAB '7YST SL.4B ----7 .,d 4 10 MIL F'"111-Y VAPOR RETARDER CONTINUOUS COMPACTH) FILL C EV 13 T �s 7- R u c-r u C ROOF RAKE GABLE DETAIL �4?_ 1rALE ws 2X6 RAFTER ANCHORED W/ JOIST HANGER TO 2X6 FASCIA BD, FASCIA BD. ANCHORED TO CONCRETE ROOF OVERHANG W/ FLASHING BETWEEN NEW 1/2' EPDXY OR SIMPSON THN ROOFING AND EXISTING SCREWS 0 8" O.C. MEMBRANE ROOFING ON [ UTILITY RM. 2X8 DBL BEAM EA. END ANCHORED W/ HANGER TO LEDGER ANCHORS ANCHOR ED::M_GEt END ALL LEDGER 2 '_ PO - �EPDXY BOLTS OR SIMPSON TITEN SCREWS @ 8" O.C. DETAIL (:I t —UTILITY ROOD SCALE; 1-1/112"4-01 (HALF SIZE Im Na Date DwcrWm /1\ 10/22/21 Permit comment zis-10/29/21 Permit comment ARCHITECT Graphic Designer AR 0013444 Orlando, Florida 32804 407-628-8981 FAX: 407-628-8982 ;m=110 on- 0,101- 'vmim to Fr*d Nw 20-008 -Frawirg mft ELEVATION & SECTIONA., scaw 1/4 V-0" (AS NOTED) .... EXHAUST — FAN !■ II• T - II 11 II 11 II II II II II II II II II II II II II II II 10 II II II I I I I I II � II II ■ II '' II I r-------------..-----------------T I I aundry IILwink Shower I I I � I LAUNDRY p14'-411 Xi°-b'° I I r-----a r------ i m CL N I I I I I I I I I I I j f I ! I ® ! ®— — — — — — — — — — — — ---_--®_—_-- ® I I I II 3 .-- _-_-------------------- __---.._-_.-_-_ s 8 HALF SIZE) I I P_-4 p I I 1 I I p I I I I I I I I I I I I I I I I I I 1 p 1 I I I I I I I � I � I I I I I I I � I I I I DUCTLESS SPLIT HEAT PUMP SCHEDULE MARK SCU-1/SHP-1 SCU-1/SHP-2 SCU-1/SHP-3 SCU-1,/SHP-4 SCU-1/SHP-5 NOMINAL TONS OF CU 1.5 .5 .5 1.0 L 75 TOTAL COOLING LOAD 18 6 6 12 9 AHU CONFIGURATION WALL MOUNT WALL MOUNT WALL MOUNT WAkLL MOUNT WALL MOUNT AHU DIMENSIONS D X W X H (IN.) 31 X12)(13 31 X12X13 31 X12X13 51 Xl2X13 31 X12X13 SUPPLY AIR (CFM) ENTERING AIR DRY BULB (DEG. F.) 80 80 80 80 80 ENTERING AIR WET BULB (DEC, F.) 67' 67 67 _ 67 67 VOLT/O 208/230/1 -®— CONDENSER UNIT MCA 42-� SERVED KITCHEN/DINING BEDROOM BEDROOM MU,j,TU- 'URPOSE LIVING MANUFACTURER MITSUBISHI MITSUBISHI MITSUBISHI 0ITSUBISHI 1 MITSUBISHI SSHP MODEL # MSZ GL18 MSZ GL06 MSZ GL06 MSZ ZI-12.NAU1 MSZ GL09 SSCU MODEL # MXZ 8C48/AV1 — MINIMUM EFFICIENCY AT ARI 18.9 SEER ---- - — - REMARKS _ 1 THRU 7 1 THRU 7 1 THRU 7 ! THRU9M7 THRU 7 -'I 1. PROVIDE WITH AUTO RESTART, EVAPORATOR COIL. FREEZE PROTECTION AND LOW AMBIENT TEMPERATURE CONTROLS 2. PROVIDE WITH COOLING/HEATING THERMOSTAT OR REMOTE CONTROLLER 3. 957 OUTSIDE AIR AMBIENT 4. MCA = MINIMUM CIRCUIT AMPACITY 5. EVAP FAN IS FED ELECTRICAL_ FROM CU 6. PROVIDE WITH 5 MINUTE TIME DELAY RELAY TO PREVENT COMPRESSOR FROM SHORT CYCLING 7. COOLING LOADS EXCLUDE EVAPORATOR FAN HEAT 8, CONDENSER SIZE - 52-11/16 X41--11/32 X 13 + 1 ' i ♦'Nal1 ! REFRIGERANT LINES. ROUTE FROM CU. ACROSS 2 ROOF ON OUTSIDE THRU THE GABLE END, INTO ATTIC AND DOWN THRU CEILING AT EACH SHP (AHU). PROVIDE 3/4" DIAMETER LINES AT INDIVIDUAL AHU'S DOWN TO GRADE. INSULATE HORIZONTAL LINES INSIDE UNCOOLED SPACES, ATTICS, AND WALLS. s !j 4 SHP-2 THRU SHP-5 BOTTOM TO BE MOUNTED ON WALL 0 80" AFF. POWER, CONTROL, REFRIGERATED SUPPLIED TO EACH FROM THE CONDENSER (CU) 05 SHP-1 BOTTOM MOUNTED ON WALL ABOVE 96"AFF CONDENSER (CU) ELECTRICAL DISCONNECT AT �� UNIT ON ROOF--220V, 60A, 1PH fi •- r •:MIf -kifialm EXHAUST H"OD SECTIONS 0 Napammorm Deft Deecr"m 1 10/22/21 Permit comment 10 29/21 Permit comment ARCHITECT Graphic Designer 0013444 FortPierce, _ 34982 407-304-0264 PrCied No.- f# SCHEDULE MECHANICAL b DETAILSPLAN 10-20-21 Drawn re a r--.--•--•— I I CW FROM WELL 1 3 2 i r-- — a�---- --- --- --- — _ i CO I L I I qas I I I I I I I I I I� TO SEPTIC TANK 2 q (SEE SITE PLAN) r7 c0 LIVING AREA Conditioned = 2451 50 FT Unconanionea Artacnea. Utility = 27b t Cu t-'l carport = b3i 50 FT porch = 241 Sa FT gross under roof = 3309 5(2 FT 1i I"1r = ►0111111 IR b SANITARY LINE oco SANITARY CLEANOUT —CW- - - — COLD WATER LINE — • - — - - --dW HOT WATER LINE MANIFOLD (optional) -Gam — . — — - GAS (PROPANE) LINE PLUMBING PLAN SCALE 1/4'-1'-0' (1/S' HALF SIZE) PLUMBING —PLAN —NOTES 1. PLUMBING WATER PIPING TO BE COPPER TUBING INSIDE RESIDENCE. EXTERIOR PIPING TO BE PVC. WATER LINES SHOWN ARE SCHEMATIC. LINE SHOULD BE RUN IN ATTIC OR WALLS TO PROVIDE THE SHORTEST RUN AT PLUMBERS DISCRETION. 2. THE KITCHEN RANGE/GRILL TO HAVE GAS (PROPANE) SUPPLIED FROM TANK LOCATED NEAR DRIVE. REFER TO SITE PLAN SHEET - A.01 FOR APPROXIMATE LOCATION. 3. SANITARY PIPING TO BE PVC, UNLESS OTHERWISE NOTED (UON). 4. NEW POTABLE WELL LOCATED TO WEST OF EXISTING WELL. ( REFER TO SITE PLAN). SUPPLY SHALL BE TO THE REVERSE OSMOSIS UNIT AND THEN TO MANIFOLD S WATER HEATER S. NEW SEPTIC TANKI SYSTEM LOCATED IN AREA TO WEST OF CARPORT. (REFER TO SITE PLAN). 6. THE WELL WATER TO BE RUN THROUGH THE REVERSE OSMOSIS UNIT AND DISTRIBUTED IN ATTIC SPACE WHERE POSSIBLE. SURFACE MOUNT PIPING WHERE NOT POSSIBLE TO CONCEAL IN ATTIC OR WALLS. 7. PLUMBING CLEAN OUTS (CO) SHALL BE INSTALLED AS SHOW, OR AS DIRECTED BY CODE AND OWNER. 8. WATER SUPPLY FOR WASHER, REFRIGERATORS, DISHWASHERS, KITCHEN SINK, LAVATORIES, AND TOILETS SHALL HAVE VALVES AT FIXTURE CONNECTIONS. 9. BATHROOM TOILETS SHALL HAVE BOTH COLD AND HOT WATER FOR INSTALLATION OF A BIDET ATTACHMENT. 10. ALL PLUMBING ,SHALL CONFORM WITH CURRENT STATE AND LOCAL CODES. 11. DISHWASHERS (2) SHALL HAVE ONLY HOT WATER SUPPLY. E. I I M Ask" �11 ARCHrrECT Graphic igner ..,, ... Fort Pierce, FI 34982 407-304-0264 readesignlegmail.com Remodel for M/M Mark Fick RESIDENCE PLUMBING PLAN Scale 1 /4„ _ 1 —0,f le" Dot& 8-31-21 I 0 0 0 0 9 -07 - Z =1 I'M S SINK CAW WTO VENT SCALE : ws ARCHITECT -aphic Designer 419LOWAAA� Fort Pierce, F1 34982 407-304-0264 readesignlogmail.com model for M Mark Fick SIDENCE INDIAN RIVER DRIVE 'PIERCE, FL FILE Copy Projed No.: 20-008 Xaw*V 7ft . 0 PRELIMINARY PLANS Xa*ft Na: P3.2 3calo 1/4 1 P-0$0 Mm Data 8-31-21 wn Br. rea %.A %ru Lay- ELECTRICAL GENERAL—N 8 ELECTRICAL LEGEND ft. IDate, TO POWER POLE 1. ALL WORK DONE SHALL CONFORM TO ALL STATE OF FLORIDA CODES ® CHIME AND LOCAL ORDINANCES. REFER TO SHEET AO.1 CODE ANALYSIS. CEILING MOUNTED LIGHT OSD SMOKE DETECTOR 2 10/29/21 Permit comment 2. ALL OUTLETS SHALL BE NEC REQUIRED ARCFAULT OUTLETS. 0 ® RECESSED CAN OSDM SMOKE & CARBON 3, OUTLETS IN KITCHEN AND BATHROOMS SHALL BE GFI PROTECTED. MONOXIDE DETECTOR 4. OUTLETS ON EXTERIOR SHALL BE WEATHER PROTECTED AND GFI. WALL MOUNT LIGHT DUPLEX RECEPTACLE 220V. OUTLET ti ® RECESSED WALL WASH LIGHT � SPECIALTY J.B. 14 Z 2 X 2 RECESSED LIGHT FIXTURE WP WATERPROOF RECEPT. r----------`-----------------T---— — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — ---T-1 & FLOOR RECEPTACLE 12 I J 1 2 X 4 RECESSED LIGHT FIXTURE PRE —WIRED -- I ❑ ___=====II-----____ ❑ ❑ o ❑ I I ® GARAGE DOOR OPENER aundry t-- I I I ® 1 X 4 RECESSED LIGHT FIXTURE I ULT Sink Shower GFI I I IFI NRORRDUPTARECEPT. 1 X 4 WALL MOUNTED FIXTURE / I I I I A TELEPHONE JACK LAUNDRY ' INTERCOM COMPUTER BOX � 14- X -fir — I f I CJ 1 X 4 SURFACE MOUNTED / I III I FLUORESCENT LIGHT I i r i L >A ® '� �� \ I ' III Tv W/ CONDUIT TO ABOVE CLG. I I D?V(bl i i_ z Gar Ot't I I PULL CHAIN LIGHT IQ CABLE JACK 2i M K�' I p I I I I PC r0 DISCONNECT SWITCH }11 1 1_ t _ III -� WALL SCONCE ELECTRICAL METER 4 — _JBATH PANEL MUD/ROOM R . R/'_ Vnn " X 6'-011 — HYBRID ELECTRIC WATER HEATER-2'=b"— Oe F. i I220V.1 locket L----J VT twL 3: 14'-1" X 2'-1 R .� L Tt_ 1 12 4 3060 dbl II AM MA 524RGFI _ �_-- 1€ __ F1 POT RACK d 15 j I� I I Q GFI g FI DOV. TrackJ Lts ' II ti Kitchen/ Dining-- G- 1I 3 A I I II I I II I II 11 I I II I I II I I II WP sh48 wP sh48 1 I I I I I �pRGH I I I I I I I I I I I I I I � I ®------------- — — — — — — — — — — — AUTO CHARGING III I 220V, 50A I w wP 1706, Q wP I I I <P L��l I 1 < 3 LIN. I 5 91 II pocket ' owe w i ci I 1 jf I� r Bed R GFI ii� ITH 2 m Ai3 i dp — II . i i GABS 1 i I I li 3 II _ m OSD OSDM I I 068 QSD it I Future .� 13050 sh v ll 5065 3 I I (� J 13 --- 1 � I GD J - - --- FiL 12P9�u>3�+ai�tER I 1 GFI l I I 3066 6 I I �1 „pocket I 1 �l 1� 3 \ I I / `FI \ I I GAB. GF Livin Rom LIN. MUL I -FURFOS RM. I I � � qp I I I qp j I � I I map OSD pocket OSD I ~ Bntl"l� QSDM `4 ---------------------------------- I I ------------ ---------------- ----------------------- I 505b Fixed(056 Fixed 16 I I SO I I I \----------------- _j move Exist under Soffit 10 i 12 ELECTRICAL PLAN ID FLOOD LIGHTS CHANDELIER WALL SWITCH JUNCTION BOX DOOR BELL/ --E] GARAGE DOOR SWITCH Q AUTO CHARGING STATION (220V, 50A) ® ELECTRICAL PANEL CEILING FAN w/ LITE KIT ® FAN/LIGHT COMBINATION FAN/MOTOR ELECTRICAL PLAN KEYNOTES 0 1.0 SWITCH FOR UNDER COUNTER LIGHTING. 2.(S SWITCH FOR POT RACK LIGHTING. Q SWITCH FOR TRACK LIGHTING. 3. JUNCTION BOX FOR MINI —SPLIT #1. 4. JUNCTION BOX FOR MINI —SPLIT #2 5. JUNCTION BOX FOR MINI —SPLIT #3. 6• JUNCTION BOX FOR MINI —SPLIT #4. 7• JUNCTION BOX FOR MINI —SPLIT #5. 8. JUNCTION BOX/ DISCONNECT FOR MINI —SPLIT CONDENSER ON THE ROOF. 9-JUNCTION BOX FOR GATE OPERATOR (220V). 10.FEED TO GATE POST LIGHTS. 11. JUNCTION BOX FOR KITCHEN HOOD. 12. SENSOR FLOOD LIGHTS (OWNER OPTION). 13.JUNCTION BOX FOR ATTIC FAN. 14.JUNCTION BOX FOR POWER TO SEPTIC SYSTEM. 15.CONDUIT UNDER FLOOR WITH POWER TO ISLAND REQUIREMENTS. 16.JUNCTION BOX FOR DOOR BELL/ CAMERA. 17.JUNCTION BOX FOR WATER PRESSURE TANK. Fort Pierce, FI 34982 407-304-0264 readesign1 •gmail.com Remodel for M/M Mark Fick RESIDENCE Ewa*" TNw . . ELECTRICAL PLAN E)rawVNo.: E 3.1 Scale! 1/4 99 = 1 !—Q„ k"DaW 8-31-21 E 3.1 SCALE 1/4'=1'-0' (1/8' HALF SIZE) Drawn Br. re a Checked ®r Panel -A (Interior) 200amp WATER 120/240, 1 ph HFATER 42 Circuit AC-1 DISCONNECT Cmdemrowr I ae I INSIDE -LECTRICAL RISER DIAGRAM NTS No. Dais Demr"m 1/23/20 Revised Framing plan & connectors - - - - - - - - - - - - - ---- - - - - - - - - L- - - - - --- - - - - - - - ELEC771RIC METER Conduit BASE­320amp, 342 & 146 Bond 0 1201240, 1p 200 AMP 125 AMP 125 AMP 1101240V 1101240V 11 0/240V 1PH 1PH 1PH y DISCONNECT L DISCONNECT <==>'2':'Conduit to (GARAGE) (SHOP) #2 CU G:­=x- Ff"L 2" Conduit 343/0 & 146 Bond (2) -3/411xl 0'. COPPER ARCHITECT 00 3 TYPE Graphic Designer lot 0 SERVICE. LIB. # AR 0013444 VOLTAGE MOUNTING FOLM mm C =1 147, mm. a VOL= ........... s Wa mrfv"' L5C CA' 1 (71 P k' 111"K F fA �A ....... ... ---------- --- so IV --------------- ............. ej . , (_ -, 1 -1 :D U -------------- ----- - ----------- - ---- ------- 6" a Alk LP ----- 'POO ml� zz, �j Ij ........................... v 2.S 7-7 Fort Pierce, FI 34982 407-304-0264 Prx4ft4 No; 20-008 DrawkV Tffiv ELECTRICAL PANEL SCHEDULE ONE -LINE & DATA Imm Date 9-14-21 Drawn W. re® Chec*od Br. I