Loading...
HomeMy WebLinkAboutAPPROVED Therma-Tru Product Evaluation ReportR W R W Building Consultants, Inc. B Consulting and Engineering Services for the Building Industry C P.O. Box 230 Valrico, FL 33595 Phone 813.659.9197 Florida Board of Professional Engineers Certificate of Authorization No. 9813 Product Category Sub Category Manufacturer Product Name Therma Tru Corporation "Classic Craft" and "Classic Craft Rustic Series" Exterior Swinging Exterior Door 118 Industrial Drive Opaque Fiberglass Door Doors Assemblies Edgerton, OH 43517 Inswing / Outswing Phone 419.298.1740 "Impact" Scope: This is a Product Evaluation report issued by R W Building Consultants, Inc. and Lyndon F. Schmidt, P.E. (System ID It 1998) for Therma Tru Corporation based on Rule Chapter No. 61 G20-3, Method 1 D of the State of Florida Product Approval, Department of Business & Professional Regulation. RW Building Consultants and Lyndon F. Schmidt, P.E. do not have nor will acquire financial interest in the company manufacturing or distributing the product or in any other entity involved in the approval process of the product named herein. Limitations: 1. This product has been evaluated and is in compliance with the 5th Edition (2014) Florida Building Code (FBC) excluding the "High Velocity Hurricane Zone". 2. Product anchors shall be as listed and spaced as shown on details. Anchor embedment to base material shall be beyond wall dressing or stucco. 3. When used in wind-borne debris regions this product complies with section 1609.1.2 of the FBC as an impact resistant product and does not require the use of an external impact resistant covering. This product meets missile level "D" and includes Wind Zone 4 as defined in ASTM E 1996 and Section 1609.1.2.2 of the FBC. 4. For 2X stud framing construction, anchoring of these units shall be the same as that shown for 2X buck masonry construction. 5. Site conditions that deviate from the details of this drawing require further engineering analysis by a licensed engineer or registered architect. 6. See drawing FL-6993.1 for size and design pressure limitations. Supporting Documents: 1. Test Report No. TEL 2005-02-21-004 TEL 06-1031-4 2. Drawing No. No. FL 6993.1 3. Calculations Anchoring Test Standard ASTM E330-02 ASTM E 1886/1996-02 ASTM E331-02 Prepared bV RW Building Consultants, Inc. (CA #9813) Prepared by RW Building Consultants, Inc. (CA #9813) 4. Quality Assurance Certificate of Participation issued by National Accreditation and Management Institute, certifying that Therma Tru Corporation is manufacturing products within a quality assurance program that complies with ISO/IEC 17020 and Guide 53. Sheet 1 of 1 Testing Laboratory Signed by Testing Evaluation Lab.,lnc. Wendell W. Haney, P.E. Testing Evaluation Lab.,lnc. Wendell W. Haney, P.E. Signed & Sealed by Lyndon F. Schmidt, P.E.