HomeMy WebLinkAboutWind load Gray JB DESIGN & PERMITTING , INC .
Date:09/07/21
Project:Gray Residence/10600 S Ocean Dr,Unit 1010,Jensen Beach,FL
Re:Wind Loads
MecaWind v2351
Software Developer: Meca Enterprises Inc., www.meca.biz, Copyright © 2020
Calculations Prepared by: Calculations Prepared For:
Client: Gray Residence
Date: Sep 07, 2021 Project #: 21009
Designer: Julio Gonzalez, P.E. Location: 10600 S Ocean Dr., Unit 1010, Jensen Beach, FL 34957
Description:
Windows and Door Retrofit
File Location : D:\AHP 21009 Gray WL\Wind Loads\Gray Residence mecawind.wnd
Basic Wind Parameters
Wind Load Standard = ASCE 7-16 Exposure Category = D
Wind Design Speed = 170.0 mph Risk Category = II
Structure Type = Building Building Type = Enclosed
Building Inputs
RoofType: Building Roof Type = Flat Flat Roof =
RfHt Roof Height = 130.000 ft W Building Width = 71.000 ft
L Building Length = 278.000 ft OR Type of Overhang = None
Parapet Type of Parapet = Parapet Par Is there a Parapet = True
PHt Height of Parapet = 3.000 ft Por Parapet Porosity = Solid
P GCPi Parapet Int Press = +/-0.00 OH ALL None = 0.000 ft
Main Wind Force Resisting System (MWFRS) Calculations per Ch 27 Part 1:
h = Mean Roof Height above grade = 130.000 ft
Kh = 15 ft [4.572 m]I Z <Zg -->(2.01*(Z/zg)^(2/Alpha) (Table 26.10-11= 1.500
Not = Topographic Factor is 1 since no Topographic feature specified = 1.000
Kd = Wind Directionality Factor per Table 26.6-1 = 0.85
Zg = Elevation above Sea Level = 0.000 ft
Ke = Ground Elevation Factor: Ke = e^-(0.0000362*Zg) {Table 26.9-11 = 1.000
GCPi = Ref Table 26.13-1 for Enclosed Building = +/-0.18
RA = Roof Area = 19738.00 sq ft
LF = Load Factor based upon ASO Design = 0.60 `,��
qh = (0.00256 * Kh * Kzt * Kd * Ke * V^2) * LF = 56.59 psf F /nV
qin = For Negative Internal Pressure of Enclosed Building use qh*LF = 56.59 psf ��, O • Z
gip = For Positive Internal Pressure of Enclosed Building use qh*LF = 56.59 psf � `\• G�E
V C lJ[�
Gust Factor Calculation: : �� �\ ` ��
Gust Factor Category I Rigid Structures - Simplified Method ^ •�•
G1 = For Rigid Structures (Nat. Freq.>1 Hz) use 0.65 = 0.85 I`
Gust Factor Category II Rigid Structures - Complete Analysis ♦ 'Bic�itally75�ed i1 1;lio Gowealez
Z. = 0.6 Ht = 78.000 ft I q •Y1 DN:E=admin@jbdtear-US
I'm
= Cc * (33 / zm) 0.167 = 0.130 Ju118 6bl zaleZ CN=Julio Gonzalez,r-US-
Lzm = L (Zm / 33) ^ Epsilon = 723.787 �_ �te2021.09.0722►32:44-QM'00'
Q = (1 / (1 + 0.63 * ((B
+ Ht) / Lzm)^0.63))^0.5 = 0.884 13
G2 = 0.925*((1+1.7*lzm*3.4*Q)/(1+1.7*3.4*lzm)) = 0.879 [/,
Gust Factor Used in Analysis : S T A T E OF v. Z.
= Lessor Of G1 Or G2 = 0.850 �O•• •
Components and Cladding (C&C) Calculations per Ch 30 Part 3: �' •• O R
Theta = Slope of Roof = 0.0 Deg .C1 •• •rl••.•• _N`G.
h = Mean Roof Height above grade = 130.000 ftft
1.500
Kzt = Topographic2Factor isg1 si(nce0no(Topographicpha featureble specified2 . lF= 1.000 ,''f��
Kd = Wind Directionality Factor per Table 26.6-1 = 0.85
GC
Pi = Ref Table 26.13-1 for Enclosed Building = +/-0.18
LF = Load Factor based upon ASD Design = 0.60
qh = (0.00256 * Kh * Kzt * Kd * Ke * V^2) * LF = 56.59 psf
LHD = Least Horizontal Dimension: Min(B, L) = 71.000 ft
al =Min(0.1 * LHD, 0.4 * h = 7.100 ft
a =Max(al, 0.04 * LHD, 3 ft [0.9 ml) = 7.100 ft
Effective Wind Area for CSC per Ch 30 Part 3
Description Zone Elev Width Span 1/3 Area Ref GCp GCp
Length Rule Fig Max Min
ft ft ft ft sq ft
Mark 1 4 100.00 4.271 5.208 No 22.24 30.6-1 0.890 -0.893
Mark 2 4 100.00 2.917 8.000 No 23.33 30.6-1 0.886 -0.890
Wind Pressures for C&C per Ch 30 Part 3
All wind pressures include a load factor of 0.6
Description Zone qi q_ww. q_oth P_WW P Ww P_Oth P_Oth P_Max P_Min
Max Min Max Min
ft psf psf psf psf psf psf psf psf psf
Mark 1 4 56.59 54.07 56.59 58.31 -58.49 60.56 -60.74 60.56 -60.74
Mark 2 4 56.59 54.07 56.59 58.07 -58.33 60.31 -60.58 60.31 -60.58
GCp = Walls and Flat Roofs (Slope < 10 Deg) use Fig 30.56-1
= Per Fig 30.5-1 Note 6 Roof Slopes >= 10 Deg use Fig 30.3-2A, B and C
qi = qh for Enclosed buildings
q ww = qz for Windward walls
q orb qh for Leeward walls, Side walls and Roofs
P_WW = Press on Windward Walls: q_ww * GCp - qi * ('/-GCpi) [Eqn 30.5-1]
P_Oth = Press on Leeward/Side/Roof: q_oth GCp - qi (+/-GCpi) [Eqn 30.5-11
P_Max = Max Positive Pressure on C&C component: Max(P_WW, P_Oth)
P_Min = Max negative pressure on C&C component: Min(P_WW, P_Oth)
* Per Para 30.2.2 the Minimum Pressure for C&C is 9.60 psf [0.460 kPa] {Includes LF)