(E) MIN. 60 A AC DISCONNECT
(LOCKABLE PER NEC 705.22).
LOCATE OUTDOOR IN
ACCESSIBLE LOCATION
NOTES:
1. REFER TO SHEET PV.4 FOR ALL APPLICABLE ELECTRICAL NOTES.
2. SYSTEM MEETS REQUIREMENTS OF NEC 2017 690.12 FOR RAPID
SHUTDOWN. INSTALL PER MANUFACTURER INSTRUCTIONS.
3. ALL CONDUCTORS SHALL BE COPPER UNLESS NOTED OTHERWISE. MINIMUM
CONDUCTOR SIZES SHOWN THIS SHEET.
4. THIS SHEET IS DIAGRAMMATIC IN NATURE AND MAY NOT DEPICT ALL
REQUIRED COMPONENTS OR CIRCUITS AS THEY MAY EXIST. THE PURPOSE OF
THIS DIAGRAM IS TO SHOW THE MAJOR POWER SYSTEM COMPONENTS
AND CIRCUITS. CONSULT EQUIPMENT MANUFACTURERS' INSTALLATION
MANUALS PRIOR TO INSTALLATION AND COMMISSIONING.
CIRCUIT TYPE QTY.SIZE
(AWG)
MIN.
CONDUIT
SIZE
PHASE CONDUCTOR
QTY.SIZE
(AWG)
NEUTRAL CONDUCTOR
QTY.SIZE
(AWG)
GROUND CONDUCTOR MAX.
CIRCUIT
LENGTH
1 AC
2 AC 3/4"2 #6 1 #8 86'
WIRE & CONDUIT SCHEDULE
1. CONDUCTOR & CONDUIT SIZES SHOWN ARE MINIMUM REQUIRED. LARGER SIZES MAY BE USED.
2. ALL CONDUCTORS SHALL BE THHN OR THWN-2 UNLESS OTHERWISE NOTED.
3. MAXIMUM CIRCUIT LENGTHS ARE BASED ON A MAXIMUM 2% VOLTAGE DROP.
BRANCH NO. 1
(16) MODULES & (16) MICROINVERTERS
G G
L1
L2
L1
L2
#6 AWG SOLID CU EQUIPMENT GROUND CONDUCTOR CONT. RUN TO GROUND LUG ON
RACKING SYSTEM. ALL ROOFTOP COMPONENTS BONDED TO RACKING SYSTEM PER NEC
690.43. MICROINVERTERS CONTAIN INTEGRATED EQUIPMENT GROUNDING.
G
L1 L2
N
N
(E) ENPHASE IQ COMBINER 80
A SOLAR COMBINER PANEL -
NEMA 3R ENCLOSURE
20A/2P
L1
L2
G
1 #6
(E) JUNCTION BOX
NEMA 3R ENCLOSURE
DC-SIDE
MODEL
RATED POWER
Voc
PHOTOVOLTAIC SYSTEM POWER TABLE
MODULE QTY.
MANUFACTURER
Isc
Vmpp
Impp
1
1
1
PARALLEL
SERIES
1
1
1
AC-SIDE
CONT. CURRENT
FREQUENCY
MODULE QTY.
MODEL
VOLTAGE
CONT. POWER
MANUFACTURER
MAX. BRANCH
PV MODULE DC-INPUT MICROINVERTER
240 VAC
16.00 A AC
60 HZ
16
3840 W
---
20 A
---
---
16
BRANCH NO. 1
QTY.1
240 VAC
16.00 A AC
60 HZ
16
3840 W
---
20 A
---
---
16
HOME RUN
OCPD RATING
** MODULE CHARACTERISTICS AT STC: CELL TEMPERATURE @ 25° C, SPECTRUM AM1.5, IRRADIANCE @ 1000 W/M²
10A/2P
L1
L2
ENPHASE
ENVOY
(FACTORY
WIRED)
ENPHASE
DROP
CABLE
SYSTEM
TERMINATOR CAP
INSTALLED
ON END OF
ENPHASE BUS
CABLE SYSTEM
ENPHASE BUS
CABLE TYP.
-+-+-+-+ENPHASE IQ7
MICROINVERTER
TYP.
3/4"2 #10 1 #10 1 #8 95'
L1
L2
2
G
N
CTRL
(N) TESLA 200 A
BACKUP GATEWAY 2
WITH OPTIONAL
PANEL KIT INSTALLED
30A/2P
L1
L2
20A/2P
L1
L2
L1 L2
L1 L1 L2 L2
N1
G
L1 L2
N
N
(N) 60A
MAIN
BREAKER
(N) MIN. 125 A
PROTECTED
LOAD PANEL
TESLA POWERWALL 2
CTRL GNL2L1
STORAGE CAPACITY
BATTERY
INVERTER
ENCLOSURE
MAX. OUTPUT CURRENT
AC GRID BREAKER
MAX. AC OUTPUT POWER
BATTERY STORAGE SYSTEM: (1) TESLA POWERWALL 2
INTEGRAL LITHIUM-ION (13.5 KWH)
TESLA POWERWALL 2 & BACKUP GATEWAY
NEMA 3R (POWERWALL 2 & BACKUP GATEWAY)
24 A - PER UNIT
30 A/2P - PER UNIT
5000 W (CONTINUOUS, 240 VAC) - TOTAL
13.5 KWH TOTAL (13.5 KWH PER UNIT)
MAX. DC INPUT POWER 7600 W (PV), 5000 W (BATTERY, CONTINUOUS) - TOTAL
EXISTING EARTH GROUND
GROUNDING ELECTRODE
L1 L2 N G
G
(N) MIN. 60 A AC DISCONNECT
(LOCKABLE PER NEC 705.22).
LOCATE IN ACCESSIBLE
LOCATION
200A MAIN
BREAKER
(V.I.F.)
60A/2P
G
L1 L2
N
N
EXISTING EARTH GROUND
GROUNDING ELECTRODE
(E) 200A MAIN
DISTRIBUTION
PANEL (V.I.F.)
L1
L2
L2L1
N
L2L1
TO UTILITY GRID
120/240 VAC
SINGLE PHASE
BI-DIRECTIONAL
(TYP.) UTILITY
KWH METER
L1 L2 N
(E) CIRCUIT TO
REMAIN
(E) CIRCUIT TO
REMAIN
NOTE: COMPONENTS SHOWN WITHIN DASHED LINES ARE
EXISTING TO REMAIN AND APPROVED UNDER PREVIOUS PERMIT.
THE ENERGY STORAGE SYSTEM BEING ADDED WILL INTEGRATE
WITH EXISTING PV EQUIPMENT.
---
---
1.00 A AC
60 HZ
1
IQ7
240 VAC
240 W
ENPHASE
16
---
340 W
40.66 VDC
10.52 ADC
33.94 VDC
10.02 ADC
QCELLS
DUO BLK-G6
340 W
40.66 VDC
10.52 ADC
33.94 VDC
10.02 ADC
2
NOTE: OCPD SIZED FOR INPUT
CURRENT FOR ENERGY STORAGE
SYSTEM FROM GRID. UTILITY
INTERACTIVE OUTPUT CURRENT IS
LIMITED TO 16A AND COMPLIES
WITH NEC 705.12(B)(2)(3)(a).
DRAWING #
SHEET OF
DATE
DRAWN BY:
CHECKED BY:
PROJECT:PHOTOVOLTAIC SOLAR ENERGY SYSTEMPROJECT ADDRESS:REC. NO. #
SCALE AS NOTED
DESIGNER HEREBY EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE PLANS. THESE PLANS AND DRAWINGS ARE NOT TO BE REPRODUCED,CHANGED OR COPIED IN ANY FORM OR MANNER WHATSOEVER WITHOUT FIRST OBTAINING THE EXPRESS PERMISSION AND CONSENT OF THE DESIGNER, NOR ARE THEY TO BEASSIGNED TO ANY PARTY WITHOUT FIRST OBTAINING SAID WRITTEN PERMISSION AND CONSENT.WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALE DIMENSIONS: CONTRACTORS SHALL VERIFY AND BERESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF ANY VARIATION FROM THEDIMENSIONS AND CONDITIONS SHOWN BY THESE DRAWINGS.950 SUNSHINE LN, ALTAMONTE SPRINGS, FLWWW.UMASOLAR.COMENGINEERING@UMASOLAR.COMSLROREVDATEBYREMARKDOCUMENT NOT
VALID WITHOUT
SIGN AND SEAL
FL PE #81305
JOHN L. ANTONELLI, P.E.
29127PROJECT NAME:FORT PIERCE, FL 349515207 ECHO PINES CIRCLE EAST UTZ RESIDENCE11
JLA
JLA
10/14/21
PV.3L