Loading...
HomeMy WebLinkAboutAPPROVED Sched 40GAS PIPING INSTALLATIONS TABLE 402,4(27) SCHEDULE 40 METALLIC PIPE Gas Undiluted Propane inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 1.50 INTENDED USE Pipe sizing between 2 psig service and line pressure regulator. PIPE SIZE (inch) Nominal '/_ '14 1 1' 14E 1 2 1 211, 3 4 Actual ID 0.622 tne 1.049 1.380 1 1.610 1 2.067 1 2.469 3.068 4.026 Length (ft) Capacity In Thousands of Btu per Hour 10 2,680 10,500 21,600 1 32,400 62,400 99,500 176,000 359,000 20 1,840 3,850 7,240 14,900 22,300 42,900 68,400 121,000 247,000 1,480 5,820 11,900 17,900 34,500 54,900 97,100 198,000 40 1,260 2,640 4,980 10,200 15,300 29,500 47,000 83,100 170,000 50 1,120 2,340 4,410 9,060 13,600 26,100 41,700 73,700 150,000 60 1,010 2,120 4,000 8,210 12,300 23,700 1 37,700 66.700 136,000 70 934 1,950 3,680 7,550 11,300 21,800 34,700 61,400 125,000 BO 869 1,820 3,420 7,020 10,500 20,300 32.300 57,100 116,000 90 815 1,700 3,210 6,590 9,880 19,000 30,300 53,600 109,000 100 770 1.610 3,030 6,230 9,330 18,000 28,600 50,600 103,000 125 682 1,430 2,690 5,520 8,270 15,900 25,400 44,900 91,500 150 618 1,290 2,440 5,000 7,490 14,400 23.000 40,700 82,900 175 569 1,190 2,240 4,600 6,890 13,300 21,200 37,400 76,300 200 529 1,110 2,080 4,280 6,410 12,300 19,700 34,800 71,000 250 469 981 11850 3.790 5,680 10,900 17,400 30,800 62.900 300 425 1 869 1,670 3,440 5,150 9,920 15,800 27,900 57,000 350 391 817 1.540 1 3,160 4,740 9.120 14,500 25,700 52.400 400 364 760 1,430 2,940 4,410 8,490 13,500 23,900 48,800 450 341 714 1,340 2,760 4,130 7,960 12.700 22,400 45,800 500 322 674 1,270 2,610 3,910 7,520 12,000 21,200 43,200 550 306 640 1,210 2,480 3,710 7140 11,400 20,100 41,100 600 292 L 611 1,150 2,360 3,540 6,820 10,900 19,200 39,200 650 280 585 1,100 2,260 3,390 6,530 10,400 18,400 37,500 700 269 562 1,060 2,170 3,260 6,270 9,990 17,700 36,000 750 259 541 1,020 2,090 3,140 6,040 9,630 17,000 34,700 800 250 523 985 2,020 3,03D 5,830 9,300 16,400 33.500 850 242 506 953 1,960 2,930 5.640 9,000 15,900 32,400 900 235 490 924 1,900 2,840 5,470 8,720 15,400 3 L 500 950 228 476 997 1,940 2,760 5,310 8,470 15,000 30.500 1,000 222 463 873 1,790 2.680 5,170 8,240 14,600 29,700 1,100 210 440 $29 1,700 2,550 4,910 7,930 13,800 28,200 1,200 201 420 791 1,620 2,430 4,680 7,470 13,200 26,9D0 1,300 192 402 757 1,550 2,330 4,490 7,150 12,600 25,800 1,400 185 386 727 1,490 2,240 4,310 6,870 12,100 24,800 1,500 178 1 372 701 1,440 2,160 4,150 6.620 11,700 23,900 1,600 172 359 677 1,390 2,080 4,010 6,390 11,300 23,000 1,700 166 348 655 1,340 2.010 3,880 6,1Bo 10,900 22,300 1,800 161 337 635 1,300 1,950 3.760 6,000 10,600 21,600 1,900 157 327 617 1 1,270 1,900 3,650 5,820 10,300 21,000 2,000 152 318 600 1,230 1,840 3,550 5,660 10,000 20,400 . .. 1 - -- 111,11, 1 1wt. - wy.o min, r pounu per square mcn = 6.89:) KYa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0,0283 m'/h, 1 degree = 0.01745 red. Note: All table entries have been rounded to three significant digits. 52 FLORIDA BUILDING CODE - FUEL GAS 64th EDITION (2017) 11Copyright ®im7 ]CC AEI, RIGHTS RESERVED. Accessed by Lilly Silva on Jan 30, 201x 5:00:34 AM pursuant to License Agreement with ICC. No further reproduction or distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECTTO CIVIL. AND CRIMINAL PENALTIES THEREUNDER.