In-Place Density Test Report
Client:D. R. Horton America's Builder UES Technician:Mark Rogers
6123 Lyons Road
Coconut Creek, FL 33073
Date Tested:12/01/2021
Project:CMT CREEKSIDE
Yorktown Drive & Okeechobee Road,Fort Pierce, St Lucie County, FL
Type of Test:
Area Tested:Lot 97 - 3300 Homestead Drive, Ft.
Pierce
Field:ASTM D-6938 Nuclear Gauge Method
Material:Backfill Laboratory:ASTM D1557 Modified Proctor
Reference Datum:0 = Top of Final Grade
The tests below meet the 95% minimum compaction requirement.
Test
No.Location of Test Range
Maximum
Density
(pcf)
Optimum
Moisture
(%)
Field Dry
Density
(pcf)
Field
Moisture
(%)
Soil
Compaction
(%)
Pass
or
Fail
1 Northside of house 0-1 ft 109.0 11.7 105.0 10.9 96 Pass
2 Southside of house 0-1 ft 109.0 11.7 104.0 11.3 95 Pass
3 Eastside of house 0-1 ft 109.0 11.7 103.8 11.0 95 Pass
4 Westside of house 0-1 ft 109.0 11.7 104.6 11.4 96 Pass
Remarks: Tests performed along outside perimeter of structure.
Permit: 2105-0821
Reviewed By
GFA International, Inc
FBPE Registry No.4930
Alex Albandoz, P.E.
STATE OF FLORIDA
Professional Engineer No. 92555
This item has been digitally signed and sealed by Alex Albandoz,
P.E. on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.