Loading...
HomeMy WebLinkAboutFEEDER LOAD CALCULATIONS it ... .. j y; STAN(DAIR SERVICE/FEEDER LOAD CALCULATION one Family Dwelling NEC Article 310 'i General Lighting ,j: 2439 Sq. Feet x 3 VA - 7317 VA Small Appliance .!: 2 Ci rcui is x 1.500 VA = 3000 VA Laundry . . . , . , 2 Circuits x 1500 VA - 3000 VA Total General Light & Small Appliance . . , . , a 1.3317 VA The First 3000 VA % 1.00% - 3000 VA Rema l ni n 1.0317 VA 0 35% v 1611 VA GENERAL LIGHTING, SMALL. APPLIANCE LAUNDRY DEMAND LOAD (NEC 220,42) : 6611 VA Heating Demand : 10000 VA 4 100% 10000 VA LARGER OF HEATING OR COOLING DEMAND LOADS (Heating) (NEC 220.60) . . . 10000 YEA Range : 5000 VA GOOFING EQUIPMENT DEMAND LOAD (NEC 220,55) . . . . . . . . . . . . . . . . . . . . . . . . . 4000 VA Dryer: 4500 vA DRYER DEMAND LOAD (NEC 220.54) . . . . . . . . . . . . . . , . . . . . . . . . . . . . . . . . . . . . : 4500 VA stater Heater: 3500 VA Dishwasher 1200 VA Disposal 1200 VA well Pump 4500 VA Fixed Appliance Total ; 1.045-0 VA 10400 VA 9 75% remand: 7800 VA FIXED APPLIANCE DEMAND LOAD (NEc 220,53) . . . . . . . . . . . . . . . . . . ; 7800 VlA. Largest Motor; well Pump a 000 VA 25% OF LARGEST MOTOR LOAD (220,14) . . . . . . . . . . 0 . . . . . . . . . . . . . . . . . . . . . . ; 1125 VA NETCOMPUTED LOAD . . . ! . . . , . , . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34036 VA 120/240 VOLT SERVICE/FEEDER LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142 AMP NEUTRAL LOAD (NEC 220.61) : General Lighting . . . . . . . . . . 6611 VA Appliances . . . . . . . . . . . . . . . 3600 VA cooking . . . . . . . . . . . . . . . . . 2800 VA Dryer . . . . . . • . . . . . . . . . . . . . : 3150 VA Largest Motor , . . . . . , . . » . , 1125 VA Heating/cooling 0 VA Total Neutral Demand Load . 17286 VA 72 AMP