Loading...
HomeMy WebLinkAboutMANUAL JCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-10 07:12:42 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\WORSNOP RESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Project Summary Jun 09, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information WORSNOP RESIDENCE, JWN BUILDERS, LLC.For: LOT 634 VENTURE OUT, JENSEN BEACH, FL Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh26736 Struc ture Btuh17368 Ducts Btuh4755 Ducts Btuh4342 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh31491 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh20624 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh3625 Ducts Btuh1808 Central vent (0 cfm)Btuh0 CoolingHeating (none) 18761876Area (ft²)Equipment latent load Btuh5433 1526015260Volume (ft³) Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh26057 Equiv. AVF (cfm)5197 Req. total capacity at 0.70 SHR ton2.5 Heating Equipment Summary Cooling Equipment Summary Make Make Trane Trade Trade TRANE Model Cond 4TTR4031L1 AHRI ref Coil TEM6A0C36H31++TDR AHRI ref 7567544 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW9.1 Sensible cooling Btuh20580 Heating output Btuh31061 Latent cooling Btuh8820 Temperature rise °F29 Total cooling Btuh29400 Actual air flow cfm980 Actual air flow cfm980 Air flow factor cfm/Btuh0.031 Air flow factor cfm/Btuh0.045 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.80 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-10 07:12:42 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\WORSNOP RESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Jun 09, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House FOYER 2 Exposed wall 257.4 ft 14.0 ft 3 Room height 8.1 ft 8.0 heat/coolft 4 Room dimensions ft116.8x1.0 5 Room area 1875.5 ft²116.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 503 264 1354 842 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 75 0 1365 1124 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 48 0 874 720 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 75 0 1365 1124 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 40 0 732 603 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 722 665 3408 2118 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 4 0 71 132 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 15 0 273 507 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 4 0 81 150 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 30 0 546 1013 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 22.4322.43 4 0 73 90 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 280 203 1039 646 80 60 305 190 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 12 12 218 180 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 36 36 650 536 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 20 20 371 306 20 20 371 306 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.9110.91 9 9 164 98 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 swsw 5.125.12 3.183.18 54 54 275 171 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 568 511 2618 1627 32 26 133 83 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 6 0 109 203 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 30 0 546 1013 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 12 0 218 405 6 0 109 203 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 9 0 164 304 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 1001 1001 1586 1369 0 0 0 0 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 1001 149 5660 0 117 14 532 0 6 c) AED excursion 0 12 Envelope loss/gain 23762 15279 1451 793 12 a) Infiltration 2974 839 157 44 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1250 0 Subtotal (lines 6 to 13)26736 17368 1608 837 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 26736 17368 1608 837 15 Duct loads 18%25%4755 4342 18%25%286 209 Total room load 31491 21710 1894 1046 Air required (cfm)Air required (cfm)980 980 59 47 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-10 07:12:42 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 E:\Documnets\Wrightsoft HVAC\WORSNOP RESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Jun 09, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name POWDER RM M TOILET 2 Exposed wall 6.0 ft 14.6 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x6.0 ft30.0x1.0 5 Room area 36.0 ft²30.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 0 0 0 0 33 29 149 92 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 22.4322.43 0 0 0 0 4 0 73 90 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 0 0 0 0 48 39 200 124 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.9110.91 0 0 0 0 9 9 164 98 WW 13AB-0fcs13AB-0fcs 0.1830.183 swsw 5.125.12 3.183.18 0 0 0 0 36 36 183 114 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 48 42 215 134 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 6 0 109 203 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 0 0 0 0 22 22 35 30 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 36 6 228 0 30 15 555 0 6 c) AED excursion 78 -10 Envelope loss/gain 553 415 1358 539 12 a) Infiltration 67 19 163 46 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)620 434 1521 585 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 620 434 1521 585 15 Duct loads 18%25%110 108 18%25%271 146 Total room load 730 542 1792 731 Air required (cfm)Air required (cfm)23 24 56 33 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-10 07:12:42 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 3 E:\Documnets\Wrightsoft HVAC\WORSNOP RESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Jun 09, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M BATH MASTER BEDROOM 2 Exposed wall 11.5 ft 14.3 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft75.5x1.0 ft185.5x1.0 5 Room area 75.5 ft²185.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 58 54 276 171 115 100 510 317 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 4 0 81 150 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 15 0 273 507 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 22.4322.43 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.9110.91 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 swsw 5.125.12 3.183.18 18 18 92 57 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 16 16 82 51 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 6 6 9 8 7 7 11 9 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 76 12 437 0 186 14 542 0 6 c) AED excursion -5 -1 Envelope loss/gain 977 432 1336 832 12 a) Infiltration 129 36 160 45 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 350 900 Subtotal (lines 6 to 13)1105 818 1496 1777 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1105 818 1496 1777 15 Duct loads 18%25%197 205 18%25%266 444 Total room load 1302 1023 1762 2222 Air required (cfm)Air required (cfm)41 46 55 100 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-10 07:12:42 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 4 E:\Documnets\Wrightsoft HVAC\WORSNOP RESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Jun 09, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC W/D 2 Exposed wall 3.1 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft27.0x1.0 ft13.5x1.0 5 Room area 27.0 ft²13.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 25 25 130 81 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 22.4322.43 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.9110.91 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 swsw 5.125.12 3.183.18 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 0 0 0 0 0 0 0 0 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 27 3 117 0 14 0 0 0 6 c) AED excursion -1 0 Envelope loss/gain 247 79 0 0 12 a) Infiltration 35 10 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)282 89 0 0 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 282 89 0 0 15 Duct loads 18%25%50 22 18%25%0 0 Total room load 332 111 0 0 Air required (cfm)Air required (cfm)10 5 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-10 07:12:42 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 5 E:\Documnets\Wrightsoft HVAC\WORSNOP RESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Jun 09, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name KITCHEN/LIVING RM WIC 2 Exposed wall 63.1 ft 9.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft425.2x1.0 ft5.0x4.0 5 Room area 425.2 ft²20.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 251 136 697 433 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 75 0 1365 1124 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 40 0 732 603 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 142 127 650 404 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 15 0 273 507 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 22.4322.43 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 0 0 0 0 32 32 164 102 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.9110.91 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 swsw 5.125.12 3.183.18 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 112 103 528 328 40 40 205 127 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 9 0 164 304 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 0 0 0 0 20 20 32 27 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 425 63 2399 0 20 9 342 0 6 c) AED excursion -63 -5 Envelope loss/gain 6807 3640 743 252 12 a) Infiltration 706 199 101 28 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)7513 3839 844 280 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 7513 3839 844 280 15 Duct loads 18%25%1336 960 18%25%150 70 Total room load 8849 4799 994 351 Air required (cfm)Air required (cfm)275 217 31 16 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-10 07:12:42 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 6 E:\Documnets\Wrightsoft HVAC\WORSNOP RESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Jun 09, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name STAIRS UP BEDROOM 2 Exposed wall 13.0 ft 27.3 ft 3 Room height 12.9 heat/coolft 8.0 heat/coolft 4 Room dimensions ft13.0x4.0 ft198.0x1.0 5 Room area 52.0 ft²198.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 0 0 0 0 99 99 507 315 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 22.4322.43 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 0 0 0 0 120 72 370 230 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 12 12 218 180 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 36 36 650 536 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.9110.91 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 swsw 5.125.12 3.183.18 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 168 162 830 516 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 6 0 109 203 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 52 52 82 71 198 198 314 271 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 32 8 304 0 32 4 169 0 6 c) AED excursion 70 17 Envelope loss/gain 1326 860 2229 1549 12 a) Infiltration 235 66 306 86 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1561 926 2536 1635 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1561 926 2536 1635 15 Duct loads 18%25%278 232 18%25%451 409 Total room load 1838 1158 2986 2044 Air required (cfm)Air required (cfm)57 52 93 92 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-10 07:12:42 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 7 E:\Documnets\Wrightsoft HVAC\WORSNOP RESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Jun 09, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name SINKS LINEN CLST 2 Exposed wall 0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x7.0 ft2.0x6.0 5 Room area 42.0 ft²12.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 22.4322.43 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.9110.91 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 swsw 5.125.12 3.183.18 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 42 42 67 57 12 12 19 16 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -1 0 Envelope loss/gain 67 57 19 16 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)67 57 19 16 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 3 2 -19 -16 14 Subtotal 69 59 0 0 15 Duct loads 18%25%12 15 18%25%0 0 Total room load 82 73 0 0 Air required (cfm)Air required (cfm)3 3 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-10 07:12:42 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 8 E:\Documnets\Wrightsoft HVAC\WORSNOP RESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Jun 09, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name AHU CLST TOILET 2 Exposed wall 0 ft 6.3 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft5.0x5.0 ft48.0x1.0 5 Room area 25.0 ft²48.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 0 0 0 0 51 47 239 149 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 4 0 71 132 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 22.4322.43 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.9110.91 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 swsw 5.125.12 3.183.18 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 25 25 40 34 48 48 76 66 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -1 1 Envelope loss/gain 40 34 386 347 12 a) Infiltration 0 0 71 20 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)40 34 457 367 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -40 -34 11 9 14 Subtotal 0 0 468 376 15 Duct loads 18%25%0 0 18%25%83 94 Total room load 0 0 551 470 Air required (cfm)Air required (cfm)0 0 17 21 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-10 07:12:42 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 9 E:\Documnets\Wrightsoft HVAC\WORSNOP RESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Right-J® Worksheet Jun 09, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name STORAGE WIC SITTING RM 2 Exposed wall 7.3 ft 68.1 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft42.0x1.0 ft527.0x1.0 5 Room area 42.0 ft²527.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13AB-0fcs13AB-0fcs 0.1830.183 nn 5.125.12 3.183.18 0 0 0 0 251 128 657 408 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 75 0 1365 1124 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 48 0 874 720 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ee 5.125.12 3.183.18 58 58 298 185 142 127 650 404 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 15 0 273 507 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 22.4322.43 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ss 5.125.12 3.183.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.9110.91 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 swsw 5.125.12 3.183.18 0 0 0 0 0 0 0 0 WW 13AB-0fcs13AB-0fcs 0.1830.183 ww 5.125.12 3.183.18 0 0 0 0 152 122 625 388 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 30 0 546 1013 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 42 42 67 57 527 527 836 721 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 0 0 2 0 7 1 32 0 6 c) AED excursion -4 -89 Envelope loss/gain 367 239 5857 5197 12 a) Infiltration 81 23 762 215 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)449 262 6619 5411 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 17 14 29 24 14 Subtotal 465 276 6648 5436 15 Duct loads 18%25%83 69 18%25%1182 1359 Total room load 548 345 7830 6795 Air required (cfm)Air required (cfm)17 16 244 307 2021-Jun-10 07:12:48 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\WORSNOP RESIDENCE.rup Calc = MJ8 Front Door faces: S Job:Duct System Summary Jun 09, 2021Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information WORSNOP RESIDENCE, JWN BUILDERS, LLC.For: LOT 634 VENTURE OUT, JENSEN BEACH, FL CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm980cfm980 Total effective length (TEL)ft166 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st2115.09.2VlFx0x07.01.00092932986hBEDROOM st4142.018.2VlFx0x06.01.00047591894hFOYER st5142.013.8VlFx0x07.01.0001081384425hKITCHEN/LIVING RM st5142.013.8VlFx0x07.01.0001081384425hKITCHEN/LIVING RM -A st4142.017.3VlFx0x06.01.00046411023cM BATH st4142.024.2VlFx0x05.01.00033561792hM TOILET st1122.06.0VlFx0x04.01.000510332hM WIC st4142.017.2VlFx0x07.01.000100552222cMASTER BEDROOM st5142.014.7VlFx0x05.01.0002423542cPOWDER RM st2115.010.4VlFx0x04.01.0003373cSINKS st3115.013.1VlFx0x08.01.0001531223397cSITTING RM st3115.09.2VlFx0x08.01.0001531223397cSITTING RM-A st6135.023.7VlFx0x06.01.00052571838hSTAIRS UP st3115.012.1VlFx0x04.01.0001617548hSTORAGE WIC st2115.09.5VlFx0x05.01.0002117470cTOILET st6135.025.7VlFx0x04.01.0001631994hWIC 2021-Jun-10 07:12:48 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 E:\Documnets\Wrightsoft HVAC\WORSNOP RESIDENCE.rup Calc = MJ8 Front Door faces: S Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 210 227 1.000 513 9.0 0x0 VinlFlx st1 st5 Peak AVF 298 241 1.000 675 9.0 0x0 VinlFlx st1 st6 Peak AVF 88 68 1.000 449 6.0 0x0 VinlFlx st2 st2 Peak AVF 201 185 1.000 575 8.0 0x0 VinlFlx st3 Peak AVF 261 322 1.000 591 10.0 0x0 VinlFlx st1 Peak AVF 519 473 1.000 660 12.0 0x0 VinlFlx Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 9800 980 0 0 0 0 x0 0 VlFx ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������