HomeMy WebLinkAboutsoil report GFA INTERNATIONAL FLORIDA’S LEADING ENGINEERING SOURCE Report of Geotechnical Exploration Worsnop Residence 10701 South Ocean Drive (Lot 634) Jensen Beach, Florida May 5, 2021 GFA Project No. 3330.2100052.0000 For: Lois Denise Worsnop Since 1988 Florida’s Leading Engineering Source Environmental • Geotechnical • Construction Materials Testing • Threshold and Special Inspections • Plan Review & Code Compliance 607 NW Commodity Cove • Port St. Lucie, Florida 34986 • (772) 924-3575 • (772) 924-3580 (fax) • www.teamgfa.com OFFICES THROUGHOUT FLORIDA May 5, 2021 Ms. Lois Denise Worsnop 10701 South Ocean Drive (Lot 634) Jensen Beach, Florida 34957 Subject: Report of Geotechnical Exploration Worsnop Residence 10701 South Ocean Drive (Lot 634), Jensen Beach, Florida GFA Project No. 3330.2100052.0000 Dear Ms. Worsnop: GFA International, Inc. (GFA) has completed the subsurface exploration and geotechnical engineering evaluation for the above referenced project in accordance with the geotechnical and engineering service agreement for this project. The scope of services was completed in accordance with our Proposal No. 21-6679.00 dated February 23, 2021, planned in conjunction with and authorized by you. EXECUTIVE SUMMARY The purpose of our subsurface exploration was to classify the nature of the subsurface soils and general geomorphic conditions at the site and evaluate their impact upon the proposed construction. This report contains the results of our subsurface exploration and our engineering interpretations of these with respect to the project characteristics described to us, including providing recommendations for foundation design. Per our prior telephone discussions and email correspondence, GFA understands that you plan to construct a new residence to replace the existing modular home at 10701 South Ocean Drive (Lot 634) in Jensen Beach, Florida. Design details, plans, or anticipated foundation loads for the planned residence are not available at this time. The recommendations provided herein are based upon the above considerations. If the stated conditions are incorrect or if the project description is revised, please inform GFA so that we may review our recommendations with respect to any modifications. One (1) standard penetration test (SPT) boring, advanced to an approximate depth of 40 feet below the existing ground surface, was completed for this study. The subsurface soil conditions encountered in the boring generally consisted of very loose to medium dense fine sand (SP) and sand and cemented sand (GP) to the termination depth. As an exception, a layer of very loose organic clayey fine sand containing some fibrous organics (SC-OL) was present from a depth of approximately 7 to 8.5 feet below the ground surface. Worsnop Residence Geotechnical Exploration Report 10701 South Ocean Drive (Lot 634), Jensen Beach, Florida May 5, 2021 GFA Project No. 3330.2100052.0000 Page 2 of 10 ____________________________________________________________________________________ Based on the results of our field exploration, the very loose fine sand and organic soils present between approximate depths of 4 and 10 feet are not suitable for support of the new residence upon conventional shallow foundations due to the potential for the occurrence of excessive total and differential settlements and associated structural distress. Therefore, GFA recommends that either helical pile foundations or in-situ soil improvement be considered for this site. For the helical pile alternative, the piles would be designed and positioned to support the structure foundations and ground floor slab. To obtain the design axial capacity (to be determined by the project structural engineer), the piles will likely have to be installed and seated into the sand and cemented sand (GP) soils encountered below a depth of 23.5 feet in boring B-1. Note that the actual length of the installed helical piles will depend on achieving the required torque and corresponding design capacity. As an alternative to helical pile foundations, in-situ soil improvement consisting of shallow soil- mix columns could be performed below the structure footprint so that the residence could utilize a conventional shallow foundation system. This technique consists of advancing a rotary tool into the ground to a depth of 10 feet or deeper below the surface at several locations while injecting lean Portland cement grout into the soils. During withdrawal from the ground, the mixing head continues to rotate to further blend the soil and grout. For either of the above approaches, the near surface subgrade soils should be densified by compaction from the stripped surface prior to placing fill to attain design grade. The top 2 feet below stripped grade should be compacted to a minimum of 95 percent of modified Proctor (ASTM D 1557) maximum dry density. In general, fill required to attain design grades should be placed in 12-inch thick lifts and compacted to achieve the same criteria stated above. We appreciate the opportunity to be of service during this phase of the project and look forward to a continued association. Please do not hesitate to contact us if you have any questions or comments, or if we may further assist you as your plans proceed. Respectfully Submitted, GFA International, Inc. Florida Registry No. 4930 This item has been digitally signed and sealed by John Kent, P.E. on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. John Kent, P.E. Erik Soderstrom, E.I. Sr. Project Engineer Geotechnical Department Manager Florida Registration No. 63218 Distribution: Lois Denise Worsnop 1 pdf Worsnop Residence Geotechnical Exploration Report 10701 South Ocean Drive (Lot 634), Jensen Beach, Florida May 5, 2021 GFA Project No. 3330.2100052.0000 Page 3 of 10 ____________________________________________________________________________________ TABLE OF CONTENTS 1.0 INTRODUCTION ................................................................................................................. 4 1.1 Scope of Services ........................................................................................................... 4 1.2 Project Description .......................................................................................................... 4 2.0 OBSERVATIONS ................................................................................................................ 4 2.1 Site Description ............................................................................................................... 4 2.2 Field Exploration ............................................................................................................. 4 2.3 Visual Classification ........................................................................................................ 5 2.4 Geomorphic Conditions ................................................................................................... 5 2.5 Hydrogeological Conditions ............................................................................................. 6 3.0 ENGINEERING EVALUATION AND RECOMMENDATIONS.............................................. 6 3.1 General ........................................................................................................................... 6 3.2 Helical Pile Foundations .................................................................................................. 6 3.3 Shallow Soil Mixing ......................................................................................................... 8 3.4 Site Preparation .............................................................................................................. 8 3.5 Fill Placement and Compactioin ...................................................................................... 8 3.6 Quality Control and Vibration Monitoring ......................................................................... 9 4.0 REPORT LIMITATIONS ...................................................................................................... 9 5.0 BASIS FOR RECOMMENDATIONS ..................................................................................10 Appendix A - Vicinity Map Appendix B - Test Location Plan Appendix C - Notes Related to Borings Appendix D - Log of Boring Records Appendix E - Discussion of Soil Groups Worsnop Residence Geotechnical Exploration Report 10701 South Ocean Drive (Lot 634), Jensen Beach, Florida May 5, 2021 GFA Project No. 3330.2100052.0000 Page 4 of 10 ____________________________________________________________________________________ 1.0 INTRODUCTION 1.1 Scope of Services The objective of our geotechnical services was to collect subsurface data for the subject project, summarize the test results, and discuss any apparent site conditions that may have geotechnical significance for the proposed residential construction. The following scope of services is provided within this report: 1. Prepare boring logs depicting the subsurface soil conditions encountered during our field exploration. 2. Review the soil samples obtained during our field exploration for classification and additional testing if necessary. 3. Evaluate the existing soil conditions found during our exploration with respect to helical pile foundations or shallow soil-mix column ground improvement for the proposed construction. 4. Provide recommendations for site preparation and earthwork construction. 1.2 Project Description Per our prior telephone discussions and email correspondence, GFA understands that you plan to construct a new residence to replace the existing modular home at 10701 South Ocean Drive (Lot 634) in Jensen Beach, Florida. Additional information or plans for the proposed construction are not available at this time. The recommendations provided herein are based upon the above considerations. If the stated conditions are incorrect or if the project description is revised, please inform GFA so that we may review our recommendations with respect to any modifications. 2.0 OBSERVATIONS 2.1 Site Description Per our prior telephone discussions and email correspondence, GFA understands that you plan to construct a new residence to replace the existing modular home at 10701 South Ocean Drive (Lot 634) in Jensen Beach, Florida. Design details, plans, or anticipated foundation loads for the planned residence are not available at this time. 2.2 Field Exploration One (1) standard penetration test (SPT) boring, advanced to an approximate depth of 40 feet below the existing ground surface, was completed for this study. The approximate boring location is illustrated on the Test Location Plan in Appendix B. Worsnop Residence Geotechnical Exploration Report 10701 South Ocean Drive (Lot 634), Jensen Beach, Florida May 5, 2021 GFA Project No. 3330.2100052.0000 Page 5 of 10 ____________________________________________________________________________________ The Standard Penetration Tests (SPT) were performed in general accordance with ASTM D 1586, “Standard Test Method for Standard Penetration Test (SPT) and Split-Barrel Sampling of Soils.” The SPT test procedure consists of driving a 1.4-inch I.D. split-barrel sampler into the soil profile using a 140-pound hammer falling 30 inches. The number of blows per foot, for the second and third 6-inch increment, is referred to as the N-value. The N-value has been empirically correlated with various soil properties and provides an indication of soil strength. The upper 4 feet of the boring were advanced by hand augering due to potential near surface buried utility line conflicts. The augered portion of the boring was performed in general accordance with ASTM D 1452, “Standard Practice for Soil Exploration and Sampling by Auger Borings.” Hand Cone Penetrometer (HCP) tests were conducted at approximate one-foot depth intervals in the augered portion of the boring. The HCP test, in conjunction with information about the soil type, is empirically correlated to the relative density of subsurface soils. Site specific survey staking of the boring was not provided for our field exploration. The indicated depth and location of the boring was approximated based upon existing grade and by estimating distances and relationships to the existing residence and other landmarks at the site. 2.3 Visual Classification Soil samples recovered from our field exploration were returned to our laboratory where they were visually classified by a geotechnical engineer in general accordance with the Unified Soil Classification System (ASTM D 2487). After reviewing the samples, no laboratory testing was deemed necessary. The samples will be retained in our laboratory for 30 days and then discarded unless we are notified otherwise in writing. The recovered samples were not evaluated, either visually or analytically, for chemical composition or environmental hazards. GFA will be pleased to perform these services for an additional fee, if required. 2.4 Geomorphic Conditions The geology of the site as mapped on the USDA Soil Survey website consists of Arents, 0 to 5 percent slopes (4). Arents are areas where the soils have been generally altered by grading, shaping, and covered with fill. Therefore, the soils can be variable. Note that the Soil Survey generally extends to a maximum depth of 80 inches below ground surface and is not indicative of deeper soil conditions. The boring log resulting from our field exploration is presented in Appendix D - Log of Boring Records. The log contains the soil descriptions, the standard penetration test (SPT) N-values, and the hand cone penetrometer (HCP) values logged during the drilling and sampling activities. The soil boring data is specific to the boring location only and the soil conditions may vary between the strata interfaces indicated on the log. The soil classifications and descriptions shown on the log are based upon visual characterizations of the recovered samples using the Unified Soil Classification System. See Appendix E - Discussion of Soil Groups, for a detailed description of soil groups. Worsnop Residence Geotechnical Exploration Report 10701 South Ocean Drive (Lot 634), Jensen Beach, Florida May 5, 2021 GFA Project No. 3330.2100052.0000 Page 6 of 10 ____________________________________________________________________________________ The subsurface soil conditions encountered in the boring generally consisted of very loose to medium dense fine sand (SP) and sand and cemented sand (GP) to the termination depth. As an exception, a layer of very loose organic clayey fine sand containing some fibrous organics (SC-OL) was present from a depth of approximately 7 to 8.5 feet below the ground surface. 2.5 Hydrogeological Conditions On the date of our field exploration (April 20, 2021), groundwater was encountered in the boring at a depth of approximately 6 feet below the existing ground surface. The groundwater table will fluctuate seasonally depending upon local rainfall and other site specific and/or local influences, including tidal variations in the adjacent Jensen Beach Inlet. Brief ponding of stormwater may occur across the site after heavy or extended rainfall events. No additional evaluation was included in our scope of work in relation to the wet seasonal high groundwater table or any existing well fields in the vicinity. Well fields may influence water table levels and cause significant fluctuations. If a more comprehensive water table analysis is necessary, please contact our office for additional guidance. 3.0 ENGINEERING EVALUATION AND RECOMMENDATIONS 3.1 General Our geotechnical engineering evaluation of the site and subsurface conditions at the property, with respect to the planned construction, and our recommendations for site preparation and foundation support, are based upon (1) our site observations, (2) the field data obtained, and (3) our understanding of the project information and structural conditions as presented in this report. If the stated conditions are incorrect, or if the project description is revised, please inform GFA so that we may review our recommendations with respect to any modifications. We note that the applicability of geotechnical recommendations is very dependent upon project characteristics, specifically (1) improvement locations, (2) grade alterations, (3) and actual applied structural loads. For that reason, GFA must be provided with and review the preliminary and final site and grading plans, and structural design loads to validate all recommendations provided in this report. Without performing this review, our recommendations should not be relied upon for final design or construction of any site improvements. Based on the results of our field exploration, the very loose fine sand and organic soils present between approximate depths of 4 and 10 feet are not suitable for support of the new residence upon conventional shallow foundations due to the potential for the occurrence of excessive total and differential settlements and associated structural distress. Therefore, GFA recommends that either helical pile foundations or in-situ soil improvement be considered for this site. 3.2 Helical Pile Foundations Helical piles consist of galvanized steel shafts with helical flight augers on the bottom shaft. The shaft sections are bolted together as they are augered into the subsurface. The torque applied to the piles during drilling is correlated to the axial compression capacity of the helical pile. The Worsnop Residence Geotechnical Exploration Report 10701 South Ocean Drive (Lot 634), Jensen Beach, Florida May 5, 2021 GFA Project No. 3330.2100052.0000 Page 7 of 10 ____________________________________________________________________________________ steel shafts are cut at the appropriate cut-off elevations, and typically pile caps, grade beams, or footings are cast on the top of the helical piles. To obtain the design axial capacity (to be determined by the project structural engineer), the helical piles will likely have to be installed and seated into the sand and cemented sand (GP) encountered below a depth of 23.5 feet in boring B-1. The actual design of the piles (number, depth, spacing, etc.) will be performed by a structural engineer or a deep foundation specialty contractor. Note that the actual length of the installed helical piles will depend on achieving the required torque and corresponding design capacity. GFA recommends that the piles be spaced at least 3 diameters (largest helical diameter) apart center-to-center. Each pile must be installed with a minimum of twice its design capacity. The capacity of several piles must be verified by shear pins or other calibration techniques as required by the 2020 Florida Building Code, Seventh Edition as discussed below. In accordance with Section 1810.3.3.1.9 of the 2020 Florida Building Code, Seventh Edition, the allowable axial design load, Pa, of helical piles should be determined as follows: Pa = 0.5 Pu (Equation 18-4) where Pu is the least value of: 1. Sum of the areas of the helical bearing plates times the ultimate bearing capacity of the soil or rock comprising the bearing stratum. 2. Ultimate capacity determined from well-documented correlations with installation torque. 3. Ultimate capacity determined from load tests. 4. Ultimate axial capacity of pile shaft. 5. Ultimate axial capacity of pile shaft couplings. 6. Sum of the ultimate axial capacity of helical bearing plates affixed to the pile. Helical pile design and installation is proprietary in nature. The locations and required capacity of the piles must be designed by a structural engineer or other qualified professional. It is recommended that a representative of GFA monitor the helical pile installation in accordance with the Florida Building Code. We estimate that properly designed and installed helical piles will experience total in-service settlement on the order of one-half (0.5) inch or less. Differential settlement is estimated not to exceed one-quarter (0.25) inch. Required fill and backfill around pile caps and grade beams should consist of clean sand having less than 5 percent fines (percent of dry weight passing the U.S. No. 200 sieve). The fill should be placed in 8-inch maximum thick lifts with each lift compacted to at least 95 percent of modified Proctor (ASTM D 1557) maximum dry density. Achieving the recommended level of compaction should be confirmed by performing field density tests. Worsnop Residence Geotechnical Exploration Report 10701 South Ocean Drive (Lot 634), Jensen Beach, Florida May 5, 2021 GFA Project No. 3330.2100052.0000 Page 8 of 10 ____________________________________________________________________________________ 3.3 Shallow Soil-Mixing As an alternative to helical pile foundations, in-situ soil improvement consisting of shallow soil- mix columns can be performed below the structure footprint so that the residence can utilize a conventional shallow foundation system. This technique consists of advancing a rotary tool into the ground to a depth of 10 feet or deeper below the surface at several locations while injecting lean Portland-cement grout into the soils. Shallow soil mixing is performed using a 16-inch proprietary mixing head attached to a hollow stem drilling tube driven by a high torque rotary drilling machine capable of developing 4,000 to 10,000 ft-lbs. of torque. Neat Portland cement is mixed with a horizontal mixer manufactured by ChemGrout or equivalent. The neat cement grout is thoroughly mixed at a W/C ratio of 0.05/1 to 0.07/1, depending on ambient conditions and other factors and pumped through the hollow stem rotary drilling rig to the mixing head rotating at a rate of 20 to 60 RPM. The penetration rate depends on the soil porosity. Larger soil voids require a slower rate to allow the volume pumped to match or exceed the void volume. A steel rebar (size #6 to #8) is inserted vertically into the grout immediately upon completion of the grout column. The contractor and the Geotechnical Engineer typically discuss options for grout design, penetration rate, and grout volume. A test grout column should be performed prior to production grouting for the Engineer to observe grout column form. A load test can be performed to determine the capacity of the column. 3.4 Site Preparation Initial site preparation should consist of removing all structures, concrete slabs, surface vegetation, near surface roots, and other deleterious materials within, and to five (5) feet beyond, the perimeter of the construction footprint. Foundations and below grade remains of former structures located within the footprint of the construction should also be removed. Similarly, irrigation and utility lines should be removed or properly abandoned so that they will not adversely impact new overlying structures. 3.5 Fill Placement and Compaction Prior to placing fill to attain design grade, the stripped surface should be compacted until the upper 2 feet of soil achieves at least 95 percent of modified Proctor maximum dry density (ASTM D 1557). We recommend using a steel drum vibratory roller having sufficient static weight and vibratory impact to achieve the required compaction. Due to the proximity of the site to the adjacent residences, GFA recommends that the roller operate in the static mode. Density tests should be performed on the compacted surface at a frequency of not less than one test per 2,500 square feet, or a minimum of three (3) tests, whichever is greater. The density tests should be performed using either the nuclear method (ASTM D 6839) or the sand cone method (ASTM D 1556). Hand Cone Penetrometer (HCP) tests may also be performed to evaluate soil density. Fill should be inorganic (i.e., contain less than 5 percent by weight organic material) and classified as SP, SW, GP, GW, SP-SM, SW-SM, GW-GP, or GP-GM. GFA does not recommend using fill materials having silt/clay-size soil fines contents exceeding 12 Worsnop Residence Geotechnical Exploration Report 10701 South Ocean Drive (Lot 634), Jensen Beach, Florida May 5, 2021 GFA Project No. 3330.2100052.0000 Page 9 of 10 ____________________________________________________________________________________ percent. In general, fill required to attain design grades should be placed in maximum 12-inch thick loose lifts and compacted to at least 95 percent of modified Proctor maximum dry density (ASTM D 1557). Each lift of fill should be compacted and tested prior to the placement of the next lift. Density tests should be performed within the fill at the same frequency noted above. 3.6 Quality Control and Vibration Monitoring We strongly recommend that a GFA representative be on site during the helical pile installation or the soil mixing operations. This is necessary to determine if the work is being performed in accordance with the project plans and specifications, provide an accurate record of the pile installation or soil mixing, and afford an opportunity to correct any anomalous conditions that may be encountered. The proposed construction will be close to nearby residential structures and roadways that could be susceptible to damage from vibrations generated at the site during site preparation and foundation installation. We recommend that these structures and other bordering landmarks be monitored using a seismograph to determine the extent of vibration absorption they are experiencing during all aspects of construction. The seismograph used for monitoring at the site should have the capability to measure ground velocities along vertical, transverse, and longitudinal axes. The project Structural Engineer should establish allowable ground velocities that the bordering facilities can safely withstand without incurring damage. A proposal for GFA personnel to provide the vibration monitoring during construction will be provided upon request. 4.0 REPORT LIMITATIONS This consulting report has been prepared for the exclusive use of Ms. Lois Denise Worsnop and members of the design team for the proposed new residence located at 10701 South Ocean Drive (Lot 634) in Jensen Beach, Florida. This report has been prepared in accordance with generally accepted local geotechnical engineering practices; no other warranty, either express or implied, is made. The evaluation submitted in this report is based in part upon the data collected during a field exploration. However, the nature and extent of variations throughout the subsurface profile may not become evident until construction. If variations then appear evident, it may be necessary to reevaluate information and professional opinions provided in this report. In the event changes are made in the nature, design, or location of the proposed residence, the evaluation and opinions contained in this report should not be considered valid unless the changes are reviewed, and conclusions modified or verified in writing by GFA. GFA should be provided the opportunity to review the final design plans and specifications to determine if GFA’s recommendations have been properly interpreted, communicated, and implemented. If GFA is not afforded the opportunity to participate in construction related aspects of foundation installation recommended in this report or any report addendum, GFA cannot accept responsibility for the interpretation of our recommendations made in this report or in a report addendum for foundation performance. Worsnop Residence Geotechnical Exploration Report 10701 South Ocean Drive (Lot 634), Jensen Beach, Florida May 5, 2021 GFA Project No. 3330.2100052.0000 Page 10 of 10 ____________________________________________________________________________________ 5.0 BASIS FOR RECOMMENDATIONS The recommendations presented in this report are based on the data obtained from the boring performed at the location indicated on the Test Location Plan in Appendix B. This report does not reflect any variations which may occur away from the boring. While the boring is representative of the subsurface conditions at its location and vertical reach, local variations characteristic of the subsurface soils of the region are anticipated and may be encountered. The delineation between soil types shown on the boring log is approximate and the descriptions represent our interpretation of the subsurface conditions at the designated boring location on the specific date drilled. Any third-party reliance of our geotechnical report or parts thereof is strictly prohibited without the expressed written consent of GFA International, Inc. The applicable SPT methodology (ASTM D 1586) and auger boring methodology (ASTM D 1452) used in performing the boring, and for determining penetration resistance and soil relative density, is specific to the sampling tools utilized and does not reflect the ease or difficulty to advance other tools or materials. Appendix A - Vicinity Map Site Vicinity Map Worsnop Residence 10701 South Ocean Drive (Lot 634), Jensen Beach, Florida PROJECT NO: 3330.2100052.0000 DRAFTED BY: JR REVIEWED BY: JK DATE: 5/4/2021 gfhgfghfgh N Site Location Appendix B - Test Location Plan Test Location Plan Worsnop Residence 10701 South Ocean Drive (Lot 634), Jensen Beach, Florida PROJECT NO: 3330.2100052.0000 DRAFTED BY: JR REVIEWED BY: JK DATE: 5/4/2021 gfhgfghfgh N Legend Approximate 40’ Standard Penetration Test Boring Location B-1 Appendix C - Notes Related to Borings NOTES RELATED TO BORING RECORDS AND GENERALIZED SUBSURFACE PROFILES 1.Groundwater levels (if encountered) were recorded either during or following the boring completion on the date indicated. Fluctuations in groundwater levels are common - see the report text for a discussion. 2.The boring locations were identified in the field by estimated distances and offsets from existing reference marks and/or other site landmarks. 3.The completed boreholes were backfilled to adjacent site grade using drilling spoils and patched with asphalt cold mix in pavement areas. 4.The Log of Boring records represent our interpretation of soil conditions based on visual classification of the soil samples recovered from the borings. 5.The Log of Boring records are subject to the limitations, conclusions, and recommendations presented in the report text. 6.The Standard Penetration Test (SPT) N-values contained on the Log of Boring records refer to the total blow counts of a 140-pound drop hammer falling 30 inches required to drive a split-barrel sampler a total distance of 12 inches into soil strata at specific depth intervals. 7.The Hand Cone Penetrometer (HCP) values contained on Log of Boring records and the Cone Penetration Test (CPT) values contained on the Cone Penetration Sounding logs refer to the cone tip resistance recorded when pushing the cone tip into the soil strata at specific depth intervals. 8.The soil and/or rock strata interfaces shown on the Log of Boring records are approximate and may vary from those shown on the logs. The soil and/or rock descriptions shown on the Log of Boring records refer to conditions at the specific location tested. Soil/rock conditions may vary between test locations. 9.Relative density for coarse-grained soils (sands/gravels) and consistency for fine-grained soils (silts/clays) are described as follows: Coarse Grained Soils (Sands and Gravels) Fine Grained Soils (Silts and Clays) SPT N-Value HCP Value (kg/cm2) CPT Value (tsf) Relative Density SPT N-Value HCP Value (kg/cm2) CPT Value (tsf) Consistency 0-4 0-16 0-20 Very Loose 0-2 0-20 0-3 Very Soft 5-10 17-36 21-40 Loose 3-4 21-35 4-6 Soft 11-30 37-116 41-120 Med. Dense 5-8 >35 7-12 Firm 31-50 117-196 121-200 Dense 9-15 13-25 Stiff >50 >196 >200 Very Dense 16-30 26-50 Very Stiff >30 >50 Hard 10.Grain size descriptions are as follows: Description Particle Size Limits Boulder Greater than 12 inches Cobble 3 to 12 inches Coarse Gravel 3/4 to 3 inches Fine Gravel No. 4 sieve to 3/4 inch Coarse Sand No. 10 to No. 4 sieve Medium Sand No. 40 to No. 10 sieve Fine Sand No. 200 to No. 40 sieve Fines (Silt/Clay) Smaller than No. 200 sieve 11.Definitions for modifiers used in soil/rock descriptions: Proportion Modifier Approximate Root Diameter Modifier <5% Trace Less than 1/32" Fine roots 5% to 12% Little 1/32" to 1/4” Small roots 12% to 30% Some 1/4” to 1" Medium roots 30% to 50% And Greater than 1" Large roots Organic Soils: Soils containing vegetative tissue in various stages of decomposition having a fibrous to amorphous texture. Usually having a dark brown to black color and an organic odor. Organic Content Modifiers: <25%: Slightly to Highly Organic; 25% to 75%: Muck; >75%: Peat Appendix D - Log of Boring Records 80 80 80 80 2 1 0 1 1 0 0 0 0 0 2 4 5 7 13 4 5 4 Light brown fine sand, trace shell (SP) Gray fine sand, little silt, trace shell (SP) Dark gray organic clayey fine sand, some fibrous organics (SC-OL) Gray fine sand, little shell (SP) 4.0 7.0 8.5 1 2 3 4 5 6 7 1 WOH 2 20 9 HAMMER TYPE HOLE DIAMETER 3 in DRILLER JB/PS DRILL RIG GeoProbe METHOD SPT HOLE DEPTH 40 ft DATE STARTED 4/20/21 COMPLETED 4/20/21 AT TIME OF DRILLING 6.00 ft NOTE: GROUND WATER LEVEL: DRILLING CONTRACTOR Universal Engineering Sciences LATITUDE LONGITUDE SAMPLEGRAPHICLOGBLOWCOUNTSMATERIAL DESCRIPTION SAMPLENUMBERN VALUE(Continued Next Page) PROJECT NUMBER 3330.2100052.0000 PROJECT LOCATION 10701 S Ocean Dr Lot 634, Jensen Beach, FL PROJECT NAME Worsnop Residence LOG OF BORING B-1 PAGE 1 OF 2 CLIENT Lois Denise Worsnop DEPTH(ft)5 10 15 20 MOISTURECONTENT (%)FINESCONTENT (%)ORGANICCONTENT (%)SPT LOGS - GFA DATA TEMPLATE.GDT - 5/4/21 07:56 - Z:\PROJECTS\_UES PROJECT SETUP\3330.2100052.0000- WORSNOP RESIDENCE - GEO\21-6679.00 - WORSNOP PROPOSED RESIDENCE - GEO\GEO\APPENDICES NORMAL\SPT LOGS.GPJUniversal Engineering Sciences 607 NW Commodity Cove Port Saint Lucie, Florida 34986 (772) 924-3575 4 9 17 2 2 6 4 4 5 2 5 2 Gray fine sand, little shell (SP) (continued) Light gray sand and cemented sand, trace silt and shell (GP) Gray sand and cemented sand, little silt (GP) Bottom of borehole at 40.0 feet. 23.5 33.5 40.0 8 9 10 11 26 8 9 7SAMPLE GRAPHICLOGBLOWCOUNTSMATERIAL DESCRIPTION SAMPLENUMBERN VALUEPROJECT NUMBER 3330.2100052.0000 PROJECT LOCATION 10701 S Ocean Dr Lot 634, Jensen Beach, FL PROJECT NAME Worsnop Residence LOG OF BORING B-1 PAGE 2 OF 2 CLIENT Lois Denise Worsnop DEPTH(ft)25 30 35 40 MOISTURECONTENT (%)FINESCONTENT (%)ORGANICCONTENT (%)SPT LOGS - GFA DATA TEMPLATE.GDT - 5/4/21 07:56 - Z:\PROJECTS\_UES PROJECT SETUP\3330.2100052.0000- WORSNOP RESIDENCE - GEO\21-6679.00 - WORSNOP PROPOSED RESIDENCE - GEO\GEO\APPENDICES NORMAL\SPT LOGS.GPJUniversal Engineering Sciences 607 NW Commodity Cove Port Saint Lucie, Florida 34986 (772) 924-3575 Appendix E - Discussion of Soil Groups DISCUSSION OF SOIL GROUPS COARSE GRAINED SOILS General. A soil is classified as coarse-grained if more than 50 percent of a representative sample of the material is retained on the No. 200 sieve. GW and SW Groups. These groups comprise well-graded gravelly and sandy soils containing little or no plastic fines (less than 5 percent passing the No. 200 sieve). The low fines content does not noticeably change the shear strength characteristics of these soils and does not interfere with their free-draining characteristics. GP and SP Groups. Poorly graded gravels and sands containing little or no plastic fines (less than 5 percent passing the No. 200 sieve) are in the GP and SP groups. The materials can be called uniform gravels, uniform sands, or non-uniform mixtures of very coarse materials and very fine sand, with intermediate sizes lacking (sometimes called skip-graded, gap-graded, or step-graded). This last group often results from borrow pit excavation in which gravel and sand layers are mixed. GM and SM Groups. In general, the GM and SM groups comprise gravels or sands with fines (more than 12 percent passing the No. 200 sieve) having little or no plasticity. The plasticity index and liquid limit of soils in these groups plot below the “A” line on the plasticity chart. The gradation of the material is not considered significant and both well and poorly graded materials are included. GC and SC Groups. In general, the GC and SC groups comprise gravelly or sandy soils containing fines (more than 12 percent passing the No, 200 sieve) having plasticity characteristics. The plasticity index and liquid limit of soils in these groups plot above the “A” line on the plasticity chart. FINE GRAINED SOILS General. A soil is classified as fine-grained if more than 50 percent of a representative sample of the material passes the No. 200 sieve. ML and MH Groups. These groups comprise inorganic silts (ML) and elastic silts (MH) having either low (L) or high (H) liquid limits, respectively. ML soils have a liquid limit of less than 50 while MH soils have a liquid limit of 50 and greater. Silts and elastic silts can also contain varying amounts of sand and gravel. Also included in this group are loess sediments and rock flours. CL and CH Groups. These groups comprise low plasticity (lean) clays (CL) and medium to high plasticity (fat) clays (CH) having either low (L) or high (H) liquid limits, respectively. CL soils have a liquid limit of less than 50 while CH soils have a liquid limit of 50 and greater. The low plasticity clays can also be sandy clays or silty clays. The moderate to high plasticity clays can also be sandy clays and include some volcanic clays. OL and OH Groups. These groups comprise organic silts and clays. The soils are characterized by the presence of organic odor and/or dark color. The OL and OH soils are differentiated by determining and comparing their liquid limit values before and after oven drying representative soil samples. HIGHLY ORGANIC SOILS The highly organic soils are usually very soft and compressible and have undesirable construction characteristics. Particles of leaves, grasses, branches, or other fibrous vegetative matter are common components of these soils. They are not subdivided and are classified into one group with the symbol PT. Peat humus and swamp soils with a highly organic texture are typical soils of the group.