Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
85 Pinewood Ln PSL Prop Manual J(3)
9 @ Load Short Form Job: 1468 wri htsoft Date: 4/14/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project Information For: Peavy Residence,NisAirAir Conditioning 85 Pinewood Ln,Fort Pierce,FL 34947 Design Information Htg Clg Infiltration Outside db(°F) 41 90 Method Simplified Inside db(°F) 70 75 Construction quality Average Design TD(°F) 29 15 Fireplaces 0 Daily range - L Inside humidity(%) 30 50 Moisture difference(gr/Ib) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S036-230C** AHRI ref Coil CBA27UHE-036-230*++TDR AHRI ref 204289057 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 7.3 kW Sensible cooling 24220 Btuh Heating output 24896 Btuh Latent cooling 10380 Btuh Temperature rise 20 °F Total cooling 34600 Btuh Actual airflow 1153 cfm Actual airflow 1153 cfm Air flow factor 0.044 cfm/Btuh Air flow factor 0.054 cfim/Btuh Static pressure 0.85 in H2O Static pressure 0.85 in H2O Space thermostat Load sensible heat ratio 0.74 ROOM NAME Area Htg load Clg load Htg AVF CIg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) Laundry 44 785 905 35 49 Bed 2 167 2585 1528 114 82 Bath 58 913 405 40 22 Hall 34 0 0 0 0 Lin 6 0 0 0 0 Hers 57 911 306 40 16 His 32 41 27 2 1 Lin 2 10 0 0 0 0 Master Bath 149 3512 1707 155 92 Master Bed 371 4993 3218 220 173 Kitchen 193 276 3188 12 171 Foyer/DR 164 3544 2345 156 126 Pantry 15 0 0 0 0 Living Room 409 3030 4837 134 260 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. w rig htsoft, 2021-Oct-19 13:56:46 A- II,-=Iae,-"e—«awa.=m , Right-Sute®Universal 202121.0.08RSU29066 Pagel ACCA ..zits\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N Wtr Clst 24 384 129 17 7 Bed 3 152 2788 1644 123 88 Den 127 2391 1241 105 67 House 2010 26152 21479 1153 1153 Other equip loads 2877 1528 Equip.@ 0.95 RSM 21949 Latent cooling 8133 TOTALS 2010 29030 30082 1153 1153 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. w rig htsoft, 2021-Oct-19 13:56:46 A- II,-=Iae,-"e—«awa.—,, Right-Sute®Urrversal202121.0.08RSU29066 Page ACCA ...nts\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N 9 @ Load Short Form Job: 1468 wri htsoft Date: 4/14/2021 Inlaw By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project Information For: Peavy Residence,NisAirAir Conditioning 85 Pinewood Ln,Fort Pierce,FL 34947 Design Information Htg Clg Infiltration Outside db(°F) 41 90 Method Simplified Inside db(°F) 70 75 Construction quality Average Design TD(°F) 29 15 Fireplaces 0 Daily range - L Inside humidity(%) 30 50 Moisture difference(gr/Ib) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Generic Make Generic Trade Trade Model SEER 18.0,HSPF 9.1 Cond SEER 18.0,HSPF 9.1 AHRI ref Coil AHRI ref Efficiency 9.1 HSPF Efficiency 14.7 EER, 18 SEER Heating input Sensible cooling 11007 Btuh Heating output 15646 Btuh @ 47°F Latent cooling 4717 Btuh Temperature rise 27 °F Total cooling 15724 Btuh Actual airflow 524 cfm Actual airflow 524 cfm Air flow factor 0.049 cfm/Btuh Air flow factor 0.049 cfim/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.78 Capacity balance point=32°F ROOM NAME Area Htg load Clg load Htg AVF CIg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) Master Bed 2 175 2758 2270 135 112 Kitchen 2 128 2358 3805 115 188 Living Room 2 187 3347 3718 164 183 WIC 59 563 195 28 10 M Bath 2 88 1688 633 83 31 Inlaw 637 10713 10621 524 524 Other equip loads 1087 577 Equip.@ 0.95 RSM 10684 Latent cooling 3156 TOTALS 637 1 11801 1 13839 1 524 1 524 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. w rig htsoft, 2021-Oct-19 13:56:46 A II,-=Iae,-"e--.,C—P, Right-Sute®Universal 202121.0.08RSU29066 Page ACCA ..zits\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N Building Analysis Job: 1468 +� wrightsoft° na Date: 4/14/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Peavy Residence,NisAirAir Conditioning 85 Pinewood Ln,Fort Pierce,FL 34947 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(T) 70 75 Elevation: 26 ft Design TD(T) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 2.4 56.9 Dry bulb(T) 41 90 Infiltration: Daily range(T) - 15 ( L ) Method Simplified Wet bulb(T) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 amme Component Btuh/ft2 Btuh %of load Walls 3.1 5136 17.7 Ventilation Glazing 17.5 3335 11.5 walls Doors 3.7 148 0.5 Ceilings 1.0 1992 6.9 Floors 3.2 6482 22.3 Ducts Infiltration 1.6 2620 9.0 Glazing_' Ducts 6439 22.2 Piping 0 0 Other Humidification 0 0 Ceilings Ventilation 2877 9.9 Infiltration Adjustments 0 Total 1 290301 100.01 Floors Component Btuh/ft2 Btuh %of load Walls 1.9 3194 13.9 walls Ventilation Glazing 21.0 4012 17.4 Doors 3.7 150 0.7 Ceilings 0.6 1223 5.3 Internal Gains Floors 0 0 0 Glazing,/ Infiltration 0.4 696 3.0 Ducts 7185 31.2 Ventilation 1528 6.6 Internal gains 5020 21.8 Other Blower 0 0 Ceilings Adjustments 0 Infiltration Total 23007 100.01Ducts Latent Cooling Load=8133 Btuh Overall U-value=0.100 Btuh/ft2-°F Data entries checked. w rig htsoft- 2021-Oct-19 13:56:46 ^.-k-I-1. °^.111-,1^,p°11 Right-SuteO Universal 2021 21.0.08 RSU29066 Page 1 ACCA nts\wrightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N Building Analysis Job: 1468 +� wrightsoft° na Date: 4/14/2021 Inlaw By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Peavy Residence,NisAirAir Conditioning 85 Pinewood Ln,Fort Pierce,FL 34947 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(°F) 70 75 Elevation: 26 ft Design TD(°F) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 2.4 56.9 Dry bulb(T) 41 90 Infiltration: Daily range(T) - 15 ( L ) Method Simplified Wet bulb(T) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 amme Component Btuh/ft2 Btuh %of load Walls 3.2 2248 19.1 ventilation Glazing 17.5 1657 14.0 walls Doors 0 0 0 Ceilings 1.0 631 5.4 Ducts Floors 4.5 2897 24.5 Infiltration 1.6 1256 10.6 Glazing Ducts 2023 17.1 Piping 0 0 Humidification 0 0 Infiltration Ventilation 1087 9.2 Ceilings Adjustments 0 Total 1 111801 1 100.01 Floors • • • Component Btuh/ftz Btuh %of load Walls 2.0 1438 12.8 walls Ventilation Glazing 27.1 2565 22.9 Doors 0 0 0 Ceilings 0.6 388 3.5 Floors 0 0 0 Internal Gains Infiltration 0.4 334 3.0 Glazing) Ducts 2337 20.9 Ventilation 577 5.2 Internal gains 3560 31.8 Blower 0 0 Ceilings Adjustments 0 Infiltration Total 11199 100.0 Ducts Latent Cooling Load=3156 Btuh Overall U-value=0.123 Btuh/ft2--°F Data entries checked. w rig htsoft- 2021-Oct-19 13:56:46 ^.-k-I-1. °^.111-,1^,p°11 Right-SuteO Universal 2021 21.0.08 RSU29066 Page 2 ACCA nts\wrightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N om Constructions Job: 1468 +� wrightsoft Component Date: 4/14/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Peavy Residence,NisAirAir Conditioning 85 Pinewood Ln,Fort Pierce,FL 34947 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(T) 70 75 Elevation: 26 ft Design TD(T) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(grAb) 2.4 56.9 Dry bulb(T) 41 90 Infiltration: Daily range(T) - 15 ( L ) Method Simplified Wet bulb(T) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ftUF W-T/Btuh Btuh/ft' Btuh Btuh/ft' Btuh Walls Blk Wall,Stucco Ext,R-4.1 Ext Bd Inl,8"Thk, 1/2"Gyp Bd Int Fnsh ne 382 0.109 5.1 3.15 1204 2.02 770 se 199 0.109 5.1 3.15 628 2.02 402 sw 463 0.109 5.1 3.15 1459 2.02 933 nw 372 0.109 5.1 3.15 1171 2.02 749 all 1416 0.109 5.1 3.15 4461 2.02 2853 Knee wall,R-30 KW Ins, 1/2"Gyp Bd Int Fnsh se 10 0.042 30.0 1.21 11 0.74 7 nw 29 0.042 30.0 1.21 35 0.74 21 all 39 0.042 30.0 1.21 46 0.74 29 Partitions Fnn Wall, 1/2"Gyp Bd Ext,R-11 Cav Ins, 1/2"Gyp Bd Int Fnsh,2"A", 16" 214 0.101 11.0 2.94 629 1.46 312 OC Stud Windows Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.24); ne 4 0.580 0 16.8 67 22.6 91 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(2 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.24); ne 31 0.580 0 16.8 525 22.6 706 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(5.2 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Low-e;NFRC rated(SHGC=0.16); se 8 0.490 0 14.2 107 14.2 107 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(1.25 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Low-e;NFRC rated(SHGC=0.22); se 18 0.620 0 18.0 325 21.1 382 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(4.17 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.22); se 31 0.620 0 18.0 561 21.4 668 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(5.2 ft window ht, 1 ft sep.);6.8 ft head ht 'Pk wrightsoft"' 2021-Oct-1913:56:46 --k=de-•,.ea«a-a. ,P=. Right-Sute®Universal 202121.0.08RSU29066 Pagel ACCA nts\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.16); se 8 0.490 0 14.2 107 11.1 83 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23);7 ft overhang(1.25 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Low-e: Impact,Clear Low-e;NFRC rated(SHGC=0.24); sw 16 0.580 0 16.8 262 18.8 294 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23);2 ft overhang(5.2 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.24); nw 22 0.580 0 16.8 377 22.6 507 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(5.17 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.21); nw 53 0.650 0 18.8 1005 22.0 1175 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 10.5 ft overhang(6.67 ft window ht, 1 ft sep.);6.8 ft head ht Doors Fbrgls Door se 40 0.127 7.0 3.69 148 3.73 150 Ceilings Attic,Metal Roof,R-30 Ceil Ins, 1/2"Gyp Bd Int Fnsh 2010 0.034 30.0 0.99 1992 0.61 1223 Floors On Grade Depth,Tile Flr Fnsh 226 0.989 0 28.7 6482 0 0 wrightsoft- 2021-Oct-19 13:56:46 --1-de-•,.e a«a-a. ,P=. Right-Site®Urrversal 2021 21.0.08 RSU29066 Page 2 ACCA nts\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N Constructions Job: 1468 +� wrightsoft° Component Date: 4/14/2021 Inlaw By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Peavy Residence,NisAirAir Conditioning 85 Pinewood Ln,Fort Pierce,FL 34947 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(T) 70 75 Elevation: 26 ft Design TD(T) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(grAb) 2.4 56.9 Dry bulb(T) 41 90 Infiltration: Daily range(T) - 15 ( L ) Method Simplified Wet bulb(T) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ftUF W-T/Btuh Btuh/ft' Btuh Btuh/ft' Btuh Walls Blk Wall,Stucco Ext,R-4.1 Ext Bd Inl,8"Thk, 1/2"Gyp Bd Int Fnsh ne 192 0.109 5.1 3.15 605 2.02 387 se 208 0.109 5.1 3.15 655 2.02 419 sw 137 0.109 5.1 3.15 433 2.02 277 nw 176 0.109 5.1 3.15 555 2.02 355 all 714 0.109 5.1 3.15 2248 2.02 1438 Partitions (none) Windows Impact,Clear Low-e: Impact,Clear Low-e;NFRC rated(SHGC=0.24); ne 4 0.580 0 16.8 67 22.6 91 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(2 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.24); sw 16 0.580 0 16.8 262 21.8 340 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(5.2 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.24); sw 10 0.580 0 16.8 160 21.1 200 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(3.17 ft window ht, 1 ft sep.);6.8 ft head ht nw 10 0.580 0 16.8 160 22.6 215 all 19 0.580 0 16.8 320 21.9 415 Impact,Clear Low-e: Impact,Clear Low-e;NFRC rated(SHGC=0.21); sw 34 0.650 0 18.8 631 14.0 470 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23);6 ft overhang(6.7 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Low-e: Impact,Clear Low-e;NFRC rated(SHGC=0.24); nw 22 0.580 0 16.8 377 22.6 507 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(5.17 ft window ht, 1 ft sep.);6.8 ft head ht Doors (none) 'Pk wrightsoft- 2021-Oct-1913:56:46 --1-de-•,.e a«a-a. ,P=. Right-Sutee Universal 2021 21.0.08 RSU29066 Page 3 ACCA nts\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N Ceilings Attic,Metal Roof,R-30 Ceil Ins, 1/2"Gyp Bd Int Fnsh 637 0.034 30.0 0.99 631 0.61 388 Floors On Grade Depth,Tile Flr Fnsh 101 0.989 0 28.7 2897 0 0 wrightsoft- 2021-Oct-19 13:56:46 --1-de-•,.e a«a-a. ,P=. Right-Site®Urrversal 2021 21.0.08 RSU29066 Page 4 ACCA nts\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N Pro S Job: 1468 +� wrightsoft° Project Date: 4/14/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Peavy Residence,NisAirAir Conditioning 85 Pinewood Ln,Fort Pierce,FL 34947 Notes: Design Information Weather: St Lucie Co Intl,FL,US Winter Design Conditions Summer Design Conditions Outside db 41 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 29 °F Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 19713 Btuh Structure 14294 Btuh Ducts 6439 Btuh Ducts 7185 Btuh Central vent(90 cfm) 2877 Btuh Central vent(90 cfm) 1528 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 29030 Btuh Use manufacturer's data n Rate/swin multiplier 0.95 Infiltration Equipmen�sensible load 21949 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2389 Btuh Ducts 2255 Btuh Central vent(90 cfm) 3489 Btuh Heatingg Coolingg Outside air Area(ft�) 2010 2010 Equipment latent load 8133 Btuh Volume(ft3) 17711 17711 Air changes/hour 0.28 0.14 Equipment Total Load(Sen+Lat) 30082 Btuh Equiv.AVF(cfm) 82 41 Req.total capacity at 0.70 SHR 2.6 ton Heating Equipment Summary Cooling Equipment Summary Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S036-230C** AHRI ref Coil CBA27UHE-036-230*++TDR AHRI ref 204289057 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 7.3 kW Sensible cooling 24220 Btuh Heating output 24896 Btuh Latent cooling 10380 Btuh Temperature rise 20 °F Total cooling 34600 Btuh Actual airflow 1153 cfm Actual airflow 1153 cfm Air flow factor 0.044 cfm/Btuh Air flow factor 0.054 cfm/Btuh Static pressure 0.85 in H2O Static pressure 0.85 in H2O Space thermostat Load sensible heat ratio 0.74 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrigF�tsoft 2021-Oct-1913:56:46 Right-Site®Universal 2021 21.0.08 RSU29066 Page 1 ACCA nts\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N Pro S Job: 1468 +� wrightsoft° Project Date: 4/14/2021 Inlaw By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Peavy Residence,NisAirAir Conditioning 85 Pinewood Ln,Fort Pierce,FL 34947 Notes: Design Information Weather: St Lucie Co Intl,FL,US Winter Design Conditions Summer Design Conditions Outside db 41 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 29 °F Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 8690 Btuh Structure 8284 Btuh Ducts 2023 Btuh Ducts 2337 Btuh Central vent(34 cfm) 1087 Btuh Central vent(34 cfm) 577 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 11801 Btuh Use manufacturer's data n Rate/swin multiplier 0.95 Infiltration Equipmen�sensible load 10684 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 1162 Btuh Ducts 676 Btuh Central vent(34 cfm) 1318 Btuh Heatingg Cooling Outside air Area(ft�) 637 637 Equipment latent load 3156 Btuh Volume(ft3) 5096 5096 Air changes/hour 0.46 0.23 Equipment Total Load(Sen+Lat) 13839 Btuh Equiv.AVF(cfm) 39 20 Req.total capacity at 0.70 SHR 1.3 ton Heating Equipment Summary Cooling Equipment Summary Make Generic Make Generic Trade Trade Model SEER 18.0,HSPF 9.1 Cond SEER 18.0,HSPF 9.1 AHRI ref Coil AHRI ref Efficiency 9.1 HSPF Efficiency 14.7 EER, 18 SEER Heating input Sensible cooling 11007 Btuh Heating output 15646 Btuh @ 47°F Latent cooling 4717 Btuh Temperature rise 27 °F Total cooling 15724 Btuh Actual airflow 524 cfm Actual airflow 524 cfm Air flow factor 0.049 cfm/Btuh Air flow factor 0.049 cfim/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.78 Capacity balance point=32°F Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wriQhtsoft- 2021-Oct-19 13:56:46 ^.,.I,1 °.,,....°..,,ill,., Right-Sute®Universal 202121.0.08RSU29066 Page 2 ACCA nts\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1468 House Date: 4/14/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name House Laundry 2 E)posed wal I 226.0 It 10.5 It 3 Room height 8.8 ft 8.0 ft heat/000l 4 Room dimensions 8.0 x 5.5 It 5 Room area 2009.5 fF 44.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 417 382 1204 770 0 0 0 0 T-jImpact,Clear Lowe 0.580 ne 16.82 22.64 4 0 67 91 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 31 0 525 706 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 296 199 628 402 0 0 0 0 11 Impaa Clear Low-e 0.490 se 14.21 14.22 8 4 107 107 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.13 18 3 325 382 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 31 4 561 668 0 0 0 0 D Fbrgls Door 0.127 se 3.69 3.73 40 40 148 150 0 0 0 0 Knee wall,R-30 KW 1 0.042 se 1.21 0.74 17 10 11 7 0 0 0 0 Impact,ClearLow-e 0.490 se 14.21 11.08 8 8 107 83 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 479 463 1459 933 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 18.85 16 7 262 294 0 0 0 0 G Impact,ClearLow-e 0.650 sw 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 447 372 1171 749 0 0 0 0 Impaa Clear Low-e 0.580 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 22 0 377 507 0 0 0 0 Impaa Clear Low-e 0.650 nw 18.85 22.04 53 0 1005 1175 0 0 0 0 W Knee wall,R-30 KW 1 0.042 nw 1.21 0.74 29 29 35 21 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.46 214 214 6291 312 84 84 247 123 C AttiG Metal Roof,R 0.034 0.99 0.61 2010 2010 1992 1223 44 44 44 27 F On Grade Depth,Tile 0.989 28.68 0.00 2010 226 6482 0 44 11 301 0 6 c)AED excursion 0 -47 Envelope loss/gain 17093 8579 592 102 12 a) Infiltration 2620 696 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 4 920 0 0 Appliances/other 4100 500 Subtotal(lines 6 to 13) 19713 14294 592 602 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 19713 14294 592 602 15 Dud loads 33% 50% 64391 7185 33% 50%1 193 303 FFT-o tal room load 26152 21479 785 905 required(dm) 1153 1153 35 49 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -ri- rigF�tsoft° 2021-Od-1913:56:46 Right-Sute@Unversal2021 21.0.08 RSU29066 Page 1 nts\W ri htsoft HVAC\85 Pinewood Ln PSL Prop.r p Calc=MJ8 Front Door faces:N + wrightsoft" Right-J®Worksheet Job: 1468 House Date: 4/14/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Bed 2 Bath 2 E)posed wal I 26.0 It 8.5 ft 3 Room height 8.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 11.5 x 14.5 It 1.0 x 57.8 It 5 Room area 166.8 fF 57.8 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 116 100 316 202 68 64 202 129 T-jImpact,Clear Lowe 0.580 ne 16.82 22.64 0 0 0 0 4 0 67 91 Impaa Clear Low-e 0.580 ne 16.82 22.64 16 0 262 353 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 11 Impaa Clear Low-e 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 3.73 0 0 0 0 0 0 0 0 Knee wall,R-30 KW 1 0.042 se 1.21 0.74 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 18.85 0 0 0 0 0 0 0 0 G Impact,ClearLow-e 0.650 sw 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 0 0 0 0 W Knee wall,R-30 KW 1 0.042 nw 1.21 0.74 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.46 92 92 270 134 0 0 0 0 C AttiG Metal Roof,R 0.034 0.99 0.61 167 167 165 101 58 58 57 35 F On Grade Depth,Tile 0.989 28.68 0.00 167 26 746 0 58 9 244 0 6 c)AED excursion -77 -21 Envelope loss/gain 1760 714 570 234 12 a) Infiltration 180 48 106 28 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 250 0 Subtotal(lines 6 to 13) 1940 1012 676 262 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 8 4 13 7 14 Subtotal 1948 1017 688 269 15 Dud loads 33% 50% 6361 511 33% 50%1 225 135 FFTotal room load 2585 1528 913 405 Airrequired(dm) 114 82 40 22 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -ri- rigl-tsoft- 2021-Od-1913:56:46 Right-Suite@Unversal2021 21.0.08 RSU29066 Page 2 nts\W ri htsoft HVAC\85 Pinewood Ln PSL Prop.r p Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1468 House Date: 4/14/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Hall Lin 2 E)q)osed wal I O ft O ft 3 Room height 8.0 It heat/000l 8.0 ft heat/cool 4 Room dimensions 4.0 x 8.5 It 2.0 x 3.0 It 5 Room area 34.0 ft2 6.0 ft Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 11 Impaa Clear Low-e 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 3.73 0 0 0 0 0 0 0 0 Knee wall,R-30 KW 1 0.042 se 1.21 0.74 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 18.85 0 0 0 0 0 0 0 0 G Impact,ClearLow-e 0.650 sw 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 0 0 0 0 W Knee wall,R-30 KW 1 0.042 nw 1.21 0.74 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C AttiG Metal Roof,R 0.034 0.99 0.61 34 34 34 21 6 6 6 4 F On Grade Depth,Tile 0.989 28.68 0.00 34 0 0 0 6 0 0 0 6 c)AED excursion -2 0 Envelope loss/gain 34 19 6 3 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 34 19 6 3 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution -34 -19 -6 -3 14 Subtotal 0 0 0 0 15 Dud loads 33% 50%1 01 0 33% 50%1 0 0 Total room load 0 0 0 0 Air required(dm) 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -ri- rigF�tsoft° 2021-Od-1913:56:46 Right-Suite@Unversal2021 21.0.08 RSU29066 Page 3 nts\W ri htsoft HVAC\85 Pinewood Ln PSL Prop.r p Calc=MJ8 Front Door faces:N + wrightsoft" Right-J®Worksheet Job: 1468 House Date: 4/14/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Hers His 2 E)q)osed wal I 9.5 ft O ft 3 Room height 8.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 6.0 x 9.5 It 1.0 x 31.5 It 5 Room area 57.0 ft' 31.5 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 11 Impaa Clear Low-e 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 3.73 0 0 0 0 0 0 0 0 Knee wall,R-30 KW 1 0.042 se 1.21 0.74 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 76 76 239 153 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 18.85 0 0 0 0 0 0 0 0 G Impact,ClearLow-e 0.650 sw 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 0 0 0 0 W Knee wall,R-30 KW 1 0.042 nw 1.21 0.74 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C AttiG Metal Roof,R 0.034 0.99 0.61 57 57 56 35 32 32 31 19 F On Grade Depth,Tile 0.989 28.68 0.00 57 10 272 0 32 0 0 0 6 c)AED excursion -16 -1 Envelope loss/gain 568 172 31 18 12 a) Infiltration 118 31 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 687 203 31 18 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 687 203 31 18 15 Dud loads 33% 50% 224 102 33% 50%1 10 9 Total room load 911 306 41 27 Air required(dm) 40 16 2 1 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -ri- rigl-tsoft- 2021-Od-1913:56:46 Right-Sute@Unversal202121.0.08RSU29066 Page nts\W ri htsoft HVAC\85 Pinewood Ln PSL Prop.r p Calc=MJ8 Front Door faces:N + wrightsoft" Right-J®Worksheet Job: 1468 House Date: 4/14/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Lin 2 Master Bath 2 E)posed wal I 6.5 ft 27.0 It 3 Room height 8.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 4.0 x 2.5 It 1.0 x 149.0 It 5 Room area 10.0 ft2 149.0 fF Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Bilk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 52 52 164 105 T-jImpact,Clear Lowe 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Bilk Wall,Stucco Ext 0.109 se 3.15 2.02 32 32 101 64 96 78 246 157 11 Impaa Clear Low-e 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 18 3 325 382 Impaa Clear Low-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 3.73 0 0 0 0 0 0 0 0 Knee wall,R-30 KW 1 0.042 se 1.21 0.74 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 Bilk Wall,Stucco Ext 0.109 sw 3.15 2.02 20 20 63 40 68 68 214 137 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 18.85 0 0 0 0 0 0 0 0 G Impact,ClearLow-e 0.650 sw 0.00 0.00 0 0 0 0 0 0 0 0 Bilk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 0 0 0 0 W Knee wall,R-30 KW 1 0.042 nw 1.21 0.74 0 0 0 0 0 0 0 0 P Frm Wall,IQ"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C AttiG Metal Roof,R 0.034 0.99 0.61 10 10 10 6 149 149 148 91 F On Grade Depth,Tile 0.989 28.68 0.00 10 7 186 0 149 27 774 0 6 c)AED excursion -10 53 Envelope loss/gain 360 101 1870 924 12 a) Infiltration 81 21 336 89 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 441 123 2206 1014 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution -441 -123 441 123 14 Subtotal 0 0 2647 1136 15 Dud loads 33% 50%1 0 0 33% 50% 865 571 FFTotal room load 0 0 3512 1707 Airrequired(dm) 0 0 155 92 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -ri- rigl-tsoft- 2021-Od-1913:56:46 Right-Suite@Unversal2021 21.0.08 RSU29066 Page 5 nts\W ri htsoft HVAC\85 Pinewood Ln PSL Prop.r p Calc=MJ8 Front Door faces:N + wrightsoft" Right-J®Worksheet Job: 1468 House Date: 4/14/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Master Bed Kitchen 2 E)q)osed wal I 45.0 ft 0 ft 3 Room height 8.5 ft heat/000l 10.0 ft heat/cool 4 Room dimensions 1.0 x 370.5 ft 1.0 x 193.3 ft 5 Room area 370.5 fF 193.3 fF Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 89 89 281 180 0 0 0 0 T-jImpact,Clear Lowe 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 11 Impaa Clear Low-e 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 3.73 0 0 0 0 0 0 0 0 Knee wall,R-30 KW 1 0.042 se 1.21 0.74 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 170 170 536 343 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 18.85 0 0 0 0 0 0 0 0 G Impact,ClearLow-e 0.650 sw 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 123 101 318 203 0 0 0 0 Impaa Clear Low-e 0.580 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 22 0 377 507 0 0 0 0 Impaa Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 0 0 0 0 W Knee wall,R-30 KW 1 0.042 nw 1.21 0.74 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 01 0 0 0 C AtUQ Metal Roof,R 0.034 0.99 0.61 371 371 367 225 193 193 192 118 F On Grade Depth,Tile 0.989 28.68 0.00 371 45 1291 0 193 0 0 0 6 c)AED excursion 25 -165 Envelope loss/gain 3169 1484 192 -48 12 a) Infiltration 595 158 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 2 460 Appliances/other 500 1700 Subtotal(lines 6 to 13) 3764 2141 192 2112 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 16 9 14 Subtotal 3764 2141 208 2122 15 Dud loads 33% 50% 1229 1076 33% 50% 68 1066 FFTotal room load 4993 3218 276 3188 Air required(dm) 220 173 12 171 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -ri- rigl-tsoft- 2021-Od-1913:56:46 Right-Suite@Unversal2021 21.0.08 RSU29066 Page 6 nts\W ri htsoft HVAC\85 Pinewood Ln PSL Prop.r p Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1468 House Date: 4/14/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Foyer/DR Pantry 2 E)posed wal I 26.5 It 0 It 3 Room height 9.5 It heat/000l 8.0 It heat/000l 4 Room dimensions 1.0 x 163.8 It 3.0 x 5.0 It 5 Room area 163.8 fF 15.0 ft Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 168 89 282 180 0 0 0 0 11 Impaa Clear Low-e 0.490 se 14.21 14.22 8 4 107 107 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 31 4 561 668 0 0 0 0 D Fbrgls Door 0.127 se 3.69 3.73 40 40 148 150 0 0 0 0 Knee wall,R-30 KW 1 0.042 se 1.21 0.74 17 10 11 7 0 0 0 0 Impact,ClearLow-e 0.490 se 14.21 11.08 8 8 107 83 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 29 29 90 57 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 18.85 0 0 0 0 0 0 0 0 G Impact,ClearLow-e 0.650 sw 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 0 0 0 0 W Knee wall,R-30 KW 1 0.042 nw 1.21 0.74 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.46 38 38 112 55 0 0 0 0 C AttiG Metal Roof,R 0.034 0.99 0.61 164 164 162 100 15 15 15 9 F On Grade Depth,Tile 0.989 28.68 0.00 164 27 760 0 15 0 0 0 6 c)AED excursion 66 -1 Envelope loss/gain 2339 1472 15 8 12 a) Infiltration 332 88 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 2672 1561 15 8 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 -15 -8 14 Subtotal 2672 1561 0 0 15 Dud loads 33% 50% 8731 784 33% 50%1 0 0 FFTotal room load 3544 2345 0 0 Airrequired(dm) 156 126 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -ri- rigF�tsoft° 2021-Od-1913:56:46 Right-Suite@Unversal2021 21.0.08 RSU29066 Page 7 nts\W ri htsoft HVAC\85 Pinewood Ln PSL Prop.r p Calc=MJ8 Front Door faces:N + wrightsoft" Right-J®Worksheet Job: 1468 House Date: 4/14/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Living Room Wtr clst 2 E)posed wal I 14.5 It 4.0 ft 3 Room height 10.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 1.0 x 408.8 It 6.0 x 4.0 It 5 Room area 408.8 fF 24.0 ft' Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 11 Impact,Clear Lowe 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 3.73 0 0 0 0 0 0 0 0 Knee wall,R-30 KW 1 0.042 se 1.21 0.74 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 32 32 101 64 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 18.85 0 0 0 0 0 0 0 0 G Impact,ClearLow-e 0.650 sw 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 116 63 197 126 0 0 0 0 Impact,Clear Lowe 0.580 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.650 nw 18.85 22.04 53 0 1005 1175 0 0 0 0 W Knee wall,R-30 KW 1 0.042 nw 1.21 0.74 29 29 35 21 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C AttiG Metal Roof,R 0.034 0.99 0.61 409 409 405 249 24 24 24 15 F On Grade Depth,Tile 0.989 28.68 0.00 409 15 416 0 24 4 115 0 6 c)AED excursion 228 -7 Envelope loss/gain 2059 1799 239 72 12 a) Infiltration 225 60 50 13 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 2 460 0 0 Appliances/other 900 0 Subtotal(lines 6 to 13) 2284 3219 289 86 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2284 3219 289 86 15 Dud loads 33% 50% 7461 1618 33% 50%1 94 43 FFTotal room load 3030 4837 384 129 Airrequired(dm) 134 260 17 7 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -ri- rigl-tsoft- 2021-Od-1913:56:46 Right-Suite@Unversal2021 21.0.08 RSU29066 Page 8 nts\W ri htsoft HVAC\85 Pinewood Ln PSL Prop.r p Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1468 House Date: 4/14/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Bed 3 Den 2 E)posed wal I 26.0 It 22.0 ft 3 Room height 8.0 It heat/000l 8.0 ft heat/cool 4 Room dimensions 1.0 x 151.8 It 11.5 x 11.0 It 5 Room area 151.8 fF 126.5 fF Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 92 76 241 154 0 0 0 0 T-jImpact,Clear Lowe 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 16 0 262 353 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 11 Impaa Clear Low-e 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 3.73 0 0 0 0 0 0 0 0 Knee wall,R-30 KW 1 0.042 se 1.21 0.74 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 84 68 216 138 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 18.85 0 0 0 0 16 7 262 294 G Impact,ClearLow-e 0.650 sw 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 116 116 365 234 92 92 290 185 Impaa Clear Low-e 0.580 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 0 0 0 0 W Knee wall,R-30 KW 1 0.042 nw 1.21 0.74 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C AttiG Metal Roof,R 0.034 0.99 0.61 152 152 150 92 127 127 125 77 F On Grade Depth,Tile 0.989 28.68 0.00 152 26 746 0 127 22 631 0 6 c)AED excursion -83 57 Envelope loss/gain 1765 751 1524 751 12 a) Infiltration 323 86 274 73 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 250 0 Subtotal(lines 6 to 13) 2088 1086 1798 824 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 14 8 4 2 14 Subtotal 2102 1094 1802 826 15 Dud loads 33% 50% 6861 550 33% 50%1 589 415 FFT-o tal room load 2788 1644 2391 1241 required(dm) 123 88 105 67 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -ri- 2021-Od-1913:56:46 Right-Suite@Unversal2021 21.0.08 RSU29066 Page 9 nts\W ri htsoft HVAC\85 Pinewood Ln PSL Prop.r p Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1468 Inla w Date: 4/14/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Inlaw Master Bed 2 2 E)posed wal I 101.0 It 26.5 It 3 Room height 8.0 it 8.0 It heat/000l 4 Room dimensions 12.5 x 14.0 It 5 Room area 637.0 fF 175.0 fF Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 196 192 605 387 112 112 353 226 T-jImpact,Clear Lowe 0.580 ne 16.82 22.64 4 0 67 91 0 0 0 0 Impaa Clear Low-e 0.580 ne 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 208 208 655 419 0 0 0 0 11 Impaa Clear Low-e 0.490 se 0.00 0.00 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 0.00 0.00 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 0.00 0.00 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 0.00 0.00 0 0 0 0 0 0 0 0 Knee wall,R-30 KW 1 0.042 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.490 se 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 196 137 433 277 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.08 10 2 160 200 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.82 16 2 262 340 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 G Impact,ClearLow-e 0.650 sw 18.85 14.02 34 34 631 470 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 208 176 555 355 100 78 245 156 Impaa Clear Low-e 0.580 nw 16.82 22.64 10 0 160 215 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 22 0 377 507 22 0 377 507 Impaa Clear Low-e 0.650 nw 0.00 0.00 0 0 0 0 0 0 0 0 W Knee wall,R-30 KW 1 0.042 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 0.00 0.00 0 0 0 0 0 0 0 0 C AttiG Metal Roof,R 0.034 0.99 0.61 637 637 631 388 175 175 173 106 F On Grade Depth,Tile 0.989 28.68 0.00 637 101 2897 0 175 27 760 0 6 c)AED excursion 742 187 Envelope loss/gain 7434 4391 1908 1183 12 a) Infiltration 1256 334 330 88 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 2 460 0 0 Appliances/other 3100 500 Subtotal(lines 6 to 13) 8690 8284 2237 1771 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 8690 8284 2237 1771 15 Dud loads 23% 28% 20231 2337 23% 28%1 521 499 FFTotal room load 10713 10621 2758 2270 Airrequired(dm) 524 524 135 112 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -ri- 2021-Od-1913:56:46 Right-Sute@Unversal2021 21.0.08 RSU29066 Page 10 nts\W ri htsoft HVAC\85 Pinewood Ln PSL Prop.np Calc=MJ8 Front Door faces:N + wrightsoft" Right-J®Worksheet Job: 1468 Inla w Date: 4/14/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Kitchen 2 Living Room 2 2 E)posed wal I 23.0 ft 27.0 ft 3 Room height 8.0 ft heat/000l 8.0 ft heat/000l 4 Room dimensions 13.5 x 9.5 ft 1.0 x 186.8 ft 5 Room area 128.3 fF 186.8 fF Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.580 ne 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 96 96 302 193 11 Impact,Clear Lowe 0.490 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.620 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.620 se 0.00 0.00 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 0.00 0.00 0 0 0 0 0 0 0 0 Knee wall,R-30 KW 1 0.042 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.490 se 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 76 67 210 134 120 71 223 143 Impact,ClearLow-e 0.580 sw 16.82 21.08 10 2 160 200 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.82 0 0 0 0 16 2 262 340 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 G Impact,ClearLow-e 0.650 sw 18.85 14.02 0 0 0 0 34 34 631 470 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 108 99 310 199 0 0 0 0 Impact,Clear Lowe 0.580 nw 16.82 22.64 10 0 160 215 0 0 0 0 Impact,Clear Lowe 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.650 nw 0.00 0.00 0 0 0 0 0 0 0 0 W Knee wall,R-30 KW 1 0.042 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 0.00 0.00 0 0 0 0 0 0 0 0 C AttiG Metal Roof,R 0.034 0.99 0.61 128 128 127 78 187 187 185 114 F On Grade Depth,Tile 0.989 28.68 0.00 128 23 660 0 187 27 774 0 6 c)AED excursion 136 421 Envelope loss/gain 1626 962 2379 1681 12 a) Infiltration 286 76 336 89 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 1 230 1 230 Appliances/other 1700 900 Subtotal(lines 6 to 13) 1912 2968 2715 2900 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1912 2968 2715 2900 15 Dud loads 23% 28% 445 837 23% 28% 632 818 FFTotal room load 2358 3805 3347 3718 Air required(dm) 115 188 164 183 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -ri- rigl-tsoft- 2021-Od-1913:56:46 Right-Sute@Unversal2021 21.0.08 RSU29066 Page 11 nts\W ri htsoft HVAC\85 Pinewood Ln PSL Prop.r p Calc=MJ8 Front Door faces:N + wrightsoft°° Right-J®Worksheet Job: 1468 Inla w Date: 4/14/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name WIC M Bath 2 2 E)posed wal I 6.0 ft 18.5 It 3 Room height 8.0 It heat/000l 8.0 ft heat/000l 4 Room dimensions 1.0 x 59.0 ft ft 1.0 x 88.0 5 Room area 59.0 ft2 88.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 84 80 252 161 T-jImpact,Clear Lowe 0.580 ne 16.82 22.64 0 0 0 0 4 0 67 91 Impaa Clear Low-e 0.580 ne 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 48 48 151 97 64 64 202 129 11 Impaa Clear Low-e 0.490 se 0.00 0.00 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 0.00 0.00 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.620 se 0.00 0.00 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 0.00 0.00 0 0 0 0 0 0 0 0 Knee wall,R-30 KW 1 0.042 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.490 se 0.00 0.00 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.08 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.82 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 0.00 0.00 0 0 0 0 0 0 0 0 G Impact,ClearLow-e 0.650 sw 18.85 14.02 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.650 nw 0.00 0.00 0 0 0 0 0 0 0 0 W Knee wall,R-30 KW 1 0.042 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Frm Wall,12"Gyp B 0.101 0.00 0.00 0 0 0 0 0 0 0 0 C AttiG Metal Roof,R 0.034 0.99 0.61 59 59 58 36 88 88 87 54 F On Grade Depth,Tile 0.989 28.68 0.00 59 6 172 0 88 19 531 0 6 c)AED excursion 0 -2 Envelope loss/gain 382 132 1139 433 12 a) Infiltration 75 20 230 61 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 456 152 1369 494 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 456 152 1369 494 15 Dud loads 23% 28% 1061 43 23% 28%1 319 139 FFTotal room load 563 195 1688 633 Airrequired(dm) 28 10 83 31 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -ri- 2021-Od-1913:56:46 Right-Sute@Unversal2021 21.0.08 RSU29066 Page 12 nts\W ri htsoft HVAC\85 Pinewood Ln PSL Prop.r p Calc=MJ8 Front Door faces:N Duct System Summary Job: 1468 +� wrightsoft D S S Date: 4/14/2021 House By: Chris Bateman Air CaICS, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project Information For: Peavy Residence,NisAirAir Conditioning 85 Pinewood Ln,Fort Pierce,FL 34947 Heating Cooling External static pressure 0.85 in H2O 0.85 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0.85 in H2O 0.85 in H2O Supply/return available pressure 0.604/0.246 in H2O 0.604/0.246 in H2O Lowest friction rate 0.314 in/100ft 0.314 in/100ft Actual airflow 1153 cfm 1153 cfm Total effective length(TEL) 271 ft SupplyDetail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FIR (in) (in) Matl Ln(ft) Ln(ft) Trunk Bat, h 913 48 26 0.503 4.0 Ox 0 Wx 25.2 95.0 st2 Bed 2 h 2585 137 98 0.456 6.0 Ox 0 Wx 32.5 100.0 st2 Bed 3 h 2788 148 106 0.445 6.0 Ox 0 Wx 35.9 100.0 st2 Den h 2391 127 80 0.439 6.0 Ox 0 Wx 37.5 100.0 st2 Foyer/DR h 1772 94 76 0.571 5.0 Ox 0 Wx 10.9 95.0 st4 Foyer/DR-A h 1772 94 76 0.328 6.0 Ox 0 Wx 59.0 125.0 st6 Hers h 911 48 20 0.343 4.0 Ox 0 VI Fx 51.3 125.0 st6 His h 41 2 2 0.358 4.0 Ox0 VI Fx 48.9 120.0 st6 Kitchen c 1594 7 103 0.459 5.0 Ox0 VI Fx 31.6 100.0 st3 Kitchen-A c 1594 7 103 0.465 5.0 Ox0 VI Fx 30.1 100.0 st3 Laundry c 905 42 58 0.618 4.0 Ox0 VI Fx 7.8 90.0 st4 Living Room c 2419 80 156 0.451 6.0 Ox 0 VI Fx 34.0 100.0 st3 Living Room-A c 2419 80 156 0.453 6.0 Ox 0 Wx 33.5 100.0 st3 Master Bath h 3512 186 110 0.329 7.0 Ox 0 Wx 58.7 125.0 st6 Master Bed h 2497 132 104 0.314 6.0 Ox 0 Wx 67.7 125.0 st6 Master Bed-A h 2497 132 104 0.330 6.0 Ox 0 Wx 58.2 125.0 st6 Wtr Clst h 384 20 8 0.337 4.0 Ox 0 Wx 54.4 125.0 st6 wrightsoft® 2021-Oct-1913:56:48 A= AMA=-I1 •", _ -.=—— Right-Sute®Universal 2021 21.0.08 RSU29066 Page 1 ACCA ..zits\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N SupplyDetail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st2 PeakAVF 459 310 0.439 842 10.0 0 x 0 VinlFlx st6 PeakAVF 615 423 0.314 783 12.0 0 x 0 VinlFlx st3 st3 PeakAVF 790 940 0.314 879 14.0 0 x 0 VinlFlx st4 PeakAVF 135 134 0.571 689 6.0 0 x 0 VinlFlx TableReturn Branch Detail Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening(in) Matl Trunk rb8 Ox 0 148 106 78.3 0.314 552 7.0 Ox 0 VI Fx rt2 rb7 Ox0 137 98 77.1 0.319 512 7.0 Ox 0 VIFx rt2 rb9 Ox0 395 385 0 0 0 0 Ox 0 VIFx rb1 Ox0 705 795 76.6 0.321 569 16.0 Ox 0 VIFx r2 TableReturn Trunk Detail Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk rt2 PeakAVF 989 999 0.314 716 16.0 0 x 0 VinlFlx Bolditalic values have been manually overridden wrightsoft® 2021-Oct-1913:56:48 A AMAT-I1-•", _ -.1-p-. Right-Sute®Uriversal 202121.0.08 RSU29066 Page 2 ACCA ...nts\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N Duct System Summary Job: 1468 +� wrightsoft D S S Date: 4/14/2021 Inlaw By: Chris Bateman Air CaICS, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project Information For: Peavy Residence,NisAirAir Conditioning 85 Pinewood Ln,Fort Pierce,FL 34947 Heating Cooling External static pressure 0.70 in H2O 0.70 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0.70 in H2O 0.70 in H2O Supply/return available pressure 0.485/0.215 in H2O 0.485/0.215 in H2O Lowest friction rate 0.344 in/100ft 0.344 in/100ft Actual airflow 524 cfm 524 cfm Total effective length(TEL) 203 ft SupplyDetail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FIR (in) (in) Matl Ln(ft) Ln(ft) Trunk Kitchen c 3805 138 225 0.350 8.0 Ox0 VIFx 23.6 115.0 st5 Living Room 2 c 1859 98 110 0.443 6.0 Ox 0 VI Fx 14.5 95.0 st1 Living Room 2-A c 1859 98 110 0.344 6.0 Ox 0 VI Fx 25.9 115.0 st5 M Bath 2 h 1688 99 37 0.465 5.0 Ox0 VIFx 9.3 95.0 st1 Master Bed 2 h 1379 81 67 0.351 5.0 Ox 0 VI Fx 23.3 115.0 st5 Master Bed 2-A h 1379 81 67 0.353 5.0 Ox 0 VI Fx 22.2 115.0 st5 wlc h 563 33 12 0.468 4.0 Ox0 VIFx 8.5 95.0 st1 SupplyDetail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st5 PeakAVF 398 470 0.344 861 10.0 0 x 0 VinlFlx st1 st1 PeakAVF 629 629 0.344 801 12.0 0 x 0 VinlFlx TableReturn Branch Detail Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening(in) Matl Trunk rb2 Ox0 195 146 60.5 0.356 558 8.0 Ox 0 VIFx rt1 rb11 Ox0 434 483 62.6 0.344 452 14.0 Ox 0 VIFx rt1 wrightsoft® 2021-Oct-1913:56:48 A= AMA=-I1 •", _ -.=—— Right-Sute®Universal 202121.0.08 RSU29066 Page 3 ACCA ...ntsmrightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N TableReturn Trunk Detail Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk rt1 PeakAVF 629 629 0.344 588 14.0 0 x 0 VinlFlx wrightsoft® 2021-Oct-1913:56:48 A AMAT-I1-•", _ -.=—— Right-Sute®Urrversal 2021 21.0.08 RSU29066 Page 4 ACCA ...nts\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N Manual S ComplianceReport Job: 1468 +� wrightsoft° Date: 4/14/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project Information For: Peavy Residence,NisAirAir Conditioning 85 Pinewood Ln,Fort Pierce,FL 34947 Cooling Equipment Design Conditions Outdoor design DB: 90.4°F Sensible gain: 23007 Btuh Entering coil DB: 77.4°F Outdoor design WB: 77.4°F Latent gain: 8133 Btuh Entering coil WB: 64.5°F Indoor design DB: 75.0°F Total gain: 31140 Btuh Indoor RH: 50% Estimated airflow: 1153 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Lennox Model: ML14XC1S036-230C**+CBA27UHE-036-230*++TDR Actual airflow: 1153 cfm Sensible capacity: 24220 Btuh 105%of load Latent capacity: 10380 Btuh 128%of load Total capacity: 34600 Btuh 111%of load SHR: 70% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 29030 Btuh Entering coil DB: 67.2°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elecstrip Manufacturer: Model: Actual airflow: 1153 cfm Output capacity: 7.3 kW 86%of load Temp.rise: 50 °F Meets all requirements ofACCA Manual S. wrightsoft, 2021-Oct-19 13:56:48 A II,-=Io-•", _ -.=—— Right-Sute®Universal 2021 21.0.08 RSU29066 Page 1 ACCA nts\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N Manual S ComplianceReport Job: 1468 +� wrightsoft° Date: 4/14/2021 Inlaw By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project Information For: Peavy Residence,NisAirAir Conditioning 85 Pinewood Ln,Fort Pierce,FL 34947 Cooling Equipment Design Conditions Outdoor design DB: 90.4°F Sensible gain: 11199 Btuh Entering coil DB: 77.0°F Outdoor design WB: 77.4°F Latent gain: 3156 Btuh Entering coil WB: 64.2°F Indoor design DB: 75.0°F Total gain: 14354 Btuh Indoor RH: 50% Estimated airflow: 524 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Generic Model: SEER 18.0,HSPF 9.1 Actual airflow: 524 cfm Sensible capacity: 13343 Btuh 119%of load Latent capacity: 4324 Btuh 137%of load Total capacity: 17667 Btuh 123%of load SHR: 76% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 11801 Btuh Entering coil DB: 67.6°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Generic Model: SEER 18.0,HSPF 9.1 Actual airflow: 524 cfm Output capacity: 15646 Btuh 133%of load Capacity balance: 32 °F Supplemental heat required: 0 Btuh Economic balance: -99 °F Meets all requirements ofACCA Manual S. wrightsoft, 2021-Oct-19 13:56:48 A —1-11-•", _ -.1-p-. Right-Sute®Universal 2021 21.0.08 RSU29066 Page 2 ACCA nts\W rightsoft HVAC\85 Pinewood Ln PSL Prop.rup Calc=MJ8 Front Door faces:N