Loading...
HomeMy WebLinkAboutSigned Energy Code 2FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/maybe greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and se/ection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 -one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed 2020 Duct Leakage Test Report -Performance Method (usually one page) 10/19/2021 1:57:16 PM EnergyGauge®USA 7.0.00 - FlaRes2020 FHC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: 85 Pinewood Ln PSL Prop Builder Name: PSL Prop Street: 85 Pinewood Ln Permit Office: City, State, Zip: Fort Pierce , FL , 34947 Permit Number: Owner: Peavy Residence Jurisdiction: St. Lucie Design Location: FL, ST_LUCIE_CO_INTL County: St. Lucie (Florida Climate Zone 2 ) 1. New construction or existing New (From Plans) 10. Wall Type42686.5 sqft.) Insulation Area 2. Single family or multiple family Detached a. Concrete Block - Ext Insul, Exterior R=4.1 2447.50 ft2 b. Interior Frame - Wood, Interior R=11.0 193.00 ft2 3. Number of units, if multiple family 1 c. Frame - Wood, Exterior R=30.0 46.00 ft2 4. Number of Bedrooms 4 d. N/A R= ft2 11. Ceiling Types (2647.0 sqft.) Insulation Area 5. Is this a worst case? Yes a. Under Attic (Vented) R=30.0 2647.00 ft2 6. Conditioned floor area above grade (ft2) 2647 b. N/A R= ft2 Conditioned floor area below grade (ft2) 0 c. N/A R= ft2 /. Windows(284.5 sqft.) Description Area 12. Ducts a. Sup: Attic, Ret: Attic, AH: Attic R ft2 6 802 a. U-Factor: Dbl, U=0.58 133.78 ft2 b. Sup: Attic, Ret: Attic, AH: Attic 6 254 SHGC: SHGC=0.24 b. U-Factor: Dbl, U=0.65 86.67 ft2 13. Cooling systems kBtu/hr Efficiency SHGC: SHGC=0.21 a. Central Unit 34.6 SEER:16.00 c. U-Factor: Dbl, U=0.62 49.06 ft2 b. Central Unit 15.7 SEER:18.00 SHGC: SHGC=0.22 14. Healing systems kBtu/hr Efficiency Area Weighted Average Overhang Depth: 3.579 ft. Area Weighted Average SHGC: 0.223 a. Electric Strip Heat 24.9 COP:1.00 b. Electric Heat Pump 15.7 HSPF:9.10 3, Skylights Area C. U-Factor.(AVG) N/A ft2 15, Hot water systems SHGC(AVG): N/A a. Electric Cap: 50 gallons 9. Floor Types (2646.9 sqft.) Insulation Area EF: 0.960 a. Slab -On -Grade Edge Insulation R=0.0 2646.90 ft2 b. Conservation features b. NIA R= ft2 None c. N/A R= ft2 16. Credits Pstal Total Proposed Modified Loads: 75.06 Glass/Floor Area: 0,107 PASS Total Baseline Loads: 77,94 I hereby certify that the plans and specifications covered by Review of the plans and *114E SOP this calculation are in compliance with the Florida Energy specifications covered by this 1'Qa '_ s FOB, Code. calculation indicates compliance y��,'' 'ss,o�\e aG with the Florida Energy Code. time: ". •;:',, i1 °„ O PREPARED BY: `" DATE: 10 9/2021 Before construction is completed this building will be inspected for compliance with Section 553.908 I hereby certify that this building, as ig is i pliance Florida Statutes. with the Florida Energy Code. , COb {yg'CRJ OWNER/A E T: BUILDING OFFICIAL: DATE: a .21 DATE: - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory -sealed in accordance with R403.3.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 7.00 ACH50 (R402.4.1.2). - Compliance with a proposed duct leakage on requires a Duct Leakage Test Report confirming duct leakage to outdoors, tested in accordance with ANSI/RESNET/ICC 380, is not greater than 0.000 Qn for whole house. 10l19/2021 1:57 PM 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 1 of 7 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT PROJECT Title: 85 Pinewood Ln PSL Prop Bedrooms: 4 Address Type: Street Address Building Type: User Conditioned Area: 2647 Lot # Owner Name: Peavy Residence Total Stories: 1 Block/Subdivision: # of Units: 1 Worst Case: Yes PlatBook: Builder Name: PSL Prop Rotate Angle: 90 Street: 85 Pinewood Ln Permit Office: Cross Ventilation: No County: St. Lucie Jurisdiction: St. Lucie Whole House Fan: No City, State, Zip: Fort Pierce , Family Type: Detached FL , 34947 New/Existing: New (From Plans) Comment: CLIMATE / Design Temp Int Design Temp Heating Design Daily Temp Design Location TMY Site 97.5 % 2.5 % Winter Summer Degree Days Moisture Range FL, ST_LUCIE_CO_INTL FL_VERO_BEACH_MUNI 39 90 70 75 299 58 Medium BLOCKS Number Name Area Volume 1 House 2010 17711.5 2 Inlaw 637 5096 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InTI ID Finished Cooled Heated 1 Laundry 44 352 No 0 1 Yes Yes Yes 2 Bed 2 167 1336 No 0 1 1 Yes Yes Yes 3 Bath 58 464 No 0 1 Yes Yes Yes 4 Hall 34 272 No 0 1 Yes Yes Yes 5 Lin 6 48 No 0 1 Yes Yes Yes 6 Hers 57 456 No 0 1 Yes Yes Yes 7 His 32 256 No 0 1 Yes Yes Yes 8 Lin 2 10 80 No 0 1 Yes Yes Yes 9 Master Bath 149 1192 No 0 1 Yes Yes Yes 10 Master Bed 371 3153.5 No 0 1 1 Yes Yes Yes 11 Kitchen 193 1930 Yes 2 1 Yes Yes Yes 12 Dining Room 164 1558 No 0 1 Yes Yes Yes 13 Pantry 15 120 No 0 1 Yes Yes Yes 14 Living Room 407 4070 No 2 1 Yes Yes Yes 15 Wtr Clst 24 192 No 0 1 Yes Yes Yes 16 Bed 3 152 1216 No 0 1 1 Yes Yes Yes 17 Den 127 1016 No 0 1 Yes Yes Yes 18 Master Bed 2 175 1400 No 0 1 1 Yes Yes Yes 19 Kitchen 2 128 1024 Yes 1 1 Yes Yes Yes 20 Living Room 2 187 1496 No 1 1 Yes Yes Yes 21 WIC 59 472 No 0 1 Yes Yes Yes 10/19/2021 1:57 PM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 7 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfiI ID Finished Cooled Hea 22 M Bath 88 704 No 0 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab -On -Grade Edge Insulatio Laundry 10.5 ft 0 44 ft2 ____ 1 0 0 2 Slab -On -Grade Edge Insulatio Bed 2 26 it 0 166.8 ft2 1 0 0 3 Slab -On -Grade Edge Insulatio Bath 8.5 It 0 57.8 ft2 ____ 1 0 0 4 Slab -On -Grade Edge Insulatio Hall 1 it 0 34 112 ____ 1 0 0 5 Slab -On -Grade Edge Insulatio Lin 1 it 0 6 ft2 1 0 0 6 Slab -On -Grade Edge Insulatio Hers 9.5 ft 0 57 112 ____ 1 0 0 7 Slab -On -Grade Edge Insulatio His 1 It 0 31.5 ft2 ____ 1 0 0 8 Slab -On -Grade Edge Insulatio Lin 2 6.5 ft 0 10 ft2 ____ 1 0 0 9 Slab -On -Grade Edge Insulatio Master Bath 27 it 0 149 ft2 ____ 1 0 0 10SIab-On-Grade Edge Insulatio Master Bed 45 it 0 370.5 112 ____ 1 0 0 11Slab-On-Grade Edge Insulatio Kitchen 1 ft 0 193.3 ft2 ____ 1 0 0 12SIab-On-Grade Edge Insulatio Dining Room 26.5 it 0 163.8 ft2 1 0 0 13SIab-On-Grade Edge Insulatio Pantry 1 it 0 15 ft2 ____ 1 0 0 14SIab-On-Grade Edge Insulatio Living Room 14.5 ft 0 408.8 ft2 1 0 0 15Slab-On-Grade Edge Insulatio Wtr Clsl 4 it 0 24 ft2 1 0 0 16SIab-On-Grade Edge Insulatio Bed 3 26 ft 0 151.8 112 _ 1 0 0 17SIab-On-Grade Edge Insulatio Den 22 it 0 126.5 ft2 ____ 1 0 0 1 &Slab -On -Grade Edge Insulatio Master Bed 2 26.5 it 0 175 ft2 ____ 1 0 0 19SIab-On-Grade Edge Insulatio Kitchen 2 23 ft 0 128.3 ft2 ____ 1 0 0 20SIab-On-Grade Edge Insulatio Living Room 2 27 it 0 186.8 ft2 1 0 0 21SIab-On-Grade Edge Insulatio WIC 6 it 0 59 ft2 1 0 G _ 22SIab-On-Grade Edge Insulatio M Bath 2 18.5 it 0 88 ft2 1 0 0 ROOF / Roof Gable Roof Rad Solar SA Emill Emill Deck Pitch V # Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg) 1 Hip Metal 2960 ft2 0 ft2 Medium N 0.3 No 0.9 No 0 26.57 / ATTIC V # Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 Full attic Vented 300 2647 ft2 N N rnonn onnR_�n�n IKIPI IT Al IMMARV CNFCKI IRT REPORT Am CEILING # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic (Vented) Laundry 30 Blown 44 ft' 0.1 Wood 2 Under Attic (Vented) Bed 2 30 Blown 167 ft' 0.1 Wood 3 Under Attic (Vented) Bath 30 Blown 58 W 0.1 Wood 4 Under Attic (Vented) Hall 30 Blown 34 ft' 0.1 Wood 5 Under Attic (Vented) Lin 30 Blown 6 ft' 0.1 Wood 6 Under Attic (Vented) Hers 30 Blown 57 ft' 0.1 Wood 7 Under Attic (Vented) His 30 Blown 32 W 0.1 Wood 8 Under Attic (Vented) Lin 2 30 Blown 10 ft' 0.1 Wood 9 Under Attic (Vented) Master Bath 30 Blown 149 ft' 0.1 Wood 10 Under Attic (Vented) Master Bed 30 Blown 371 ft' 0.1 Wood I I Under Attic (Vented) Kitchen 30 Blown 193 ft' 0.1 Wood 12 Under Attic (Vented) Dining Room 30 Blown 164 ft' 0.1 Wood 13 Under Attic (Vented) Pantry 30 Blown 15 ft' 0.1 Wood 14 Under Attic (Vented) Living Room 30 Blown 407 ft' 0.1 Wood 15 Under Attic (Vented) Wtr Clsl 30 Blown 24 ft' 0.1 Wood 16 Under Attic (Vented) Bed 3 30 Blown 152 ft' 0.1 Wood 17 Under Attic (Vented) Den 30 Blown 127 ft' 0.1 Wood _ 18 Under Attic (Vented) Master Bed 2 30 Blown 175 ft' 0.1 Wood 19 Under Attic (Vented) Kitchen 2 30 Blown 128 W 0.1 Wood 20 Under Attic (Vented) Living Room 2 30 Blown 187 ft' 0.1 Wood 21 Under Attic (Vented) WIC 30 Blown 59 ft' 0.1 Wood 22 Under Attic (Vented) M Bath 2 30 Blown 88 ft' 0.1 Wood WALLS Adjacent Cavity Width Height Sheathing Framing Solar Below Space P _ i o pr In Ft In -Brea R_val P Frarri^^ Qhc^ C.. e% _ 1 NW=>NE Laundry Interior Frame - Wood Laundry 11 8 0 8 0 64.0 ft' 0 0.25 0.8 0 _ 2 SW=>N Laundry Interior Frame - Wood Laundry 11 2 6 8 0 20.0 ft' 0 0.25 0.8 0 3 SW=>N Exterior Concrete Block - Ext Insul Bed 2 4.1 14 6 8 0 116.0 W 0 0 0.3 0 4 NW=>NE Laundry Interior Frame - Wood Bed 2 11 11 6 8 0 92.0 ft' 0 0.25 0.8 0 5 SW=>N Exterior Concrete Block - Ext Insul Bath 4.1 8 6 8 0 68.0 ft' 0 0 0.3 0 _ 6 NE=>SE Exterior Concrete Block - Ext Insul Hers 4.1 9 6 8 0 76.0 ft' 0 0 0.3 0 7 NE=>SE Exterior Concrete Block- Ext Insul Lin 2 4.1 2 6 8 0 20.0 k' 0 0 0.3 0 8 NW=>NE Exterior Concrete Block - Ext Insul Lin 2 4.1 4 0 8 0 32.0 ft° 0 0 0.3 0 9 NE=>SE Exterior Concrete Block - Ext InsMasler Bath 4.1 8 6 8 0 68.0 ft' 0 0 0.3 0 _ 10 SW=>N Exterior Concrete Block - Ext InsMasler Bath 4.1 6 6 8 0 52.0 ft' 0 0 0.3 0 11 NW=>NE Exterior Concrete Block - Ext InsMasler Bath 4.1 12 0 8 0 96.0 ft' 0 0 0.3 0 _ 12 NE=>SE Exterior Concrete Block - Ext Ins011aster Bed 4.1 20 0 8 6 170.0 ft2 0 0 0.3 0 13 SE=>SW Exterior Concrete Block - Ext InsMaster Bed 4.1 14 6 8 6 123.3 W 0 0 0.3 0 14 SW=>N Exterior Concrete Block - Ext Instlitasler Bed 4.1 10 6 8 6 89.3 ft' 0 0 0.3 0 _ 15 NE=>SE Exterior Concrete Block - Ext Indaining Room 4.1 3 0 9 6 28.5 ft' 0 0 0.3 0 16 NW=>NE Exterior Concrete Block - Ext InEDIning Room 4.1 17 9 9 6 168.6 ft' 0 0 0.3 0 _ 17 NW=>NE Exterior Frame - Wood Dining Room 30 8 6 2 0 17.0 ft' 0 0.1 0.3 0 18 SW=>N Laundry Interior Frame - Wood Dining Room 11 8 6 2 0 17.0 ft' 0 0.25 0.8 0 10/19/2021 1:57 PM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 7 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT WALLS Adjacent �rnt T^ Space Cavity Width Height Sheathing Framing Solar Below - # Wall TYp= a---EL--I Fl a ----Area RA/glue-Fraction- Absor_G _ 19 SE=>SW Exterior Concrete Block - Ext Insbtaing Room 41 11 7 W 0 115.8 ft' 0 0 0.3 0 20 SE=>SW Exterior Frame - Wood Living Room 30 14 6 2 0 29.0 ft2 0 0.1 0.3 0 21 NE=>SE Exterior Concrete Block - Ext Insul Wtr Clsl 4.1 4 0 8 0 32,0 ft2 0 0 0.3 0 22 SE=>SW Exterior Concrete Block - Ext msul Bed 3 4,1 14 6 8 0 116.0 ft' 0 0 0,3 0 _23 SW=>N Exterior Concrete Block - Ext Insul Bed 3 4,1 11 6 8 0 92,0 ft' 0 0 0.3 0 24 NE=>SE Exterior Concrete Block - Ext Insul Den 4,1 10 6 8 0 84,0 ft' 0 0 0.3 0 25 SE=>SW Exterior Concrete Block - Ext Insul Den 4.1 11 6 8 0 92.0 ff 0 0 0.3 0 _26 SE=>SW Exterior Concrete Block - Ext InNbster Bed 2 4A 12 6 8 0 100.0 ft2 0 0 0.3 0 27 SW=>N Exterior Concrete Block- Ext In3dhster Bed 2 4.1 14 0 8 0 112.0 ft' 0 0 0.3 0 _28 NE=>SE Exterior Concrete Block - Ext InsuKitchen 2 41 9 6 8 0 76.0 ft' 0 0 0.3 0 29 SE=>SW Exterior Concrete Block- Ext InsuKitchen 2 4.1 13 6 8 0 108.0 ft' 0 0 0.3 0 _30 NE=>SE Exterior Concrete Block - Ext InddLing Room 4.1 15 0 8 0 120.0 ft' 0 0 0.3 0 _31 NW=>NE Exterior Concrete Block- Ext InEWUng Room 4A 12 0 8 0 96,0 ft' 0 0 0.3 0 _32 NW=>NE Exterior Concrete Block -Ext Insul WIC 4.1 6 0 8 0 48.0 ft' 0 0 0.3 0 33 SW=>N Exterior Concrete Block- Ext InsulM Bath 2 4.1 10 6 8 0 84.0 ft' 0 0 0.3 0 34 NW=>NE Exterior Concrete Block - Ext InsulM Bath 2 4.1 8 0 8 0 64.0 ft' 0 0 0.3 0 DOORS # Ornl Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 NW=>NE Insulated Dining Room None .13 6 6 8 40 IF WINDOWS Orientation shown is the entered orientation => chan ed to Worst Case. / Wall Overhang V # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening 1 SW=>NW 3 Metal Low-E Double Yes 0.58 0.24 Y 15.5 ft' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5 2 SW=>NW 5 Metal Low-E Double Yes 0.58 0.24 Y 4.0 ft2 1 It 0 in 1 It 0 in Drapes/blinds Exterior 5 3 NW=>NE 11 Metal Low-E Double Yes 0.62 0.22 Y 18.1 W 1 ft 0 in 1 it 0 in Drapes/blinds Exterior 5 4 SE=>SW 13 Metal Low-E Double Yes 0.58 0.24 Y 22.4 ft' 1 it 0 in 1 It 0 in Drapes/blinds Exterior 5 5 NW=>NE16 Metal Low-E Double Yes 0.49 0.16 Y 7.5 ft' 1 It 0 in 1 B 0 in Drapes/blinds Exterior 5 6 NW=>NE16 Metal Low-E Double Yes 0.62 0.22 Y 31.0 fl' 1 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5 7 NW=>NE17 Metal Low-E Double Yes 0.49 0.16 Y 7.5 ft' 7 it 0 in 1 it 0 in Drapes/blinds Exterior 5 8 SE=>SW 19 Metal Low-E Double Yes 0.65 0.21 Y 53.3 W 10 it 6 in 1 ft 0 in Drapes/blinds Exterior 5 9 SW=>NW23 Metal Low-E Double Yes 0.58 0.24 Y 15.5 W 1 it 0 in 1 ft 0 in Drapes/blinds Exterior 5 10 NE=>SE 24 Metal Low-E Double Yes 0.58 0.24 Y 15.5 ft' 2 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5 11 SE=>SW 26 Metal Low-E Double Yes 0,58 0.24 Y 22.4 W 1 It 0 in 1 It 0 in Drapes/blinds Exterior 5 12 NE=>SE 28 Metal Low-E Double Yes 0.58 0.24 Y 9.5 ft' 1 it 0 in 1 it 0 in Drapes/blinds Exterior 5 13 SE=>SW 29 Metal Low-E Double Yes 0.58 0.24 Y 9.5 W 1 ft 0 in 1 ft0 in Drapes/blinds Exterior 5 14 NE=>SE 30 Metal Low-E Double Yes 0.58 0.24 Y 15.5 ft' 1 It 0 in 1 It 0 in Drapes/blinds Exterior 5 15 NE=>SE 30 Metal Low-E Double Yes 0.65 0.21 Y 33.3 W 6 If 0 in 1 ft 0 in Drapes/blinds Exterior 5 16 SW=>NW33 Metal Low-E Double Yes 0.58 0.24 Y 4.0 ft2 1 It 0 in 1 110 in Drapes/blinds Exterior 5 10/19/2021 1:57 PM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 7 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT GARAGE # Floor Area Ceiling Area Exposed Wall Perimeter Avg, Wall Height Exposed Wall Insulation 1 382.8 ft' 382.8 ft' 64 ft 8 ft 1 INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000383 2660.9 145.98 274.07 .1301 7 HEATING SYSTEM # System Type Subtype Speed Efficiency Capacity Block Ducts 1 2 Electric Strip Heat/ Electric Heat Pump/ None Split COP:1 24.9 kBtu/hr Singl HSPF:9.1 15.72 kBtu/hr i 2 sys#1 sys#2 COOLING SYSTEM # System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 2 Central Unit/ Central Unit/ Split Split Singl SEER: 16 34.6 kBtu/hr 1038 cfm 0.85 Singl SEER: 18 15.72 kBtu/hr cfm 0.85 1 2 sys#1 sys#2 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Electric None Garage 0.96 50 gal 60.9 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Cart # Company Name Collector Storage System Model # Collector Model # Area Volume FEF None None ft' DUCTS / # ---- Supply ---- Location R-Value Area ---- Return ---- Air CFM 25 CFM25 Location Area Leakage Type Handler TOT OUT ON RLF HVAC # Heat Coal 1 2 Attic 6 802 W Attic 6 254 ft' Attic Attic 802 ft' Proposed On Attic --- cfm 0.0 cfm 0.00 254 ft' Default Leakage Attic (Default) (Default) 0.50 1 1 2 2 10/19/2021 1:57 PM 7.0.00 - FlaRes2020 FBC 7ih Edition (2020) Compliant Software Page 6 of 7 FnRnn Ranz;_2ron INPUT SUMMARY CHECKLIST REPORT TEMPERATURES Programablje Thermostarrt: Y Ceiling Fans:Coo r[ Jun[ ] (XI j j IX) Aug r IX) NovrDec Has [XI Jan (X� Feb [X� Mar Apr May Jun Jul Sep rrXll € Oct Nov Dec Venting I1 1 Jan [[[((( 111 Feb lIX Mar lXl Jun ll[ 11) Jul [l( J1J Aug l(( 11 Sep [X] [ Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling (WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling (WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating (WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating (WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 MASS Mass Type Area Thickness Furniture Fraction Space Default(8 Ibs/sq.ft. 0 ft' 0 ft 0.3 Laundry Default(8 Ibs/sq.ft. ft' ft 0.3 Bed 2 Default(8 lbs/sq.ft. ft2 ft 0.3 Bath Default(8 lbs/sq.ft. ft' ft 0.3 Hall Default(8 lbs/sq.ft, ft' ft 0.3 Lin Default(8 lbs/sq.ft. ft2 ft 0.3 Hers Default(8 lbs/sq.ft. ft' ft 0.3 His Default(8 Ibs/sq.ft. ft' ft 0.3 Lin 2 Default(8 Ibs/sq.ft. ft' ft 0.3 Master Bath Default(8 Ibs/sq.ft. ft' ft 0.3 Master Bed Default(8 lbs/sq.ft. ft' ft 0.3 Kitchen Default(8 Ibs/sq.ft. ft2 it 0.3 Dining Room Default(B Ibs/sq.ft. ft' ft 0.3 Pantry Default(8 Ibs/sq.ft. W ft 0.3 Living Room Default(8 Ibs/sq.ft. ft' ft 0.3 Wtr Clst Default(8 Ibs/sq.ft. ft' ft 0.3 Bed 3 Default(8 lbs/sq.ft. ft' ft 0.3 Den Default(8 Ibs/sq.ft. ft2 ft 0.3 Master Bed 2 Default(B Ibs/sq.ft. ft' ft 0.3 Kitchen 2 Default(8 Ibs/sq.ft. ft' ft 0.3 Living Room 2 Default(8 lbs/sq.ft. ft' ft 0.3 WIC Default(8 Ibs/s .ft. ft' ft 0.3 M Bath 2 10/19/2021 1:57 PM 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 7 of 7 FORM R405-2020 ENERGY PERF®R ANCE LEVEL (EPL) DIG LAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 96 The lower the EnergyPerfoi mance Index, the more efficient the home. 85 Pinewood Ln, Fort Pierce, FL, 34947 1. New construction or existing New (From Plans) 10. Wall Type and Insulation a. Concrete Block - Ext Insul, Exterior 2. Single family or multiple family Detached b. Interior Frame - Wood, Interior 3. Number of units, if multiple family 1 c. Frame - Wood, Exterior 4. Number of Bedrooms 4 d. N/A 11. Ceiling Type and insulation level 5. Is this a worst case? Yes a. Under Attic (Vented) 6. Conditioned floor area (ft2) 2647 b. N/A c. N/A 7. Windows'* Description Area 12. Ducts, location &insulation level a. U-Factor: Dbl, U=0.58 133.78 ft2 a. Sup: Attic, Rot: Attic, AH: Attic SHGC: SHGC=0.24 b. Sup: Attic, Ret Attic, AH: Attic b. U-Factor: Dbl, U=0.65 86.67 f' SHGC: SHGC=0.21 13. Cooling systems c. U-Factor: ON, U=0.62 49.06 ft2 a. Central Unit SHGC: SHGC=0.22 b. Central Unit d. U-Factor: other (see details) 15.00 ft2 14. Healing systems SHGC: other (see details) a. Electric Strip Heat Area Weighted Average Overhang Depth: 3.579 ft. b. Electric Heal Pump Area Weighted Average SHGC: 0.223 8. Skylights Description Area 15. Hot water systems a. U-Factor(AVG): N/A ft2 a. Electric SHGC(AVG): N/A b. Conservation features 9. Floor Types Insulation Area None a. Slab -On -Grade Edge Insulation R=0.0 2646.90 ft2 Credits (Performance method) b. N/A R= ft2 c. N/A R= ft2 I certify that this home has complied with the Florida Energy Efficiency Code for Building Construction through the above energy saving features which will be installed (or exceeded) in this home before final insp606rwi, a new Display Card will be completed based on installed Code comBuilder Signature: Date: �d1f921 Address of New Home: City/FL Zip:}`1Qi`[�tFI Insulation Area R=4.1 2447.50 ft2 R=11.0 193.00 ft2 R=30.0 46.00 ft2 R= ft2 In Area R=30.0 2647.00 ft2 R= ft2 R= ft2 R ft2 6 802 6 254 kBlu/hr Efficiency 34.6 SEER:'16.00 15.7 SEER:18.00 kBtu/hr Efficiency 24.9 COP:1.00 15.7 HSPF:9.10 Cap: 5D gallons EF: 0.96 Pstat *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 10/19/2021 1:57 PM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Reauirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 85 Pinewood Ln Permit Number: Fort Pierce , FL , 34947 MANDATORY REQUIREMENTS = See individual code sections for full details. V SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory).The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer s instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. R402.4.2 Fireplaces. New wood -burning fireplaces shall have fight -fitting Flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 chin per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 10/19/2021 1:57 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Soilware Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) ❑R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gaskeled and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. ❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 last (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. SECTION R403 SYSTEMS R403.1 Controls. ❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heal shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct lightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or III, Florida Statutes, to be "substantially as free' in accordance with Section R403.3.3. ❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. ❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturers air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage lest shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where on = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. ❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying Fluids above 105°F (41°C) or below 55°F (WC) shall be insulated to a minimum of R-3. ❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. ❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5A.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1A Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall ❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. ❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the limes when heated water is used in the occupancy. 10/19/2021 1:57 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software 0age 2 of 5 MANDATORY REQUIREMENTS" (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 1000F to 140OF (380C to 600C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all slated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.24 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the spaces) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. ❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFMANATT) AIRFLOW RATE MAXIMU (CFM) HRV or ERV Any 1.2 cfm(watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested In accordance with HVI Standard 916 10l19l2021 1:57 PM EnergyGauge®USA 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.12 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design healing load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. ❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: i. A separate cooling or heating system is utilized to provide cooling or healing to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections ❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow It and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40'F (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. ❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ElR403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool healing systems. 3. Where pumps are powered exclusively from on -site renewable generation. 10/19/2021 1:57 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5 R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at ❑ the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for healers manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. ❑R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. ❑ R403.11 Portable spas (Mandatory). The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3A of the Florida Building Code, Residential. R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not.be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 10/19/2021 1:57 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7ih Edition (2020) Compliant Software Page 5 of 5 2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1 A AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: 85 Pinewood Ln PSL Prop Builder Name: PSL Prop Street: 85 Pinewood Ln Permit Office: City, State, Zip: Fort Pierce , FL , 34947 Permit Number: U Owner: Peavy Residence Jurisdiction: St. Lucie w Design Location: FL, ST_LUCIE_CO_INTL o COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. requirements Breaks or joints in the air barrier shall be sealed. The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit Ceiling/attic the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls Walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace wall . Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on Narrow cavities installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spa s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind non no an widna. Exterior walls adjacent to showers and tubs shall Shower/tub The air barrier installed at exterior walls adjacent to showers and on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids I between fire sprinkler cover plates and walls or call nus. a. In addition, inspection of log walls snail be In accordance WnO me provisions or IVV-vuu. 10/19/2027 1:57 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7lh Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: St. Lucie Permit #: Job Information Builder: PSL Prop Community: Lot: NA Address: 85 Pinewood Ln City: Fort Pierce State: FL Zip: 34947 Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ERI Method O PRESCRIPTIVE METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes per hour at a pressure of 0.2 inch w.g. (50 Pascals) in Climate Zones 1 and 2. O PERFORMANCE or ERI METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding the selected ACH(50) value, as shown on Form R405-2020 (Performance) or R406-2020 (ERI), section labeled as infiltration, sub -section ACH50. ACH(50) specified on Form R405-2020-Energy Calc (Performance) or R406-2020 (ERI): E7.000 x 60 = 22808 — Method for calculating building volume: CFM(50) Building Volume ACH(50) Q Retrieved from architectural plans 1-1 PASS • Code software calculated When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (1) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 10/19/2021 1:57:33 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Duct Leakage Test Report Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction Job Information Builder: PSL Prop St. Lucie Address: 85 Pinewood Ln City: Fort Pierce Duct Leakage Test Results System 1 cfm25 System 2 cfm25 System 3 cfm25 Sum of others cfm25 Total of all cfm25 2647 — Qn Total of all Total Conditioned systems Square Footage ❑ PASS ❑FAIL Community: Permit #: State: FL Lot: NA Zip: 34947 � Prescriptive Method cfm25 (Total) To qualify as "substantially leak free" Qn Total must be less than or equal to 0.04 if air handler unit is installed. If air handler unit is not installed, Qn Total must be less than or equal to 0.03. This testing method meets the requirements in accordance with Section R403.3.3. Is the air handler unit installed during testing? ❑ YES (") ElNO (-003) � Performance/ERI Method cfm25 (Out or Total) To qualify using this method, On must not be greater than the proposed duct leakage Qn specified on Form R405-2020 or F Leakage Type selected on Form Qn specified on Form R405-2020 R405-2020 (EnergyCalc) orR406-2020 (EnergyCalc) orR406-2020 Proposed On 0.00 Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes. Testing Company Company Name: Phone: I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected compliance path as stated above, either the Prescriptive Method or Performance Method. Signature of Tester: Printed Name of Tester: License/Certification #: Date of Test: Issuing Authority: 10/19/2021 1:57:38 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1