Certificate of Authorization #32455
353 Christian Street, Unit #13
Oxford, CT 06478
(203) 262-9245
ENGINEER EVALUATE TEST CONSULT
EVALUATION REPORT
Polyglass USA, Inc.
1111 West Newport Center Drive
Deerfield Beach, FL 33442
(954) 233-1330
Evaluation Report P9290.02.08-R26
FL1654-R28
Date of Issuance: 02/11/2008
Revision 26: 06/09/2021
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product descr ibed herein has been evaluated for
compliance with the 7th Edition (2020) Florida Building Code sections noted herein.
DESCRIPTION: Polyglass Modified Bitumen Roof Systems for use in FBC non-HVHZ jurisdictions
LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance or production facility location(s) changes, or Code provisions that relate to the product(s) change.
Acceptance of our Evaluation Reports by the named client constitutes agreement to notify NEMO ETC, LLC of any
changes to the product(s), the Quality Assurance or the production facility location(s). NEMO ETC, LLC requires a
complete review of its Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Florida Product Approval Number (FL#) preceded by the words “NEMO|etc. Evaluated” may be
displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its
entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manuf acturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 5, plus a 98-page Appendix.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert
Nieminen, P.E. on 06/09/2021. This does not serve as an
electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. NEMO ETC, LLC does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO ETC, LLC is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing produ cts for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
©2018, NEMO ETC, LLC
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION FL1654-R28
Polyglass Modified Bitumen Roof Systems Revision 26: 06/09/2021
Page 2 of 5
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Modified Bitumen Roof Systems
Compliance Statement: Polyglass Modified Bitumen Roof Systems, as produced by Polyglass USA, Inc., have
demonstrated compliance with the following sections of the 7th Edition (2020) Florida Building Code through
testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and
Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section Property Standard Year
1504.3.1 Wind resistance FM 4474 2011
1504.3.1 Wind resistance UL 1897 2012
1504.6 Accelerated weathering ASTM G155 2013
1504.7 Impact resistance FM 4470, Section 4.6 2016
1507.10.2 Material standard ASTM D4601 2012
1507.10.2 Material standard ASTM D4897 2009
1507.11.2 Material standard ASTM D6162 2015
1507.11.2 Material standard ASTM D6163 2015
1507.11.2 Material standard ASTM D6164 2011
1507.11.2 Material standard ASTM D6222 2011
1507.11.2 Material standard ASTM D6509 2015
3. REFERENCES:
Entity Exam Reference Date Entity Exam Reference Date
ERD (TST11294) FM 4470/4474 PLYG-CTL13945.05.17-1 5/30/2017 FM (TST1867) FM 4470 3020703 7/30/2004
ERD (TST11294) FM 4470/4474 PLYG-CTL13945.05.17-3 5/30/2017 FM (TST1867) FM 4470/4474 3018332 1/31/2006
ERD (TST6049) FM 4470/4474 P13760.09.09 9/10/2009 FM (TST1867) FM 4470/4474 3023368 3/20/2006
ERD (TST6049) FM 4470/4474 P13770.09.09 9/10/2009 FM (TST1867) FM 4470/4474 3024594 5/23/2006
ERD (TST6049) FM 4470/4474 P30540.11.09-R1 11/30/2009 FM (TST1867) FM 4470/4474 3023458 7/18/2006
ERD (TST6049) FM 4470/4474 P30550.12.09 12/2/2009 FM (TST1867) FM 4470/4474 3030668 9/12/2007
ERD (TST6049) FM 4470/4474 P33970.03.11 3/15/2011 FM (TST1867) FM 4470/4474 3032172 6/12/2009
ERD (TST6049) D6163 P33960.03.11 3/15/2011 FM (TST1867) FM 4470/4474 3049631 4/21/2014
ERD (TST6049) D6509 P37590.03.13-1-R1 2/5/2013 FM (TST1867) FM 4470/4474 3057029 2/2/2017
ERD (TST6049) D6163 P37590.03.13-2-R1 2/5/2013 FM (TST1867) FM 4470 3001334 1/25/2000
ERD (TST6049) D6222 P37590.03.13-5-R1 2/6/2013 FM (TST1867) FM 4470 3014751 8/27/2003
ERD (TST6049) FM 4470/4474 P39680.03.13 3/4/2013 FM (TST1867) FM 4470 3007170 1/13/2004
ERD (TST6049) D6164 P37590.03.13-3A 3/6/2013 NEMO (TST6049) Criticality 4S-PLYG-18-001.06.18 6/23/2018
ERD (TST6049) D6164 / G155 P37590.07.13-1 7/2/2013 NEMO (TST6049) FM 4474 4L-PLYG-18-003.08.18 8/21/2018
ERD (TST6049) FM 4470/4474 P41630.08.13 8/6/2013 NEMO (TST6049) Criticality 4S-PLYG-18-001.10.18 10/3/2018
ERD (TST6049) D4601 P45940.09.13 9/4/2013 NEMO (TST6049) D4897 4S-PLYG-18-002.11.18-2 11/16/2018
ERD (TST6049) D4601 P44370.10.13 10/4/2013 NEMO (TST6049) FM 4474 4L-PLYG-18-003.11.18 11/28/2018
ERD (TST6049) D6163 (Table 2) P33960.05.14 5/8/2014 NEMO (TST6049) D6164 4S-PLYG-18-002.11.18-3 11/28/2018
ERD (TST6049) D6164 / G155 P35660.10.14 10/3/2014 NEMO (TST6049) FM 4474 4L-PLYG-18-003.01.19 1/11/2019
ERD (TST6049) FM 4470/4474 SC6160.11.14 11/10/2014 NEMO (TST6049) D6163 4S-PLYG-18-002.01.19-A 1/24/2019
ERD (TST6049) D6163 / G155 P45440SC.03.15-1 3/31/2015 NEMO (TST6049) D6162 / G155 4S-PLYG-18-002.01.19-B 1/25/2019
ERD (TST6049) D6163 / G155 P45440SC.03.15-2-R1 3/31/2015 NEMO (TST6049) Criticality 2i-PLYG-19-SSCRT-01.A 2/6/2019
ERD (TST6049) D6162 SC5170.05.15 5/8/2015 NEMO (TST6049) FM 4474 4L-PLYG-18-003.04.19-A 4/8/2019
ERD (TST6049) FM 4474 SC8085.05.15 5/19/2015 NEMO (TST6049) D6163 4S-PLYG-18-002.05.19-H 5/20/2019
ERD (TST6049) D6162 SC5170.12.15 12/29/2015 NEMO (TST6049) D6222 / G155 4S-PLYG-18-002.05.19-C 5/20/2019
ERD (TST6049) FM 4470/4474 SC9455.15 4/1/2016 NEMO (TST6049) D6222 / G155 4S-PLYG-18-002.05.19-D 5/20/2019
ERD (TST6049) FM 4470/4474 PLYG-SC8905.05.16-1 5/17/2016 NEMO (TST6049) D6164 4S-PLYG-18-002.05.19-N 5/31/2019
ERD (TST6049) FM 4470/4474 PLYG-SC8905.05.16-2 5/17/2016 NEMO (TST6049) Criticality 4S-PLYG-18-001.06.19.A 7/17/2019
ERD (TST6049) FM 4470/4474 PLYG-SC10815.07.16-R1 9/23/2016 NEMO (TST6049) D6164 4S-PLYG-18-002.08.19-I 9/6/2019
ERD (TST6049) UL 1897 PLYG-SC12025.10.16 10/12/2016 NEMO (TST6049) D6164 / G155 4S-PLYG-18-002.09.19-J 9/6/2019
ERD (TST6049) FM 4470/4474 PLYG-SC11475.16 11/17/2016 NEMO (TST6049) FM 4474 4a-ICP-19-LSWUS-01.A 11/8/2019
ERD (TST6049) FM 4470/4474 PLYG-SC13235.01.17 1/17/2017 NEMO (TST6049) D4601 4q-PLYG-19-SSMBB-02.A 12/13/2019
ERD (TST6049) FM 4470/4474 PLYG-SC13920.05.17 5/30/2017 NEMO (TST6049) D6164 4q-PLYG-19-SSMBB-04.A 1/2/2020
ERD (TST6049) FM 4470/4474 PLYG-SC13945.05.17 5/30/2017 NEMO (TST6049) D6164 / G155 4q-PLYG-19-SSMBB-04.B 1/2/2020
ERD (TST6049) FM 4470/4474 PLYG-SC15760.09.17 9/11/2017 NEMO (TST6049) D6222 / G155 4q-PLYG-19-SSMBB-05.A 7/23/2020
FM (TST1867) FM 4470 2W7A7.AM 8/4/1994 NEMO (TST6049) FM 4474 4a-PLYG-20-LSWUS-01.A 8/28/2020
FM (TST1867) FM 4470 0D3A3.AM 4/4/1997 NEMO (TST6049) FM 4474 4a-PLYG-20-LSWUS-02.A 10/5/2020
FM (TST1867) FM 4470 2D0A0.AM 12/23/1998 NEMO (TST6049) D6164 4q-PLYG-20-SSMBB-04.A 10/21/2020
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION FL1654-R28
Polyglass Modified Bitumen Roof Systems Revision 26: 06/09/2021
Page 3 of 5
Entity Exam Reference Date Entity Exam Reference Date
FM (TST1867) FM 4470 2D5A9.AM 6/22/1999 NEMO (TST6049) FM 4474 4a-PLYG-21-LSWUS-01.A 6/7/2021
FM (TST1867) FM 4470 3006646 1/4/2000 NEMO (TST6049) Criticality 4i-PLYG-21-LSWUS-02.A 6/7/2021
FM (TST1867) FM 4470 3000857 1/12/2000 PRI (TST5878) TAS 114 PUSA-188-02-01 2/8/2017
FM (TST1867) FM 4470 3004091 1/12/2000 PRI (TST5878) TAS 114 PUSA-188-02-02 2/8/2017
FM (TST1867) FM 4470 3001334 2/15/2000 PRI (TST5878) TAS 114 PUSA-188-02-03 2/8/2017
FM (TST1867) FM 4470 3006115 5/2/2001 PRI (TST5878) TAS 114 PUSA-202-02-01 5/17/2017
FM (TST1867) FM 4470 3012321 7/29/2002 PRI (TST5878) TAS 114 PUSA-202-02-02 5/17/2017
FM (TST1867) FM 4470 3014692 8/5/2003 M-D (CER1592) Prop. for Rev. 10-0823 10/12/2010
FM (TST1867) FM 4470 3019317 6/30/2004 UL (QUA9625) Quality Control Service Confirm 9/13/2018
UL (QUA9625) Quality Control Florida BCIS Current
4. PRODUCT DESCRIPTION:
This Evaluation Report covers Polyglass Modified Bitumen Roof Systems installed in accordance with Polyglass
USA, Inc. published installation instructions and the Limitations / Conditions of Use herein.
TABLE 1: EVALUATED MEMBRANES
Type Product Material Standard Plant(s) Reference Type Grade
Base Sheets
Polyglass G2 Base ASTM D4601 II N/A AL
Polyflex SA Base ASTM D4601 II N/A FL
Elastobase SA ASTM D4601 II N/A PA
Elastovent ASTM D4897 N/A N/A PA
Polybase V (formerly “Polyglass Base”) ASTM D6509 N/A N/A FL
APP, Smooth-
Surface Membranes
Polybond ASTM D6222 I S FL
Polyflex ASTM D6222 I S FL
APP, Granule-
Surface Membranes
Polybond G ASTM D6222 I G FL
Polyflex G ASTM D6222 I G FL
Polyflex G FR ASTM D6222 I G FL
Polyfresko G ASTM D6222 I G NV
Polyfresko G FR ASTM D6222 I G NV
Polyflex SA P ASTM D6222 I G FL, TX
Polyflex SA P FR ASTM D6222 I G TX
Polyfresko G SA ASTM D6222 I G NV
Polyfresko G SA FR ASTM D6222 I G NV
SBS, Smooth-
Surface Membranes
Elastoshield VP HT (formerly “Elastoshield HT”) ASTM D6162 III S FL, PA
Elastobase V (formerly “Elastobase”) ASTM D6163 I S FL
Elastoflex V ASTM D6163 I S FL
Elastoflex SA V ASTM D6163 I S FL, PA, TX
Elastoflex SA V FR ASTM D6163 I S FL, PA, TX
Elastoflex SA V Plus ASTM D6163 I S FL, TX
Elastoflex SA V Plus FR ASTM D6163 I S FL, TX
Elastobase P ASTM D6164 I S FL, TX
Elastoflex SA Base HD ASTM D6164 I S PA, TX
Elastoflex S6 ASTM D6164 I S FL
Elastoshield TS ASTM D6164 I S PA
Elastoflex S6 HP ASTM D6164 II S NV
Polyreflect ASTM D6164 I S FL
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION FL1654-R28
Polyglass Modified Bitumen Roof Systems Revision 26: 06/09/2021
Page 4 of 5
TABLE 1 (CONTINUED): EVALUATED MEMBRANES
Type Product Material Standard Plant(s) Reference Type Grade
SBS, Granule
Surface Membranes
Elastoshield HT G ASTM D6162 III G FL
Elastoshield HT G FR ASTM D6162 III G FL
Elastoflex V G ASTM D6163 I G FL, PA
Elastoflex V G FR ASTM D6163 I G FL, PA
Elastoflex S6 G ASTM D6164 I G FL, PA
Elastoflex S6 G FR ASTM D6164 I G FL
Elastoshield TS G ASTM D6164 I G FL, TX
Elastoshield TS G FR ASTM D6164 I G FL, TX
Elastoflex SA P ASTM D6164 I G FL, TX
Elastoflex SA P FR ASTM D6164 I G FL, TX
5. LIMITATIONS:
5.1 This is a Building Code Evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting
or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC High Velocity Hurricane Zone jurisdictions (i.e., Broward and Miami-Dade
Counties).
5.3 This Evaluation Report pertains to above-deck roof components. Roof decks and structural members shall be in
accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
5.4 This Evaluation Report does not include evaluation of fire classificat ion. Refer to FBC 1505 for requirements and
limitations regarding roof assembly fire classification. Refer to FBC 2603 for requirements and limitations concerning
the use of foam plastic insulation.
5.5 This Evaluation Report does not include evaluation of roof edge termination. Refer to FBC 1504.5 for requirements
and limitations regarding edge securement for low -slope roofs.
5.6 Refer to FBC 1511 for requirements and limitations regarding recover installations.
5.6.1 For mechanically attached components over existing roof decks, fasteners shall be tested in the existing deck for
withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum
requirements for the system. Testing shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard
TAS 105.
5.6.2 For bonded insulation or membrane over existing substrates in a re-roof (tear off) or recover installation, the existing
deck or existing roof surface shall be examined for compatibility with the adhesive to be installed. If any surface
conditions exist that bring system performance into question, field uplift testing in accordance with ANSI/SPRI IA-
1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124 shall be conducted on
mock-ups of the proposed new roof assembly.
5.6.3 For bonded insulation or membrane over existing substrates in a recover installation, the existing roof system shall
be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having
Jurisdiction, as documented through field uplift testing in accordance with ASTM E907, FM Loss Prevention Data
Sheet 1-52 or Testing Application Standard TAS 124.
5.7 Refer to Appendix 1 for system attachment requirements for wind load resistance.
5.7.1 “MDP” = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads,
and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been
applied). Refer to FBC 1609 for determination of design wind loads.
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION FL1654-R28
Polyglass Modified Bitumen Roof Systems Revision 26: 06/09/2021
Page 5 of 5
5.7.2 For mechanically attached components or partially-bonded insulation, the maximum design pressure for the
selected assembly shall meet or exceed at least the Zone 1 PRIME design pressure determined in accordance with
FBC Chapter 16. Elevated pressure zones shall employ an attachment density designed by a qualified design
professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss
Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137.
Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data
Sheet 1-29 (February 2020) for Zone 2/3 enhancements.
5.7.3 For assemblies with all components fully bonded in place, the maximum design pressure for the selected assembly
shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No rational analysis is
permitted for these systems.
5.8 All components in the roof assembly shall have quality assurance audit in accordance with F.A.C. Rule 61G20-3.
Refer to the Product Approval of the component manufacturer for components listed in Appendix 1 that are
produced by a Product Manufacturer other than the report holder on Page 1 of this Evaluation Report.
6. INSTALLATION:
Polyglass Modified Bitumen Roof Systems shall be installed in accordance with Polyglass USA, Inc. published
installation instructions, subject to the Limitations / Conditions of Use noted herein.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction to properly evaluate the installation of this
product.
8. MANUFACTURING PLANTS:
Contact the named QA entity for manufacturing facilities covered by F.A.C. Rule 61G20-3 QA requirements. Refer
to Section 4 herein for products and production locations having met codified material standards.
9. QUALITY ASSURANCE ENTITY:
UL, LLC – QUA9625: (414) 248-6409, karen.buchmann@ul.com
- THE 98-PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT -
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 1 of 98
APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE
TABLE DECK APPLICATION TYPE DESCRIPTION PAGE
1A Wood New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 6
1B Wood New or Reroof (Tear-Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 6-12
1C Wood New, Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 13-14
1D Wood New, Reroof (Tear-Off) or Recover B-1 Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 15
1E Wood New, Reroof (Tear-Off) or Recover C-1 Mech. Attached Insulation, Bonded Roof Cover 16-19
1F Wood New, Reroof (Tear-Off) or Recover D-2 Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 19-23
1G Wood New or Reroof (Tear-Off) E-2 Non-Insulated, Mech. Attached Base Sheet (nails), Bonded Roof Cover 23-28
1H Wood New, Reroof (Tear-Off) or Recover E-2 Non-Insulated, Mech. Attached Base Sheet (screws & plates), Bonded Roof Cover 29-36
1I Wood New or Reroof (Tear-Off) F Non-Insulated, Bonded Roof Cover 36-37
2A Steel or Structural concrete New, Reroof (Tear-Off) or Recover B-1 Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 38-43
2B Steel or Structural concrete New, Reroof (Tear-Off) or Recover C-1 Mech. Attached Insulation, Bonded Roof Cover 44-50
2C Steel or Structural concrete New, Reroof (Tear-Off) or Recover D-2 Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 50-52
2D Steel or Structural concrete New, Reroof (Tear-Off) or Recover D-2 Insulated, Mech. Attached Velociflex, Bonded Roof Cover 53-54
3A Structural concrete New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 55-69
3B Structural concrete New or Reroof (Tear-Off) F Non-Insulated, Bonded Roof Cover 69
4A Lightweight concrete New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 70-74
4B Lightweight concrete New or Reroof (Tear-Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 74-76
4C Lightweight concrete New or Reroof (Tear-Off) E-2 Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 77-81
5A Cementitious wood fiber New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 82-83
5B Cementitious wood fiber Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 83-84
5C Cementitious wood fiber Reroof (Tear-Off) or Recover B-1 Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 85
5D Cementitious wood fiber Reroof (Tear-Off) or Recover C-1 Mech. Attached Insulation, Bonded Roof Cover 85
5E Cementitious wood fiber Reroof (Tear-Off) or Recover E-2 Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 85
6A Existing gypsum Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 86-90
6B Existing gypsum Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 91
6C Existing gypsum Reroof (Tear-Off) or Recover C-1 Mech. Attached Insulation, Bonded Roof Cover 91
6D Existing gypsum Reroof (Tear-Off) or Recover E-2 Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 91
7A Various Recover A-1 Bonded Insulation, Bonded Roof Cover 92-98
7B Various Recover F Non-Insulated, Bonded Roof Cover 98
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 2 of 98
The following notes apply to the systems outlined herein:
1 The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having
Jurisdiction.
2 Fasteners shall be of sufficient length for the following engagements:
➢ Wood Deck: Minimum 1-inch plywood penetration or wood plank embedment.
➢ Steel Deck: Minimum 0.75-inch steel penetration and engage the top flute of the steel deck.
➢ Structural Concrete: Minimum 1-inch embedment into pilot hole in accordance with published installation instructions.
3 Unless otherwise noted, insulation may be any one layer or combination of FBC Approved (Local or Statewide) board(s) that meet FBC 1505 and, for foam plastic, FBC Chapter 26, when installed with the roof
cover.
4 Minimum 200 psi, minimum 2-inch thick FBC Approved lightweight insulating concrete may be substituted for rigid insulation board for System Types B-1, C-1, C-2, D-1 or D-2, whereby fasteners are installed
through the lightweight insulating concrete to engage the structural deck. The structural deck shall be of equal or greater type, thickness and strength to the steel and structural concrete deck listings. Roof
decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. This is a wind uplift resistance allowance and does not purport to address
non-wind-uplift-related issues, such as deck venting or moisture levels within the LWIC and the potential effect on overlying components.
5 Preliminary insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (February 2020).
6 Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer’s published
instructions.
➢ Hot asphalt (HA): Full coverage at 25-30 lbs/square.
➢ DuPont INSTA STIK Quik Set Insulation Adhesive (D-IS): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c.
➢ H.B. Fuller Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c.
➢ H.B. Fuller Millennium PG-1 Pump Grade Adhesive (M-PG1): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c.
➢ OMG OlyBond 500 (OB500): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c. Note: OlyBond Classic may be used where OlyBond 500 is referenced.
➢ OlyBond Classic (OB Classic): Full coverage at 1 gal/square.
➢ ICP Adhesive & Sealants Polyset CR-20: Continuous 2.5-3.5-inch wide ribbons, 12-inch o.c.
➢ Note: When multiple layers(s) of insulation and/or coverboard are installed in ribbon-applied adhesive, board joints shall be staggered.
➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
7 Unless otherwise noted, all insulations are flat-stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following
Maximum Design Pressure (MDP) limitations. In no case shall these values be used to ‘increase’ the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in
the tables, then the thinner board listed below may be used as a drop-in for the equivalent thicker material listed in the table.
➢ M-OSFA: MDP = -157.5 psf (Min. 0.5-inch thick)
➢ M-PG1: MDP = -157.5 psf (Min. 0.5-inch thick)
➢ OB500: MDP = -45.0 psf (Min. 0.5-inch thick Multi-Max FA-3)
➢ OB500: MDP = -187.5 psf (Min. 0.5-inch thick ISO 95+ GL)
➢ OB500: MDP = -315.0 psf (Min. 0.5-inch thick ENRGY 3)
➢ OB500: MDP = -487.5 psf (Min. 0.5-inch thick ACFoam II)
➢ Polyset CR-20: MDP = -117.5 psf (Min. 1.0-inch thick)
8 For adhered roof insulation and board-size: Unless otherwise noted, refer to Section 2.2.10.6.2 of FM Loss Prevention Data Sheet 1-29 (February 2020).
9 For mechanically attached components or partially-bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed at least the Zone 1 PRIME design pressure determined in
accordance with FBC Chapter 16. Elevated pressure zones shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 3 of 98
ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk* carry the limitations set forth in
Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (February 2020) for Zone 2/3 enhancements.
10 For assemblies with all components fully bonded, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No
rational analysis is permitted for these systems.
11 For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the
minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105.
12 For bonded insulation or membrane over existing substrates in a re-roof (tear off) or recover installation, the existing deck or existing roof surface shall be examined for compatibility with the adhesive to be
installed. If any surface conditions exist that bring system performance into question, field uplift testing in accordance shall be conducted on mock-ups of the proposed new roof assembly. For bonded
insulation or membrane over existing substrates in a recover installation, the existing roof system shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority
Having Jurisdiction, as documented through field uplift testing. Field uplift testing shall be in accordance with ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
13 Refer to FBC 1511 for requirements and limitations regarding recover installations. For Structural Concrete Deck or Recover Applications using System Type C-1, C-2, D-1 or D-2, the insulation is optional.
Alternatively, an FBC Approved insulation board or coverboard may be used as a separation layer. Board products shall be preliminarily attached prior to roof cover installation (Note 5 herein). The separator
component shall be documented as meeting FBC 1505 and, for foam plastic, FBC Chapter 26, when installed with the roof cover in Recover applications.
14 Lightweight insulating concrete (LWIC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWIC is referenced, refer to current
LWIC Product Approval for specific deck construction and limitations. Unless otherwise noted, for systems where specific LWIC is not referenced, the minimum design mix shall be 300 psi. In all cases, the
minimum top-coat thickness is 2-inches. For LWIC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1. For “pre-existent” LWIC references, listings were established through testing
over lightweight concrete cast using only foaming agent (ASTM C896), water and Portland cement (ASTM C150), with no proprietary additives, in accordance with procedures adopted by Miami-Dade BCCO
(FBC CER1592). Use of these listings in new construction or re-roof (tear-off) applications is at the discretion of the Designer or Record and Authority Having Jurisdiction.
15 For bonded membrane applications, unless otherwise noted, refer to the following.
MEMBRANE / ADHESIVE COMBINATIONS
REFERENCE LAYER MATERIAL APPLICATION
BP-AA
(Base and Ply sheets,
Asphalt-Applied)
Base Ply One or more plies Polyglass G2 Base, FBC Approved ASTM D4601, Type II Hot Asphalt at 20-40
lbs/square Ply One or more plies Polyglass Ply IV, Polyglass Ply VI, FBC Approved ASTM D2178, Type IV or VI
Note: Asphalt-applied sheets or insulation shall not be applied to poly-film surfaced membranes.
SBS-CA1
Base Ply One ply Elastobase V (sand/sand), Elastoflex V, Elastoflex S6, Elastoflex S6 HP, Elastoshield VP HT PG350 at 1.5-2.0
gal/square Cap Ply Elastoshield HT G, Elastoshield HT G FR, Elastoflex V G, Elastoflex V G FR, Elastoflex S6, Elastoflex S6 HP, Elastoflex S6 G, Elastoflex
S6 G FR, Elastoshield TS G, Elastoshield TS G FR, Polyfresko G SBS (sand-backed), Polyfresko G SBS FR (sand-backed)
SBS-CA2
Base Ply One ply Elastobase V (sand/sand), Elastoflex V, Elastoflex S6, Elastoflex S6 HP Polyplus 35 at 1.5-2.0
gal/square Cap Ply Elastoshield HT G, Elastoshield HT G FR, Elastoflex V G, Elastoflex V G FR, Elastoflex S6, Elastoflex S6 HP, Elastoflex S6 G, Elastoflex
S6 G FR, Elastoshield TS G, Elastoshield TS G FR, Polyfresko G SBS (sand-backed), Polyfresko G SBS FR (sand-backed)
SBS-AA
(SBS, Asphalt-Applied)
Base Ply or Ply One or more plies Elastobase V (sand/sand or poly/sand), Elastobase P (sand/sand or poly/sand), Elastoflex V, Elastoflex S6,
Elastoflex S6 HP, Elastoshield VP HT Hot Asphalt at 20-40
lbs/square Cap Ply Elastoshield HT G, Elastoshield HT G FR, Elastoflex V, Elastoflex V G, Elastoflex V G FR, Elastoflex S6, Elastoflex S6 HP, Elastoflex S6 G,
Elastoflex S6 G FR, Elastoshield TS G, Elastoshield TS G FR, Polyfresko G SBS (sand-backed), Polyfresko G SBS FR (sand-backed)
Note: Asphalt-applied sheets or insulation shall not be applied to poly-film surfaced membranes.
SBS-TA
(SBS, Torch-Applied)
Base Ply or Ply One or more plies Elastobase V (sand/poly), Elastobase V (poly/poly), Elastoflex V, Elastoflex S6, Elastoflex S6 HP, Elastoshield VP
HT, Elastoshield TS
Torch-Applied
Cap Ply
Elastoshield HT G, Elastoshield HT G FR, Elastoflex V, Elastoflex V G, Elastoflex V G FR, Elastoflex S6, Elastoflex S6 HP, Elastoflex S6
G, Elastoflex S6 G FR, Elastoshield TS G, Elastoshield TS G FR, Polyfresko G SBS (poly-film backed), Polyfresko G SBS FR (poly-film
backed)
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 4 of 98
MEMBRANE / ADHESIVE COMBINATIONS
REFERENCE LAYER MATERIAL APPLICATION
SBS-SA-H
(SBS, Self-Adhering, Hybrid Systems) Base Ply Elastobase SA Self-adhering (followed
by torch-applied sheet)
SBS-SA
(SBS, Self-Adhering)
Base Ply One or more plies Elastoflex SA V, Elastoflex SA V FR, Elastoflex SA V Plus, Elastoflex SA V Plus FR, Elastoflex SA Base HD
Self-Adhering Cap Ply Elastoflex SA P, Elastoflex SA P FR, Polyreflect
Note: Unless otherwise noted, permissible membrane substrates for SBS-SA are limited to the SBS-SA Base Ply options herein,
Elastobase V or Elastobase P with a poly-film top surface.
APP-CA1 Cap Ply Polyflex G FR PG350 at 1.5-2.0
gal/square
APP-TA
(APP, Torch-Applied)
Base Ply or Ply One or more plies Polybase V, Polyflex, Polybond Torch-Applied Cap Ply Polyflex, Polyflex G, Polyflex G FR, Polybond, Polybond G, Polyfresko G, Polyfresko G FR
APP-SA-H
(APP, Self-Adhering, Hybrid Systems) Base Ply Polyflex SA Base Self-adhering (followed
by torch-applied sheet)
APP-SA
(APP, Self-Adhering)
Cap Ply Polyflex SA P, Polyflex SA P FR, Polyfresko G SA, Polyfresko G SA FR
Self-Adhering Note: Unless otherwise noted, permissible membrane substrates for APP-SA are limited to the SBS-SA Base Ply options herein,
Elastobase V or Elastobase P with a poly-film top surface.
16 Vapor barrier options for use over structural concrete deck followed by bonded insulation carry the following MDP limitations. The lesser of the MDP listings below vs. those in Table 3A applies.
VAPOR BARRIER OPTIONS; STRUCTURAL CONCRETE DECK; FOLLOWED BY ADHESIVE-APPLIED INSULATION PER TABLE 3A:
OPTION
# PRIMER VAPOR BARRIER INSULATION ADHESIVE MDP (PSF) TYPE (NOTE 15) APPLICATION
C-VB-1. PG100 Elastoflex SA V Plus Self-Adhering D-IS or CR-20, 12-inch o.c. -60.0
C-VB-2. PG100 Polybase V Torch-applied D-IS or CR-20, 12-inch o.c. -75.0
C-VB-3. PG100 Elastoflex SA P Self-Adhering D-IS, 12-inch o.c. -75.0
C-VB-4. PG100 Polyflex or Polybond Torch-applied M-OSFA, M-PG-1, OB500 or CR-20, 12-inch o.c. -121.7
C-VB-5. PG100 Elastoflex SA P Self-Adhering M-OSFA, 12-inch o.c. -157.5
C-VB-6. PG100 Polyflex or Polybond Torch-applied M-OSFA, M-PG-1, OB500 or CR-20, 6-inch o.c. -185.0
C-VB-7. PG100 Elastoflex SA P Self-Adhering CR-20, 12-inch o.c. -270.0
C-VB-8. PG100 Elastoflex SA V, Elastoflex SA V FR, Elastoflex SA V Plus, Elastoflex SA V Plus FR Self-Adhering M-OSFA, M-PG-1, OB500 or CR-20, 12-inch o.c. -240.0
C-VB-9. PG100 SBS-TA (with sanded-top-surface) Torch-applied M-OSFA, M-PG-1, OB500 or CR-20, 12-inch o.c. -240.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 5 of 98
17 The following surfacing may be applied to the Cap Ply without adverse effect on the system wind load performance. Refer to current Florida Product Approval for approved Polyglass and KM Coatings roof coatings
for application limitations and a Roofing Materials Directory for fire ratings associated with coating usage.
SURFACING OPTIONS FOR POLYGLASS MODIFIED BITUMEN ROOF SYSTEMS
OPTION # SURFACING FLORIDA PRODUCT APPROVAL
SURF-1. PG 300 FL10291
SURF-2. PG 600 FL10291
SURF-3. PG 650 FL10291
SURF-4. PG 700 FL10291
SURF-5. PG 700 QS FL10291
SURF-6. PG 800 FL10291
SURF-7. Polyplus 60 FL10291
SURF-8. Polyplus 65 FL10291
SURF-9. PolyBrite 60-FC NOA 20-0611.01
SURF-10. PolyBrite 70 FL10291
SURF-11. PolyBrite 70 QS FL10291
SURF-12. PolyBrite 75 FL10291
SURF-13. PolyBrite 71 HS FL10291
SURF-14. PolyBrite 90 FL10291
SURF-15. PolyBrite 90.1 NOA 19-0610.02
SURF-16. PolyBrite 95 FL10291
SURF-17. PolyBrite 95.1 NOA 19-0610.02
SURF-18. KM Acryl 15 FL27409
SURF-19. KM Acryl 15 QS FL27409
SURF-20. KM Acryl 25 FL27409
SURF-21. KM Acryl 25 QS FL27409
SURF-22. KM Acryl 40 HS FL27409
SURF-23. KM Acryl 85 FL27409
SURF-24. KM PS#250 FL27409
SURF-25. KM PS#220 FL27409
SURF-26. Turbo-Set FL10291
18 “MDP” = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 6 of 98
TABLE 1A: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
SELF-ADHERING BASE PLY:
W-1
Min. 15/32-
inch
plywood
Min. 1.5-inch Polytherm, ACFoam II, Polytherm
G, ACFoam III, ENRGY-3, Polytherm H, H-Shield,
H-Shield CG, Multi-Max FA3
D-IS, M-OSFA,
OB500 or CR-20
(Optional) additional
layers(s) of base
insulation
D-IS, M-OSFA,
OB500 or CR-20 SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -52.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
W-2
Min. 15/32-
inch
plywood
Min. 1.5-inch Polytherm, ACFoam II, Polytherm
G, ACFoam III, ENRGY-3, Polytherm H, H-Shield,
H-Shield CG, Multi-Max FA3
D-IS, M-OSFA,
OB500 or CR-20
(Optional) additional
layers(s) of base
insulation
D-IS, M-OSFA,
OB500 or CR-20 APP-SA-H (Optional) APP-TA APP-TA -52.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
W-3
Min. 15/32-
inch
plywood
Min. 1.5-inch Polytherm, ACFoam II, Polytherm
G, ACFoam III, ENRGY-3, Polytherm H, H-Shield,
H-Shield CG, Multi-Max FA3
D-IS, M-OSFA,
OB500 or CR-20
(Optional) additional
layers(s) of base
insulation
D-IS, M-OSFA,
OB500 or CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -52.5
TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
W-4
Min.
15/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at min.
2-inch lap and 18-
inch o.c. at two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.75-inch Fesco
Board
(homogeneous) or
min. 0.5-inch
Structodek High
Density Fiberboard
Roof Insulation
Hot asphalt
BP-AA
or SBS-
AA
(Optional)
BP-AA or
SBS-AA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
W-5
Min.
15/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at min.
2-inch lap and 18-
inch o.c. at two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 7 of 98
TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
W-6
Min.
15/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at min.
2-inch lap and 12-
inch o.c. at two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.75-inch Fesco
Board
(homogeneous) or
min. 0.5-inch
Structodek High
Density Fiberboard
Roof Insulation
Hot asphalt
BP-AA
or SBS-
AA
(Optional)
BP-AA or
SBS-AA
SBS-AA,
SBS-TA,
APP-TA
-52.5
W-7
Min.
15/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at min.
2-inch lap and 12-
inch o.c. at two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-52.5
W-8
Min.
19/32-
inch
plywood
Polyglass G2 Base,
Elastobase V,
Elastobase P
(sanded-top),
Elastovent,
CertainTeed
Glasbase, Firestone
MB Base, JM Perma-
Ply 28 or GAFGLAS
#75
32 ga., 1-5/8-
inch diameter
tin caps with
11 ga. annular
ring shank
nails
8-inch o.c. at min.
4-inch lap and 8-
inch o.c. at three
(3), equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, Polytherm
G, ACFoam III, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.75-inch Fesco
Board
(homogeneous) or
min. 0.5-inch
Structodek High
Density Fiberboard
Roof Insulation
Hot asphalt
BP-AA
or SBS-
AA
(Optional)
BP-AA or
SBS-AA
SBS-AA,
SBS-TA,
APP-TA
-60.0
W-9
Min.
19/32-
inch
plywood
Polyglass G2 Base,
Elastobase V,
Elastobase P
(sanded-top),
Elastovent,
CertainTeed
Glasbase, Firestone
MB Base, JM Perma-
Ply 28 or GAFGLAS
#75
32 ga., 1-5/8-
inch diameter
tin caps with
11 ga. annular
ring shank
nails
8-inch o.c. at min.
4-inch lap and 8-
inch o.c. at three
(3), equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, Polytherm
G, ACFoam III, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-60.0
W-10
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap Fasteners
12-inch o.c. at min.
4-inch lap and 12-
inch o.c. at two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.75-inch Fesco
Board
(homogeneous) or
min. 0.5-inch
Structodek High
Density Fiberboard
Roof Insulation
Hot asphalt
BP-AA
or SBS-
AA
(Optional)
BP-AA or
SBS-AA
SBS-AA,
SBS-TA,
APP-TA
-60.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 8 of 98
TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
W-11
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap Fasteners
12-inch o.c. at min.
4-inch lap and 12-
inch o.c. at two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-60.0
W-12
Min.
15/32-
inch
plywood
Elastobase V,
Elastobase
P(sanded-top) or
Elastovent
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
8-inch o.c. at min.
4-inch lap and 8-
inch o.c. at four (4),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-67.5
W-13
Min.
15/32-
inch
plywood
Polyglass G2 Base Simplex MAXX
Cap
9-inch o.c. at min.
4-inch lap and 9-
inch o.c. at four (4),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-82.5
W-14
Min.
15/32-
inch
plywood
Polyglass G2 Base,
Elastobase V,
Elastobase P
(sanded-top) or
Elastovent
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
6-inch o.c. at min.
4-inch lap and 6-
inch o.c. at five (5)
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-90.0
W-15
Min.
15/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
6-inch o.c. at min.
2-inch lap and 6-
inch o.c. at two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-90.0
W-16
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top) or
Elastovent
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
6-inch o.c. at min.
4-inch lap and 6-
inch o.c. at four (4),
equally spaced,
staggered center
rows
Min. 2-inch Polytherm,
ACFoam II, III,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3 or ENRGY-3
D-IS, OB500,
CR-20 or M-
OSFA, atop
fastener rows,
7-inch o.c.
Min. 0.25-inch
DensDeck, DensDeck
Prime or SECUROCK
Gypsum-Fiber Roof
Board
D-IS,
OB500, CR-
20 or M-
OSFA
BP-AA,
SBS-
AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-60.0*
SELF-ADHERING BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 9 of 98
TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
W-17
Min.
15/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at min.
2-inch lap and 18-
inch o.c. at two,
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-45.0*
W-18
Min.
15/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at min.
2-inch lap and 12-
inch o.c. at two,
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-52.5
W-19
Min.
19/32-
inch
plywood
Polyglass G2 Base,
Elastobase V,
Elastobase P
(sanded-top),
Elastovent,
CertainTeed
Glasbase, Firestone
MB Base, JM Perma-
Ply 28 or GAFGLAS
#75
32 ga., 1-5/8-
inch diameter
tin caps with
11 ga. annular
ring shank
nails
8-inch o.c. at min.
4-inch lap and 8-
inch o.c. at three
(3), equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, Polytherm
G, ACFoam III, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-60.0
W-20
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap Fasteners
12-inch o.c. at min.
4-inch lap and 12-
inch o.c. at two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-60.0
W-21
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
6-inch o.c. at min.
4-inch lap and 6-
inch o.c. at four (4),
equally spaced,
staggered center
rows
Min. 2-inch Polytherm,
ACFoam II, III,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3 or ENRGY-3
D-IS, OB500,
CR-20 or M-
OSFA, atop
fastener rows,
7-inch o.c.
(Optional) Additional
layers of base
insulation
D-IS,
OB500, CR-
20 or M-
OSFA
SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-60.0*
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 10 of 98
TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
W-22
Min.
15/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at min.
2-inch lap and 18-
inch o.c. at two,
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -45.0*
W-23
Min.
15/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at min.
2-inch lap and 12-
inch o.c. at two,
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -52.5
W-24
Min.
19/32-
inch
plywood
Polyglass G2 Base,
Elastobase V,
Elastobase P
(sanded-top),
Elastovent,
CertainTeed
Glasbase, Firestone
MB Base, JM Perma-
Ply 28 or GAFGLAS
#75
32 ga., 1-5/8-
inch diameter
tin caps with
11 ga. annular
ring shank
nails
8-inch o.c. at min.
4-inch lap and 8-
inch o.c. at three
(3), equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, Polytherm
G, ACFoam III, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -60.0
W-25
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap Fasteners
12-inch o.c. at min.
4-inch lap and 12-
inch o.c. at two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -60.0
W-26
Min.
15/32-
inch
plywood
Polyglass G2 Base,
Elastobase V,
Elastobase P
(sanded-top) or
Elastovent
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
8-inch o.c. at min.
4-inch lap and 8-
inch o.c. at four (4),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -67.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 11 of 98
TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
W-27
Min.
15/32-
inch
plywood
Polyglass G2 Base Simplex MAXX
Cap
9-inch o.c. at min.
4-inch lap and 9-
inch o.c. at four (4),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -82.5
W-28
Min.
15/32-
inch
plywood
Polyglass G2 Base,
Elastobase V,
Elastobase P
(sanded-top) or
Elastovent
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
6-inch o.c. at min.
4-inch lap and 6-
inch o.c. at five (5)
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -90.0
W-29
Min.
15/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
6-inch o.c. at min.
2-inch lap and 6-
inch o.c. at two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck Prime,
SECUROCK Gypsum-
Fiber Roof Board
Hot asphalt APP-
SA-H
(Optional)
APP-TA APP-TA -90.0
W-30
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
6-inch o.c. at min.
4-inch lap and 6-
inch o.c. at four (4),
equally spaced,
staggered center
rows
Min. 2-inch Polytherm,
ACFoam II, III,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3 or ENRGY-3
D-IS, OB500,
CR-20 or M-
OSFA, atop
fastener rows,
7-inch o.c.
(Optional) Additional
layers of base
insulation
D-IS,
OB500, CR-
20 or M-
OSFA
APP-
SA-H
(Optional)
APP-TA APP-TA -60.0*
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
W-31
Min.
15/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at min.
2-inch lap and 18-
inch o.c. at two,
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA-
H
(Optional)
SBS-TA SBS-TA -45.0*
W-32
Min.
15/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap
9-inch o.c. at min.
2-inch lap and 12-
inch o.c. at two,
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA-
H
(Optional)
SBS-TA SBS-TA -52.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 12 of 98
TABLE 1B: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8)
Base
Ply Ply Cap Ply
W-33
Min.
19/32-
inch
plywood
Polyglass G2 Base,
Elastobase V,
Elastobase P
(sanded-top),
Elastovent,
CertainTeed
Glasbase, Firestone
MB Base, JM Perma-
Ply 28 or GAFGLAS
#75
32 ga., 1-5/8-
inch diameter
tin caps with
11 ga. annular
ring shank
nails
8-inch o.c. at min.
4-inch lap and 8-
inch o.c. at three
(3), equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, Polytherm
G, ACFoam III, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA-
H
(Optional)
SBS-TA SBS-TA -60.0
W-34
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
Simplex MAXX
Cap Fasteners
12-inch o.c. at min.
4-inch lap and 12-
inch o.c. at two (2),
equally spaced,
staggered center
rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-3,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA-
H
(Optional)
SBS-TA SBS-TA -60.0
W-35
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
32 ga., 1-5/8-
inch diameter
tin caps with
12 ga. annular
ring shank
nails
6-inch o.c. at min.
4-inch lap and 6-
inch o.c. at four (4),
equally spaced,
staggered center
rows
Min. 2-inch Polytherm,
ACFoam II, III,
Polytherm H, H-Shield,
H-Shield CG, Multi-
Max FA3 or ENRGY-3
D-IS, OB500,
CR-20 or M-
OSFA, atop
fastener rows,
7-inch o.c.
(Optional) Additional
layers of base
insulation
D-IS,
OB500, CR-
20 or M-
OSFA
SBS-SA-
H
(Optional)
SBS-TA SBS-TA -60.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 13 of 98
TABLE 1C: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
W-36
Min.
15/32-
inch
plywood
Polyglass G2
Base,
Elastobase V,
Elastobase P
(sanded-top)
or Elastovent
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Round Metal Plate
with OMG HD, OMG Flat Bottom
Plate (Accutrac) with Roofgrip
#14 or Trufast 3” Metal Insulation
Plate with Trufast #14 HD.
10-inch o.c. at
min. 4-inch lap
and 10-inch o.c. at
three (3), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck,
DensDeck Prime,
SECUROCK
Gypsum-Fiber
Roof Board
Hot asphalt
BP-AA,
SBS-AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-52.5
W-37
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
or Elastovent
OMG Flat Bottom Plates
(square) with Roofgrip #12
12-inch o.c. at
min. 4-inch lap
and 12-inch o.c. at
two (2), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.75-inch
Fesco Board
(homogeneous)
or min. 0.5-inch
Structodek High
Density
Fiberboard Roof
Insulation
Hot asphalt BP-AA or
SBS-AA
(Optional)
BP-AA or
SBS-AA
SBS-AA,
SBS-TA,
APP-TA
-60.0
W-38
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
or Elastovent
OMG Flat Bottom Plates
(square) with Roofgrip #12
12-inch o.c. at
min. 4-inch lap
and 12-inch o.c. at
two (2), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck,
DensDeck Prime,
SECUROCK
Gypsum-Fiber
Roof Board
Hot asphalt
BP-AA,
SBS-AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-60.0
W-39
Min.
15/32-
inch
plywood
Polyglass G2
Base,
Elastobase V,
Elastobase P
(sanded-top)
or Elastovent
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Round Metal Plate
with OMG HD, OMG Flat Bottom
Plate (Accutrac) with Roofgrip
#14 or Trufast 3” Metal Insulation
Plate with Trufast #14 HD.
9-inch o.c. at min.
4-inch lap and 9-
inch o.c. at four
(4), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck,
DensDeck Prime,
SECUROCK
Gypsum-Fiber
Roof Board
Hot asphalt
BP-AA,
SBS-AA,
SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-82.5
SELF-ADHERING BASE PLY:
W-40
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
or Elastovent
OMG Flat Bottom Plates
(square) with Roofgrip #12
12-inch o.c. at
min. 4-inch lap
and 12-inch o.c. at
two (2), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck,
DensDeck Prime,
SECUROCK
Gypsum-Fiber
Roof Board
Hot asphalt SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-60.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 14 of 98
TABLE 1C: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
W-41
Min.
15/32-
inch
plywood
Polyglass G2
Base,
Elastobase V,
Elastobase P
(sanded-top)
or Elastovent
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Round Metal Plate
with OMG HD, OMG Flat Bottom
Plate (Accutrac) with Roofgrip
#14 or Trufast 3” Metal Insulation
Plate with Trufast #14 HD.
10-inch o.c. at
min. 4-inch lap
and 10-inch o.c. at
three (3), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck,
DensDeck Prime,
SECUROCK
Gypsum-Fiber
Roof Board
Hot asphalt APP-SA-H (Optional)
APP-TA APP-TA -52.5
W-42
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
or Elastovent
OMG Flat Bottom Plates
(square) with Roofgrip #12
12-inch o.c. at
min. 4-inch lap
and 12-inch o.c. at
two (2), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck,
DensDeck Prime,
SECUROCK
Gypsum-Fiber
Roof Board
Hot asphalt APP-SA-H (Optional)
APP-TA APP-TA -60.0
W-43
Min.
15/32-
inch
plywood
Polyglass G2
Base,
Elastobase V,
Elastobase P
(sanded-top)
or Elastovent
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Round Metal Plate
with OMG HD, OMG Flat Bottom
Plate (Accutrac) with Roofgrip
#14 or Trufast 3” Metal Insulation
Plate with Trufast #14 HD.
9-inch o.c. at min.
4-inch lap and 9-
inch o.c. at four
(4), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck,
DensDeck Prime,
SECUROCK
Gypsum-Fiber
Roof Board
Hot asphalt APP-SA-H (Optional)
APP-TA APP-TA -82.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
W-44
Min.
19/32-
inch
plywood
Elastobase V,
Elastobase P
(sanded-top)
or Elastovent
OMG Flat Bottom Plates
(square) with Roofgrip #12
12-inch o.c. at
min. 4-inch lap
and 12-inch o.c. at
two (2), equally
spaced, staggered
center rows
(Optional) Min. 1.5-
inch Polytherm,
ACFoam II, ENRGY-
3, Polytherm H, H-
Shield, H-Shield CG,
Multi-Max FA3
Hot asphalt
Min. 0.25-inch
DensDeck,
DensDeck Prime,
SECUROCK
Gypsum-Fiber
Roof Board
Hot asphalt SBS-SA-H (Optional)
SBS-TA SBS-TA -60.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 15 of 98
TABLE 1D: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
W-45
Min. 19/32-
inch
plywood
Min. 1.5-inch ENRGY 3,
H-Shield or Polytherm
Dekfast PLT-H-2-7/8 with Dekfast
#12 or Trufast 3” Metal Insulation
Plate with Trufast DP
1 per
1.3 ft2
Min. 0.75-inch Fesco Board
(homogeneous) or min. 0.5-inch
Structodek High Density
Fiberboard Roof Insulation
Hot asphalt
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA,
SBS-TA,
APP-TA
-60.0
W-46
Min. 15/32-
inch
plywood
Min. 2-inch Polytherm,
ACFoam II, ENRGY-3,
EnergyGuard Polyiso
Insulation, H-Shield or
Multi-Max FA3
Dekfast #14 with Dekfast PLT-H-
2-7/8, OMG #14 HD with OMG 3”
Galvalume Steel Plates or Trufast
#14 HD with Trufast 3-inch
Insulation Plates
1 per
1.0 ft2
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum Fiber Roof
Board
Hot asphalt SBS-AA, SBS-
TA, APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-75.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
W-47
Min. 15/32-
inch
plywood
Min. 2-inch Polytherm,
ACFoam II, ENRGY-3,
EnergyGuard Polyiso
Insulation, H-Shield or
Multi-Max FA3
Dekfast #14 with Dekfast PLT-H-
2-7/8, OMG #14 HD with OMG 3”
Galvalume Steel Plates or Trufast
#14 HD with Trufast 3-inch
Insulation Plates
1 per
1.0 ft2
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum Fiber Roof
Board
Hot asphalt APP-SA-H (Optional) APP-TA APP-TA -75.0
TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer
(Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
W-48
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.25-inch DensDeck Prime or
SECUROCK Gypsum-Fiber Roof
Board
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD.
1 per
2.0 ft2
BP-AA, SBS-
AA, SBS-TA,
APP-TA
(Optional) BP-
AA, SBS-AA,
SBS-TA, APP-TA
SBS-AA, SBS-
TA, APP-TA -30.0
W-49
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.25-inch DensDeck Prime or
SECUROCK Gypsum-Fiber Roof
Board
Dekfast #14 with Dekfast PLT-H-2-7/8, OMG #14
HD with OMG 3” Galvalume Steel Plates or Trufast
#14 HD with Trufast 3-inch Insulation Plates
1 per
1.8 ft2
SBS-AA, SBS-
TA, APP-TA
(Optional) SBS-
AA, SBS-TA,
APP-TA
SBS-AA, SBS-
TA, APP-TA -45.0
W-50
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.25-inch DensDeck Prime or
SECUROCK Gypsum-Fiber Roof
Board
Dekfast #14 with Dekfast PLT-H-2-7/8, OMG #14
HD with OMG 3” Galvalume Steel Plates or Trufast
#14 HD with Trufast 3-inch Insulation Plates
1 per
1.0 ft2
SBS-AA, SBS-
TA, APP-TA
(Optional) SBS-
AA, SBS-TA,
APP-TA
SBS-AA, SBS-
TA, APP-TA -75.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 16 of 98
TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer
(Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
W-51
Min. 19/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.5-inch Structodek High
Density Fiberboard Roof Insulation
or min. 0.25-inch DensDeck,
DensDeck Prime or SECUROCK
Gypsum-Fiber Roof Board
Dekfast PLT-H-2-7/8 with Dekfast #12 DP 1 per
1.3 ft2
(Optional if
using AA Ply)
BP-AA, SBS-
AA
(Optional if
using AA Base)
BP-AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA, SBS-
TA, APP-TA -82.5
SELF-ADHERING BASE PLY:
W-52
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch Polytherm, ACFoam II,
H-Shield or Polytherm
Dekfast #14 with Dekfast PLT-H-2-7/8, OMG #14
HD with OMG 3” Galvalume Steel Plates or Trufast
#14 HD with Trufast 3-inch Insulation Plates
1 per
2.7 ft2 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-30.0
W-53
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.25-inch DensDeck Prime or
SECUROCK Gypsum-Fiber Roof
Board
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD.
1 per
2.0 ft2 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-30.0
W-54
Min. 15/32-
inch
plywood
One or more layers,
any combination, min.
1-inch, loose laid
Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board optionally primed
with POLYBRITE 745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast
#14 with Dekfast PLT-H-2-7/8 or Dekfast PLT-R-3
or OMG #14 Roofgrip with OMG 3 in. Round Metal
Plate, OMG 3 in. Ribbed Galvalume Plate (Flat) or
Accutrac Flat Bottom Plate or Trufast #14 HD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
2.0 ft2 SBS-SA None SBS-SA -45.0
W-55
Min. 15/32-
inch
plywood
One or more layers,
any combination, min.
1-inch, loose laid
Min. 0.25-inch DensDeck Prime
optionally primed with POLYBRITE
745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast
#14 with Dekfast PLT-H-2-7/8 or OMG #14
Roofgrip with OMG 3 in. Round Metal Plate or
Accutrac Flat Bottom Plate or Trufast #14 HD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
2.0 ft2 SBS-SA None SBS-SA -45.0
W-56
Min. 15/32-
inch
plywood
One or more layers,
any combination, min.
1-inch, loose laid
Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board optionally primed
with POLYBRITE 745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast
DF-#14 with Dekfast PLT-H-2-7/8 or OMG #14
Roofgrip with OMG 3 in. Round Metal Plate or
Accutrac Flat Bottom Plate or Trufast #14 HD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
1.8 ft2 SBS-SA
(Optional when
using torch-
applied Cap Ply)
SBS-TA, APP-TA
SBS-SA, APP-
SA, SBS-TA or
APP-TA
-45.0
W-57
Min. 15/32-
inch
plywood
One or more layers,
any combination, min.
1-inch, loose laid
Min. 0.25-inch DensDeck Prime
optionally primed with POLYBRITE
745 or WB3000
OMG #14 Roofgrip with OMG 3 in. Round Metal
Plate or Trufast #14 HD Fasteners with Trufast 3”
Metal Insulation Plate
1 per
1.8 ft2 SBS-SA
(Optional when
using torch-
applied Cap Ply)
SBS-TA, APP-TA
SBS-SA, APP-
SA, SBS-TA or
APP-TA
-45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 17 of 98
TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer
(Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
W-58
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof Board or
SECUROCK Gypsum-Fiber Roof
Board
Dekfast #14 with Dekfast PLT-H-2-7/8, OMG #14
HD with OMG 3” Galvalume Steel Plates or Trufast
#14 HD with Trufast 3-inch Insulation Plates
1 per
1.0 ft2 SBS-SA (Optional) SBS-
TA, APP-TA
SBS-TA, APP-
TA -60.0
W-59
APA rated,
19/32 CAT,
0.578 in.,
Exposure 1
OSB or min.
19/32” APA
rated
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch ACFoam II, ACFoam III,
EnergyGuard Polyiso Insulation,
ENRGY 3, ENRGY 3 CGF, H-Shield, H-
Shield CG, ISO 95+ GL, Multi-Max
FA3, Polytherm or Ultra-Max
optionally primed with POLYBRITE
745 or WB3000
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate*
1 per
1.3 ft2 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-67.5*
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 180 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce minimum withdrawal resistance
W-60
Min. 19/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch ACFoam II, ACFoam III,
EnergyGuard Polyiso Insulation,
ENRGY 3, ENRGY 3 CGF, H-Shield, H-
Shield CG, ISO 95+ GL, Multi-Max
FA3, Polytherm or Ultra-Max
optionally primed with POLYBRITE
745 or WB3000
Dekfast PLT-H-2-7/8 or Dekfast PLT-R-3 with
Dekfast #12, OMG 3 in. Galvalume Plate (non-
ribbed) or OMG AccuTrac Plate with #12 Roofgrip
or Trufast 3” Metal Insulation Plate with Trufast
DP
1 per
1.3 ft2 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-67.5*
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
W-61
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch Polytherm, ACFoam II,
H-Shield or Polytherm
Dekfast #14 with Dekfast PLT-H-2-7/8, OMG #14
HD with OMG 3” Galvalume Steel Plates or Trufast
#14 HD with Trufast 3-inch Insulation Plates
1 per
2.7 ft2 APP-SA-H (Optional) APP-
TA APP-TA -30.0
W-62
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.25-inch DensDeck Prime or
SECUROCK Gypsum-Fiber Roof
Board
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD.
1 per
2.0 ft2 APP-SA-H (Optional) APP-
TA APP-TA -30.0
W-63
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.25-inch DensDeck Prime or
SECUROCK Gypsum-Fiber Roof
Board
Dekfast #14 with Dekfast PLT-H-2-7/8, OMG #14
HD with OMG 3” Galvalume Steel Plates or Trufast
#14 HD with Trufast 3-inch Insulation Plates
1 per
1.8 ft2 APP-SA-H (Optional) APP-
TA APP-TA -45.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 18 of 98
TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer
(Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
W-64
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch Polytherm, ACFoam II,
H-Shield or Polytherm H
Dekfast #14 with Dekfast PLT-H-2-7/8, OMG #14
HD with OMG 3” Galvalume Steel Plates or Trufast
#14 HD with Trufast 3-inch Insulation Plates
1 per
2.7 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -30.0
W-65
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.25-inch DensDeck Prime or
SECUROCK Gypsum-Fiber Roof
Board
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD.
1 per
2.0 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -30.0
W-66
Min. 15/32-
inch
plywood
One or more layers,
any combination, min.
1-inch, loose laid
Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board optionally primed
with POLYBRITE 745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast
#14 with Dekfast PLT-H-2-7/8 or Dekfast PLT-R-3
or OMG #14 Roofgrip with OMG 3 in. Round Metal
Plate, OMG 3 in. Ribbed Galvalume Plate (Flat) or
Accutrac Flat Bottom Plate or Trufast #14 HD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
2.0 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -45.0
W-67
Min. 15/32-
inch
plywood
One or more layers,
any combination, min.
1-inch, loose laid
Min. 0.25-inch DensDeck Prime
optionally primed with POLYBRITE
745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast
#14 with Dekfast PLT-H-2-7/8 or OMG #14
Roofgrip with OMG 3 in. Round Metal Plate or
Accutrac Flat Bottom Plate or Trufast #14 HD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
2.0 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -45.0
W-68
Min. 15/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof Board or
SECUROCK Gypsum-Fiber Roof
Board
Dekfast #14 with Dekfast PLT-H-2-7/8, OMG #14
HD with OMG 3” Galvalume Steel Plates or Trufast
#14 HD with Trufast 3-inch Insulation Plates
1 per
1.0 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -60.0
W-69
APA rated,
19/32 CAT,
0.578 in.,
Exposure 1
OSB or min.
19/32” APA
rated
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch ACFoam II, ACFoam III,
EnergyGuard Polyiso Insulation,
ENRGY 3, ENRGY 3 CGF, H-Shield, H-
Shield CG, ISO 95+ GL, Multi-Max
FA3, Polytherm or Ultra-Max
optionally primed with POLYBRITE
745 or WB3000
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate*
1 per
1.3 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -67.5*
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 180 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized to
produce minimum withdrawal resistance
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 19 of 98
TABLE 1E: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer
(Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
W-70
Min. 19/32-
inch
plywood
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch ACFoam II, ACFoam III,
EnergyGuard Polyiso Insulation,
ENRGY 3, ENRGY 3 CGF, H-Shield, H-
Shield CG, ISO 95+ GL, Multi-Max
FA3, Polytherm or Ultra-Max
optionally primed with POLYBRITE
745 or WB3000
Dekfast PLT-H-2-7/8 or Dekfast PLT-R-3 with
Dekfast #12, OMG 3 in. Galvalume Plate (non-
ribbed) or OMG AccuTrac Plate with #12 Roofgrip
or Trufast 3” Metal Insulation Plate with Trufast
DP
1 per
1.3 ft2 SBS-SA-H (Optional) SBS-
TA SBS-TA -67.5*
TABLE 1F: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
W-71 Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P,
Elastovent,
Polyglass G2 Base,
CertainTeed
Glasbase, Firestone
MB Base, JM Perma-
Ply 28 or GAFGLAS
#75
OMG Flat Bottom Plates (square) with Roofgrip
#14, Dekfast PLT-H-2-7/8 with Dekfast #14 or
Trufast 3” Metal Insulation Plate with Trufast
#14 HD
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
(Optional) BP-
AA, SBS-AA, SBS-
TA or APP-TA
SBS-AA, SBS-
TA, APP-TA -52.5
W-72 Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P or
Elastovent
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
(Optional) BP-
AA, SBS-AA, SBS-
TA or APP-TA
SBS-AA, SBS-
TA, APP-TA -60.0
W-73
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
One or more
layers, any
combination
Loose-laid
Elastobase V,
Elastobase P or
Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-
SA, SBS-AA,
SBS-TA, APP-
TA
-67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized
to produce minimum withdrawal resistance
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 20 of 98
TABLE 1F: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
W-74
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
One or more
layers, any
combination
Loose-laid Polybase V
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
APP-TA APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized
to produce minimum withdrawal resistance
W-75 Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Polyglass G2 Base,
Elastobase V,
Elastobase P or
Elastovent
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast
#14 HD.
10-inch o.c. at min. 4-inch lap and
10-inch o.c. at three (3), equally
spaced, staggered center rows
(Optional) BP-
AA, SBS-AA, SBS-
TA or APP-TA
SBS-AA, SBS-
TA, APP-TA -75.0
W-76 Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached Polybase V
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast
#14 HD.
10-inch o.c. at min. 4-inch lap and
10-inch o.c. at three (3), equally
spaced, staggered center rows
(Optional) APP-
TA APP-TA -75.0
W-77
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB or
min. 15/32” APA
rated plywood
One or more
layers, any
combination
Loose-laid
Elastobase V,
Elastobase P or
Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
9-inch o.c. at min. 2-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-
SA, SBS-AA,
SBS-TA, APP-
TA
-90.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized
to produce minimum withdrawal resistance
W-78
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB or
min. 15/32” APA
rated plywood
One or more
layers, any
combination
Loose-laid Polybase V
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
9-inch o.c. at min. 2-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
APP-TA APP-TA -90.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized
to produce minimum withdrawal resistance
W-79 Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Polyglass G2 Base,
Elastobase V,
Elastobase P or
Elastovent
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast
#14 HD.
9-inch o.c. at min. 4-inch lap and
9-inch o.c. at four (4), equally
spaced, staggered center rows
(Optional) BP-
AA, SBS-AA, SBS-
TA or APP-TA
SBS-AA, SBS-
TA, APP-TA -90.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 21 of 98
TABLE 1F: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
W-80 Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached Polybase V
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast
#14 HD.
9-inch o.c. at min. 4-inch lap and
9-inch o.c. at four (4), equally
spaced, staggered center rows
(Optional) APP-
TA APP-TA -90.0
W-81 Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P or
Elastovent
Trufast #12 DP or Trufast #14 HD with Trufast 3”
Metal Insulation Plates
6-inch o.c. at min. 4-inch lap and
6-inch o.c. at three (3), equally
spaced, staggered center rows
(Optional) BP-AA
or SBS-AA SBS-AA -90.0
W-82 Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P or
Elastovent
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at min. 4-inch lap and
6-inch o.c. at three (3), equally
spaced, staggered center rows
(Optional) BP-
AA, SBS-AA, SBS-
TA, APP-TA
SBS-AA, SBS-
TA or APP-TA -90.0
W-83 Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached Polybase V
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at min. 4-inch lap and
6-inch o.c. at three (3), equally
spaced, staggered center rows
(Optional) APP-
TA APP-TA -90.0
W-84
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB or
min. 15/32” APA
rated plywood
One or more
layers, any
combination
Loose-laid
Elastobase V,
Elastobase P or
Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
6-inch o.c. at min. 4-inch lap and
6-inch o.c. at three (3), equally
spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-
SA, SBS-AA,
SBS-TA, APP-
TA
-105.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized
to produce minimum withdrawal resistance
W-85
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB or
min. 15/32” APA
rated plywood
One or more
layers, any
combination
Loose-laid Polybase V
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
6-inch o.c. at min. 4-inch lap and
6-inch o.c. at three (3), equally
spaced, staggered center rows
APP-TA APP-TA -105.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized
to produce minimum withdrawal resistance
W-86 Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P or
Elastovent
Trufast #12 DP or Trufast #14 HD with Trufast 3”
Metal Insulation Plates
6-inch o.c. at min. 4-inch lap and
6-inch o.c. at five (5), equally
spaced, staggered center rows
(Optional) BP-AA
or SBS-AA SBS-AA -120.0
W-87 Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P or
Elastovent
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at min. 4-inch lap and
6-inch o.c. at five (5), equally
spaced, staggered center rows
(Optional) BP-
AA, SBS-AA, SBS-
TA, APP-TA
SBS-AA, SBS-
TA or APP-TA -120.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 22 of 98
TABLE 1F: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
W-88 Min. 15/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached Polybase V
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at min. 4-inch lap and
6-inch o.c. at five (5), equally
spaced, staggered center rows
(Optional) APP-
TA APP-TA -120.0
SELF-ADHERING BASE PLY:
W-89 Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P (poly-
film top)
Dekfast PLT-H-2-7/8 with Dekfast #14 or Trufast
3” Metal Insulation Plate with Trufast #14 HD
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center rows
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-52.5*
W-90 Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P (poly-
film top)
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center rows
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-60.0*
W-91
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
One or more
layers, any
combination
Loose-laid
Elastobase V,
Elastobase P (poly-
film top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
SBS-SA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized
to produce minimum withdrawal resistance
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
W-92 Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P (poly-
film top)
Dekfast PLT-H-2-7/8 with Dekfast #14 or Trufast
3” Metal Insulation Plate with Trufast #14 HD
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center rows
APP-SA-H APP-TA -52.5*
W-93 Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P (poly-
film top)
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center rows
APP-SA-H APP-TA -60.0*
W-94
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
One or more
layers, any
combination
Loose-laid
Elastobase V,
Elastobase P (poly-
film top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
APP-SA-H APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized
to produce minimum withdrawal resistance
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
W-95 Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P (poly-
film top)
Dekfast PLT-H-2-7/8 with Dekfast #14 or Trufast
3” Metal Insulation Plate with Trufast #14 HD
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center rows
SBS-SA-H SBS-TA -52.5*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 23 of 98
TABLE 1F: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
W-96 Min. 19/32-inch
plywood
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P (poly-
film top)
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two, equally
spaced, staggered center rows
SBS-SA-H SBS-TA -60.0*
W-97
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
One or more
layers, any
combination
Loose-laid
Elastobase V,
Elastobase P (poly-
film top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and
12-inch o.c. at two (2), equally
spaced, staggered center rows
SBS-SA-H SBS-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be utilized
to produce minimum withdrawal resistance
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
NO BASE PLY:
W-98 Min. 15/32-inch
plywood Elastobase V, Elastobase P Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 18-inch o.c. at
two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -45.0*
W-99
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB
Elastobase V, Elastobase P
or Elastovent
32 ga., 1-5/8-inch diameter tin caps with 12 ga.
annular ring shank nails
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -45.0
W-100
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 12 ga.
annular ring shank nails
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows None SBS-SA, APP-SA -45.0
W-101
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB
Polybase V 32 ga., 1-5/8-inch diameter tin caps with 12 ga.
annular ring shank nails
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows None APP-TA -45.0
W-102 Min. 15/32-inch
plywood Elastobase V, Elastobase P Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 12-inch o.c. at
two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -52.5
W-103 Min. 15/32-inch
plywood
Elastobase V, Elastobase P
or Elastovent
Original Simplex Cap Nails (1-inch metal head
diameter, 11 gauge x min. 1.25-inch long annular
grooved shank)
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -52.5
W-104 Min. 15/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
Original Simplex Cap Nails (1-inch metal head
diameter, 11 gauge x min. 1.25-inch long annular
grooved shank)
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows None SBS-SA, APP-SA -52.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 24 of 98
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
W-105 Min. 15/32-inch
plywood Polybase V
Original Simplex Cap Nails (1-inch metal head
diameter, 11 gauge x min. 1.25-inch long annular
grooved shank)
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows None APP-TA -52.5
W-106
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB or
min. 15/32” APA
rated plywood
Elastobase V (sanded top) Simplex MAXX Cap
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
None SBS-AA, SBS-TA,
APP-TA -60.0
W-107
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB or
min. 15/32” APA
rated plywood
Elastobase V (poly-film
top) Simplex MAXX Cap
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
None SBS-TA, APP-TA -60.0
W-108
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB or
min. 15/32” APA
rated plywood
Polybase V Simplex MAXX Cap
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
None APP-TA -60.0
W-109
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB or
min. 15/32” APA
rated plywood
Elastobase V (poly-film
top)
Simplex MAXX Cap
Note: MAXX Caps are to be primed with PG100
or ASTM D41 primer
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
None SBS-SA, APP-SA -60.0
W-110 Min. 19/32-inch
plywood
Elastobase V, Elastobase P,
Elastovent, Polyglass G2
Base, CertainTeed
Glasbase, Firestone MB
Base, JM Perma-Ply 28 or
GAFGLAS #75
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails
8-inch o.c. at min. 4-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
None SBS-AA, SBS-TA,
APP-TA -60.0
W-111 Min. 19/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails
8-inch o.c. at min. 4-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
None SBS-SA, APP-SA -60.0
W-112 Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase V, Elastobase P
or Elastovent
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails
8-inch o.c. at min. 4-inch lap and 8-inch o.c. at
four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -67.5
W-113 Min. 15/32-inch
plywood Polybase V 32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails
8-inch o.c. at min. 4-inch lap and 8-inch o.c. at
four (4), equally spaced, staggered center rows None APP-TA -67.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 25 of 98
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
W-114 Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase V, Elastobase P Simplex MAXX Cap
10-inch o.c. at min. 4-inch lap and 10-inch o.c.
at three (3), equally spaced, staggered center
rows
None SBS-AA, SBS-TA,
APP-TA -75.0
W-115 Min. 15/32-inch
plywood Polybase V Simplex MAXX Cap
10-inch o.c. at min. 4-inch lap and 10-inch o.c.
at three (3), equally spaced, staggered center
rows
None APP-TA -75.0
W-116 Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase V, Elastobase P Simplex MAXX Cap 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at
four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -90.0
W-117 Min. 15/32-inch
plywood Polybase V Simplex MAXX Cap 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at
four (4), equally spaced, staggered center rows None APP-TA -90.0
W-118 Min. 15/32-inch
plywood Elastobase V, Elastobase P Simplex MAXX Cap 6-inch o.c. at min. 2-inch lap and 6-inch o.c. at
two (2), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -90.0
W-119 Min. 19/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails.
4-inch o.c. at min. 4-inch lap and 4-inch o.c. at
four (4), equally spaced, staggered center rows None SBS-SA, APP-SA -97.5
W-120 Min. 15/32-inch
plywood Elastobase V, Elastobase P Simplex MAXX Cap
6-inch o.c. at min. 2-inch lap and 6-inch o.c. at
three (3), equally spaced, staggered center
rows
None SBS-AA, SBS-TA,
APP-TA -105.0
W-121 Min. 19/32-inch
plywood
Elastobase V, Elastobase P
or Elastovent
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails
6-inch o.c. at min. 4-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows None SBS-AA, SBS-TA,
APP-TA -112.5
W-122 Min. 19/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails. Note: Tin caps are to be
primed with PG100 or ASTM D41 primer.
6-inch o.c. at min. 4-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows None SBS-SA, APP-SA -112.5
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
W-123 Min. 15/32-inch
plywood Elastobase V, Elastobase P Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 18-inch o.c. at
two (2), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-45.0*
W-124
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB
Elastobase V, Elastobase P
or Elastovent
32 ga., 1-5/8-inch diameter tin caps with 12 ga.
annular ring shank nails
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-45.0
W-125
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB
Polybase V 32 ga., 1-5/8-inch diameter tin caps with 12 ga.
annular ring shank nails
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows APP-TA APP-TA -45.0
W-126 Min. 15/32-inch
plywood Elastobase V, Elastobase P Simplex MAXX Cap 9-inch o.c. at min. 2-inch lap and 12-inch o.c. at
two (2), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-52.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 26 of 98
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
W-127 Min. 15/32-inch
plywood
Elastobase V, Elastobase P
or Elastovent
Original Simplex Cap Nails (1-inch metal head
diameter, 11 gauge x min. 1.25-inch long annular
grooved shank)
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-52.5
W-128 Min. 15/32-inch
plywood Polybase V
Original Simplex Cap Nails (1-inch metal head
diameter, 11 gauge x min. 1.25-inch long annular
grooved shank)
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows APP-TA APP-TA -52.5
W-129
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB or
min. 15/32” APA
rated plywood
Elastobase V (sanded top) Simplex MAXX Cap
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-AA, SBS-TA,
APP-TA -60.0
W-130
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB or
min. 15/32” APA
rated plywood
Elastobase V (poly-film
top) Simplex MAXX Cap
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
SBS-TA SBS-TA, APP-TA -60.0
W-131
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB or
min. 15/32” APA
rated plywood
Polybase V Simplex MAXX Cap
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
APP-TA APP-TA -60.0
W-132 Min. 19/32-inch
plywood
Elastobase V, Elastobase P,
Elastovent, Polyglass G2 Base,
CertainTeed Glasbase,
Firestone MB Base, JM Perma-
Ply 28 or GAFGLAS #75
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails
8-inch o.c. at min. 4-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-60.0
W-133 Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase V, Elastobase P
or Elastovent
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails
8-inch o.c. at min. 4-inch lap and 8-inch o.c. at
four (4), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-67.5
W-134 Min. 15/32-inch
plywood Polybase V 32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails
8-inch o.c. at min. 4-inch lap and 8-inch o.c. at
four (4), equally spaced, staggered center rows APP-TA APP-TA -67.5
W-135 Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase V, Elastobase P Simplex MAXX Cap
10-inch o.c. at min. 4-inch lap and 10-inch o.c.
at three (3), equally spaced, staggered center
rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-75.0
W-136 Min. 15/32-inch
plywood Polybase V Simplex MAXX Cap
10-inch o.c. at min. 4-inch lap and 10-inch o.c.
at three (3), equally spaced, staggered center
rows
APP-TA APP-TA -75.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 27 of 98
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
W-137 Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase V, Elastobase P Simplex MAXX Cap 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at
four (4), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-90.0
W-138 Min. 15/32-inch
plywood Polybase V Simplex MAXX Cap 9-inch o.c. at min. 4-inch lap and 9-inch o.c. at
four (4), equally spaced, staggered center rows APP-TA APP-TA -90.0
W-139 Min. 15/32-inch
plywood Elastobase V, Elastobase P Simplex MAXX Cap 6-inch o.c. at min. 2-inch lap and 6-inch o.c. at
two (2), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-90.0
W-140 Min. 15/32-inch
plywood Elastobase V, Elastobase P Simplex MAXX Cap
6-inch o.c. at min. 2-inch lap and 6-inch o.c. at
three (3), equally spaced, staggered center
rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-105.0
W-141 Min. 19/32-inch
plywood
Elastobase V, Elastobase P
or Elastovent
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails
6-inch o.c. at min. 4-inch lap and 6-inch o.c. at
four (3), equally spaced, staggered center rows
BP-AA, SBS-AA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-112.5
SELF-ADHERING BASE PLY:
W-142
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 12 ga.
annular ring shank nails
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -45.0
W-143 Min. 15/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
Original Simplex Cap Nails (1-inch metal head
diameter, 11 gauge x min. 1.25-inch long annular
grooved shank)
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -52.5
W-144
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB or
min. 15/32” APA
rated plywood
Elastobase V (poly-film
top)
Simplex MAXX Cap
Note: MAXX Caps are to be primed with PG100
or ASTM D41 primer
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -60.0
W-145 Min. 19/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails
8-inch o.c. at min. 4-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -60.0
W-146 Min. 19/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails.
4-inch o.c. at min. 4-inch lap and 4-inch o.c. at
four (4), equally spaced, staggered center rows SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -97.5
W-147 Min. 19/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails. Note: Tin caps are to be
primed with PG100 or ASTM D41 primer.
6-inch o.c. at min. 4-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows
Elastoflex SA V
Plus, Elastoflex SA
V Plus FR
SBS-SA, APP-SA,
SBS-TA, APP-TA -112.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 28 of 98
TABLE 1G: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (NAILS), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
W-148 Min. 15/32-inch
plywood
Polybase V, Elastobase V,
Elastobase P (poly-film
top)
Original Simplex Cap Nails (1-inch metal head
diameter, 11 gauge x min. 1.25-inch long annular
grooved shank)
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows APP-SA-H APP-TA -52.5
W-149 Min. 19/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails
8-inch o.c. at min. 4-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
APP-SA-H APP-TA -60.0
W-150 Min. 19/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails.
4-inch o.c. at min. 4-inch lap and 4-inch o.c. at
four (4), equally spaced, staggered center rows APP-SA-H APP-TA -97.5
W-151 Min. 19/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails. Note: Tin caps are to be
primed with PG100 or ASTM D41 primer.
6-inch o.c. at min. 4-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows APP-SA-H APP-TA -112.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
W-152
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 12 ga.
annular ring shank nails
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows SBS-SA-H SBS-TA -45.0
W-153 Min. 15/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
Original Simplex Cap Nails (1-inch metal head
diameter, 11 gauge x min. 1.25-inch long annular
grooved shank)
6-inch o.c. at min. 3-inch lap and 6-inch o.c. at
four (4), equally spaced, staggered center rows SBS-SA-H SBS-TA -52.5
W-154
APA rated, 7/16
CAT, 0.418 in.,
Exposure 1 OSB or
min. 15/32” APA
rated plywood
Elastobase V (poly-film
top)
Simplex MAXX Cap
Note: MAXX Caps are to be primed with PG100
or ASTM D41 primer
8-inch o.c. at min. 3-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
SBS-SA-H SBS-TA -60.0
W-155 Min. 19/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails
8-inch o.c. at min. 4-inch lap and 8-inch o.c. at
three (3), equally spaced, staggered center
rows
SBS-SA-H SBS-TA -60.0
W-156 Min. 19/32-inch
plywood
Elastobase V, Elastobase P
(poly-film top)
32 ga., 1-5/8-inch diameter tin caps with 11 ga.
annular ring shank nails.
4-inch o.c. at min. 4-inch lap and 4-inch o.c. at
four (4), equally spaced, staggered center rows SBS-SA-H SBS-TA -97.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 29 of 98
TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
NO BASE PLY:
W-157 Min. 19/32-inch
plywood
Elastobase V, Elastobase
P, Elastovent, Polyglass
G2 Base, CertainTeed
Glasbase, Firestone MB
Base, JM Perma-Ply 28 or
GAFGLAS #75
OMG Flat Bottom Plates (square) with Roofgrip
#14, Dekfast PLT-H-2-7/8 with Dekfast #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
None SBS-AA, SBS-TA,
APP-TA -52.5
W-158 Min. 19/32-inch
plywood
Elastobase V, Elastobase
P or Elastovent
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
None SBS-AA, SBS-TA,
APP-TA -60.0
W-159
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
Elastobase V, Elastobase
P or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
None SBS-AA, SBS-TA,
APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-160
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
Elastobase V, Elastobase
P (poly-film top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
None SBS-SA, APP-SA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-161
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
Polybase V
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
None APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-162 Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase V, Elastobase
P or Elastovent
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD.
10-inch o.c. at min. 4-inch lap and 10-inch
o.c. at three (3), equally spaced, staggered
center rows
None SBS-AA, SBS-TA,
APP-TA -75.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 30 of 98
TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
W-163 Min. 15/32-inch
plywood Polybase V
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD.
10-inch o.c. at min. 4-inch lap and 10-inch
o.c. at three (3), equally spaced, staggered
center rows
None APP-TA -75.0
W-164
APA rated, 7/16 CAT,
0.418 in., Exposure 1
OSB or min. 15/32”
APA rated plywood
Elastobase V, Elastobase
P or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
9-inch o.c. at min. 2-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
None SBS-AA, SBS-TA,
APP-TA -90.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-165
APA rated, 7/16 CAT,
0.418 in., Exposure 1
OSB or min. 15/32”
APA rated plywood
Polybase V
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
9-inch o.c. at min. 2-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
None APP-TA -90.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-166 Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase V, Elastobase
P or Elastovent
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD.
9-inch o.c. at min. 4-inch lap and 9-inch o.c.
at four (4), equally spaced, staggered center
rows
None SBS-AA, SBS-TA,
APP-TA -90.0
W-167 Min. 15/32-inch
plywood Polybase V
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD.
9-inch o.c. at min. 4-inch lap and 9-inch o.c.
at four (4), equally spaced, staggered center
rows
None APP-TA -90.0
W-168 Min. 15/32-inch
plywood
Elastobase V, Elastobase
P or Elastovent
Trufast #12 DP or Trufast #14 HD with Trufast 3”
Metal Insulation Plates
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at three (3), equally spaced, staggered center
rows
None SBS-AA -90.0
W-169 Min. 15/32-inch
plywood
Elastobase V, Elastobase
P or Elastovent
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at three (3), equally spaced, staggered center
rows
None SBS-AA, SBS-TA or
APP-TA -90.0
W-170 Min. 15/32-inch
plywood Polybase V
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at three (3), equally spaced, staggered center
rows
None APP-TA -90.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 31 of 98
TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
W-171
APA rated, 7/16 CAT,
0.418 in., Exposure 1
OSB or min. 15/32”
APA rated plywood
Elastobase V, Elastobase
P or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at three (3), equally spaced, staggered center
rows
None SBS-AA, SBS-TA,
APP-TA -105.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-172
APA rated, 7/16 CAT,
0.418 in., Exposure 1
OSB or min. 15/32”
APA rated plywood
Polybase V
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at three (3), equally spaced, staggered center
rows
None APP-TA -105.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-173 Min. 15/32-inch
plywood
Elastobase V, Elastobase
P or Elastovent
Trufast #12 DP or Trufast #14 HD with Trufast 3”
Metal Insulation Plates
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at five (5), equally spaced, staggered center
rows
None SBS-AA -120.0
W-174 Min. 15/32-inch
plywood
Elastobase V, Elastobase
P or Elastovent
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at five (5), equally spaced, staggered center
rows
None SBS-AA, SBS-TA or
APP-TA -120.0
W-175 Min. 15/32-inch
plywood Polybase V
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at five (5), equally spaced, staggered center
rows
None APP-TA -120.0
ASPHALT-APPLIED OR TORCH-APPLIED BASE PLY:
W-176 Min. 19/32-inch
plywood
Elastobase V, Elastobase
P, Elastovent, Polyglass
G2 Base, CertainTeed
Glasbase, Firestone MB
Base, JM Perma-Ply 28 or
GAFGLAS #75
OMG Flat Bottom Plates (square) with Roofgrip
#14, Dekfast PLT-H-2-7/8 with Dekfast #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-52.5
W-177 Min. 19/32-inch
plywood
Elastobase V, Elastobase
P or Elastovent
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-60.0
W-178
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
Elastobase V, Elastobase
P or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-67.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 32 of 98
TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-179
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
Polybase V
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
APP-TA APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-180 Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase V, Elastobase
P or Elastovent
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD.
10-inch o.c. at min. 4-inch lap and 10-inch
o.c. at three (3), equally spaced, staggered
center rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-75.0
W-181 Min. 15/32-inch
plywood Polybase V
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD.
10-inch o.c. at min. 4-inch lap and 10-inch
o.c. at three (3), equally spaced, staggered
center rows
APP-TA APP-TA -75.0
W-182
APA rated, 7/16 CAT,
0.418 in., Exposure 1
OSB or min. 15/32”
APA rated plywood
Elastobase V, Elastobase
P or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
9-inch o.c. at min. 2-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-90.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-183
APA rated, 7/16 CAT,
0.418 in., Exposure 1
OSB or min. 15/32”
APA rated plywood
Polybase V
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
9-inch o.c. at min. 2-inch lap and 12-inch o.c.
at two (2), equally spaced, staggered center
rows
APP-TA APP-TA -90.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 159 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-184 Min. 15/32-inch
plywood
Polyglass G2 Base,
Elastobase V, Elastobase
P or Elastovent
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD.
9-inch o.c. at min. 4-inch lap and 9-inch o.c.
at four (4), equally spaced, staggered center
rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-90.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 33 of 98
TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
W-185 Min. 15/32-inch
plywood Polybase V
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3”
Round Metal Plate with OMG HD, OMG Flat
Bottom Plate (Accutrac) with Roofgrip #14 or
Trufast 3” Metal Insulation Plate with Trufast #14
HD.
9-inch o.c. at min. 4-inch lap and 9-inch o.c.
at four (4), equally spaced, staggered center
rows
APP-TA APP-TA -90.0
W-186 Min. 15/32-inch
plywood
Elastobase V, Elastobase
P or Elastovent
Trufast #12 DP or Trufast #14 HD with Trufast 3”
Metal Insulation Plates
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at three (3), equally spaced, staggered center
rows
BP-AA or SBS-AA SBS-AA -90.0
W-187 Min. 15/32-inch
plywood
Elastobase V, Elastobase
P or Elastovent
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty (min. 1-5/8-inch long) with OMG 3” Round
Metal Plates or OMG Flat Bottom Metal Plates
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at three (3), equally spaced, staggered center
rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-90.0
W-188 Min. 15/32-inch
plywood Polybase V
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at three (3), equally spaced, staggered center
rows
APP-TA APP-TA -90.0
W-189
APA rated, 7/16 CAT,
0.418 in., Exposure 1
OSB or min. 15/32”
APA rated plywood
Elastobase V, Elastobase
P or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at three (3), equally spaced, staggered center
rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-105.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-190
APA rated, 7/16 CAT,
0.418 in., Exposure 1
OSB or min. 15/32”
APA rated plywood
Polybase V
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at three (3), equally spaced, staggered center
rows
APP-TA APP-TA -105.0
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 103 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-191 Min. 15/32-inch
plywood
Elastobase V, Elastobase
P or Elastovent
Trufast #12 DP or Trufast #14 HD with Trufast 3”
Metal Insulation Plates
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at five (5), equally spaced, staggered center
rows
BP-AA or SBS-AA SBS-AA -120.0
W-192 Min. 15/32-inch
plywood
Elastobase V, Elastobase
P or Elastovent
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at five (5), equally spaced, staggered center
rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-AA, SBS-TA,
APP-TA
-120.0
W-193 Min. 15/32-inch
plywood Polybase V
OMG #12 Standard Roofgrip or OMG #14 Heavy
Duty with OMG 3” Round Metal Plates or OMG
Flat Bottom Metal Plates
6-inch o.c. at min. 4-inch lap and 6-inch o.c.
at five (5), equally spaced, staggered center
rows
APP-TA APP-TA -120.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 34 of 98
TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
W-194
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
Elastobase V (sanded
top) or Elastovent
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 1 screws per plate in center hole*
9-inch o.c. at min. 4-inch lap and 9-inch o.c.
at four (4), equally spaced center rows
BP-AA, SBS-AA, SBS-
TA, APP-TA
SBS-AA, SBS-TA,
APP-TA -127.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-195
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
Elastobase V (poly-film
top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 1 screws per plate in center hole*
9-inch o.c. at min. 4-inch lap and 9-inch o.c.
at four (4), equally spaced center rows SBS-TA SBS-TA, APP-TA -127.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
W-196
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
Polybase V Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 1 screws per plate in center hole*
9-inch o.c. at min. 4-inch lap and 9-inch o.c.
at four (4), equally spaced center rows APP-TA APP-TA -127.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
SELF-ADHERING BASE PLY:
W-197 Min. 19/32-inch
plywood
Elastobase V, Elastobase
P (poly-film top)
Dekfast PLT-H-2-7/8 with Dekfast #14 or Trufast
3” Metal Insulation Plate with Trufast #14 HD
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -52.5*
W-198 Min. 19/32-inch
plywood
Elastobase V, Elastobase
P (poly-film top)
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -60.0*
W-199
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
Elastobase V, Elastobase
P (poly-film top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 35 of 98
TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
W-200
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
Elastobase V (poly-film
top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 1 screws per plate in center hole*
Note: Versa-Fast Plates shall be primed with
PG100 or ASTM D41 primer.
9-inch o.c. at min. 4-inch lap and 9-inch o.c.
at four (4), equally spaced center rows SBS-SA SBS-SA, APP-SA,
SBS-TA, APP-TA -127.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
W-201 Min. 19/32-inch
plywood
Elastobase V, Elastobase
P (poly-film top)
Dekfast PLT-H-2-7/8 with Dekfast #14 or Trufast
3” Metal Insulation Plate with Trufast #14 HD
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
APP-SA-H APP-TA -52.5*
W-202 Min. 19/32-inch
plywood
Elastobase V, Elastobase
P (poly-film top)
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
APP-SA-H APP-TA -60.0*
W-203
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
Elastobase V, Elastobase
P (poly-film top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
APP-SA-H APP-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
W-204 Min. 19/32-inch
plywood
Elastobase V, Elastobase
P (poly-film top)
Dekfast PLT-H-2-7/8 with Dekfast #14 or Trufast
3” Metal Insulation Plate with Trufast #14 HD
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
SBS-SA-H SBS-TA -52.5*
W-205 Min. 19/32-inch
plywood
Elastobase V, Elastobase
P (poly-film top)
OMG Flat Bottom Plates (square) with Roofgrip
#12
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
SBS-SA-H SBS-TA -60.0*
W-206
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
Elastobase V, Elastobase
P (poly-film top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 2 screws per plate installed 180° into the
holes of the plate, parallel to the width-direction
of the sheet*
12-inch o.c. at min. 4-inch lap and 12-inch
o.c. at two (2), equally spaced, staggered
center rows
SBS-SA-H SBS-TA -67.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 199 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 36 of 98
TABLE 1H: WOOD DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET (SCREWS & PLATES), BONDED ROOF COVER
System
No. Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap
W-207
APA rated, 19/32
CAT, 0.578 in.,
Exposure 1 OSB or
min. 19/32” APA
rated plywood
Elastobase V (poly-film
top)
Trufast Versa Fasteners (min. ¾” penetration) &
Plates; 1 screws per plate in center hole*
Note: Versa-Fast Plates shall be primed with
PG100 or ASTM D41 primer.
9-inch o.c. at min. 4-inch lap and 9-inch o.c.
at four (4), equally spaced center rows SBS-SA-H SBS-TA -127.5
Note: *For re-roof or recover construction, field withdrawal resistance testing (Note 11) shall yield minimum 141 lbf. Additional Versa-Fast Fasteners within each Versa-Fast Plate may be
utilized to produce minimum withdrawal resistance
TABLE 1I: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE F: NON-INSULATED, BONDED ROOF COVER
System
No. Deck (Note 1) Primer Roof Cover (Note 15) MDP (psf) Joint Treatment Base Ply Ply Cap Ply
SELF-ADHERING BASE PLY:
W-208
APA rated,
7/16 CAT,
0.418 in.,
Exposure 1 OSB
None OSB joints are covered with 4-inch wide strips of Elastoflex SA V, rolled into
place to create continuous bond.
Elastoflex SA V Plus
or Elastoflex SA V
Plus FR
(Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -52.5
W-209 Min. 15/32-
inch plywood None None SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -90.0
W-210 Min. 15/32-
inch plywood PG100 None SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -97.5
W-211 Min. 15/32-
inch plywood (Optional) PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled
into place to create continuous bond.
Elastoflex SA V or
Elastoflex SA V FR
(Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -97.5
W-212 Min. 15/32-
inch plywood
POLYBRITE 745
or WB3000 None SBS-SA (Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -105.0
W-213 Min. 15/32-
inch plywood (Optional) PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled
into place to create continuous bond.
Elastoflex SA V Plus
or Elastoflex SA V
Plus FR
(Optional) SBS-SA, SBS-
TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -135.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
W-214 Min. 15/32-
inch plywood (Optional) PG100 None APP-SA-H (Optional) APP-TA APP-TA -90.0
W-215 Min. 15/32-
inch plywood (Optional) PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled
into place to create continuous bond. APP-SA-H (Optional) APP-TA APP-TA -135.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 37 of 98
TABLE 1I: WOOD DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE F: NON-INSULATED, BONDED ROOF COVER
System
No. Deck (Note 1) Primer Roof Cover (Note 15) MDP (psf) Joint Treatment Base Ply Ply Cap Ply
W-216 Min. 15/32-
inch plywood None None SBS-SA-H (Optional) SBS-TA SBS-TA -90.0
W-217 Min. 15/32-
inch plywood PG100 None SBS-SA-H (Optional) SBS-TA SBS-TA -97.5
W-218 Min. 15/32-
inch plywood (Optional) PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled
into place to create continuous bond. SBS-SA-H (Optional) SBS-TA SBS-TA -97.5
W-219 Min. 15/32-
inch plywood
POLYBRITE 745
or WB3000 None SBS-SA-H (Optional) SBS-TA SBS-TA -105.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 38 of 98
TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT- OR TORCH-APPLIED BASE PLY:
S-1.
Min. 22 ga., type
B, Grade 33 steel
or min. 2,500 psi
structural
concrete
Min. 1.5-inch Polytherm,
ACFoam II, ENRGY 3, H-
Shield or Polytherm
Dekfast PLT-H-2-7/8 with Dekfast
#14, Trufast 3” Metal Insulation
Plate with Trufast #14 HD or OMG
3-inch Galv Plate with OMD HD
1 per
2.0 ft2
Min. 0.75-inch Fesco Board
(homogeneous) or min. 0.5-inch
Structodek High Density
Fiberboard Roof Insulation
Hot asphalt
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
S-2.
Min. 22 ga., type
B, Grade 33 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3, H-
Shield or Polytherm
Dekfast PLT-H-2-7/8 with Dekfast
#14, Trufast 3” Metal Insulation
Plate with Trufast #14 HD or OMG
3-inch Galv Plate with OMD HD
1 per
4.0 ft2
Min. 0.75-inch Fesco Board
(homogeneous) or min. 0.5-inch
Structodek High Density
Fiberboard Roof Insulation
Hot asphalt
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
S-3.
Min. 22 ga., type
B, Grade 33 steel
or min. 2,500 psi
structural
concrete
Min. 1.5-inch ENRGY 3,
H-Shield or Polytherm
Dekfast PLT-H-2-7/8 with Dekfast
#14 or Trufast 3” Metal Insulation
Plate with Trufast #14 HD
1 per
1.3 ft2
Min. 0.75-inch Fesco Board
(homogeneous) or min. 0.5-inch
Structodek High Density
Fiberboard Roof Insulation
Hot asphalt
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-90.0
S-4.
Min. 22 ga., type
B, Grade 33 steel
or min. 2,500 psi
structural
concrete
Min. 1.5-inch ENRGY 3,
H-Shield or Polytherm
Dekfast PLT-H-2-7/8 with Dekfast
#14 or Trufast 3” Metal Insulation
Plate with Trufast #14 HD
1 per
1.3 ft2
Min. 0.75-inch Fesco Board
(homogeneous) or min. 0.5-inch
Structodek High Density
Fiberboard Roof Insulation
Hot asphalt
BP-AA, SBS-
AA (Top
surface
primed
with PG100
primer)
SBS-SA, SBS-TA or
APP-TA
SBS-SA,
APP-SA,
SBS-TA or
APP-TA
-90.0
S-5.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
4.0 ft2
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof
Board or SECUROCK Gypsum-
Fiber Roof Board
D-IS
SBS-AA,
SBS-TA,
APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-30.0*
S-6.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof
Board or SECUROCK Gypsum-
Fiber Roof Board
D-IS
SBS-AA,
SBS-TA,
APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 39 of 98
TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
S-7.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
4.0 ft2
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof
Board, SECUROCK Gypsum-
Fiber Roof Board or SECUROCK
Glass-Mat Roof Board, min.
7/16-inch DEXcell Cement Roof
Board or min. 0.5-inch
SECUROCK Cement Roof Board
M-OSFA or
M-PG1
SBS-AA,
SBS-TA,
APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-30.0*
S-8.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof
Board, SECUROCK Gypsum-
Fiber Roof Board or SECUROCK
Glass-Mat Roof Board, min.
7/16-inch DEXcell Cement Roof
Board or min. 0.5-inch
SECUROCK Cement Roof Board
M-OSFA or
M-PG1
SBS-AA,
SBS-TA,
APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0
S-9.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
4.0 ft2
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof
Board or SECUROCK Gypsum-
Fiber Roof Board
OB500
SBS-AA,
SBS-TA,
APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-30.0*
S-10.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof
Board or SECUROCK Gypsum-
Fiber Roof Board
OB500
SBS-AA,
SBS-TA,
APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0
S-11.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
4.0 ft2
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
CR-20
SBS-AA,
SBS-TA,
APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-30.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 40 of 98
TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
S-12.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
CR-20
SBS-AA,
SBS-TA,
APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0
S-13.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, Polytherm G,
ACFoam III, Polytherm H
or H-Shield
Dekfast PLT-R-3 with Dekfast #14,
OMG 3” Galvalume Steel Plates
with OMG #14 Roofgrip
1 per
1.0 ft2
Additional optional layer(s)
base insulation followed by min.
0.25-inch DensDeck Prime
CR-20
SBS-AA,
SBS-TA,
APP-TA
(Optional) SBS-AA,
SBS-TA, APP-TA
SBS-AA,
SBS-TA,
APP-TA
-105.0
SELF-ADHERING BASE PLY:
S-14.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
4.0 ft2
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
PRIMER: POLYBRITE 745 or
WB3000
D-IS SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-30.0*
S-15.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
PRIMER: POLYBRITE 745 or
WB3000
D-IS SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
S-16.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
4.0 ft2
Min. 0.25-inch DensDeck,
DensDeck Prime, SECUROCK
Gypsum-Fiber Roof Board or
SECUROCK Glass-Mat Roof
Board, min. 7/16-inch DEXcell
Cement Roof Board or min. 0.5-
inch SECUROCK Cement Roof
Board
PRIMER: POLYBRITE 745 or
WB3000
M-OSFA or
M-PG1 SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-30.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 41 of 98
TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
S-17.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck,
DensDeck Prime, SECUROCK
Gypsum-Fiber Roof Board or
SECUROCK Glass-Mat Roof
Board, min. 7/16-inch DEXcell
Cement Roof Board or min. 0.5-
inch SECUROCK Cement Roof
Board
PRIMER: POLYBRITE 745 or
WB3000
M-OSFA or
M-PG1 SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
S-18.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
4.0 ft2
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
PRIMER: POLYBRITE 745 or
WB3000
OB500 SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-30.0*
S-19.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
PRIMER: POLYBRITE 745 or
WB3000
OB500 SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
S-20.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
4.0 ft2
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
PRIMER: POLYBRITE 745 or
WB3000
CR-20 SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-30.0*
S-21.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
PRIMER: POLYBRITE 745 or
WB3000
CR-20 SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 42 of 98
TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
S-22.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, Polytherm G,
ACFoam III, Polytherm H
or H-Shield
Dekfast PLT-R-3 with Dekfast #14,
OMG 3” Galvalume Steel Plates
with OMG #14 Roofgrip
1 per
1.0 ft2
Additional optional layer(s)
base insulation followed by min.
0.25-inch DensDeck Prime
CR-20 SBS-SA (Optional) SBS-TA,
APP-TA
SBS-TA,
APP-TA -97.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
S-23.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, Polytherm G,
ACFoam III, Polytherm H
or H-Shield
Dekfast PLT-R-3 with Dekfast #14,
OMG 3” Galvalume Steel Plates
with OMG #14 Roofgrip
1 per
1.0 ft2
Additional optional layer(s)
base insulation followed by min.
0.25-inch DensDeck Prime
CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -97.5
COLD-APPLIED BASE PLY:
S-24.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
4.0 ft2
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof
Board or SECUROCK Gypsum-
Fiber Roof Board
D-IS SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-30.0*
S-25.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof
Board or SECUROCK Gypsum-
Fiber Roof Board
D-IS SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
S-26.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
4.0 ft2
Min. 0.25-inch DensDeck,
DensDeck Prime, DEXcell FA
Glass Mat Roof Board,
SECUROCK Gypsum-Fiber Roof
Board or SECUROCK Glass-Mat
Roof Board, min. 7/16-inch
DEXcell Cement Roof Board or
min. 0.5-inch SECUROCK
Cement Roof Board
M-OSFA or
M-PG1
SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-30.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 43 of 98
TABLE 2A: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
S-27.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck,
DensDeck Prime, DEXcell FA
Glass Mat Roof Board,
SECUROCK Gypsum-Fiber Roof
Board or SECUROCK Glass-Mat
Roof Board, min. 7/16-inch
DEXcell Cement Roof Board or
min. 0.5-inch SECUROCK
Cement Roof Board
M-OSFA or
M-PG1
SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
S-28.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
4.0 ft2
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof
Board or SECUROCK Gypsum-
Fiber Roof Board
OB500 SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-30.0*
S-29.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof
Board or SECUROCK Gypsum-
Fiber Roof Board
OB500 SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
S-30.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
4.0 ft2
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
CR-20 SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-30.0*
S-31.
Min. 22 ga., type
B, Grade 40 steel
or min. 2,500 psi
structural
concrete
Min. 2-inch Polytherm,
ACFoam II, ENRGY 3,
EnergyGuard Polyiso
Insulation, Polytherm H,
H-Shield or Multi-Max
FA3
Dekfast PLT-H-2-7/8 with Dekfast
#14, OMG 3” Galvalume Ribbed
Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plate
with Trufast #14 HD
1 per
1.6 ft2
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
CR-20 SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 44 of 98
TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No. Deck (Note 1) Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
ASPHALT- OR TORCH-APPLIED BASE PLY:
S-32.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.75-inch JM Fesco Board
(homogeneous) or min. 1.5-inch
JM Fesco Board (laminated)
OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate
with #12 Roofgrip (steel only) or OMG #14 Heavy Duty,
Dekfast PLT-H-2-7/8 with Dekfast #12 DP (steel only) or
Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast
#12 DP (steel only) or Trufast #14 HD
1 per
2.0 ft2
(Optional if
using AA Ply)
BP-AA, SBS-
AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
S-33.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.5-inch Structodek High
Density Fiberboard Roof
Insulation or G-P FiberBase HD
or HD Excel
OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate
with #12 Roofgrip (steel only) or OMG #14 Heavy Duty,
Dekfast PLT-H-2-7/8 with Dekfast #12 DP (steel only) or
Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast
#12 DP (steel only) or Trufast #14 HD
1 per
4.0 ft2
(Optional if
using AA Ply)
BP-AA, SBS-
AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
S-34.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate
with #12 Roofgrip (steel only) or OMG #14 Heavy Duty,
Dekfast PLT-H-2-7/8 with Dekfast #12 DP (steel only) or
Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast
#12 DP (steel only) or Trufast #14 HD
1 per
4.0 ft2
(Optional if
using AA Ply)
BP-AA, SBS-
AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
S-35.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 2-inch H-Shield WF
OMG AccuTrac Plate or OMG 3 in. Ribbed Galvalume Plate
with #12 Roofgrip (steel only) or OMG #14 Heavy Duty,
Dekfast PLT-H-2-7/8 with Dekfast #12 DP (steel only) or
Dekfast #14, Trufast 3” Metal Insulation Plate with Trufast
#12 DP (steel only) or Trufast #14 HD
1 per
4.0 ft2
(Optional if
using AA Ply)
BP-AA, SBS-
AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
S-36.
Min. 22 ga., type B,
Grade 40 steel; 6 ft
span; 5/8” puddle
welds, 6” o.c.
One or more layers,
any combination,
min. 1.5” thick, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
Dekfast PLT-H-2-7/8 or PTL-R-3 plates with Dekfast DF-
#12-PH3, DF-#14-PH3 or DF-#15-PH3 fasteners or OMG 3
in. Galvalume Steel Plate, 3 in. Ribbed Galvalume Plate
(Flat) or AccuTrac Flat Bottom Plate with OMG #12
Roofgrip, #14 Roofgrip or OMG #15 Roofgrip fasteners or
Trufast 3” Metal Insulation Plate with Trufast #12 DP,
Trufast #14 HD or Trufast #15 EHD fasteners
1 per
2.0 ft2
SBS-TA or
APP-TA
(Optional) SBS-TA
or APP-TA
SBS-TA or
APP-TA -52.5
S-37.
Min. 22 ga., type B,
Grade 40 steel; 6 ft
span; 5/8” puddle
welds, 6” o.c.
One or more layers,
any combination,
min. 1.5” thick, loose
laid
Min. 0.25-inch DensDeck Prime
Dekfast PLT-H-2-7/8 or PTL-R-3 plates with Dekfast DF-
#12-PH3, DF-#14-PH3 or DF-#15-PH3 fasteners or OMG 3
in. Galvalume Steel Plate, 3 in. Ribbed Galvalume Plate
(Flat) or AccuTrac Flat Bottom Plate with OMG #12
Roofgrip, #14 Roofgrip or OMG #15 Roofgrip fasteners or
Trufast 3” Metal Insulation Plate with Trufast #12 DP,
Trufast #14 HD or Trufast #15 EHD fasteners
1 per
2.0 ft2
SBS-TA or
APP-TA
(Optional) SBS-TA
or APP-TA
SBS-TA or
APP-TA -60.0
S-38.
Min. 22 ga., type B,
Grade 40 steel; 6 ft
span; 5/8” puddle
welds, 6” o.c.
One or more layers,
any combination,
min. 1.5” thick, loose
laid
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
Dekfast PLT-H-2-7/8 or PTL-R-3 plates with Dekfast DF-
#12-PH3, DF-#14-PH3 or DF-#15-PH3 fasteners or OMG 3
in. Galvalume Steel Plate, 3 in. Ribbed Galvalume Plate
(Flat) or AccuTrac Flat Bottom Plate with OMG #12
Roofgrip, #14 Roofgrip or OMG #15 Roofgrip fasteners or
Trufast 3” Metal Insulation Plate with Trufast #12 DP,
Trufast #14 HD or Trufast #15 EHD fasteners
1 per
1.6 ft2
SBS-TA or
APP-TA
(Optional) SBS-TA
or APP-TA
SBS-TA or
APP-TA -67.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 45 of 98
TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No. Deck (Note 1) Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
S-39.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.5-inch SECUROCK
Gypsum-Fiber Roof Board
OMG 3-inch Galvalume Steel Plate with OMG #14
HD
1 per
1.8 ft2
(Optional if
using AA Ply)
BP-AA, SBS-
AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-75.0
S-40.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.5-inch Structodek High
Density Fiberboard Roof
Insulation or min. 0.25-inch
DensDeck, DensDeck Prime or
SECUROCK Gypsum-Fiber Roof
Board
Dekfast PLT-H-2-7/8 with Dekfast #12 (steel only)
or #14 or Trufast 3” Metal Insulation Plate with
Trufast DP (steel only) or HD
1 per
1.3 ft2
(Optional if
using AA Ply)
BP-AA, SBS-
AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-82.5
SELF-ADHERING BASE PLY:
S-41.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch Polytherm,
ACFoam II, H-Shield or
Polytherm
Dekfast PLT-H-2-7/8 with Dekfast #12 DP (steel only) or
Dekfast #14, OMG AccuTrac Flat Bottom Plate with #12
Roofgrip (steel only) or OMG #14 Heavy Duty, Trufast 3”
Metal Insulation Plate with Trufast #12 DP (steel only) or
Trufast #14 HD
1 per
2.7 ft2 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-30.0
S-42.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch DensDeck Prime
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8 or
OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round
Metal Plate or Trufast #14 HD or Trufast #15 EHD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
2.7 ft2 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-37.5*
S-43.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8 or
OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round
Metal Plate or Accutrac Flat Bottom Plate or Trufast #14
HD or Trufast #15 EHD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
2.7 ft2 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-37.5*
S-44.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch DEXcell FA Glass
Mat Roof Board
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8,
isofast PLT-S-2-3/4X2-3/4 or Dekfast PLT-R-3 or OMG #14
Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal
Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or
Trufast #15 EHD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
2.7 ft2 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-37.5*
S-45.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch H-Shield or
Polytherm
OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel
only) or OMG #14 Heavy Duty, Trufast 3” Metal Insulation
Plate with Trufast #12 DP (steel only) or Trufast #14 HD
1 per
2.0 ft2 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-45.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 46 of 98
TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No. Deck (Note 1) Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
S-46.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board optionally primed
with POLYBRITE 745 or WB3000
Dekfast PLT-H-2-7/8 with Dekfast #14, OMG 3” Galvalume
Ribbed Plates with OMG #14 Roofgrip or Trufast 3” Metal
Insulation Plates with Trufast #14 HD Fasteners
1 per
2.0 ft2 SBS-SA None
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0*
S-47.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board optionally primed
with POLYBRITE 745 or WB3000
OMG 3 in. Galvalume Plate (non-ribbed) with #12
Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast
PLT-H-2-7/8 with Dekfast #12 DP (steel only) or Dekfast
#14, Trufast 3” Metal Insulation Plate with Trufast #12 DP
(steel only) or Trufast #14 HD
1 per
2.0 ft2 SBS-SA (Optional) SBS-SA,
SBS-TA or APP-TA
SBS-SA,
APP-SA,
SBS-TA or
APP-TA
-45.0*
S-48.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with
Dekfast PLT-H-2-7/8 or Dekfast PLT-R-3 or OMG #14
Roofgrip with OMG 3 in. Round Metal Plate, OMG 3 in.
Ribbed Galvalume Plate (Flat) or Accutrac Flat Bottom
Plate or Trufast #14 HD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
2.0 ft2 SBS-SA None SBS-SA -45.0
S-49.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch DensDeck Prime
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with
Dekfast PLT-H-2-7/8 or OMG #14 Roofgrip with OMG 3 in.
Round Metal Plate or Accutrac Flat Bottom Plate or
Trufast #14 HD Fasteners with Trufast 3” Metal Insulation
Plate
1 per
2.0 ft2 SBS-SA None SBS-SA -45.0
S-50.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8 or
OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round
Metal Plate or Accutrac Flat Bottom Plate or Trufast #14
HD or Trufast #15 EHD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
1.8 ft2 SBS-SA
(Optional when
using torch-
applied Cap Ply)
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA or
APP-TA
-45.0
S-51.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch DensDeck Prime
optionally primed with
POLYBRITE 745 or WB3000
OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round
Metal Plate or Trufast #14 HD or Trufast #15 EHD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
1.8 ft2 SBS-SA
(Optional when
using torch-
applied Cap Ply)
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA or
APP-TA
-45.0
S-52.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch H-Shield or
Polytherm optionally primed
with POLYBRITE 745 or WB3000
Dekfast PLT-H-2-7/8 with Dekfast #12 DP (steel only) or
Dekfast #14
1 per
2.0 ft2 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-60.0
S-53.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board optionally primed
with POLYBRITE 745 or WB3000
OMG 3 in. Galvalume Plate (non-ribbed) with #12
Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast
PLT-H-2-7/8 with Dekfast #12 DP (steel only) or Dekfast
#14, Trufast 3” Metal Insulation Plate with Trufast #12 DP
(steel only) or Trufast #14 HD
1 per
1.6 ft2 SBS-SA (Optional) SBS-TA
or APP-TA
SBS-TA or
APP-TA -60.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 47 of 98
TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No. Deck (Note 1) Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
S-54.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch ACFoam II,
ACFoam III, EnergyGuard Polyiso
Insulation, ENRGY 3, ENRGY 3
CGF, H-Shield, H-Shield CG, ISO
95+ GL, Multi-Max FA3,
Polytherm or Ultra-Max
optionally primed with
POLYBRITE 745 or WB3000
Dekfast PLT-H-2-7/8 or Dekfast PLT-R-3 with Dekfast #12
(steel only) or Dekfast #14, OMG 3 in. Galvalume Plate
(non-ribbed) or OMG AccuTrac Plate with #12 Roofgrip
(steel only) or OMG #14 Heavy Duty or Trufast 3” Metal
Insulation Plate with Trufast #12 DP (steel only) or Trufast
#14 HD
1 per
1.3 ft2 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-67.5*
S-55.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board optionally primed
with POLYBRITE 745 or WB3000
OMG 3 in. Galvalume Plate (non-ribbed) with #12
Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast
PLT-H-2-7/8 with Dekfast #12 DP (steel only) or Dekfast
#14, Trufast 3” Metal Insulation Plate with Trufast #12 DP
(steel only) or Trufast #14 HD
1 per
1.3 ft2 SBS-SA (Optional) SBS-TA
or APP-TA
SBS-TA or
APP-TA -72.5
S-56.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.5-inch SECUROCK
Gypsum-Fiber Roof Board OMG 3-inch Galvalume Steel Plate with OMG #14 HD 1 per
1.8 ft2 SBS-SA (Optional) SBS-TA SBS-TA -75.0
S-57.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8 or
OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round
Metal Plate or Accutrac Flat Bottom Plate or Trufast #14
HD or Trufast #15 EHD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
1.0 ft2 SBS-SA (Optional) SBS-TA,
APP-TA
SBS-TA,
APP-TA -90.0
S-58.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch DensDeck Prime
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8 or
OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round
Metal Plate or Trufast #14 HD or Trufast #15 EHD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
1.0 ft2 SBS-SA (Optional) SBS-TA,
APP-TA
SBS-TA,
APP-TA -97.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
S-59.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch Polytherm,
ACFoam II, H-Shield or
Polytherm
Dekfast PLT-H-2-7/8 with Dekfast #12 DP (steel only) or
Dekfast #14, OMG AccuTrac Flat Bottom Plate with #12
Roofgrip (steel only) or OMG #14 Heavy Duty, Trufast 3”
Metal Insulation Plate with Trufast #12 DP (steel only) or
Trufast #14 HD
1 per
2.7 ft2 APP-SA-H (Optional) APP-TA APP-TA -30.0
S-60.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch DensDeck Prime
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8 or
OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round
Metal Plate or Trufast #14 HD or Trufast #15 EHD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
2.7 ft2 APP-SA-H (Optional) APP-TA APP-TA -37.5*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 48 of 98
TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No. Deck (Note 1) Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
S-61.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8 or
OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round
Metal Plate or Accutrac Flat Bottom Plate or Trufast #14
HD or Trufast #15 EHD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
2.7 ft2 APP-SA-H (Optional) APP-TA APP-TA -37.5*
S-62.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch DEXcell FA Glass
Mat Roof Board
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8,
isofast PLT-S-2-3/4X2-3/4 or Dekfast PLT-R-3 or OMG #14
Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal
Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or
Trufast #15 EHD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
2.7 ft2 APP-SA-H (Optional) APP-TA APP-TA -37.5*
S-63.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch H-Shield or
Polytherm
OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel
only) or OMG #14 Heavy Duty, Trufast 3” Metal Insulation
Plate with Trufast #12 DP (steel only) or Trufast #14 HD
1 per
2.0 ft2 APP-SA-H (Optional) APP-TA APP-TA -45.0*
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
S-64.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch Polytherm,
ACFoam II, H-Shield or
Polytherm H
Dekfast PLT-H-2-7/8 with Dekfast #12 DP (steel only) or
Dekfast #14, OMG AccuTrac Flat Bottom Plate with #12
Roofgrip (steel only) or OMG #14 Heavy Duty, Trufast 3”
Metal Insulation Plate with Trufast #12 DP (steel only) or
Trufast #14 HD
1 per
2.7 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -30.0
S-65.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch DensDeck Prime
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8 or
OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round
Metal Plate or Trufast #14 HD or Trufast #15 EHD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
2.7 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -37.5*
S-66.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8 or
OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round
Metal Plate or Accutrac Flat Bottom Plate or Trufast #14
HD or Trufast #15 EHD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
2.7 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -37.5*
S-67.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch DEXcell FA Glass
Mat Roof Board
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8,
isofast PLT-S-2-3/4X2-3/4 or Dekfast PLT-R-3 or OMG #14
Roofgrip or #15 Roofgrip with OMG 3 in. Round Metal
Plate or Accutrac Flat Bottom Plate or Trufast #14 HD or
Trufast #15 EHD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
2.7 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -37.5*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 49 of 98
TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No. Deck (Note 1) Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
S-68.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch H-Shield or
Polytherm H
OMG AccuTrac Flat Bottom Plate with #12 Roofgrip (steel
only) or OMG #14 Heavy Duty, Trufast 3” Metal Insulation
Plate with Trufast #12 DP (steel only) or Trufast #14 HD
1 per
2.0 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -45.0*
S-69.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with
Dekfast PLT-H-2-7/8 or Dekfast PLT-R-3 or OMG #14
Roofgrip with OMG 3 in. Round Metal Plate, OMG 3 in.
Ribbed Galvalume Plate (Flat) or Accutrac Flat Bottom
Plate or Trufast #14 HD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
2.0 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -45.0
S-70.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch DensDeck Prime
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 with Polygrip Hex Plate or Dekfast #14 with
Dekfast PLT-H-2-7/8 or OMG #14 Roofgrip with OMG 3 in.
Round Metal Plate or Accutrac Flat Bottom Plate or
Trufast #14 HD Fasteners with Trufast 3” Metal Insulation
Plate
1 per
2.0 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -45.0
S-71.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch H-Shield or
Polytherm optionally primed
with POLYBRITE 745 or WB3000
Dekfast PLT-H-2-7/8 with Dekfast #12 DP (steel only) or
Dekfast #14
1 per
2.0 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -60.0
S-72.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board optionally primed
with POLYBRITE 745 or WB3000
OMG 3 in. Galvalume Plate (non-ribbed) with #12
Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast
PLT-H-2-7/8 with Dekfast #12 DP (steel only) or Dekfast
#14, Trufast 3” Metal Insulation Plate with Trufast #12 DP
(steel only) or Trufast #14 HD
1 per
1.6 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -60.0
S-73.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 1.5-inch ACFoam II,
ACFoam III, EnergyGuard Polyiso
Insulation, ENRGY 3, ENRGY 3
CGF, H-Shield, H-Shield CG, ISO
95+ GL, Multi-Max FA3,
Polytherm or Ultra-Max
optionally primed with
POLYBRITE 745 or WB3000
Dekfast PLT-H-2-7/8 or Dekfast PLT-R-3 with Dekfast #12
(steel only) or Dekfast #14, OMG 3 in. Galvalume Plate
(non-ribbed) or OMG AccuTrac Plate with #12 Roofgrip
(steel only) or OMG #14 Heavy Duty or Trufast 3” Metal
Insulation Plate with Trufast #12 DP (steel only) or Trufast
#14 HD
1 per
1.3 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -67.5*
S-74.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board optionally primed
with POLYBRITE 745 or WB3000
OMG 3 in. Galvalume Plate (non-ribbed) with #12
Roofgrip (steel only) or OMG #14 Heavy Duty, Dekfast
PLT-H-2-7/8 with Dekfast #12 DP (steel only) or Dekfast
#14, Trufast 3” Metal Insulation Plate with Trufast #12 DP
(steel only) or Trufast #14 HD
1 per
1.3 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 50 of 98
TABLE 2B: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No. Deck (Note 1) Base Insulation
Layer (Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
S-75.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.5-inch SECUROCK
Gypsum-Fiber Roof Board OMG 3-inch Galvalume Steel Plate with OMG #14 HD 1 per
1.8 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -75.0
S-76.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8 or
OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round
Metal Plate or Accutrac Flat Bottom Plate or Trufast #14
HD or Trufast #15 EHD Fasteners with Trufast 3” Metal
Insulation Plate
1 per
1.0 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -90.0
S-77.
Min. 22 ga., type B,
Grade 40 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
min. 1-inch, loose
laid
Min. 0.25-inch DensDeck Prime
optionally primed with
POLYBRITE 745 or WB3000
Polygrip #14 or Polygrip #15 with Polygrip Hex Plate or
Dekfast DF-#14 or DF-#15 with Dekfast PLT-H-2-7/8 or
OMG #14 Roofgrip or #15 Roofgrip with OMG 3 in. Round
Metal Plate or Trufast #14 HD or Trufast #15 EHD
Fasteners with Trufast 3” Metal Insulation Plate
1 per
1.0 ft2 SBS-SA-H (Optional) SBS-TA SBS-TA -97.5
COLD-APPLIED BASE PLY:
S-78.
Min. 22 ga., type B,
Grade 33 steel or
min. 2,500 psi
structural concrete
One or more layers,
any combination,
loose laid
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
Dekfast Galvalume Steel Hex with Dekfast #14, OMG 3”
Galvalume Ribbed Plates with OMG #14 Roofgrip or
Trufast 3” Metal Insulation Plates with Trufast #14 HD
Fasteners
1 per
2.0 ft2
SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0*
TABLE 2C: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
ASPHALT- OR TORCH-APPLIED BASE PLY:
S-79.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P,
Elastovent or JM
Perma-Ply 28
Roofgrip #14 with OMG Flat Bottom Plates
(square), Dekfast #14 with Dekfast PLT-H-2-7/8 or
Trufast #14 HD with Trufast 3” Metal Insulation
Plate
12-inch o.c. at min. 4-inch lap
and 18-inch o.c. at two,
equally spaced, staggered
center rows
(Optional) BP-
AA, SBS-AA,
SBS-TA or
APP-TA
SBS-AA, SBS-
TA, APP-TA -45.0*
S-80.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P,
Elastovent, Polyglass
G2 Base, CertainTeed
Glasbase, Firestone
MB Base, JM Perma-
Ply 28 or GAFGLAS #75
Roofgrip #14 with OMG Flat Bottom Plates
(square), Dekfast #14 with Dekfast PLT-H-2-7/8 or
Trufast #14 HD with Trufast 3” Metal Insulation
Plate
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
(Optional) BP-
AA, SBS-AA,
SBS-TA or
APP-TA
SBS-AA, SBS-
TA, APP-TA -52.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 51 of 98
TABLE 2C: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
S-81.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase V,
Elastobase P or
Elastovent
Roofgrip #12 (steel only) or #14 with OMG Flat
Bottom Plates (square)
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
(Optional) BP-
AA, SBS-AA,
SBS-TA or
APP-TA
SBS-AA, SBS-
TA, APP-TA -60.0
S-82.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached Polybond, Polyflex Dekfast #14 with Dekfast PLT-H-2-7/8 or OMG
Roofgrip #14 OMG Flat Bottom Plates
12-inch o.c. at the min. 4-inch
lap and 18-inch o.c. at two,
equally spaced, staggered
center rows
(Optional) BP-
AA, SBS-AA,
SBS-TA or
APP-TA
SBS-AA, SBS-
TA, APP-TA -112.5
SELF-ADHERING BASE PLY:
S-83.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase V or
Elastobase P with
poly top surface
Roofgrip #14 with OMG Flat Bottom Plates
(square), Dekfast #14 with Dekfast PLT-H-2-7/8 or
Trufast #14 HD with Trufast 3” Metal Insulation
Plate
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-52.5*
S-84.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase V or
Elastobase P with
poly top surface
Roofgrip #12 (steel only) or #14 with OMG Flat
Bottom Plates (square)
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-60.0*
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
S-85.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase V or
Elastobase P with
poly top surface
Roofgrip #14 with OMG Flat Bottom Plates
(square), Dekfast #14 with Dekfast PLT-H-2-7/8 or
Trufast #14 HD with Trufast 3” Metal Insulation
Plate
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
APP-SA-H APP-TA -52.5*
S-86.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase V or
Elastobase P with
poly top surface
Roofgrip #12 (steel only) or #14 with OMG Flat
Bottom Plates (square)
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
APP-SA-H APP-TA -60.0*
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
S-87.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase V or
Elastobase P with
poly top surface
Roofgrip #14 with OMG Flat Bottom Plates
(square), Dekfast #14 with Dekfast PLT-H-2-7/8 or
Trufast #14 HD with Trufast 3” Metal Insulation
Plate
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
SBS-SA-H SBS-TA -52.5*
S-88.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached
Elastobase V or
Elastobase P with
poly top surface
Roofgrip #12 (steel only) or #14 with OMG Flat
Bottom Plates (square)
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
SBS-SA-H SBS-TA -60.0*
COLD-APPLIED BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 52 of 98
TABLE 2C: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
S-89.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Loose
laid Elastobase V Trufast #12 DP (steel only), #14 HD or #15 EHD
with Trufast 3” Metal Insulation Plate
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at one
staggered center row
(Optional)
SBS-CA1, SBS-
CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-45.0*
S-90.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Loose
laid Elastovent Trufast #12 DP (steel only), #14 HD or #15 EHD
with Trufast 3” Metal Insulation Plate
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at one
staggered center row
(Optional)
SBS-CA1
SBS-CA1,
APP-CA1 -45.0*
S-91.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Loose
laid Elastobase V Trufast #12 DP (steel only), #14 HD or #15 EHD
with Trufast 3” Metal Insulation Plate
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
(Optional)
SBS-CA1, SBS-
CA2
SBS-CA1,
SBS-CA2,
APP-CA1
-67.5
S-92.
Min. 22 ga., type B,
Grade 33 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Loose
laid Elastovent Trufast #12 DP (steel only), #14 HD or #15 EHD
with Trufast 3” Metal Insulation Plate
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
(Optional)
SBS-CA1
SBS-CA1,
APP-CA1 -67.5
S-93.
Min. 22 ga., type B,
Grade 40 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Loose-
laid Elastoflex S6 Trufast #12 DP (steel only) or Trufast #14 HD (steel
or concrete) with Trufast 3” Metal Insulation Plate
6-inch o.c. at min. 4-inch lap
and 6-inch o.c. at one
staggered center row
(Optional)
Elastoflex S6
applied in
PG350 at 1.5-
2.0 gal/square
SBS-CA1 -75.0*
S-94.
Min. 22 ga., type B,
Grade 40 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Loose-
laid Elastoflex S6 Trufast #12 DP (steel only) or Trufast #14 HD (steel
or concrete) with Trufast 3” Metal Insulation Plate
12-inch o.c. at min. 4-inch lap
and 12-inch o.c. at two,
equally spaced, staggered
center rows
(Optional)
Elastoflex S6
applied in
PG350 at 1.5-
2.0 gal/square
SBS-CA1 -90.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 53 of 98
TABLE 2D: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED VELOCIFLEX, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
ASPHALT- OR TORCH-APPLIED BASE PLY:
S-95.
Min. 22 ga., type B, 40
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6 Trufast #14 HD with Trufast 2” Barbed Seam
Plates
18-inch o.c. within the 4-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA SBS-TA -30.0
S-96.
Min. 22 ga., type B,
Grade 40 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached Elastoshield VP HT
Trufast #15 EHD (steel only) or Trufast #14 HD (concrete
only) with Trufast 2.4” Barbed Metal Seam Plates, Trufast
2.4” Scoop Seam Plates or Trufast 2.75” Barbed Metal
Seam Plates or Dekfast #15 with Dekfast Galvalume Steel
1-1/2” x 2-3/4” Oval Barbed Plate (aka, Dekfast PLT-O2-
3/4-12B) or Dekfast Galvalume Steel 2-3/8” Round
Barbed Plate (aka, Dekfast PLT-R-2-3/8-6B)
18-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA SBS-TA -37.5
S-97.
Min. 22 ga., type B, 33
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6
Trufast #15 EHD (steel only) or Trufast #14 HD
(concrete only) with Trufast 2.4” Scoop Seam
Plates or Trufast 2.75” Barbed Metal Seam Plates
12-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA SBS-TA -45.0
S-98.
Min. 22 ga., type B, 33
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6
Trufast #15 EHD (steel only) or Trufast #14 HD
(concrete only) with Trufast 2.75” Barbed Metal
Seam Plates
6-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA SBS-TA -60.0
S-99.
Min. 22 ga., type B,
Grade 40 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6 HP
Trufast #15 EHD (steel only) or Trufast #14 HD
(concrete only) with Trufast 2.75” Barbed Metal
Seam Plates or OMG Super XHD Fasteners (steel
only) with OMG 2 3/4 Super XHD Barbed Stress
Plates
18-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA
SBS-TA
(D6164 only) -60.0
S-100.
Min. 22 ga., type B, 33
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6 HP
Trufast #15 EHD (steel only) or Trufast #14 HD
(concrete only) with Trufast 2.75” Barbed Metal
Seam Plates or OMG Super XHD Fasteners (steel
only) with OMG 2 3/4 Super XHD Barbed Stress
Plates
12-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA
SBS-TA
(D6164 only) -82.5
S-101.
Min. 22 ga., type B, 33
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoshield VP HT
Trufast #15 EHD (steel only) or Trufast #14 HD (concrete
only) with Trufast 2.4” Barbed Metal Seam Plates, Trufast
2.4” Scoop Seam Plates or Trufast 2.75” Barbed Metal
Seam Plates or Dekfast #15 with Dekfast Galvalume Steel
1-1/2” x 2-3/4” Oval Barbed Plate (aka, Dekfast PLT-O2-
3/4-12B) or Dekfast Galvalume Steel 2-3/8” Round
Barbed Plate (aka, Dekfast PLT-R-2-3/8-6B)
12-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA
SBS-TA
(D6164 only) -82.5
S-102. Min. 22 ga., type B,
Grade 80 steel
One or more
layers, any
combination
Prelim.
Attached Polyflex
Dekfast #15 HS with Dekfast Galvalume Steel 2-
3/8” Round Barbed Plate (aka, Dekfast PLT-R-2-
3/8-6B)
12-inch o.c. within the 5-inch
wide, torch-sealed side lap
(Optional)
APP-TA
SBS-TA, APP-
TA -82.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 54 of 98
TABLE 2D: STEEL OR STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED VELOCIFLEX, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Insulation Layer(s)
(Note 13) Base Sheet Roof Cover (Note 15) MDP
(psf) Type Attach Type Fasten (Note 11) Attach Base Ply Cap Ply
S-103.
Min. 22 ga., type B,
Grade 80 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached
Polybond or
Polyflex
Trufast #15 EHD (steel only) or Trufast #14 HD
(concrete only) with Trufast 2.4 in. Barbed Seam
Plates
12-inch o.c. within the 6-inch
wide, torch-sealed side lap
(Optional)
APP-TA
SBS-TA, APP-
TA -82.5
S-104.
Min. 22 ga., type B, 40
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoshield VP HT
Trufast #15 EHD (steel only) or Trufast #14 HD (concrete
only) with Trufast 2.4” Barbed Metal Seam Plates, Trufast
2.4” Scoop Seam Plates or Trufast 2.75” Barbed Metal
Seam Plates or Dekfast #15 with Dekfast Galvalume Steel
1-1/2” x 2-3/4” Oval Barbed Plate (aka, Dekfast PLT-O2-
3/4-12B) or Dekfast Galvalume Steel 2-3/8” Round
Barbed Plate (aka, Dekfast PLT-R-2-3/8-6B)
6-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA
SBS-TA
(D6164 only) -97.5
S-105.
Min. 22 ga., type B,
Grade 40 steel or min.
2,500 psi structural
concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6 HP
Trufast #15 EHD (steel only) or Trufast #14 HD
(concrete only) with Trufast 2.75” Barbed Metal
Seam Plates or OMG Super XHD Fasteners (steel
only) with OMG 2 3/4 Super XHD Barbed Stress
Plates
6-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
SBS-TA
SBS-TA
(D6164 only) -135.0
COLD-APPLIED BASE PLY:
S-106.
Min. 22 ga., type B, 40
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6 HP
Trufast #15 EHD (steel only) or Trufast #14 HD
(concrete only) with Trufast 2.75” Barbed Metal
Seam Plates or OMG Super XHD Fasteners (steel
only) with OMG 2 3/4 Super XHD Barbed Stress
Plates
18-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
Elastoflex S6
applied in
PG350 at 1.5-
2.0 gal/square
SBS-CA1 -60.0
Note: When extrapolating base sheet attachment for this system for elevated pressure zones, any additional fastener rows installed in the center of the sheet shall be stripped-in with
minimum 6-inch wide strips of torch-applied, sand-top-surfaced, Polyglass SBS modified bitumen membrane prior to placement of subsequent Base Ply or Cap Ply membranes in PG350
adhesive.
S-107.
Min. 22 ga., type B, 40
ksi steel or min. 2,500
psi structural concrete
One or more
layers, any
combination
Prelim.
Attached Elastoflex S6 HP
Trufast #15 EHD (steel only) or Trufast #14 HD
(concrete only) with Trufast 2.75” Barbed Metal
Seam Plates or OMG Super XHD Fasteners (steel
only) with OMG 2 3/4 Super XHD Barbed Stress
Plates
12-inch o.c. within the 5-inch
wide, torch-sealed or heat-
welded side laps
(Optional)
Elastoflex S6
applied in
PG350 at 1.5-
2.0 gal/square
SBS-CA1 -82.5
Note: When extrapolating base sheet attachment for this system for elevated pressure zones, any additional fastener rows installed in the center of the sheet shall be stripped-in with
minimum 6-inch wide strips of torch-applied, sand-top-surfaced, Polyglass SBS modified bitumen membrane prior to placement of subsequent Base Ply or Cap Ply membranes in PG350
adhesive.
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 55 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT OR TORCH APPLIED BASE PLY:
C-1 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield D-IS Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board D-IS BP-AA, SBS-AA (Optional) BP-AA,
SBS-AA SBS-AA -225.0
C-2 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS Min. 0.25-inch DensDeck Prime D-IS SBS-TA, APP-
TA
(Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -282.5
C-3 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof Board
D-IS SBS-TA, APP-
TA
(Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -322.5
C-4 Structural
concrete None
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, Multi-Max FA3
OB500 0.5-inch SECUROCK Cement Roof
Board OB500 SBS-TA (Optional) SBS-TA SBS-TA -187.5
C-5 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board OB500 BP-AA, SBS-AA (Optional) BP-AA,
SBS-AA SBS-AA -225.0
C-6 Structural
concrete None
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, Multi-Max FA3
OB500, 6-
inch o.c.
0.5-inch SECUROCK Cement Roof
Board
OB500, 6-
inch o.c. SBS-TA (Optional) SBS-TA SBS-TA -232.5
C-7 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-TA, APP-
TA
(Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -282.5
C-8 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof Board
OB500 SBS-TA, APP-
TA
(Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -322.5
C-9 Structural
concrete None
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, Multi-Max FA3
M-OSFA or
M-PG1
0.5-inch SECUROCK Cement Roof
Board
M-OSFA or
M-PG1 SBS-TA (Optional) SBS-TA SBS-TA -187.5
C-10 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
M-OSFA or
M-PG1 BP-AA, SBS-AA (Optional) BP-AA,
SBS-AA SBS-AA -225.0
C-11 Structural
concrete None
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, Multi-Max FA3
M-OSFA or
M-PG1, 6-
inch o.c.
0.5-inch SECUROCK Cement Roof
Board
M-OSFA or
M-PG1, 6-
inch o.c.
SBS-TA (Optional) SBS-TA SBS-TA -232.5
C-12 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1 Min. 0.25-inch DensDeck Prime M-OSFA or
M-PG1
SBS-TA, APP-
TA
(Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -282.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 56 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-13 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof Board
M-OSFA or
M-PG1
SBS-TA, APP-
TA
(Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -322.5
C-14 Structural
concrete None
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, Multi-Max FA3
CR-20 0.5-inch SECUROCK Cement Roof
Board CR-20 SBS-TA (Optional) SBS-TA SBS-TA -187.5
C-15 Structural
concrete None
Min. 1.5-inch Ultra-Max or Multi-Max FA-
3, min. 1.3-inch Polytherm G, ACFoam III
or min. 1.0-inch ISO 95+GL, Polytherm H,
H-Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 BP-AA, SBS-AA (Optional) BP-AA,
SBS-AA SBS-AA -225.0
C-16 Structural
concrete None
Min. 1.5-inch Ultra-Max or Multi-Max FA-
3, min. 1.3-inch Polytherm G, ACFoam III
or min. 1.0-inch ISO 95+GL, Polytherm H,
H-Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 APP-TA (Optional) APP-TA APP-TA -232.5
C-17 Structural
concrete None
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, Multi-Max FA3
CR-20, 6-
inch o.c.
0.5-inch SECUROCK Cement Roof
Board
CR-20, 6-
inch o.c. SBS-TA (Optional) SBS-TA SBS-TA -232.5
C-18 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-TA, APP-
TA
(Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -282.5
C-19 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof Board
CR-20 SBS-TA, APP-
TA
(Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -322.5
C-20 Structural
concrete None (Optional) Min. 2-inch Polytherm,
ACFoam II, Polytherm H or H-Shield
OB Classic
(full-
coverage)
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
OB Classic
(full-
coverage)
BP-AA, SBS-AA (Optional) BP-AA,
SBS-AA SBS-AA -225.0
C-21 Structural
concrete None (Optional) Min. 2-inch Polytherm,
ACFoam II, Polytherm H or H-Shield
OB Classic
(full-
coverage)
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
OB Classic
(full-
coverage)
APP-TA (Optional) APP-TA APP-TA -232.5
C-22 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board Hot asphalt BP-AA, SBS-AA (Optional) BP-AA,
SBS-AA SBS-AA -225.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 57 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-23 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board Hot asphalt APP-TA (Optional) APP-TA APP-TA -232.5
C-24 Structural
concrete PG100 Min. 0.75-inch Fesco Board
(homogeneous) Hot asphalt None N/A
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA, SBS-TA,
APP-TA -277.5
C-25 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.75-inch Fesco Board
(homogeneous) Hot asphalt
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA, SBS-TA,
APP-TA -290.0
C-26 Structural
concrete PG100 Min. 0.5-inch Structodek High Density
Fiberboard Roof Insulation Hot asphalt None N/A
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA, SBS-TA,
APP-TA -285.0
C-27 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt
Min. 0.5-inch Structodek High
Density Fiberboard Roof
Insulation
Hot asphalt
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA, SBS-TA,
APP-TA -480.0
C-28 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.25-inch DensDeck Prime Hot asphalt
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA, SBS-TA,
APP-TA -480.0
C-29 Structural
concrete PG100 Min. 0.25-inch DensDeck Prime Hot asphalt None N/A
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA, SBS-TA,
APP-TA -510.0
SELF-ADHERING BASE PLY TO INSULATION:
C-30 Structural
concrete
(Optional)
PG100 Min. 1.5-inch H-Shield or Multi-Max FA3 D-IS (Optional) additional layers(s) of
base insulation D-IS SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -67.5
C-31 Structural
concrete None Min. 1.5-inch Polytherm H, H-Shield D-IS (Optional) additional layers(s) of
base insulation D-IS SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -122.5
C-32 Structural
concrete
(Optional)
PG100
Min. 1.5-inch Polytherm, ACFoam II or
ENRGY 3 D-IS (Optional) additional layers(s) of
base insulation D-IS SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -135.0
C-33 Structural
concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam D-IS (Optional) additional layers of
base insulation D-IS SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -157.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 58 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-34 Structural
concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 (Optional) additional layers of
base insulation OB500 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -120.0
C-35 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II OB500 (Optional) additional layers(s) of
base insulation OB500 SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -122.5
C-36 Structural
concrete None Min. 1.5-inch ENRGY 3 OB500 (Optional) additional layers(s) of
base insulation OB500 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -127.5
C-37 Structural
concrete None Min. 1.5-inch Polytherm H or H-Shield OB500 (Optional) additional layers(s) of
base insulation OB500 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -150.0
C-38 Structural
concrete None ACFoam-HD Coverboard, ACFoam-HD
Coverboard-FR or H-Shield HD OB500 None N/A SBS-SA (Optional) SBS-SA SBS-SA -230.0
C-39 Structural
concrete None ACFoam-HD Coverboard, ACFoam-HD
Coverboard-FR or H-Shield HD
OB500, 6-
inch o.c. None N/A SBS-SA (Optional) SBS-SA SBS-SA -285.0
C-40 Structural
concrete None
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-
Shield
M-OSFA or
M-PG1
(Optional) additional layers(s) of
base insulation
M-OSFA or
M-PG1 SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -122.5
C-41 Structural
concrete None ACFoam-HD Coverboard, ACFoam-HD
Coverboard-FR or H-Shield HD
M-OSFA or
M-PG1 None N/A SBS-SA (Optional) SBS-SA SBS-SA -230.0
C-42 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of
base insulation M-OSFA SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -232.5
C-43 Structural
concrete None ACFoam-HD Coverboard, ACFoam-HD
Coverboard-FR or H-Shield HD
M-OSFA or
M-PG1, 6-
inch o.c.
None N/A SBS-SA (Optional) SBS-SA SBS-SA -285.0
C-44 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3, Polytherm H,
H-Shield, ISO 95+ GL, Multi-Max FA3,
RESISTA or UltraMax.
M-OSFA or
M-PG1
(Optional) additional layers(s) of
base insulation, optionally
primed with POLYBRITE 745 or
WB3000
M-OSFA or
M-PG1 SBS-SA None SBS-CA1, SBS-
CA2 -290.0
C-45 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
Polytherm H, H-Shield CR-20 (Optional) additional layers(s) of
base insulation CR-20 SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -122.5
C-46 Structural
concrete None ACFoam-HD Coverboard, ACFoam-HD
Coverboard-FR or H-Shield HD CR-20 None N/A SBS-SA (Optional) SBS-SA SBS-SA -230.0
C-47 Structural
concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers of
base insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -240.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 59 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-48 Structural
concrete None ACFoam-HD Coverboard, ACFoam-HD
Coverboard-FR or H-Shield HD
CR-20, 6-
inch o.c. None N/A SBS-SA (Optional) SBS-SA SBS-SA -285.0
C-49 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
OB Classic
(full-
coverage)
(Optional) additional layers(s) of
base insulation
OB Classic
(full-
coverage)
SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -270.0
C-50 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt (Optional) additional layers(s) of
base insulation Hot asphalt SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -480.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY TO INSULATION:
C-51 Structural
concrete
(Optional)
PG100 Min. 1.5-inch H-Shield or Multi-Max FA3 D-IS (Optional) additional layers(s) of
base insulation D-IS APP-SA-H (Optional) APP-TA APP-TA -67.5
C-52 Structural
concrete None Min. 1.5-inch Polytherm H, H-Shield D-IS (Optional) additional layers(s) of
base insulation D-IS APP-SA-H (Optional) APP-TA APP-TA -122.5
C-53 Structural
concrete
(Optional)
PG100
Min. 1.5-inch Polytherm, ACFoam II or
ENRGY 3 D-IS (Optional) additional layers(s) of
base insulation D-IS APP-SA-H (Optional) APP-TA APP-TA -135.0
C-54 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II OB500 (Optional) additional layers(s) of
base insulation OB500 APP-SA-H (Optional) APP-TA APP-TA -122.5
C-55 Structural
concrete None Min. 1.5-inch ENRGY 3 OB500 (Optional) additional layers(s) of
base insulation OB500 APP-SA-H (Optional) APP-TA APP-TA -127.5
C-56 Structural
concrete None Min. 1.5-inch Polytherm H or H-Shield OB500 (Optional) additional layers(s) of
base insulation OB500 APP-SA-H (Optional) APP-TA APP-TA -150.0
C-57 Structural
concrete None
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-
Shield
M-OSFA or
M-PG1
(Optional) additional layers(s) of
base insulation
M-OSFA or
M-PG1 APP-SA-H (Optional) APP-TA APP-TA -122.5
C-58 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of
base insulation M-OSFA APP-SA-H (Optional) APP-TA APP-TA -232.5
C-59 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
Polytherm H, H-Shield CR-20 (Optional) additional layers(s) of
base insulation CR-20 APP-SA-H (Optional) APP-TA APP-TA -122.5
C-60 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
OB Classic
(full-
coverage)
(Optional) additional layers(s) of
base insulation
OB Classic
(full-
coverage)
APP-SA-H (Optional) APP-TA APP-TA -270.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 60 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-61 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt (Optional) additional layers(s) of
base insulation Hot asphalt APP-SA-H (Optional) APP-TA APP-TA -480.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY TO INSULATION:
C-62 Structural
concrete
(Optional)
PG100 Min. 1.5-inch H-Shield or Multi-Max FA3 D-IS (Optional) additional layers(s) of
base insulation D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -67.5
C-63 Structural
concrete None Min. 1.5-inch Polytherm H, H-Shield D-IS (Optional) additional layers(s) of
base insulation D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -122.5
C-64 Structural
concrete
(Optional)
PG100
Min. 1.5-inch Polytherm, ACFoam II or
ENRGY 3 D-IS (Optional) additional layers(s) of
base insulation D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -135.0
C-65 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II OB500 (Optional) additional layers(s) of
base insulation OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -122.5
C-66 Structural
concrete None Min. 1.5-inch ENRGY 3 OB500 (Optional) additional layers(s) of
base insulation OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -127.5
C-67 Structural
concrete None Min. 1.5-inch Polytherm H or H-Shield OB500 (Optional) additional layers(s) of
base insulation OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -150.0
C-68 Structural
concrete None
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-
Shield
M-OSFA or
M-PG1
(Optional) additional layers(s) of
base insulation
M-OSFA or
M-PG1 SBS-SA-H (Optional) SBS-TA SBS-TA -122.5
C-69 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA (Optional) additional layers(s) of
base insulation M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -232.5
C-70 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
Polytherm H, H-Shield CR-20 (Optional) additional layers(s) of
base insulation CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -122.5
C-71 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
OB Classic
(full-
coverage)
(Optional) additional layers(s) of
base insulation
OB Classic
(full-
coverage)
SBS-SA-H (Optional) SBS-TA SBS-TA -270.0
C-72 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt (Optional) additional layers(s) of
base insulation Hot asphalt SBS-SA-H (Optional) SBS-TA SBS-TA -480.0
SELF-ADHERING BASE PLY TO COVERBOARD:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 61 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-73 Structural
concrete None Min. 1.5-inch Multi-Max FA3 D-IS
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber Roof
Board
D-IS SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -67.5
C-74 Structural
concrete None
Min. 1.5-inch, min. 2.0 pcf Insulfoam,
Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield
D-IS Min. 0.25-inch DensDeck Prime D-IS SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5
C-75 Structural
concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch DensDeck,
DensDeck Prime D-IS SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -120.0
C-76 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS
Min. 0.25-inch DensDeck Prime
optionally primed with
POLYBRITE 745 or WB3000
D-IS SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -282.5
C-77 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS Min. 0.25-inch DEXcell FA Glass
Mat Roof Board D-IS SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -322.5
C-78 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
D-IS SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -322.5
C-79 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or ISO 95+GL OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5
C-80 Structural
concrete None Min. 1.5-inch ENRGY 3 OB500 Min. 0.25-inch DensDeck,
DensDeck Prime OB500 SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -127.5
C-81 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II, H-
Shield or ISO 95+GL OB500 Min. 0.25-inch DensDeck,
DensDeck Prime OB500 SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -150.0
C-82 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield or min. 2.0 pcf
Insulfoam
OB500
ACFoam-HD Coverboard,
ACFoam-HD Coverboard-FR or H-
Shield HD
OB500 SBS-SA (Optional) SBS-SA SBS-SA -230.0
C-83 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -282.5
C-84 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500
ACFoam-HD Coverboard,
ACFoam-HD Coverboard-FR or H-
Shield HD
OB500, 6-
inch o.c. SBS-SA (Optional) SBS-SA SBS-SA -285.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 62 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-85 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500 Min. 0.25-inch DEXcell FA Glass
Mat Roof Board OB500 SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -322.5
C-86 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
OB500 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -322.5
C-87 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch DensDeck Prime M-OSFA SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5
C-88 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield or min. 2.0 pcf
Insulfoam
M-OSFA or
M-PG1
ACFoam-HD Coverboard,
ACFoam-HD Coverboard-FR or H-
Shield HD
M-OSFA or
M-PG1 SBS-SA (Optional) SBS-SA SBS-SA -230.0
C-89 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board M-OSFA SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -232.5
C-90 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1 Min. 0.25-inch DensDeck Prime M-OSFA or
M-PG1 SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -282.5
C-91 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
ACFoam-HD Coverboard,
ACFoam-HD Coverboard-FR or H-
Shield HD
M-OSFA or
M-PG1, 6-
inch o.c.
SBS-SA (Optional) SBS-SA SBS-SA -285.0
C-92 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch DEXcell FA Glass
Mat Roof Board
M-OSFA or
M-PG1 SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -322.5
C-93 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
M-OSFA or
M-PG1 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -322.5
C-94 Structural
concrete None
Min. 1.5-inch, min. 2.0 pcf Insulfoam,
Min. 2-inch Polytherm, ACFoam II, min.
1.5-inch Ultra-Max or Multi-Max FA-3,
min. 1.3-inch Polytherm G, ACFoam III or
min. 1.0-inch ISO 95+GL, Polytherm H, H-
Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch DensDeck,
DensDeck Prime CR-20 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -72.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 63 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-95 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield or min. 2.0 pcf
Insulfoam
CR-20
ACFoam-HD Coverboard,
ACFoam-HD Coverboard-FR or H-
Shield HD
CR-20 SBS-SA (Optional) SBS-SA SBS-SA -230.0
C-96 Structural
concrete None
Min. 1.5-inch, min. 2.0 pcf Insulfoam,
Min. 1.5-inch Ultra-Max or Multi-Max FA-
3, min. 1.3-inch Polytherm G, ACFoam III
or min. 1.0-inch ISO 95+GL, Polytherm H,
H-Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch DensDeck,
DensDeck Prime CR-20 SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -240.0
C-97 Structural
concrete None
Min. 1.5-inch Ultra-Max or Multi-Max FA-
3, min. 1.3-inch Polytherm G, ACFoam III
or min. 1.0-inch ISO 95+GL, Polytherm H,
H-Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -240.0
C-98 Structural
concrete None Min. 1.5-inch min. 2.0 pcf Insulfoam CR-20
ACFoam-HD Coverboard,
ACFoam-HD Coverboard-FR or H-
Shield HD
CR-20, 6-
inch o.c. SBS-SA (Optional) SBS-SA SBS-SA -240.0
C-99 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -282.5
C-100 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20
ACFoam-HD Coverboard,
ACFoam-HD Coverboard-FR or H-
Shield HD
CR-20, 6-
inch o.c. SBS-SA (Optional) SBS-SA SBS-SA -285.0
C-101 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20 Min. 0.25-inch DEXcell FA Glass
Mat Roof Board CR-20 SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -322.5
C-102 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000
CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -322.5
C-103 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
OB Classic
(full-
coverage)
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
OB Classic
(full-
coverage)
SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -350.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 64 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-104 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board Hot asphalt SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -350.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY TO COVERBOARD:
C-105 Structural
concrete None Min. 1.5-inch Multi-Max FA3 D-IS Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board D-IS APP-SA-H (Optional) APP-TA APP-TA -67.5
C-106 Structural
concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch DensDeck,
DensDeck Prime D-IS APP-SA-H (Optional) APP-TA APP-TA -120.0
C-107 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000 or
DEXcell FA Glass Mat Roof Board
D-IS APP-SA-H (Optional) APP-TA APP-TA -322.5
C-108 Structural
concrete None Min. 1.5-inch ENRGY 3 OB500 Min. 0.25-inch DensDeck,
DensDeck Prime OB500 APP-SA-H (Optional) APP-TA APP-TA -127.5
C-109 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II, H-
Shield or ISO 95+GL OB500 Min. 0.25-inch DensDeck,
DensDeck Prime OB500 APP-SA-H (Optional) APP-TA APP-TA -150.0
C-110 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof Board
OB500 APP-SA-H (Optional) APP-TA APP-TA -322.5
C-111 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof Board
M-OSFA or
M-PG1 APP-SA-H (Optional) APP-TA APP-TA -322.5
C-112 Structural
concrete None
Min. 1.5-inch, min. 2.0 pcf Insulfoam,
Min. 1.5-inch Ultra-Max or Multi-Max FA-
3, min. 1.3-inch Polytherm G, ACFoam III
or min. 1.0-inch ISO 95+GL, Polytherm H,
H-Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch DensDeck,
DensDeck Prime CR-20 APP-SA-H (Optional) APP-TA APP-TA -240.0
C-113 Structural
concrete None
Min. 1.5-inch Ultra-Max or Multi-Max FA-
3, min. 1.3-inch Polytherm G, ACFoam III
or min. 1.0-inch ISO 95+GL, Polytherm H,
H-Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 APP-SA-H (Optional) APP-TA APP-TA -240.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 65 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-114 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof Board
CR-20 APP-SA-H (Optional) APP-TA APP-TA -322.5
C-115 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
OB Classic
(full-
coverage)
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
OB Classic
(full-
coverage)
APP-SA-H (Optional) APP-TA APP-TA -350.0
C-116 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board Hot asphalt APP-SA-H (Optional) APP-TA APP-TA -350.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY TO COVERBOARD:
C-117 Structural
concrete None Min. 1.5-inch Multi-Max FA3 D-IS
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber Roof
Board
D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -67.5
C-118 Structural
concrete None Min. 1.5-inch, min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch DensDeck,
DensDeck Prime D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -120.0
C-119 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
ENRGY-3, Polytherm H or H-Shield D-IS Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -247.5
C-120 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS
Min. 0.25-inch DensDeck Prime
optionally primed with
POLYBRITE 745 or WB3000
D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -282.5
C-121 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
D-IS
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
optionally primed with
POLYBRITE 745 or WB3000 or
DEXcell FA Glass Mat Roof Board
D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -322.5
C-122 Structural
concrete None Min. 1.5-inch ENRGY 3 OB500 Min. 0.25-inch DensDeck,
DensDeck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -127.5
C-123 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II, H-
Shield or ISO 95+GL OB500 Min. 0.25-inch DensDeck,
DensDeck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -150.0
C-124 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
ENRGY-3, Polytherm H or H-Shield OB500 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -247.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 66 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-125 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -282.5
C-126 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
OB500
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof Board
OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -322.5
C-127 Structural
concrete None Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -232.5
C-128 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
ENRGY-3, Polytherm H or H-Shield M-OSFA Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -247.5
C-129 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1 Min. 0.25-inch DensDeck Prime M-OSFA or
M-PG1 SBS-SA-H (Optional) SBS-TA SBS-TA -282.5
C-130 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
M-OSFA or
M-PG1
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof Board
M-OSFA or
M-PG1 SBS-SA-H (Optional) SBS-TA SBS-TA -322.5
C-131 Structural
concrete None
Min. 1.5-inch, min. 2.0 pcf Insulfoam,
Min. 1.5-inch Ultra-Max or Multi-Max FA-
3, min. 1.3-inch Polytherm G, ACFoam III
or min. 1.0-inch ISO 95+GL, Polytherm H,
H-Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch DensDeck,
DensDeck Prime CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0
C-132 Structural
concrete None
Min. 1.5-inch Ultra-Max or Multi-Max FA-
3, min. 1.3-inch Polytherm G, ACFoam III
or min. 1.0-inch ISO 95+GL, Polytherm H,
H-Shield, H-Shield CG or ENRGY 3
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0
C-133 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
ENRGY-3, Polytherm H or H-Shield CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -247.5
C-134 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -282.5
C-135 Structural
concrete None
(Optional) Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board or
DEXcell FA Glass Mat Roof Board
CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -322.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 67 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-136 Structural
concrete None Min. 2-inch Polytherm, ACFoam II,
Polytherm H or H-Shield
OB Classic
(full-
coverage)
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
OB Classic
(full-
coverage)
SBS-SA-H (Optional) SBS-TA SBS-TA -350.0
C-137 Structural
concrete PG100
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
Hot asphalt Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board Hot asphalt SBS-SA-H (Optional) SBS-TA SBS-TA -350.0
COLD-APPLIED BASE PLY:
C-138 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H or H-Shield
D-IS
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof Board
or SECUROCK Gypsum-Fiber Roof
Board
D-IS SBS-CA1, SBS-
CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
C-139 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H or
H-Shield
D-IS
Min. 0.25-inch DensDeck Prime
or DEXcell FA Glass Mat Roof
Board
D-IS SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-140 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H or
H-Shield
D-IS Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board D-IS SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-141 Structural
concrete None Min. 1-inch ENRGY 3, Polytherm H or H-
Shield D-IS
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber Roof
Board
D-IS SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2 -232.5
C-142 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3, Polytherm H,
H-Shield ISO 95+ GL, Multi-Max FA3,
RESISTA or UltraMax or min. 2-inch
Styrofoam Brand Roofmate, Highload 60
or Plazamate
M-OSFA,
M-PG1
Min. 0.25-inch DensDeck,
DensDeck Prime, DEXcell FA Glass
Mat Roof Board, SECUROCK
Gypsum-Fiber Roof Board or
SECUROCK Glass-Mat Roof Board,
min. 7/16-inch DEXcell Cement
Roof Board or min. 0.5-inch
SECUROCK Cement Roof Board
M-OSFA or
M-PG1
SBS-CA1, SBS-
CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 68 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-143 Structural
concrete None
Min. 1-inch Polytherm or ACFoam II,
Polytherm G, ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3, Polytherm H,
H-Shield, ISO 95+ GL, Multi-Max FA3,
RESISTA or UltraMax or min. 2-inch
Styrofoam Brand Roofmate, Highload 60
or Plazamate
M-OSFA,
M-PG1
Min. 0.25-inch DensDeck Prime
or DEXcell FA Glass Mat Roof
Board, min. 7/16-inch DEXcell
Cement Roof Board or min. 0.5-
inch SECUROCK Cement Roof
Board
M-OSFA,
M-PG1 SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-144 Structural
concrete None
Min. 1-inch Polytherm or ACFoam II,
Polytherm G, ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3, Polytherm H,
H-Shield, ISO 95+ GL, Multi-Max FA3,
RESISTA or UltraMax or min. 2-inch
Styrofoam Brand Roofmate, Highload 60
or Plazamate
M-OSFA,
M-PG1
Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board
M-OSFA,
M-PG1
SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-145 Structural
concrete None
Min. 1-inch Polytherm or ACFoam II,
Polytherm G, ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3, Polytherm H,
H-Shield, ISO 95+ GL, Multi-Max FA3,
RESISTA or UltraMax or min. 2-inch
Styrofoam Brand Roofmate, Highload 60
or Plazamate
M-OSFA,
M-PG1
Min. 0.25-inch DensDeck,
DensDeck Prime, DEXcell FA Glass
Mat Roof Board, SECUROCK
Gypsum-Fiber Roof Board or
SECUROCK Glass-Mat Roof Board,
min. 7/16-inch DEXcell Cement
Roof Board or min. 0.5-inch
SECUROCK Cement Roof Board
M-OSFA,
M-PG1
SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2 -232.5
C-146 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield or Multi-Max FA3
OB500
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof Board
or SECUROCK Gypsum-Fiber Roof
Board
OB500 SBS-CA1, SBS-
CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
C-147 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield or Multi-Max FA3
OB500
Min. 0.25-inch DensDeck Prime
or DEXcell FA Glass Mat Roof
Board
OB500 SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-148 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield or Multi-Max FA3
OB500 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board OB500 SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-149 Structural
concrete None Min. 1-inch Polytherm, ACFoam II, ENRGY
3 or Multi-Max FA3 OB500
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof Board
or SECUROCK Gypsum-Fiber Roof
Board
OB500 SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2 -232.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 69 of 98
TABLE 3A: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
NOTE: FOR VAPOR BARRIER OPTIONS REFER TO NOTE 16
System
No.
Deck
(Note 1) Primer
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
C-150 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield or Multi-Max FA3
CR-20
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber Roof
Board
CR-20 SBS-CA1, SBS-
CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
C-151 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield or Multi-Max FA3
CR-20
Min. 0.25-inch DensDeck Prime
or DEXcell FA Glass Mat Roof
Board
CR-20 SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-152 Structural
concrete None
Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3,
Polytherm H, H-Shield or Multi-Max FA3
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
C-153 Structural
concrete None Min. 1-inch ENRGY 3, Polytherm H, H-
Shield, Multi-Max FA3 CR-20
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber Roof
Board
CR-20 SBS-CA1, SBS-
CA2 None SBS-CA1, SBS-
CA2 -232.5
TABLE 3B: STRUCTURAL CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE F: NON-INSULATED, BONDED BASE SHEET, BONDED ROOF COVER
System
No.
Deck
(Note 1) Primer Roof Cover (Note 15) MDP (psf) Base Ply Ply Cap Ply
ASPHALT- OR TORCH-APPLIED BASE PLY:
C-154 Structural concrete PG100 (Optional) SBS-TA (Optional) SBS-TA SBS-TA -495.0
C-155 Structural concrete PG100 BP-AA (Optional if using asphalt applied Ply) (Optional if using asphalt applied Base) BP-AA,
SBS-AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -622.5
SELF-ADHERING BASE PLY:
C-156 Structural concrete PG100 SBS-SA (Optional) SBS-SA, SBS-TA, APP-TA SBS-SA, APP-SA, SBS-TA, APP-TA -315.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
C-157 Structural concrete PG100 APP-SA-H (Optional) APP-TA APP-TA -315.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
C-158 Structural concrete PG100 SBS-SA-H (Optional) SBS-TA SBS-TA -315.0
COLD-APPLIED BASE PLY:
C-159 Structural concrete None SBS-CA1 None SBS-CA1, SBS-CA2, APP-CA1 -105.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 70 of 98
TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Lightweight Concrete
(Note 14)
Base Insulation Layer Coverboard Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
CELCORE (FL2037):
ASPHALT OR TORCH APPLIED BASE PLY:
LWC-1 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 BP-AA, SBS-
AA, APP-TA
(Optional) BP-
AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA, SBS-
TA, APP-TA -222.5
SELF-ADHERING BASE PLY:
LWC-2 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA (Optional) SBS-
SA
SBS-SA, APP-
SA -222.5
LWC-3 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-222.5
LWC-4 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-222.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
LWC-5 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 APP-SA-H (Optional) APP-
TA APP-TA -222.5
LWC-6 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 APP-SA-H (Optional) APP-
TA APP-TA -222.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
LWC-7 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA-H (Optional) SBS-
TA SBS-TA -222.5
LWC-8 Structural
concrete
Min. 200 psi, min. 2-inch
Celcore Cellular Concrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 SBS-SA-H (Optional) SBS-
TA SBS-TA -222.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 71 of 98
TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Lightweight Concrete
(Note 14)
Base Insulation Layer Coverboard Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ELASTIZELL (FL4994):
ASPHALT OR TORCH APPLIED BASE PLY:
LWC-9 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 BP-AA, SBS-
AA, APP-TA
(Optional) BP-
AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA, SBS-
TA, APP-TA -225.0
LWC-10 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 BP-AA, SBS-
AA, APP-TA
(Optional) BP-
AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA, SBS-
TA, APP-TA -180.0
SELF-ADHERING BASE PLY:
LWC-11 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500
(Optional)
Additional layers of
base insulation
OB500 SBS-SA (Optional) SBS-
SA
SBS-SA, APP-
SA -120.0
LWC-12 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-120.0
LWC-13 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
(Optional)
Additional layers of
base insulation
OB500 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-225.0
LWC-14 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-225.0
LWC-15 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA (Optional) SBS-
SA
SBS-SA, APP-
SA -180.0
LWC-16 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-180.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 72 of 98
TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Lightweight Concrete
(Note 14)
Base Insulation Layer Coverboard Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
LWC-17 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-180.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
LWC-18 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 APP-SA-H (Optional) APP-
TA APP-TA -120.0
LWC-19 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
(Optional)
Additional layers of
base insulation
OB500 APP-SA-H (Optional) APP-
TA APP-TA -225.0
LWC-20 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 APP-SA-H (Optional) APP-
TA APP-TA -225.0
LWC-21 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 APP-SA-H (Optional) APP-
TA APP-TA -180.0
LWC-22 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 APP-SA-H (Optional) APP-
TA APP-TA -180.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
LWC-23 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 SBS-SA-H (Optional) SBS-
TA SBS-TA -120.0
LWC-24 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
(Optional)
Additional layers of
base insulation
OB500 SBS-SA-H (Optional) SBS-
TA SBS-TA -225.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 73 of 98
TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Lightweight Concrete
(Note 14)
Base Insulation Layer Coverboard Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
LWC-25 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
ISO 95+ GL, Polytherm H or H-Shield OB500
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
OB500 SBS-SA-H (Optional) SBS-
TA SBS-TA -225.0
LWC-26 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA-H (Optional) SBS-
TA SBS-TA -180.0
LWC-27 Structural
concrete
Min. 200 psi, min 2-inch
Range II Elastizell
Lightweight Insulating
Concrete.
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 SBS-SA-H (Optional) SBS-
TA SBS-TA -180.0
MEARLCRETE (FL13492):
ASPHALT OR TORCH APPLIED BASE PLY:
LWC-28 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 BP-AA, SBS-
AA, APP-TA
(Optional) BP-
AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA, SBS-
TA, APP-TA -222.5
SELF-ADHERING BASE PLY:
LWC-29 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA (Optional) SBS-
SA
SBS-SA, APP-
SA -222.5
LWC-30 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-222.5
LWC-31 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA,
APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-222.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
LWC-32 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 APP-SA-H (Optional) APP-
TA APP-TA -222.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 74 of 98
TABLE 4A: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Lightweight Concrete
(Note 14)
Base Insulation Layer Coverboard Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
LWC-33 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 APP-SA-H (Optional) APP-
TA APP-TA -222.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
LWC-34 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3
CR-20
(Optional)
Additional layers of
base insulation
CR-20 SBS-SA-H (Optional) SBS-
TA SBS-TA -222.5
LWC-35 Structural
concrete
Min. 200 psi, min. 2-inch
Mearlcrete
Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, ISO 95+
GL, Polytherm H, H-Shield, H-Shield CG, Multi-
Max FA3 or min. 2.0 pcf Insulfoam
CR-20
Min. 0.25-inch
SECUROCK
Gypsum-Fiber Roof
Board
CR-20 SBS-SA-H (Optional) SBS-
TA SBS-TA -222.5
TABLE 4B: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Lightweight
Concrete
(Note 14)
Anchor Sheet
Temp
Roof
Base Insulation Top Insulation Roof Cover (Note 15)
MDP
(psf) Type Fasten
(Note 11) Attach Type
Attach
(Notes
6,7,8)
Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
LWC-36
Min. 22
ga., Type
B, vented
steel at
max. 5 ft
spans
Min. 300 psi,
min. 2-inch
Celcore Cellular
Concrete,
Elastizell
Lightweight
Insulating
Concrete or
Mearlcrete
GAFGLAS
#75 or
Elastovent
OMG CR
BSF
7-inch o.c. at
min. 4-inch
lap and 7-
inch o.c. at
two, equally
spaced
center rows
(Optional)
SBS-TA
(sanded-
top-
surface)
(Optional)
Min. 1.5-inch
Polytherm,
ACFoam II,
Polytherm H,
H-Shield,
Multi-Max
FA3 or
Polytherm
HA
Min. 1.5-inch
Thermaroof
Composite,
Polytherm
Composite, or min.
0.5-inch Structodek
High Density
Fiberboard Roof
Insulation or min.
0.75-inch Fesco
Board
(homogeneous)
HA
(Optional if
using AA
Ply) BP-AA,
SBS-AA
(Optional if
using AA
Base) BP-
AA, SBS-AA,
SBS-TA or
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 75 of 98
TABLE 4B: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Lightweight
Concrete
(Note 14)
Anchor Sheet
Temp
Roof
Base Insulation Top Insulation Roof Cover (Note 15)
MDP
(psf) Type Fasten
(Note 11) Attach Type
Attach
(Notes
6,7,8)
Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
LWC-37
Min. 22
ga., type B
steel at
max 5 ft
spans or
structural
concrete
Min. 300 psi,
min. 2-inch
thick Celcore
MF Cellular
Concrete with
Celcore HS
Rheology
Modifying
Admixture
Elastobase
V,
Elastobase
P or
Elastovent
Trufast
FM-90
8-inch o.c. at
a min. 4-inch
lap and 8-
inch o.c. at
three equally
spaced,
staggered
center rows
SBS-TA
(sanded-
top-
surface)
Min. 2-inch
Polytherm,
ACFoam II, III,
Polytherm H,
H-Shield, H-
Shield CG,
Multi-Max
FA3 or
ENRGY-3
M-OSFA,
6-inch
o.c.
Additional
Insulation Layer(s):
(Optional) Min. 0.5-
inch base insulation
flat or tapered
Coverboard: Min.
0.25-inch DensDeck
Prime or SECUROCK
Gypsum-Fiber Roof
Board
Additional
Layer(s): M-
OSFA, 4-inch
o.c.
Coverboard:
M-OSFA, 6-
inch o.c.
BP-AA, SBS-
AA, SBS-TA,
APP-TA
(Optional)
BP-AA, SBS-
AA, SBS-TA,
APP-TA
SBS-AA,
SBS-TA,
APP-TA
-60.0*
LWC-38
Min. 22
ga., Type
B, vented
steel at
max. 5 ft
spans
Min. 300 psi,
min. 2-inch
Celcore Cellular
Concrete,
Elastizell
Lightweight
Insulating
Concrete or
Mearlcrete
GAFGLAS
#75 or
Elastovent
OMG CR
BSF
7-inch o.c. at
min. 4-inch
lap and 7-
inch o.c. at
two, equally
spaced
center rows
(Optional)
SBS-TA
(sanded-
top-
surface)
Min. 1.5-inch
Polytherm,
ACFoam II,
Polytherm H,
H-Shield,
Multi-Max
FA3 or
Polytherm
HA None N/A SBS-SA
(Optional)
SBS-SA,
SBS-TA,
APP-TA
SBS-SA,
APP-SA,
SBS-TA,
APP-TA
-45.0
LWC-39
Min. 22
ga., type B
steel at
max 5 ft
spans or
structural
concrete
Min. 300 psi,
min. 2-inch
thick Celcore
MF Cellular
Concrete with
Celcore HS
Rheology
Modifying
Admixture
Elastobase
V,
Elastobase
P or
Elastovent
Trufast
FM-90
8-inch o.c. at
a min. 4-inch
lap and 8-
inch o.c. at
three equally
spaced,
staggered
center rows
SBS-TA
(sanded-
top-
surface)
Min. 2-inch
Polytherm,
ACFoam II, III,
Polytherm H,
H-Shield, H-
Shield CG,
Multi-Max
FA3 or
ENRGY-3
M-OSFA,
6-inch
o.c.
(Optional)
Additional layers of
base insulation,
min. 0.5-inch, flat
or tapered
M-OSFA, 4-
inch o.c. SBS-SA
(Optional)
SBS-TA,
APP-TA
SBS-TA,
APP-TA -60.0*
LWC-40
Min. 22
ga., Type
B, vented
steel at
max. 5 ft
spans
Min. 300 psi,
min. 2-inch
Celcore Cellular
Concrete,
Elastizell
Lightweight
Insulating
Concrete or
Mearlcrete
GAFGLAS
#75 or
Elastovent
OMG CR
BSF
7-inch o.c. at
min. 4-inch
lap and 7-
inch o.c. at
two, equally
spaced
center rows
(Optional)
SBS-TA
(sanded-
top-
surface)
Min. 1.5-inch
Polytherm,
ACFoam II,
Polytherm H,
H-Shield,
Multi-Max
FA3 or
Polytherm
HA None N/A APP-SA-H (Optional)
APP-TA APP-TA -45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 76 of 98
TABLE 4B: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Lightweight
Concrete
(Note 14)
Anchor Sheet
Temp
Roof
Base Insulation Top Insulation Roof Cover (Note 15)
MDP
(psf) Type Fasten
(Note 11) Attach Type
Attach
(Notes
6,7,8)
Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
LWC-41
Min. 22
ga., Type
B, vented
steel at
max. 5 ft
spans
Min. 300 psi,
min. 2-inch
Celcore Cellular
Concrete,
Elastizell
Lightweight
Insulating
Concrete or
Mearlcrete
GAFGLAS
#75 or
Elastovent
OMG CR
BSF
7-inch o.c. at
min. 4-inch
lap and 7-
inch o.c. at
two, equally
spaced
center rows
(Optional)
SBS-TA
(sanded-
top-
surface)
Min. 1.5-inch
Polytherm,
ACFoam II,
Polytherm H,
H-Shield,
Multi-Max
FA3 or
Polytherm
HA None N/A SBS-SA-H (Optional)
SBS-TA SBS-TA -45.0
LWC-42
Min. 22
ga., type B
steel at
max 5 ft
spans or
structural
concrete
Min. 300 psi,
min. 2-inch
thick Celcore
MF Cellular
Concrete with
Celcore HS
Rheology
Modifying
Admixture
Elastobase
V,
Elastobase
P or
Elastovent
Trufast
FM-90
8-inch o.c. at
a min. 4-inch
lap and 8-
inch o.c. at
three equally
spaced,
staggered
center rows
SBS-TA
(sanded-
top-
surface)
Min. 2-inch
Polytherm,
ACFoam II, III,
Polytherm H,
H-Shield, H-
Shield CG,
Multi-Max
FA3 or
ENRGY-3
M-OSFA,
6-inch
o.c.
(Optional)
Additional layers of
base insulation,
min. 0.5-inch, flat
or tapered
M-OSFA, 4-
inch o.c. SBS-SA-H (Optional)
SBS-TA SBS-TA -60.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 77 of 98
TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1) Lightweight Concrete (Note 14) Base Sheet (Note A below) Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
PRE-EXISTENT CELLULAR LWC:
LWC-43
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick pre-existent
cellular lightweight concrete. Note: To
qualify the LWIC under this assembly, an
OMG CR BPF shall achieve an average
withdrawal of 53 lbf when tested per TAS
105 or ANSI/SPRI FX-1
B3 or B11 OMG CR BPF
7-inch o.c. at a min. 3-inch lap and 7-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
(Optional)
BP-AA,
SBS-AA
SBS-AA, APP-
TA -45.0
CELCORE (FL2037):
ASPHALT OR TORCH APPLIED BASE PLY:
LWC-44
Min. 0.0179-inch Tensilform S-
75 or min. 0.0205-inch
Tensilform 75 at max. 5 ft
spans or structural concrete
Min. 200 psi, min. 2-inch thick Celcore
Cellular Concrete
B1, B2, B3, B7 or
B11
Trufast FM-90 or
OMG CR BPF
8-inch o.c. at a min. 3-inch lap and 16-inch
o.c. at two, equally spaced, staggered rows in
the field of the sheet
BP-AA,
SBS-AA SBS-AA -37.5
LWC-45
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 200 psi, min. 2-inch thick Celcore
Cellular Concrete B1 through B11 Trufast FM-90 or
OMG CR BPF
7-inch o.c. at a min. 3-inch lap and 7-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
BP-AA,
SBS-AA SBS-AA -45.0
LWC-46
Min. 26 ga., type HF steel at
max 5 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
B1, B2, B3, B4,
B7, B8, B10 or
B11
OMG CR BPF
9-inch o.c. at a min. 3-inch lap and 9-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
BP-AA,
SBS-AA SBS-AA -45.0
LWC-47
Min. 22 ga., type B steel at
max 6 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
B1, B2, B3, B4,
B7, B8, B10 or
B11
OMG CR BPF
7-inch o.c. at a min. 3-inch lap and 14-inch
o.c. at two, equally spaced, staggered rows in
the field of the sheet
BP-AA,
SBS-AA SBS-AA -45.0
LWC-48
Min. 22 ga., type B steel at
max 6 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
B1, B2, B3, B4,
B7, B8, B10 or
B11
OMG CR BPF
9-inch o.c. at a min. 3-inch lap and 9-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
BP-AA,
SBS-AA SBS-AA -45.0
LWC-49
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
B1, B2 or B11 Trufast Twin Loc-
Nail
9-inch o.c. at a min. 4-inch lap and 18-inch
o.c. at two, equally spaced, staggered rows in
the field of the sheet
BP-AA,
SBS-AA,
SBS-TA or
APP-TA
SBS-AA, SBS-
TA, or APP-
TA
-45.0
LWC-50
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
B2 (with poly-
film top surface)
Trufast Twin Loc-
Nail
9-inch o.c. at a min. 4-inch lap and 18-inch
o.c. at two, equally spaced, staggered rows in
the field of the sheet
SBS-TA or
APP-TA
SBS-TA or
APP-TA -45.0
LWC-51
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
B2 or B11 Trufast FM-90
8-inch o.c. at a min. 4-inch lap and 8-inch o.c.
at three equally spaced, staggered center
rows
BP-AA,
SBS-AA,
SBS-TA or
APP-TA
SBS-AA, SBS-
TA, or APP-
TA
-60.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 78 of 98
TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1) Lightweight Concrete (Note 14) Base Sheet (Note A below) Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
LWC-52
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
B2 (with poly-
film top surface) Trufast FM-90
8-inch o.c. at a min. 4-inch lap and 8-inch o.c.
at three equally spaced, staggered center
rows
SBS-TA or
APP-TA
SBS-TA or
APP-TA -60.0
LWC-53
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick Celcore
Cellular Concrete B1 through B11 Trufast FM-90 or
OMG CR BPF
7-inch o.c. at a min. 3-inch lap and 7-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
BP-AA,
SBS-AA,
SBS-TA,
APP-TA
SBS-AA, APP-
TA -75.0
LWC-54
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
Elastobase P Trufast FM-290
10-inch o.c. at a min. 4-inch lap and 10-inch
o.c. at three equally spaced, staggered center
rows
(Optional)
BP-AA,
SBS-AA,
SBS-TA or
APP-TA
SBS-AA, SBS-
TA, APP-TA -90.0
SELF-ADHERING BASE PLY:
LWC-55
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
B2 (with poly-
film top surface)
Trufast Twin Loc-
Nail
9-inch o.c. at a min. 4-inch lap and 18-inch
o.c. at two, equally spaced, staggered rows in
the field of the sheet
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-45.0
LWC-56
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
B2 (with poly-
film top surface) Trufast FM-90
8-inch o.c. at a min. 4-inch lap and 8-inch o.c.
at three equally spaced, staggered center
rows
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-60.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
LWC-57
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
B2 (with poly-
film top surface)
Trufast Twin Loc-
Nail
9-inch o.c. at a min. 4-inch lap and 18-inch
o.c. at two, equally spaced, staggered rows in
the field of the sheet
APP-SA-H APP-TA -45.0
LWC-58
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
B2 (with poly-
film top surface) Trufast FM-90
8-inch o.c. at a min. 4-inch lap and 8-inch o.c.
at three equally spaced, staggered center
rows
APP-SA-H APP-TA -60.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
LWC-59
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 225 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
B2 (with poly-
film top surface)
Trufast Twin Loc-
Nail
9-inch o.c. at a min. 4-inch lap and 18-inch
o.c. at two, equally spaced, staggered rows in
the field of the sheet
SBS-SA-H SBS-TA -45.0
LWC-60
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick Celcore MF
Cellular Concrete with Celcore HS
Rheology Modifying Admixture
B2 (with poly-
film top surface) Trufast FM-90
8-inch o.c. at a min. 4-inch lap and 8-inch o.c.
at three equally spaced, staggered center
rows
SBS-SA-H SBS-TA -60.0
ELASTIZELL (FL4994):
ASPHALT OR TORCH APPLIED BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 79 of 98
TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1) Lightweight Concrete (Note 14) Base Sheet (Note A below) Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
LWC-61
Min. 0.0179-inch Tensilform S-
75 or min. 0.0205-inch
Tensilform 75 at max. 5 ft
spans or structural concrete
Min. 200 psi, min. 2-inch thick Range II
Elastizell Lightweight Insulating Concrete B1 through B11 Trufast FM-90 or
OMG CR BPF
7.5-inch o.c. at a min. 3-inch lap and 7.5-inch
o.c. at two, equally spaced, staggered rows in
the field of the sheet
BP-AA,
SBS-AA,
SBS-TA,
or APP-TA
SBS-AA, SBS-
TA, or APP-
TA
-30.0
LWC-62
Min. 0.0179-inch Tensilform S-
75 or min. 0.0205-inch
Tensilform 75 at max. 5 ft
spans or structural concrete
Min. 200 psi, min. 2-inch thick Range II
Elastizell Lightweight Insulating Concrete
B2 (with poly-
film top surface)
Trufast FM-90 or
OMG CR BPF
7.5-inch o.c. at a min. 3-inch lap and 7.5-inch
o.c. at two, equally spaced, staggered rows in
the field of the sheet
SBS-TA or
APP-TA
SBS-TA or
APP-TA -30.0
LWC-63
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 200 psi, min. 2-inch thick Range II
Elastizell Lightweight Insulating Concrete B1 through B11 Trufast FM-90 or
OMG CR BPF
7-inch o.c. at a min. 3-inch lap and 7-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
BP-AA,
SBS-AA,
SBS-TA,
or APP-TA
SBS-AA, SBS-
TA, or APP-
TA
-45.0
LWC-64
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 200 psi, min. 2-inch thick Range II
Elastizell Lightweight Insulating Concrete
B2 (with poly-
film top surface)
Trufast FM-90 or
OMG CR BPF
7-inch o.c. at a min. 3-inch lap and 7-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
SBS-TA or
APP-TA
SBS-TA or
APP-TA -45.0
LWC-65
Min. 22 ga., type B vented
steel at max 5 ft spans or
structural concrete
Min. 350 psi, min. 2-inch thick Elastizell
with Zell-Crete Fibers, supplemental
attached with Roofgrip #21 and 3-inch
plates at 1 per 8 ft2
Elastobase P
(with poly-film
top surface)
Trufast FM-290
8-inch o.c. at a min. 4-inch lap and 8-inch o.c.
at three, equally spaced, staggered rows in
the field of the sheet
(Optional)
BP-AA,
SBS-AA,
SBS-TA,
or APP-TA
SBS-AA, SBS-
TA, or APP-
TA
-52.5
LWC-66
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 350 psi, min. 2-inch thick Elastizell
with Zell-Crete Fibers, supplemental
attached with Roofgrip #21 and 3-inch
plates at 1 per 8 ft2
B2 or B11
Trufast Twin Loc-
Nails (min. 1.8-
inch)
6-inch o.c. at a min. 4-inch lap and 6-inch o.c.
at three, equally spaced, staggered rows in
the field of the sheet
BP-AA or
SBS-AA
SBS-AA, SBS-
TA, SBS-SA,
APP-TA or
APP-SA
-60.0
LWC-67
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 350 psi, min. 2-inch thick Elastizell
with Zell-Crete Fibers, supplemental
attached with Roofgrip #21 and 3-inch
plates at 1 per 8 ft2
B2 (with poly-
film top surface)
Trufast Twin Loc-
Nails (min. 1.8-
inch)
6-inch o.c. at a min. 4-inch lap and 6-inch o.c.
at three, equally spaced, staggered rows in
the field of the sheet
SBS-TA or
APP-TA
SBS-TA or
APP-TA -60.0
SELF-ADHERING BASE PLY:
LWC-68
Min. 0.0179-inch Tensilform S-
75 or min. 0.0205-inch
Tensilform 75 at max. 5 ft
spans or structural concrete
Min. 200 psi, min. 2-inch thick Range II
Elastizell Lightweight Insulating Concrete
B2 (with poly-
film top surface)
Trufast FM-90 or
OMG CR BPF
7.5-inch o.c. at a min. 3-inch lap and 7.5-inch
o.c. at two, equally spaced, staggered rows in
the field of the sheet
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-30.0
LWC-69
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 200 psi, min. 2-inch thick Range II
Elastizell Lightweight Insulating Concrete
B2 (with poly-
film top surface)
Trufast FM-90 or
OMG CR BPF
7-inch o.c. at a min. 3-inch lap and 7-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-45.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 80 of 98
TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1) Lightweight Concrete (Note 14) Base Sheet (Note A below) Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
LWC-70
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 350 psi, min. 2-inch thick Elastizell
with Zell-Crete Fibers, supplemental
attached with Roofgrip #21 and 3-inch
plates at 1 per 8 ft2
B2 (with poly-
film top surface)
Trufast Twin Loc-
Nails (min. 1.8-
inch)
6-inch o.c. at a min. 4-inch lap and 6-inch o.c.
at three, equally spaced, staggered rows in
the field of the sheet
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-60.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
LWC-71
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 200 psi, min. 2-inch thick Range II
Elastizell Lightweight Insulating Concrete
B2 (with poly-
film top surface)
Trufast FM-90 or
OMG CR BPF
7-inch o.c. at a min. 3-inch lap and 7-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
APP-SA-H APP-TA -45.0
LWC-72
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 350 psi, min. 2-inch thick Elastizell
with Zell-Crete Fibers, supplemental
attached with Roofgrip #21 and 3-inch
plates at 1 per 8 ft2
B2 (with poly-
film top surface)
Trufast Twin Loc-
Nails (min. 1.8-
inch)
6-inch o.c. at a min. 4-inch lap and 6-inch o.c.
at three, equally spaced, staggered rows in
the field of the sheet
APP-SA-H APP-TA -60.0
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
LWC-73
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 200 psi, min. 2-inch thick Range II
Elastizell Lightweight Insulating Concrete
B2 (with poly-
film top surface)
Trufast FM-90 or
OMG CR BPF
7-inch o.c. at a min. 3-inch lap and 7-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
SBS-SA-H SBS-TA -45.0
LWC-74
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 350 psi, min. 2-inch thick Elastizell
with Zell-Crete Fibers, supplemental
attached with Roofgrip #21 and 3-inch
plates at 1 per 8 ft2
B2 (with poly-
film top surface)
Trufast Twin Loc-
Nails (min. 1.8-
inch)
6-inch o.c. at a min. 4-inch lap and 6-inch o.c.
at three, equally spaced, staggered rows in
the field of the sheet
SBS-SA-H SBS-TA -60.0
MEARLCRETE (FL13492):
ASPHALT OR TORCH APPLIED BASE PLY:
LWC-75
Min. 24 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 200 psi, min. 2-inch thick Mearlcrete B1 through B11 Trufast FM-90 or
OMG CR BPF
7.5-inch o.c. at a min. 3-inch lap and 10-inch
o.c. at two, equally spaced, staggered rows in
the field of the sheet
BP-AA,
SBS-AA SBS-AA -30.0
LWC-76
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick Mearlcrete B1, B2, B3, B7 or
B11
Trufast FM-90 or
OMG CR BPF
7-inch o.c. at a min. 4-inch lap and 7-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
BP-AA,
SBS-AA,
SBS-TA,
or APP-TA
SBS-AA, SBS-
TA, or APP-
TA
-52.5
LWC-77
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick Mearlcrete B2 (with poly-
film top surface)
Trufast FM-90 or
OMG CR BPF
7-inch o.c. at a min. 4-inch lap and 7-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
SBS-TA or
APP-TA
SBS-TA or
APP-TA -52.5
SELF-ADHERING BASE PLY:
LWC-78
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick Mearlcrete B2 (with poly-
film top surface)
Trufast FM-90 or
OMG CR BPF
7-inch o.c. at a min. 4-inch lap and 7-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
SBS-SA
SBS-SA, APP-
SA, SBS-TA
or APP-TA
-52.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 81 of 98
TABLE 4C: LIGHTWEIGHT CONCRETE DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE E-2: MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No. Deck (Note 1) Lightweight Concrete (Note 14) Base Sheet (Note A below) Roof Cover (Note 15) MDP
(psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
LWC-79
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick Mearlcrete B2 (with poly-
film top surface)
Trufast FM-90 or
OMG CR BPF
7-inch o.c. at a min. 4-inch lap and 7-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
APP-SA-H APP-TA -52.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
LWC-80
Min. 22 ga., type B steel at
max 5 ft spans or structural
concrete
Min. 300 psi, min. 2-inch thick Mearlcrete B2 (with poly-
film top surface)
Trufast FM-90 or
OMG CR BPF
7-inch o.c. at a min. 4-inch lap and 7-inch o.c.
at two, equally spaced, staggered rows in the
field of the sheet
SBS-SA-H SBS-TA -52.5
A. Base Sheets options in Table 4C are coded as follows:
➢ B1: Polyglass G2 Base; B2: Elastobase V or Elastobase P; B3: GAFGLAS #75; B4: GAFGLAS Stratavent Nailable Venting Base Sheet; B5: GAFGLAS Ply 4; B6: GAFGLAS FlexPly 6; B7: JM Perma Ply No. 28; B8: JM
Vensulation; B9: JM GlasPly IV; B10: JM GlasPly Premier; B11: Elastovent
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 82 of 98
TABLE 5A: CEMENTITIOUS WOOD FIBER DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT OR TORCH APPLIED BASE PLY:
CWF-1
Existing Min. 2.5-inch
Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
D-IS or
OB500
Min. 0.25-inch DensDeck, DensDeck
Prime, SECUROCK Gypsum-Fiber Roof
Board or min. 0.5-inch Structodek High
Density Fiberboard Roof Insulation
D-IS or OB500 BP-AA, SBS-AA
(Optional) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA, SBS-
TA, APP-TA -45.0
CWF-2
Existing Min. 2.5-inch
Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
D-IS or
OB500
Min. 0.25-inch DensDeck, DensDeck
Prime, SECUROCK Gypsum-Fiber Roof
Board
D-IS or OB500 SBS-TA or APP-
TA
(Optional) SBS-TA
or APP-TA SBS-TA, APP-TA -45.0
CWF-3
Existing Min. 2.5-inch
Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
CR-20
Min. 0.25-inch DensDeck, DensDeck
Prime, SECUROCK Gypsum-Fiber Roof
Board or min. 0.5-inch Structodek High
Density Fiberboard Roof Insulation
CR-20 BP-AA, SBS-AA
(Optional) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA, SBS-
TA, APP-TA -52.5
CWF-4
Existing Min. 2.5-inch
Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
CR-20
Min. 0.25-inch DensDeck, DensDeck
Prime, SECUROCK Gypsum-Fiber Roof
Board
CR-20 SBS-TA or APP-
TA
(Optional) SBS-TA
or APP-TA SBS-TA, APP-TA -52.5
CWF-5 Tectum Plank
(Optional) Min. 1-inch
Polytherm, ACFoam II,
Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20 Min. 0.25-inch DensDeck Prime CR-20 BP-AA, SBS-AA
(Optional) BP-AA,
SBS-AA, SBS-TA or
APP-TA
SBS-AA, SBS-
TA, APP-TA -75.0
CWF-6 Tectum Plank
(Optional) Min. 1-inch
Polytherm, ACFoam II,
Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-TA or APP-
TA
(Optional) SBS-TA
or APP-TA SBS-TA, APP-TA -75.0
SELF-ADHERING BASE PLY:
CWF-7
Existing Min. 2.5-inch
Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
D-IS or
OB500
Min. 0.25-inch DensDeck, DensDeck
Prime, SECUROCK Gypsum-Fiber Roof
Board
D-IS or OB500 SBS-SA (Optional) SBS-SA,
SBS-TA or APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-45.0
CWF-8
Existing Min. 2.5-inch
Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
CR-20
Min. 0.25-inch DensDeck, DensDeck
Prime, SECUROCK Gypsum-Fiber Roof
Board
CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA or APP-TA
SBS-SA, APP-
SA, SBS-TA,
APP-TA
-52.5
CWF-9 Tectum Plank
(Optional) Min. 1-inch
Polytherm, ACFoam II,
Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA (Optional) SBS-TA,
APP-TA SBS-TA, APP-TA -75.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 83 of 98
TABLE 5A: CEMENTITIOUS WOOD FIBER DECKS – NEW CONSTRUCTION OR REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
CWF-10
Existing Min. 2.5-inch
Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
D-IS or
OB500
Min. 0.25-inch DensDeck, DensDeck
Prime, SECUROCK Gypsum-Fiber Roof
Board
D-IS or OB500 APP-SA-H (Optional) APP-TA APP-TA -45.0
CWF-11
Existing Min. 2.5-inch
Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
CR-20
Min. 0.25-inch DensDeck, DensDeck
Prime, SECUROCK Gypsum-Fiber Roof
Board
CR-20 APP-SA-H (Optional) APP-TA APP-TA -52.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
CWF-12
Existing Min. 2.5-inch
Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
D-IS or
OB500
Min. 0.25-inch DensDeck, DensDeck
Prime, SECUROCK Gypsum-Fiber Roof
Board
D-IS or OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -45.0
CWF-13
Existing Min. 2.5-inch
Tectum Plank or
Tectum LS Plank
Min. 1.5-inch Polytherm,
ACFoam II, ISO 95+GL,
Polytherm H, H-Shield, ENRGY-3
CR-20
Min. 0.25-inch DensDeck, DensDeck
Prime, SECUROCK Gypsum-Fiber Roof
Board
CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -52.5
CWF-14 Tectum Plank
(Optional) Min. 1-inch
Polytherm, ACFoam II,
Polytherm G, ACFoam III,
Polytherm H, H-Shield
CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -75.0
TABLE 5B: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15)
MDP (psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT OR TORCH APPLIED BASE PLY:
CWF-15
Existing Min.
2.5-inch
Tectum Plank
or Tectum LS
Plank
Elastobase V,
Elastobase P,
Elastovent or
Polyglass G2
Base
Trufast
Twin
Loc-Nail
9-inch o.c. at min.
4-inch lap and 18-
inch o.c. at two,
equally spaced,
staggered center
rows
Min. 1.5-inch
Polytherm, ACFoam II,
Polytherm G, ACFoam
III, ISO95+GL,
Polytherm H, H-
Shield, ENRGY 3 or
Multi-Max FA3,
Hot asphalt
Min. 0.25-inch DensDeck,
DensDeck Prime,
SECUROCK Gypsum-Fiber
Roof Board, Min. 0.75-
inch Fesco Board
(homogeneous) or min.
0.5-inch Structodek High
Density Fiberboard Roof
Insulation
Hot asphalt BP-AA,
SBS-AA
(Optional) BP-
AA, SBS-AA,
SBS-TA or APP-
TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 84 of 98
TABLE 5B: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15)
MDP (psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
CWF-16
Existing Min.
2.5-inch
Tectum Plank
or Tectum LS
Plank
Elastobase V,
Elastobase P,
Elastovent or
Polyglass G2
Base
Trufast
Twin
Loc-Nail
9-inch o.c. at min.
4-inch lap and 18-
inch o.c. at two,
equally spaced,
staggered center
rows
Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G,
ACFoam III, ISO95+GL,
Polytherm H, H-Shield,
ENRGY 3 or Multi-Max
FA3,
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt
SBS-TA
or APP-
TA
(Optional) SBS-
TA or APP-TA
SBS-TA,
APP-TA -45.0*
SELF-ADHERING BASE PLY:
CWF-17
Existing Min.
2.5-inch
Tectum Plank
or Tectum LS
Plank
Elastobase V,
Elastobase P,
Elastovent or
Polyglass G2
Base
Trufast
Twin
Loc-Nail
9-inch o.c. at min.
4-inch lap and 18-
inch o.c. at two,
equally spaced,
staggered center
rows
Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G,
ACFoam III, ISO95+GL,
Polytherm H, H-Shield,
ENRGY 3 or Multi-Max
FA3,
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA
(Optional) SBS-
TA, SBS-SA or
APP-TA
SBS-TA,
SBS-SA,
APP-TA,
APP-SA
-45.0*
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
CWF-18
Existing Min.
2.5-inch
Tectum Plank
or Tectum LS
Plank
Elastobase V,
Elastobase P,
Elastovent or
Polyglass G2
Base
Trufast
Twin
Loc-Nail
9-inch o.c. at min.
4-inch lap and 18-
inch o.c. at two,
equally spaced,
staggered center
rows
Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G,
ACFoam III, ISO95+GL,
Polytherm H, H-Shield,
ENRGY 3 or Multi-Max
FA3,
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt APP-SA-
H
(Optional) APP-
TA APP-TA -45.0*
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
CWF-19
Existing Min.
2.5-inch
Tectum Plank
or Tectum LS
Plank
Elastobase V,
Elastobase P,
Elastovent or
Polyglass G2
Base
Trufast
Twin
Loc-Nail
9-inch o.c. at min.
4-inch lap and 18-
inch o.c. at two,
equally spaced,
staggered center
rows
Min. 1.5-inch Polytherm,
ACFoam II, Polytherm G,
ACFoam III, ISO95+GL,
Polytherm H, H-Shield,
ENRGY 3 or Multi-Max
FA3,
Hot asphalt
Min. 0.25-inch
DensDeck, DensDeck
Prime, SECUROCK
Gypsum-Fiber Roof
Board
Hot asphalt SBS-SA-
H
(Optional) SBS-
TA SBS-TA -45.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 85 of 98
TABLE 5C: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE B-1: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15)
MDP (psf) Type Fasten (Note 11) Attach Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
CWF-20
Existing Min. 2.5-inch
Tectum Plank or
Tectum LS Plank
Min. 2-inch H-
Shield or
Polytherm H
OMG Polymer GypTec Plate
with Polymer GypTec or Trufast
TL 3 in. Plate with TL Fastener
1 per
4.0 ft2
Min. 0.5-inch Structodek
High Density Fiberboard
Roof Insulation
Hot asphalt
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
TABLE 5D: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer
(Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
CWF-21
Existing Min. 2.5-
inch Tectum
Plank or Tectum
LS Plank
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.25-inch DensDeck, DensDeck Prime or
SECUROCK Gypsum-Fiber Roof Board or min. 0.5-
inch Structodek High Density Fiberboard Roof
Insulation
Trufast Twin Loc-
Nails (min. 1-inch
embedment)
1 per
2.0 ft2
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
TABLE 5E: CEMENTITIOUS WOOD FIBER DECKS – REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
CWF-22
Existing Min. 2.5-
inch Tectum Plank or
Tectum LS Plank
Elastobase V, Elastobase P, Elastovent or
Polyglass G2 Base Trufast Twin Loc-Nails 9-inch o.c. at min. 4-inch lap and 18-inch o.c.
at two, equally spaced, staggered center rows
(Optional) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 86 of 98
TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT- OR TORCH-APPLIED BASE PLY:
G-1
Existing, sound poured
gypsum or gypsum
plank
Min. 0.25-inch DensDeck, DensDeck Prime or
SECUROCK Gypsum-Fiber Roof Board CR-20 None N/A
(Optional
if using
AA Ply)
BP-AA,
SBS-AA
(Optional if using
AA Base) BP-AA,
SBS-AA, SBS-TA
or APP-TA
SBS-AA, SBS-TA,
APP-TA -245.0
G-2
Existing, sound poured
gypsum or gypsum
plank
(Optional) Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-Shield or
Styrofoam Brand Roofmate, Highload 60 or
Plazamate
CR-20 0.5-inch SECUROCK Cement
Roof Board CR-20 SBS-TA (Optional) SBS-TA SBS-TA -187.5
G-3
Existing, sound poured
gypsum or gypsum
plank
(Optional) Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-Shield or
Styrofoam Brand Roofmate, Highload 60 or
Plazamate
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 BP-AA,
SBS-AA
(Optional) BP-AA,
SBS-AA SBS-AA -225.0
G-4
Existing, sound poured
gypsum or gypsum
plank
(Optional) Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-Shield or
Styrofoam Brand Roofmate, Highload 60 or
Plazamate
CR-20, 6-
inch o.c.
0.5-inch SECUROCK Cement
Roof Board
CR-20, 6-
inch o.c. SBS-TA (Optional) SBS-TA SBS-TA -232.5
G-5
Existing, sound poured
gypsum or gypsum
plank
(Optional) Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-Shield or
Styrofoam Brand Roofmate, Highload 60 or
Plazamate
CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-TA,
APP-TA
(Optional) SBS-
TA, APP-TA SBS-TA, APP-TA -282.5
G-6
Existing, sound poured
gypsum or gypsum
plank
(Optional) Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-Shield or
Styrofoam Brand Roofmate, Highload 60 or
Plazamate
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 SBS-TA,
APP-TA
(Optional) SBS-
TA, APP-TA SBS-TA, APP-TA -322.5
SELF-ADHERING BASE PLY:
G-7
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
G-8
Existing, sound poured
gypsum or gypsum
plank
Min. 0.25-inch DensDeck Prime OB500 None N/A SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
G-9
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch min. 2.0 pcf, Insulfoam OB500 (Optional) additional layers(s) of
base insulation OB500 SBS-SA (Optional) SBS-SA SBS-SA, APP-SA -112.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 87 of 98
TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
G-10
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield OB500 (Optional) additional layers(s) of
base insulation OB500 SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -112.5
G-11
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board OB500 SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -112.5
G-12
Existing, sound poured
gypsum or gypsum
plank
Min. 0.25-inch SECUROCK Gypsum-Fiber Roof
Board OB500 None N/A SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -112.5
G-13
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-
Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch DensDeck Prime M-OSFA SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
G-14
Existing, sound poured
gypsum or gypsum
plank
Min. 0.25-inch DensDeck Prime M-OSFA None N/A SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
G-15
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-
Shield or Multi-Max FA3 M-OSFA
(Optional) additional layers(s) of
base insulation and/or min.
0.25-inch SECUROCK Gypsum-
Fiber Roof Board
M-OSFA SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -202.5
G-16
Existing, sound poured
gypsum or gypsum
plank
Min. 0.25-inch SECUROCK Gypsum-Fiber Roof
Board M-OSFA None N/A SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -202.5
G-17
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch, min. 2.0 pcf EPS insulation board,
Polytherm, ACFoam II, Polytherm G, ACFoam III,
ENRGY 3, Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
G-18
Existing, sound poured
gypsum or gypsum
plank
Min. 0.25-inch DensDeck Prime CR-20 None N/A SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
G-19
Existing, sound poured
gypsum or gypsum
plank
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-Shield or
min. 2.0 pcf Insulfoam
CR-20
ACFoam-HD Coverboard,
ACFoam-HD Coverboard-FR or
H-Shield HD
CR-20 SBS-SA (Optional) SBS-SA SBS-SA -230.0
G-20
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers of
base insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA -240.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 88 of 98
TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
G-21
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -240.0
G-22
Existing, sound poured
gypsum or gypsum
plank
Min. 0.25-inch SECUROCK Gypsum-Fiber Roof
Board CR-20 None N/A SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -240.0
G-23
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch min. 2.0 pcf Insulfoam CR-20
ACFoam-HD Coverboard,
ACFoam-HD Coverboard-FR or
H-Shield HD
CR-20, 6-
inch o.c. SBS-SA (Optional) SBS-SA SBS-SA -240.0
G-24
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-
Shield CG or Multi-Max FA3
CR-20
(Optional) additional layers(s) of
base insulation and/or min.
0.25-inch SECUROCK Gypsum-
Fiber Roof Board
CR-20 SBS-SA
(Optional) SBS-
SA, SBS-TA, APP-
TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -257.5
G-25
Existing, sound poured
gypsum or gypsum
plank
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-Shield CR-20
ACFoam-HD Coverboard,
ACFoam-HD Coverboard-FR or
H-Shield HD
CR-20, 6-
inch o.c. SBS-SA (Optional) SBS-SA SBS-SA -285.0
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
G-26
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield OB500 (Optional) additional layers(s) of
base insulation OB500 APP-SA-H (Optional) APP-
TA APP-TA -112.5
G-27
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board OB500 APP-SA-H (Optional) APP-
TA APP-TA -112.5
G-28
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-
Shield or Multi-Max FA3 M-OSFA
(Optional) additional layers(s) of
base insulation and/or min.
0.25-inch SECUROCK Gypsum-
Fiber Roof Board
M-OSFA APP-SA-H (Optional) APP-
TA APP-TA -202.5
G-29
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 APP-SA-H (Optional) APP-
TA APP-TA -240.0
G-30
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-
Shield CG or Multi-Max FA3
CR-20
(Optional) additional layers(s) of
base insulation and/or min.
0.25-inch SECUROCK Gypsum-
Fiber Roof Board
CR-20 APP-SA-H (Optional) APP-
TA APP-TA -257.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 89 of 98
TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
G-31
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
G-32
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield OB500 (Optional) additional layers(s) of
base insulation OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -112.5
G-33
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield or min. 2.0 pcf, Insulfoam OB500 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -112.5
G-34
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-
Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch DensDeck Prime M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
G-35
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3, H-
Shield or Multi-Max FA3 M-OSFA
(Optional) additional layers(s) of
base insulation and/or min.
0.25-inch SECUROCK Gypsum-
Fiber Roof Board
M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -202.5
G-36
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch, min. 2.0 pcf EPS insulation board,
Polytherm, ACFoam II, Polytherm G, ACFoam III,
ENRGY 3, Polytherm H, H-Shield, H-Shield CG or
Multi-Max FA3
CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
G-37
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0
G-38
Existing, sound poured
gypsum or gypsum
plank
Min. 1.5-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield, H-
Shield CG or Multi-Max FA3
CR-20
(Optional) additional layers(s) of
base insulation and/or min.
0.25-inch SECUROCK Gypsum-
Fiber Roof Board
CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -257.5
COLD APPLIED BASE PLY:
G-39
Existing, sound poured
gypsum or gypsum
plank
Min. 1-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, EnergyGuard Polyiso Insulation,
ENRGY 3, Polytherm H, H-Shield ISO 95+ GL, Multi-
Max FA3, RESISTA or UltraMax or min. 2-inch
Styrofoam Brand Roofmate, Highload 60 or
Plazamate
M-OSFA
Min. 0.25-inch DensDeck, DensDeck
Prime, DEXcell FA Glass Mat Roof
Board, SECUROCK Gypsum-Fiber
Roof Board or SECUROCK Glass-Mat
Roof Board, min. 7/16-inch DEXcell
Cement Roof Board or min. 0.5-inch
SECUROCK Cement Roof Board
M-OSFA SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 90 of 98
TABLE 6A: GYPSUM DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
G-40
Existing, sound poured
gypsum or gypsum
plank
Min. 1-inch Polytherm or ACFoam II, Polytherm G,
ACFoam III, EnergyGuard Polyiso Insulation,
ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL,
Multi-Max FA3, RESISTA or UltraMax or min. 2-
inch Styrofoam Brand Roofmate, Highload 60 or
Plazamate
M-OSFA
Min. 0.25-inch DensDeck Prime
or DEXcell FA Glass Mat Roof
Board, min. 7/16-inch DEXcell
Cement Roof Board or min. 0.5-
inch SECUROCK Cement Roof
Board
M-OSFA SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
G-41
Existing, sound poured
gypsum or gypsum
plank
Min. 1-inch Polytherm or ACFoam II, Polytherm G,
ACFoam III, EnergyGuard Polyiso Insulation,
ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL,
Multi-Max FA3, RESISTA or UltraMax or min. 2-
inch Styrofoam Brand Roofmate, Highload 60 or
Plazamate
M-OSFA Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board M-OSFA SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
G-42
Existing, sound poured
gypsum or gypsum
plank
Min. 1-inch Polytherm or ACFoam II, Polytherm G,
ACFoam III, EnergyGuard Polyiso Insulation,
ENRGY 3, Polytherm H, H-Shield, ISO 95+ GL,
Multi-Max FA3, RESISTA or UltraMax or min. 2-
inch Styrofoam Brand Roofmate, Highload 60 or
Plazamate
M-OSFA
Min. 0.25-inch DensDeck, DensDeck
Prime, DEXcell FA Glass Mat Roof
Board, SECUROCK Gypsum-Fiber
Roof Board or SECUROCK Glass-Mat
Roof Board, min. 7/16-inch DEXcell
Cement Roof Board or min. 0.5-inch
SECUROCK Cement Roof Board
M-OSFA SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2 -202.5
G-43
Existing, sound poured
gypsum or gypsum
plank
Min. 1-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
OB500
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof Board
or SECUROCK Gypsum-Fiber
Roof Board
OB500 SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -112.5
G-44
Existing, sound poured
gypsum or gypsum
plank
Min. 1-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
CR-20
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
CR-20 SBS-CA1,
SBS-CA2
(Optional) SBS-
CA1, SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
G-45
Existing, sound poured
gypsum or gypsum
plank
Min. 1-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
CR-20
Min. 0.25-inch DensDeck Prime
or DEXcell FA Glass Mat Roof
Board
CR-20 SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
G-46
Existing, sound poured
gypsum or gypsum
plank
Min. 1-inch Polytherm, ACFoam II, Polytherm G,
ACFoam III, ENRGY 3, Polytherm H, H-Shield or
Multi-Max FA3
CR-20 Min. 0.25-inch SECUROCK
Gypsum-Fiber Roof Board CR-20 SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
G-47
Existing, sound poured
gypsum or gypsum
plank
Min. 1-inch ENRGY 3, Polytherm H, H-Shield,
Multi-Max FA3 CR-20
Min. 0.25-inch DensDeck Prime
or SECUROCK Gypsum-Fiber
Roof Board
CR-20 SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2 -232.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 91 of 98
TABLE 6B: GYPSUM DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE A-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP
(psf) Type Fasten
(Note 11) Attach Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
G-48
Existing,
sound
poured
gypsum or
gypsum
plank
Elastobase V,
Elastobase P,
Elastovent or
Polyglass G2
Base
Trufast
FM-75 or
FM-90 or
Twin Loc-
Nails
9-inch o.c. at min.
4-inch lap and 18-
inch o.c. at two,
equally spaced,
staggered center
rows
Min. 1.5-inch
Polytherm, ACFoam II,
Polytherm G, ACFoam
III, ISO95+GL,
Polytherm H, H-Shield,
ENRGY 3 or Multi-Max
FA3
Hot asphalt
Min. 0.25-inch DensDeck,
DensDeck Prime, SECUROCK
Gypsum-Fiber Roof Board, Min.
0.75-inch Fesco Board
(homogeneous) or min. 0.5-inch
Structodek High Density
Fiberboard Roof Insulation
Hot asphalt BP-AA,
SBS-AA
(Optional)
BP-AA, SBS-
AA, SBS-TA
or APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
TABLE 6C: GYPSUM DECKS – REROOF (TEAR-OFF) OR RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer
(Note 13)
Top Insulation Layer Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Ply Cap Ply
G-49
Existing sound
poured gypsum or
gypsum plank
(Optional) One or
more layers, any
combination, loose
laid
Min. 0.25-inch DensDeck, DensDeck Prime or
SECUROCK Gypsum-Fiber Roof Board or min. 0.5-
inch Structodek High Density Fiberboard Roof
Insulation
Trufast Twin Loc-
Nails (min. 1-inch
embedment)
1 per
2.0 ft2
(Optional if
using AA Ply)
BP-AA, SBS-AA
(Optional if using AA
Base) BP-AA, SBS-AA,
SBS-TA or APP-TA
SBS-AA,
SBS-TA,
APP-TA
-45.0*
TABLE 6D: GYPSUM DECKS – REROOF (TEAR-OFF)
SYSTEM TYPE E: NON-INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Sheet Roof Cover (Note 15) MDP (psf) Type Fasten (Note 11) Attach Base Ply Cap Ply
G-50 Existing sound poured
gypsum or gypsum plank
Elastobase V, Elastobase P,
Elastovent or Polyglass G2
Base
Trufast FM-75 or FM-
90 or Twin Loc-Nails
9-inch o.c. at min. 4-inch lap and 18-inch o.c. at
two, equally spaced, staggered center rows
(Optional) BP-AA, SBS-AA, SBS-
TA or APP-TA
SBS-AA, SBS-TA,
APP-TA -45.0*
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 92 of 98
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Substrate
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
ASPHALT OR TORCH APPLIED BASE PLY:
R-1 Existing
asphaltic roof (Optional) Min. 1.5-inch Multi-Max FA3 D-IS
Min. 0.25-inch DensDeck, DensDeck
Prime or SECUROCK Gypsum-Fiber
Roof Board
D-IS
BP-AA, SBS-
AA, SBS-TA,
APP-TA
(Optional) BP-AA, SBS-
AA, SBS-TA or APP-TA
SBS-AA, SBS-TA
or APP-TA -67.5
R-2 Existing
asphaltic roof
(Optional) Min. 1.5-inch Polytherm, ACFoam II
or ENRGY 3 or min. 2.0 pcf Insulfoam D-IS
Min. 0.25-inch DensDeck, DensDeck
Prime or SECUROCK Gypsum-Fiber
Roof Board
D-IS
BP-AA, SBS-
AA, SBS-TA,
APP-TA
(Optional) BP-AA, SBS-
AA, SBS-TA or APP-TA
SBS-AA, SBS-TA,
or APP-TA -90.0
R-3 Existing
asphaltic roof
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or ISO 95+GL OB500
Min. 0.25-inch DensDeck, DensDeck
Prime or SECUROCK Gypsum-Fiber
Roof Board
OB500
BP-AA, SBS-
AA, SBS-TA,
APP-TA
(Optional) BP-AA, SBS-
AA, SBS-TA or APP-TA
SBS-AA, SBS-TA,
or APP-TA -127.5
R-4 Existing
asphaltic roof
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board M-OSFA
BP-AA, SBS-
AA, SBS-TA,
APP-TA
(Optional) BP-AA, SBS-
AA, SBS-TA or APP-TA
SBS-AA, SBS-TA,
or APP-TA -157.5
R-5 Existing
asphaltic roof
(Optional) Min. 1.5-inch Ultra-Max or Multi-
Max FA-3, min. 1.3-inch Polytherm G, ACFoam
III or min. 1.0-inch ISO 95+GL, Polytherm H, H-
Shield, H-Shield CG or ENRGY 3 or min. 2.0 pcf
Insulfoam
CR-20 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board CR-20 BP-AA, SBS-
AA
(Optional) BP-AA, SBS-
AA SBS-AA -225.0
R-6 Existing
asphaltic roof
(Optional) Min. 1.5-inch Ultra-Max or Multi-
Max FA-3, min. 1.3-inch Polytherm G, ACFoam
III or min. 1.0-inch ISO 95+GL, Polytherm H, H-
Shield, H-Shield CG or ENRGY 3 or min. 2.0 pcf
Insulfoam
CR-20 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board CR-20 APP-TA (Optional) APP-TA APP-TA -232.5
SELF-ADHERING BASE PLY:
R-7 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Multi-Max FA3 D-IS
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
or DensDeck Prime
D-IS SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -67.5
R-8 Existing
asphaltic roof
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3 or Multi-Max FA3 or min. 2.0 pcf
Insulfoam
D-IS Min. 0.25-inch DensDeck Prime D-IS SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
R-9 Existing
asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS (Optional) additional layers(s) of base
insulation D-IS SBS-SA (Optional) SBS-SA SBS-SA -90.0
R-10 Existing
asphaltic roof (Optional) Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board D-IS SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -90.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 93 of 98
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Substrate
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
R-11 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Polytherm, ACFoam II or ENRGY
3
D-IS
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
D-IS SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -90.0
R-12 Existing
asphaltic roof
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, Polytherm H or H-Shield or min. 2.0
pcf Insulfoam
OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
R-13 Existing
asphaltic roof Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 (Optional) additional layers of base
insulation OB500 SBS-SA (Optional) SBS-SA SBS-SA -120.0
R-14 Existing
asphaltic roof
(Optional) Min. 1.5-inch, min. 2.0 pcf
Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board OB500 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -120.0
R-15 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield
OB500
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
OB500 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -127.5
R-16 Existing
asphaltic roof
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-
Shield or min. 2.0 pcf Insulfoam
OB500 ACFoam-HD Coverboard, ACFoam-HD
Coverboard-FR or H-Shield HD OB500 SBS-SA (Optional) SBS-SA SBS-SA -127.5
R-17 Existing
asphaltic roof
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch DensDeck Prime M-OSFA SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
R-18 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
H-Shield or Multi-Max FA3
M-OSFA
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
M-OSFA SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -157.5
R-19 Existing
asphaltic roof
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-
Shield or min. 2.0 pcf Insulfoam
M-OSFA or
M-PG1
ACFoam-HD Coverboard, ACFoam-HD
Coverboard-FR or H-Shield HD
M-OSFA or
M-PG1 SBS-SA (Optional) SBS-SA SBS-SA -157.5
R-20 Existing
asphaltic roof
(Optional) Min. 1.5-inch min. 2.0 pcf
Insulfoam, Min. 2-inch Polytherm, ACFoam II,
min. 1.5-inch Ultra-Max or Multi-Max FA-3,
min. 1.3-inch Polytherm G, ACFoam III or min.
1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-
Shield CG or ENRGY 3
CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -72.5
R-21 Existing
asphaltic roof
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-
Shield or min. 2.0 pcf Insulfoam
CR-20 ACFoam-HD Coverboard, ACFoam-HD
Coverboard-FR or H-Shield HD CR-20 SBS-SA (Optional) SBS-SA SBS-SA -230.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 94 of 98
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Substrate
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
R-22 Existing
asphaltic roof Min. 1.5-inch min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers(s) of base
insulation CR-20 SBS-SA (Optional) SBS-SA SBS-SA -240.0
R-23 Existing
asphaltic roof (Optional) Min. 1.5-inch min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -240.0
R-24 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Ultra-Max or Multi-Max FA-3,
min. 1.3-inch Polytherm G, ACFoam III or min.
1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-
Shield CG or ENRGY 3
CR-20
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -240.0
R-25 Existing
asphaltic roof Min. 1.5-inch, min. 2.0 pcf Insulfoam IX CR-20 ACFoam-HD Coverboard, ACFoam-HD
Coverboard-FR or H-Shield HD
CR-20, 6-
inch o.c. SBS-SA (Optional) SBS-SA SBS-SA -240.0
R-26 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 2-inch Polytherm, ACFoam II, ENRGY-3,
Polytherm H or H-Shield
CR-20
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
CR-20 SBS-SA (Optional) SBS-SA,
SBS-TA, APP-TA
SBS-SA, APP-SA,
SBS-TA, APP-TA -247.5
R-27 Existing
asphaltic roof
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, Polytherm H, H-
Shield
CR-20 ACFoam-HD Coverboard, ACFoam-HD
Coverboard-FR or H-Shield HD
CR-20, 6-
inch o.c. SBS-SA (Optional) SBS-SA SBS-SA -262.5
HYBRID SYSTEMS WITH SELF-ADHERING APP BASE PLY:
R-28 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Multi-Max FA3 D-IS
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
or DensDeck Prime
D-IS APP-SA-H (Optional) APP-TA APP-TA -67.5
R-29 Existing
asphaltic roof (Optional) Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board D-IS APP-SA-H (Optional) APP-TA APP-TA -90.0
R-30 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Polytherm, ACFoam II or ENRGY
3
D-IS
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
D-IS APP-SA-H (Optional) APP-TA APP-TA -90.0
R-31 Existing
asphaltic roof
(Optional) Min. 1.5-inch, min. 2.0 pcf
Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board OB500 APP-SA-H (Optional) APP-TA APP-TA -120.0
R-32 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield
OB500
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
OB500 APP-SA-H (Optional) APP-TA APP-TA -127.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 95 of 98
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Substrate
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
R-33 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
H-Shield or Multi-Max FA3
M-OSFA
(Optional if Base Layer Insulation
installed l) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
M-OSFA APP-SA-H (Optional) APP-TA APP-TA -157.5
R-34 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Ultra-Max or Multi-Max FA-3,
min. 1.3-inch Polytherm G, ACFoam III or min.
1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-
Shield CG or ENRGY 3
CR-20
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
CR-20 APP-SA-H (Optional) APP-TA APP-TA -240.0
R-35 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 2-inch Polytherm, ACFoam II, ENRGY-3,
Polytherm H or H-Shield
CR-20
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
CR-20 APP-SA-H (Optional) APP-TA APP-TA -247.5
HYBRID SYSTEMS WITH SELF-ADHERING SBS BASE PLY:
R-36 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Multi-Max FA3 D-IS
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
or DensDeck Prime
D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -67.5
R-37 Existing
asphaltic roof
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3 or Multi-Max FA3 or min. 2.0 pcf
Insulfoam
D-IS Min. 0.25-inch DensDeck Prime D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
R-38 Existing
asphaltic roof (Optional) Min. 1.5-inch min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -90.0
R-39 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Polytherm, ACFoam II or ENRGY
3
D-IS
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
D-IS SBS-SA-H (Optional) SBS-TA SBS-TA -90.0
R-40 Existing
asphaltic roof
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, Polytherm H or H-Shield or min. 2.0
pcf Insulfoam
OB500 Min. 0.25-inch DensDeck Prime OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
R-41 Existing
asphaltic roof
(Optional) Min. 1.5-inch, min. 2.0 pcf
Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -120.0
R-42 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
Polytherm H or H-Shield
OB500
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
OB500 SBS-SA-H (Optional) SBS-TA SBS-TA -127.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 96 of 98
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Substrate
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
R-43 Existing
asphaltic roof
(Optional) Min. 1.5-inch Polytherm, ACFoam II,
ENRGY 3, H-Shield or Multi-Max FA3 M-OSFA Min. 0.25-inch DensDeck Prime M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
R-44 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Polytherm, ACFoam II, ENRGY 3,
H-Shield or Multi-Max FA3
M-OSFA
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
M-OSFA SBS-SA-H (Optional) SBS-TA SBS-TA -157.5
R-45 Existing
asphaltic roof
(Optional) Min. 1.5-inch min. 2.0 pcf
Insulfoam, Min. 2-inch Polytherm, ACFoam II,
min. 1.5-inch Ultra-Max or Multi-Max FA-3,
min. 1.3-inch Polytherm G, ACFoam III or min.
1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-
Shield CG or ENRGY 3
CR-20 Min. 0.25-inch DensDeck Prime CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -72.5
R-46 Existing
asphaltic roof (Optional) Min. 1.5-inch min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0
R-47 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 1.5-inch Ultra-Max or Multi-Max FA-3,
min. 1.3-inch Polytherm G, ACFoam III or min.
1.0-inch ISO 95+GL, Polytherm H, H-Shield, H-
Shield CG or ENRGY 3
CR-20
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -240.0
R-48 Existing
asphaltic roof
(Optional if Top Layer Insulation installed)
Min. 2-inch Polytherm, ACFoam II, ENRGY-3,
Polytherm H or H-Shield
CR-20
(Optional if Base Layer Insulation
installed) additional layers(s) of base
insulation and/or min. 0.25-inch
SECUROCK Gypsum-Fiber Roof Board
CR-20 SBS-SA-H (Optional) SBS-TA SBS-TA -247.5
COLD APPLIED BASE PLY:
R-49 Existing
asphaltic roof
(Optional) Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, Polytherm
H or H-Shield
D-IS
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof Board or
SECUROCK Gypsum-Fiber Roof Board
D-IS SBS-CA1,
SBS-CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -90.0
R-50 Existing
asphaltic roof
(Optional) Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, EnergyGuard Polyiso
Insulation, ENRGY 3, Polytherm H, H-Shield
ISO 95+ GL, Multi-Max FA3, RESISTA or
UltraMax or min. 2-inch Styrofoam Brand
Roofmate, Highload 60 or Plazamate
M-OSFA,
M-PG1
Min. 0.25-inch DensDeck, DensDeck
Prime, DEXcell FA Glass Mat Roof
Board, SECUROCK Gypsum-Fiber Roof
Board or SECUROCK Glass-Mat Roof
Board, min. 7/16-inch DEXcell Cement
Roof Board or min. 0.5-inch SECUROCK
Cement Roof Board
M-OSFA or
M-PG1
SBS-CA1,
SBS-CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 97 of 98
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Substrate
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
R-51 Existing
asphaltic roof
(Optional) Min. 1-inch Polytherm or ACFoam
II, Polytherm G, ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3, Polytherm H, H-
Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or
UltraMax or min. 2-inch Styrofoam Brand
Roofmate, Highload 60 or Plazamate
M-OSFA,
M-PG1
Min. 0.25-inch DensDeck Prime or
DEXcell FA Glass Mat Roof Board, min.
7/16-inch DEXcell Cement Roof Board
or min. 0.5-inch SECUROCK Cement
Roof Board
M-OSFA, M-
PG1 SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
R-52 Existing
asphaltic roof
(Optional) Min. 1-inch Polytherm or ACFoam
II, Polytherm G, ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3, Polytherm H, H-
Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or
UltraMax or min. 2-inch Styrofoam Brand
Roofmate, Highload 60 or Plazamate
M-OSFA,
M-PG1
Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board
M-OSFA, M-
PG1
SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
R-53 Existing
asphaltic roof
(Optional) Min. 1-inch Polytherm or ACFoam
II, Polytherm G, ACFoam III, EnergyGuard
Polyiso Insulation, ENRGY 3, Polytherm H, H-
Shield, ISO 95+ GL, Multi-Max FA3, RESISTA or
UltraMax or min. 2-inch Styrofoam Brand
Roofmate, Highload 60 or Plazamate
M-OSFA,
M-PG1
Min. 0.25-inch DensDeck, DensDeck
Prime, DEXcell FA Glass Mat Roof
Board, SECUROCK Gypsum-Fiber Roof
Board or SECUROCK Glass-Mat Roof
Board, min. 7/16-inch DEXcell Cement
Roof Board or min. 0.5-inch SECUROCK
Cement Roof Board
M-OSFA, M-
PG1
SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2 -157.5
R-54 Existing
asphaltic roof
(Optional) Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, Polytherm
H, H-Shield or Multi-Max FA3
OB500
Min. 0.25-inch DensDeck Prime,
DEXcell FA Glass Mat Roof Board or
SECUROCK Gypsum-Fiber Roof Board
OB500 SBS-CA1,
SBS-CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
R-55 Existing
asphaltic roof
(Optional) Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, Polytherm
H, H-Shield or Multi-Max FA3
OB500 Min. 0.25-inch DensDeck Prime or
DEXcell FA Glass Mat Roof Board OB500 SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
R-56 Existing
asphaltic roof
(Optional) Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, Polytherm
H, H-Shield or Multi-Max FA3
OB500 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board OB500 SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
R-57 Existing
asphaltic roof
(Optional) Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, Polytherm
H, H-Shield or Multi-Max FA3
CR-20 Min. 0.25-inch DensDeck Prime or
SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1,
SBS-CA2
(Optional) SBS-CA1,
SBS-CA2
SBS-CA1, SBS-
CA2, APP-CA1 -120.0
R-58 Existing
asphaltic roof
(Optional) Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, Polytherm
H, H-Shield or Multi-Max FA3
CR-20 Min. 0.25-inch DensDeck Prime or
DEXcell FA Glass Mat Roof Board CR-20 SBS-CA1 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
R-59 Existing
asphaltic roof
(Optional) Min. 1-inch Polytherm, ACFoam II,
Polytherm G, ACFoam III, ENRGY 3, Polytherm
H, H-Shield or Multi-Max FA3
CR-20 Min. 0.25-inch SECUROCK Gypsum-
Fiber Roof Board CR-20 SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2, APP-CA1 -127.5
NEMO|etc.
NEMO ETC, LLC Evaluation Report P9290.02.08-R26 for FL1654-R28
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION Revision 26: 06/09/2021
©2018 NEMO ETC, LLC Polyglass Modified Bitumen Roof Systems; (954) 233-1330 Appendix 1, Page 98 of 98
TABLE 7A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
System
No.
Substrate
(Notes 1 & 12)
Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP
(psf) Type Attach
(Notes 6,7,8) Type Attach
(Notes 6,7,8) Base Ply Ply Cap Ply
R-60 Existing
asphaltic roof
(Optional) Min. 1-inch ENRGY 3, Polytherm H,
H-Shield, Multi-Max FA3 CR-20 Min. 0.25-inch DensDeck Prime or
SECUROCK Gypsum-Fiber Roof Board CR-20 SBS-CA1,
SBS-CA2 None SBS-CA1, SBS-
CA2 -232.5
TABLE 7B: RECOVER APPLICATIONS
SYSTEM TYPE F: NON-INSULATED, BONDED ROOF COVER
System No. Substrate
(Notes 1 & 12) Primer Roof Cover (Note 15) MDP (psf) Base Ply Ply Cap Ply
R-61 Existing asphaltic roof PG100 BP-AA (Optional if using asphalt applied Ply) (Optional if using asphalt applied Base) BP-AA, SBS-
AA, SBS-TA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0
R-62 Existing fully-adhered, granule-
surfaced modified bitumen None Polyflex, torch-applied (Optional) Polyflex, torch-applied APP-TA -362.5
R-63 Existing fully-adhered, granule-
surfaced modified bitumen PG100 Polyflex, torch-applied (Optional) Polyflex, torch-applied APP-TA -445.0