Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-18 15:29:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\MCNALLY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Project Summary Aug 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information MCNALLY RESIDENC EFor: 357 NETTLES BLVD., JENSEN BEACH, FL Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh13597 Struc ture Btuh9871 Ducts Btuh2446 Ducts Btuh3669 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh16043 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh12863 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh2906 Ducts Btuh972 Central vent (0 cfm)Btuh0 CoolingHeating (none) 10981098Area (ft²)Equipment latent load Btuh3878 87808780Volume (ft³) Air changes/hour 0.230.45 Equipment Total Load (Sen+Lat)Btuh16741 Equiv. AVF (cfm)3466 Req. total capacity at 0.70 SHR ton1.5 Heating Equipment Summary Cooling Equipment Summary Make Make Trane Trade Trade TRANE Model Cond 4TTR6018J1 AHRI ref Coil TEM4A0B18S21++TDR AHRI ref 8676071 Efficiency 100 EFF Efficiency 13.5 EER, 16 SEER Heating input kW4.5 Sensible cooling Btuh13160 Heating output Btuh15469 Latent cooling Btuh5640 Temperature rise °F22 Total cooling Btuh18800 Actual air flow cfm627 Actual air flow cfm627 Air flow factor cfm/Btuh0.039 Air flow factor cfm/Btuh0.046 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.78 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-18 15:29:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\MCNALLY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Aug 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House CLST 3 2 Exposed wall 170.9 ft 0 ft 3 Room height 8.0 ft 8.0 heat/coolft 4 Room dimensions ft13.0x1.0 5 Room area 1097.5 ft²13.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 376 363 1453 794 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 4 0 73 60 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 9 0 164 135 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 159 141 566 309 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 18 0 328 608 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 208 111 443 242 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 25.9925.99 20 2 356 508 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 25.9925.99 40 3 721 1030 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 16.0916.09 18 3 318 282 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 16.8316.83 21 2 376 348 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 432 410 1642 897 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 4 4 73 60 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 18 18 328 192 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 86 68 273 149 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 18 0 328 608 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 107 89 358 195 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 18 0 328 484 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 815 815 1292 1115 0 0 0 0 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 330 57 2152 0 13 0 0 0 6 c) AED excursion 0 0 Envelope loss/gain 11571 8016 0 0 12 a) Infiltration 2026 555 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1300 0 Subtotal (lines 6 to 13)13597 9871 0 0 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 13597 9871 0 0 15 Duct loads 18%37%2446 3669 18%37%0 0 Total room load 16043 13540 0 0 Air required (cfm)Air required (cfm)627 627 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-18 15:29:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 E:\Documnets\Wrightsoft HVAC\MCNALLY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Aug 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 3 BATH 3 2 Exposed wall 29.0 ft 18.4 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft192.0x1.0 ft63.5x1.0 5 Room area 192.0 ft²63.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 72 72 288 158 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 76 76 304 166 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 104 45 179 98 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 25.9925.99 20 2 356 508 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 25.9925.99 40 3 721 1030 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 16.0916.09 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 16.8316.83 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 128 128 513 280 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 0 0 0 0 0 0 0 0 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 192 29 1103 0 64 18 700 0 6 c) AED excursion 111 -31 Envelope loss/gain 2872 2027 1292 292 12 a) Infiltration 343 94 219 60 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 200 0 Subtotal (lines 6 to 13)3215 2321 1511 352 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 164 38 14 Subtotal 3215 2321 1675 390 15 Duct loads 18%37%578 863 18%37%301 145 Total room load 3793 3184 1976 535 Air required (cfm)Air required (cfm)148 147 77 25 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-18 15:29:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 3 E:\Documnets\Wrightsoft HVAC\MCNALLY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Aug 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name GARAGE STORAGE KITCHEN 2 Exposed wall 2.0 ft 32.4 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft2.0x7.0 ft205.0x1.0 5 Room area 14.0 ft²205.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 16 16 64 35 176 167 669 365 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 9 0 164 135 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 84 66 262 143 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 18 0 328 608 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 25.9925.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 25.9925.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 16.0916.09 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 16.8316.83 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 0 0 0 0 205 205 325 280 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 14 2 76 0 2 0 10 0 6 c) AED excursion -3 -147 Envelope loss/gain 140 32 1758 1385 12 a) Infiltration 24 6 384 105 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 150 Subtotal (lines 6 to 13)164 38 2142 1641 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -164 -38 0 0 14 Subtotal 0 0 2142 1641 15 Duct loads 18%37%0 0 18%37%385 610 Total room load 0 0 2527 2250 Air required (cfm)Air required (cfm)0 0 99 104 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-18 15:29:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 4 E:\Documnets\Wrightsoft HVAC\MCNALLY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Aug 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name GREAT RM M BATH 2 Exposed wall 29.0 ft 8.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft222.0x1.0 ft8.0x8.0 5 Room area 222.0 ft²64.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 104 66 264 144 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 25.9925.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 25.9925.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 16.0916.09 18 3 318 282 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 16.8316.83 21 2 376 348 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 128 110 440 241 64 60 240 131 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 4 4 73 60 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 18 18 328 192 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 222 222 352 304 64 64 101 88 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 21 3 103 0 8 1 38 0 6 c) AED excursion 3 -33 Envelope loss/gain 2181 1513 453 246 12 a) Infiltration 343 94 95 26 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 100 Subtotal (lines 6 to 13)2525 1607 547 372 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 8 6 11 9 14 Subtotal 2532 1613 559 381 15 Duct loads 18%37%455 599 18%37%100 141 Total room load 2988 2212 659 522 Air required (cfm)Air required (cfm)117 102 26 24 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-18 15:29:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 5 E:\Documnets\Wrightsoft HVAC\MCNALLY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Aug 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M BEDROOM BATH 2 2 Exposed wall 27.3 ft 5.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft140.0x1.0 ft5.0x10.0 5 Room area 140.0 ft²50.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 40 36 144 79 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 4 0 73 60 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 25.9925.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 25.9925.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 16.0916.09 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 16.8316.83 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 112 112 448 245 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 107 89 358 195 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 18 0 328 484 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 140 140 222 192 50 50 79 68 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 14 3 102 0 0 0 0 0 6 c) AED excursion 24 -39 Envelope loss/gain 1458 1140 296 168 12 a) Infiltration 325 89 59 16 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 300 250 Subtotal (lines 6 to 13)1782 1529 355 435 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 8 6 49 26 14 Subtotal 1790 1535 404 460 15 Duct loads 18%37%322 570 18%37%73 171 Total room load 2112 2105 477 631 Air required (cfm)Air required (cfm)83 97 19 29 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-18 15:29:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 6 E:\Documnets\Wrightsoft HVAC\MCNALLY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Aug 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 2 CLST 2 2 Exposed wall 17.8 ft 2.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft100.0x1.0 ft2.0x5.0 5 Room area 100.0 ft²10.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 56 56 224 123 16 16 64 35 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 sese 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 25.9925.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 25.9925.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 16.0916.09 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 sese 18.2018.20 16.8316.83 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 86 68 273 149 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 18 0 328 608 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 nwnw 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nwnw 18.2018.20 26.8826.88 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 100 100 159 137 10 10 16 14 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 3 1 20 0 0 0 0 0 6 c) AED excursion 123 -5 Envelope loss/gain 1003 1139 80 44 12 a) Infiltration 210 58 24 6 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 300 0 Subtotal (lines 6 to 13)1213 1497 104 51 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 66 34 -104 -51 14 Subtotal 1280 1531 0 0 15 Duct loads 18%37%230 569 18%37%0 0 Total room load 1510 2100 0 0 Air required (cfm)Air required (cfm)59 97 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Aug-18 15:29:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 7 E:\Documnets\Wrightsoft HVAC\MCNALLY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Aug 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name HALLWAY 2 Exposed wall 0 ft 3 Room height 8.0 heat/coolft 4 Room dimensions ft6.0x4.0 5 Room area 24.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 .G 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 .G 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 .W 13A-4ocs 0.143 e 4.00 2.19 0 0 0 0 11 G 2 glazing, clr low-e 0.650 e 18.20 33.77 0 0 0 0 W 13A-4ocs 0.143 se 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 se 18.20 25.99 0 0 0 0 G 2 glazing, clr low-e 0.650 se 18.20 25.99 0 0 0 0 G 2 glazing, clr low-e 0.650 se 18.20 16.09 0 0 0 0 G 2 glazing, clr low-e 0.650 se 18.20 16.83 0 0 0 0 W 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 G 2 glazing, clr low-e 0.650 s 18.20 10.68 0 0 0 0 W 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 w 18.20 33.77 0 0 0 0 W 13A-4ocs 0.143 nw 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 nw 18.20 26.88 0 0 0 0 C 16X19-0md 0.408 -1.59 1.37 24 24 38 33 F 22A-tph 1.358 -38.02 0.00 0 0 0 0 6 c) AED excursion -3 Envelope loss/gain 38 30 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)38 30 Less external load 0 0 Less transfer 0 0 Redistribution -38 -30 14 Subtotal 0 0 15 Duct loads 18%37%0 0 Total room load 0 0 Air required (cfm)0 0 2021-Aug-18 15:29:40 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\MCNALLY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Duct System Summary Aug 18, 2021Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information MCNALLY RESIDENC EFor: 357 NETTLES BLVD., JENSEN BEACH, FL CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm627cfm627 Total effective length (TEL)ft159 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk 95.05.0VlFx0x05.01.0002919631cBATH 2 st4135.023.7VlFx0x05.01.00025771976hBATH 3 95.02.2VlFx0x07.01.00097592100cBEDROOM 2 st4135.022.3VlFx0x08.01.0001471483793hBEDROOM 3 st1115.019.2VlFx0x07.01.0001021172988hGREAT RM st1115.018.2VlFx0x07.01.000104992250cKITCHEN st2115.014.2VlFx0x05.01.0002426659hM BATH st2115.013.4VlFx0x07.01.00097832105cM BEDROOM Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 226 172 1.000 646 8.0 0x0 VinlFlx st3 st3 Peak AVF 226 172 1.000 646 8.0 0x0 VinlFlx st2 Peak AVF 108 122 1.000 455 7.0 0x0 VinlFlx st1 Peak AVF 216 207 1.000 617 8.0 0x0 VinlFlx 2021-Aug-18 15:29:40 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 E:\Documnets\Wrightsoft HVAC\MCNALLY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 6270 627 0 0 0 0 x0 0 VlFx