Private Provider Report Card
Project Client Name Century Complete Homes
Project Community Name Lakewood Park
Project Permit Number 2011 0298
Project Address 7004 Penny Lane
Private Provider Firm Weintraub Engineering & Inspections, Inc
Private Provider Name Jerry M Weintraub Lic. No. 30033 (PE)
BUILDING INSPECTIONS ADDITIONAL INSPECTIONS
Date
Performed Inspector Code Description Date
Performed Inspector Code Description
Mar 23, 2021 SC BN6056 475 Temp Toilet Jun 14, 2021 SC BN6056 133 Windows & Door Bucks
Mar 29, 2021 SC BN6056 116 Mono Pre-Pour Dec 09, 2021 BM BN983 804 Driveway (Inside right of way)
Apr 12, 2021 SC BN6056 118 Column Oct 08, 2021 BM BN983 172 Hurricane Panels(Shutters)
Apr 12, 2021 SC BN6056 128 Bond Beam Dec 06, 2021 SR -- NA --BLOWERDOOR Blower Door
May 17, 2021 SC BN6056 135 Wall Sheathing Dec 06, 2021 SR -- NA --DUCT Duct Leakage Test
Apr 22, 2021 JW BN4874 134 Roof Sheathing
May 19, 2021 SC BN6056 136 Roof Dry In / Tin Tab
Sep 29, 2021 SC BN6056 167 Roof Final
May 19, 2021 SC BN6056 137 Strapping
Jun 14, 2021 SC BN6056 145 Truss DRWG
Jun 14, 2021 SC BN6056 300 Windows and Door Flashing
Jun 14, 2021 SC BN6056 127 Windows -Mullion
Jun 14, 2021 SC BN6056 148 Window/ Door Attachment
Jul 06, 2021 DS BN7384 140 Construction Rough Framing
Jul 06, 2021 DS BN7384 651 Weather Barrier
Jul 13, 2021 BM BN983 650 Frame All (Including Rough MEP'S)
Jun 24, 2021 SC BN6056 139 Wire Lath/Siding In Progress.
Jul 13, 2021 BM BN983 141 Insulation
Sep 29, 2021 SC BN6056 800 Address Final
Dec 06, 2021 BM BN983 999 Resident Final All (Including Final
MEP'S)
PLUMBING INSPECTIONS ELECTRICAL INSPECTIONS
Mar 23, 2021 SC BN6056 420 Plumbing Rough Mar 29, 2021 SC BN6056 103 Underground/Ufer
Dec 06, 2021 BM BN983 425 Sewer connection Sep 29, 2021 SC BN6056 POWER Pre-Power
Dec 03, 2021 BM BN983 WATER Water Service
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Mar 23, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:475 - Temp Toilet Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
475 Temp Toilet
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Mar 23, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:420 - Plumbing Rough Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
420 Plumbing Rough
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Mar 29, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:103 - Underground/Ufer Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
103 Underground/Ufer
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Mar 29, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:116 - Mono Pre-Pour Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
116 Mono Pre-Pour
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Apr 12, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:118 - Column Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
118 Column
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Apr 12, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:128 - Bond Beam Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
128 Bond Beam
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Apr 22, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Jon Wolfersberger License
Num:BN4874
Inspection Type:134 - Roof Sheathing Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
134 Roof Sheathing
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Jon Wolfersberger
Email address: jwolfersberger@weintraubinspections.com
Phone: (321) 474-1459
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:May 17, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:135 - Wall Sheathing Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
135 Wall Sheathing
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:May 19, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:136 - Roof Dry In / Tin Tab Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
136 Roof Dry In / Tin Tab
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:May 19, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:137 - Strapping Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
137 Strapping
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jun 14, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:133 - Windows & Door Bucks Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
133 Windows & Door Bucks
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jun 14, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:145 - Truss DRWG Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
145 Truss DRWG
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jun 14, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:300 - Windows and Door Flashing Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
300 Windows and Door Flashing
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jun 14, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:127 - Windows -Mullion Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
127 Windows -Mullion
INSPECTION: PASS
Observations / Comments:
No mullions in any windows
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jun 14, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:148 - Window/ Door Attachment Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
148 Window/ Door Attachment
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jun 14, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:140 - Construction Rough Framing
(REINSP-4)Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
140 Construction Rough Framing
INSPECTION: FAIL
Observations / Comments:
Inspection not to approved plans 107.3.4.1 No pressure on water supply system. No water in DWV pipe. Seal
front door frame.
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jun 16, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:140 - Construction Rough Framing
(REINSP-4)Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
140 Construction Rough Framing
INSPECTION: FAIL
Observations / Comments:
Inspection not ready 110.5 Repairs from original inspection have not been completed.
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jun 18, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:140 - Construction Rough Framing
(REINSP-4)Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
140 Construction Rough Framing
INSPECTION: FAIL
Observations / Comments:
Inspection not ready 110.5 Repairs from original inspection still have not been done.
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jun 21, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:139 - Wire Lath/Siding In Progress.
(REINSP-1)Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
139 Wire Lath/Siding In Progress.
INSPECTION: FAIL
Observations / Comments:
Inspection not ready 110.5 All nails in block walls need to be sealed or pulled.
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jun 22, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:140 - Construction Rough Framing
(REINSP-4)Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
140 Construction Rough Framing
INSPECTION: FAIL
Observations / Comments:
Inspection not ready 110.5 No pressure on water supply system.
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jun 24, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:139 - Wire Lath/Siding In Progress.
(REINSP-1)Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
139 Wire Lath/Siding In Progress.
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jul 06, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:David Salmon License
Num:BN7384
Inspection Type:140 - Construction Rough Framing
(REINSP-4)Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
140 Construction Rough Framing
INSPECTION: PASS
Observations / Comments:
Noted deficiencies are corrected
INSPECTED BY:
Inspector Name: David Salmon
Email address: dsalmon@weintraubinspections.com
Phone: (407) 821-0104
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jul 06, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:David Salmon License
Num:BN7384
Inspection Type:651 - Weather Barrier Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
651 Weather Barrier
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: David Salmon
Email address: dsalmon@weintraubinspections.com
Phone: (407) 821-0104
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jul 13, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Bobby Mckinney License
Num:BN983
Inspection Type:650 - Frame All (Including Rough MEP'S)Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
650 Frame All (Including Rough MEP'S)
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Bobby Mckinney
Email address: bmckinney@weintraubinspections.com
Phone: (321) 243-7884
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Jul 13, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Bobby Mckinney License
Num:BN983
Inspection Type:141 - Insulation Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
141 Insulation
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Bobby Mckinney
Email address: bmckinney@weintraubinspections.com
Phone: (321) 243-7884
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Sep 29, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:167 - Roof Final Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
167 Roof Final
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Sep 29, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:POWER - Pre-Power Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
POWER Pre-Power
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Sep 29, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Steve Campbell License
Num:BN6056
Inspection Type:800 - Address Final Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
800 Address Final
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Steve Campbell
Email address: scampbell@weintraubinspections.com
Phone: (813) 539-0618
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Oct 08, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Bobby Mckinney License
Num:BN983
Inspection Type:172 - Hurricane Panels(Shutters)Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
172 Hurricane Panels(Shutters)
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Bobby Mckinney
Email address: bmckinney@weintraubinspections.com
Phone: (321) 243-7884
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Dec 03, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Bobby Mckinney License
Num:BN983
Inspection Type:WATER - Water Service Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
WATER Water Service
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Bobby Mckinney
Email address: bmckinney@weintraubinspections.com
Phone: (321) 243-7884
Inspector Signature
ENVELOPE LEAKAGE TEST REPORT (BLOWER DOOR TEST)
Permit Number:2011 0298 Inspection Date:Dec 06, 2021
Client Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane , Fort Pierce , Florida,
34951 Lot:909
Inspector Name:Scotty Rashko BPI ID:5066580
Inspection Type:BLOWER DOOR Jurisdiction:ST Lucie County
ACH(50) {50 pa) =4.97 SQUARE FOOTAGE =1650.0
VOLUME=13200.0 CFM =1094.2
BUILDING VOLUME CALCULATION: RETRIEVED FROM ARCHITECTURAL PLANS
Certification of Test Result
Testing:
Testing shall be conducted in accordance with ANSI/RESENT/ICC 380 and reported at a pressure or 0.2 inche
w.g.(50 Pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7),
Florida Statues, or individuals licensed as set forth in Section 489.105(3)(f),(g), or (i) or an approved third
party. A written report of the results of the test shall be signed by the party conducting the test and provided
to the code official. Testing shall be performed at any time after creation of all penetrations of the building
thermal envelope. If your Blower Door Test is less than 3ACH you will be required to introduce outside air
into your building.
During Testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the
intended weather stripping or other infiltration control measures
2. Dampers including exhaust, intake, makeup air, backdraft, and flue dampers shall be closed, but not
sealed beyond intended infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and
sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
I hereby certify that the above Air Infiltration Test result demonstrate compliance with Florida Energy Code
requirements in accordance with the Florida Building Code-Energy Conservation, 7th Edition (2020).
PASS YES
Observations/Comments
Name:Scotty Rashko Email
address:srashko@weintraubinspections.com
Signature Phone #:(407) 487-6265
DUCT LEAKAGE TEST REPORT
Permit Number:2011 0298 Inspection Date:Dec 06, 2021
Client Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane , Fort Pierce , Florida,
34951 Lot:909
Inspector Name:Scotty Rashko BPI ID:5066580
Inspection Type:Duct Blaster Jurisdiction:ST Lucie County
System 1 28.0 cfm25
System 2 cfm25
System 3 cfm25
Sum of any additional
Systems cfm25
Total of all Systems 28.0 cfm25
28.0 +
Total of all
Systems
1650.0 =
Total conditional
sq.Footage
0.02
Qn
X Pass Fail
* RE-INSPECTION IS REQUIRED IF INSPECTION FAIL
Prescriptive Method cfm25 (Total)
To qualify as "substantially leak free" Qn must
be less than or equal to 0.04 if air
handler unit is installed. If air handler unit is
not installed,Qn Total must be less than or
equal to 0.03. This testing method meets the
requirements in accordance with
Section R403.3.4
Performance Method cfm25 (Out or
Total)
To qualify as "substantially leak free" Qn must
not be greater than the proposed Duct
leakage Qn specified on form R405-2017
Leakage Type Selected
on Form R405 - 2017
(Energy Calc)
Qn specified on Form
R405-2017
(Energy Calc)
Observations/Comments
I hereby verify that the above Duct Leakage results are in accordance with the 7th Edition Florida Building
Code Requirement with the Selected Compliance path as Stated above either the Prescriptive Method or
Performance Method.
Name:Scotty Rashko Email
address:srashko@weintraubinspections.com
Signature Phone #:(407) 487-6265
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Dec 06, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Bobby Mckinney License
Num:BN983
Inspection Type:425 - Sewer connection Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
425 Sewer connection
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Bobby Mckinney
Email address: bmckinney@weintraubinspections.com
Phone: (321) 243-7884
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Dec 06, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Bobby Mckinney License
Num:BN983
Inspection Type:999 - Resident Final All (Including Final
MEP'S)Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
999 Resident Final All (Including Final MEP'S)
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Bobby Mckinney
Email address: bmckinney@weintraubinspections.com
Phone: (321) 243-7884
Inspector Signature
INSPECTION REPORT
Permit Number:2011 0298 Inspection
Date:Dec 09, 2021
Client:Century Complete Homes Community:Lakewood Park
Building Address:7004 Penny Lane LOT / Block 909
Inspector Name:Bobby Mckinney License
Num:BN983
Inspection Type:804 - Driveway (Inside right of way)Jurisdiction:ST Lucie County
CODE INSPECTION DESCRIPTION
804 Driveway (Inside right of way)
INSPECTION: PASS
Observations / Comments:
INSPECTED BY:
Inspector Name: Bobby Mckinney
Email address: bmckinney@weintraubinspections.com
Phone: (321) 243-7884
Inspector Signature