PLUMBING MANUAL
2
For technical assistance call 1.800.621.5886 or contact your regional representative
The Paralevel is designed to control the water level in a swimming pool or spa. The “Posi-Click” control makes
adjusting the water level very easy. Four clicks (or one revolution) of the adjustment wheel changes the water
level by ¼”. The Paralevel uses “Smart Sensing”, eliminating rapid cycling of the device even when the pool is
being used. The user can use 1 ½” or 2” pipe for the balance line. The water line can be plumbed with ½” or
¾” pipe. The Paralevel can also be plumbed with 2” pipe for overflow protection, offering the highest overflow
protection in the industry.
1. Paralevel should be level and plumb.
2. The Paralevel main housing is engraved with “Max High; Max Low; and
Pool Level”. The housing should be mounted so that the “Pool Level” line
is at the expected water level.
3. Maximum water pressure is 80 psi.
4. The fill rate at 50 psi is 120 gph (2880 gallons per day).
5. WARNING: Balance line and overflow line must be plumbed straight.
Failure to keep the run of pipe straight may cause an airlock.
BADBAD
BADBAD
1
2
3 4
5
SYSTEM DESIGN
PARALEVEL LAYOUT & DESIGN CRITERIA
OVERVIEW
1. Fill port. Attach ½” in the ID or ¾” on the O.D. using a ¾” SxS fitting fill line from the water supply. Be sure
to install a shut off valve and approved vacuum breaker per local codes between the water supply and the
Paralevel.
2. Top of Gunite/shotcrete (Beam). This is the top of the pool shell assuming 3” above final water level.
3. Overflow. 2” PVC pipe should be used for overflow. A 2” line will make air locks less likely. This must be
capped off if it isn’t used.
4. Pool. This is the balance line into the pool. The fill water flows into the pool from this line. This may be
plumbed with 1 ½” or 2” PVC pipe
5. 80 psi Max. This is the maximum water pressure to be used with the Paralevel.
NOTE: MAKE ALL PLUMBING CONNECTIONS WITH PVC PIPE AND PVC PRIMER AND GLUE.
3
For technical assistance call 1.800.621.5886 or contact your regional representative
INSTALLATION METHODS
TOP FRONTTOPFRONT
WATER LEVEL WHEN
POOL IS FILLED
EARS
OVERFLOW
WATER SUPPLY
LINE
BALANCE LINE
FIG. 1
FIG. 2
Straight into pool
A. Paralevel should be installed plumb and level with
the top of the housing set even with the top of
pool beam (standard 3” water clearance).
B. Use the “ears” on the sides of the main housing to
securely tie to form boards or stakes. (Fig. 1)
C. During construction the Paralevel housing must be
covered with plastic and/or tape to prevent debris
from falling inside.
90º to pool (Fig. 2)
Top View from above Front View from outside of pool
Distance from Pool
A. The Paralevel can be placed adjacent to the side
of the pool (Fig. 3), in the deck or at the equipment
pad (Fig 4) as long as straight and level pipe runs
can be maintained.
B. There cannot be any place where the pipe
rises and falls possibly creating an air lock. See
Paralevel layout and design criteria.
CAUTION: It is recommended that a separate shut
off valve and approved vacuum breaker, per local
codes, be plumbed in between the supply water
source and the Paralevel housing.
Recommended “T” arrangement at fill port as a
debris trap. (Fig. 5)
Not to be used when winterization is
required. Cannot be used in conjunction with
winterization
FIG. 3
FIG. 4
4 - 6"
3/4" OR 1/2" TEE
FIG. 5
4
For technical assistance call 1.800.621.5886 or contact your regional representative
OVERFLOW
PRESSURE TEST SEAL (LARGE)
PRESSURE TEST SEAL (SMALL)
PRESSURE TEST CAP
WATERLINE PRESSURE TEST
OVERFLOW & BALANCE LINE PRESSURE TESTING
OVERFLOW INSTALLATION INSTRUCTIONS
6. Water line pressure test only.
• Install pressure test cap with large AND small
seals. (Fig. 7a and 7b)
• Tighten cap using removal tool (Fig 7c)
7. Balance line and overflow pressure test
• Install pressure cap with large seal only
• Tighten cap using removal tool (Fig. 8a and 8b)
• Install small pressure cap with O-ring using a
3/8” socket extension (not included).
8. Basic Overflow/Balance line rough-in. (Fig. 9)
• 1 ½” or 2” PVC schedule 40 pipe should be used
• Overflow can be set as close to or as far away
from pool as necessary as long as straight and
level lines can be maintained.
• Pool water from overflow must be disposed of
in accordance with state and local codes.
• Can be plumbed into a drain sump
• Can be plumbed into a deck drainage system
• Must be capped off if not used.
9. Overflow Installation Method 1. (Fig. 10)
• Simplest installation method.
• Cut pipe at desired overflow level.
• This method shouldn’t be used in areas where
pool is winterized.
FIG. 7a
PRESSURE TEST CAP
SMALL RUBBER SEAL
LARGE RUBBER SEAL
NOTICE NO GAP,SUPPLY TUBE IS ISOLATEDFROM BALANCE LINE
FIG. 7b
PRESSURE TEST CAPPRESSURE TEST SEAL(SMALL)PRESSURE TEST SEAL(LARGE)FIG. 7c
PRESSURE TEST CAP
PRESSURE TEST SEAL (LARGE)
ORING PRESSURE TEST PLUG
NOTICE GAP,SUPPLY TUBE WILL FLOWTO BALANCE LINE
LARGE RUBBER SEAL
PRESSURE TEST CAPFIG. 8b
FIG. 8a
STUB & CAP
FOR ROUGH-IN
WATER SUPPLY
1 1/2" OR 2"
PVC PIPE
STUB & CAPFOR ROUGH IN
NORMAL
LEVEL
FIG. 9
F.A. OR THREADEDWALL FITTING
CUT AT DESIREDOVERFLOW LEVEL
WATER SUPPLY
1 1/2" OR 2"PVC PIPE
NORMAL POOLWATER LEVEL
OVERFLOW INSTALLATION METHOD 1
FIG. 10
5
For technical assistance call 1.800.621.5886 or contact your regional representative
PARALEVEL OVERFLOW SET LEVEL
WATER LEVEL PRESET PROCEDURES
Steps to Ensure Overflow is Set at Proper Level
These instructions work with the deck installed or not. If deck is installed the overflow connection must be
made outside the deck.
1. Cut off the balance line rough plumbing stub inside the pool.
2. Install a female adapter or threaded wall fitting for final finish. Alternately if a FA is not used or this step is
performed in advance of final finish prep; the balance line can be cut long. Skip to step 4.
3. Thread a pipe nipple into the fitting.
4. Attach a 90 degree elbow and a standpipe to the threaded fitting.
5. Measure and cut the standpipe to the desired overflow level (example 1 ½” below the top of beam a 1
½ pipe will fit below the deck. This will allow the pool to overfill approximately 1 ½” before spilling out the
overflow pipe. If using 2” pipe drop to 2” below beam which will allow the pool to over fill 1” before spilling.)
6. Cut the standpipe on the exterior of the pool within a few inches above the desired spill level.
7. Fill the pipe with water and allow it to settle level to the temporary standpipe inside the pool.
8. Cut the exterior stub to match the level of the water in the pipe.
9. Remove the temporary standpipe on the interior of the pool by turning the threaded pipe out of the fitting.
10. Install one of the connections to waste shown in method 1 thru 4 on page 3 in the installation manual.
This method can also be used to preset the float leveler if the pool is not full of water
1. Turn on the water supply and flush the feed line to the Paralevel.
2. After the overflow is set cut the standpipe on the interior of the pool even with the desired water level in the
finished pool.
3. Install the Paralevel float assembly per the instructions in the manual.
4. Turn on water supply.
5. Set the water level to shut off when the canister fills to the top of the standpipe.
6. Turn off the water supply.
7. When the pool is complete fill with water to almost full, remove the hose and allow the Paralevel to complete
the fill to the preset mark. This will eliminate the need to watch the pool closely so it won’t overfill on initial fill
and can help ensure the pool will be full when startup is scheduled.
1
2 " TO TOP OF BEAM
NORMAL POOL
WATER LEVEL
CUT AT DESIRED
OVERFLOW LEVEL
WATER SUPPLY
1 1/2" OR 2"
PVC PIPE
F. A. OR
THREADED WALL FITTING
SETTING OVERFLOW
6
For technical assistance call 1.800.621.5886 or contact your regional representative
OVERFLOW INSTALLATION INSTRUCTIONS
Recommended for areas where pool is winterized.
Overflow Installation Method 2. (Fig. 11)
• Cut pipe at desired overflow level.
• Add double 90º ells to guide overflow into a drain
sump.
• Do not glue ells to allow for future overflow
adjustment.
• There must be an air gap between end of overflow
pipe and drain sump to prevent siphoning.
• Drill ¼” hole in top or side of pipe as shown if pipe
extends into drain sump without an air gap.
WARNING: IF PIPE EXTENDS INTO DRAIN WITH
NO VENTING, SIPHONING WILL OCCUR.
Overflow Installation Method 3. (Fig. 12)
• Vent line is flush with tile.
• Cut pipe at desired overflow level.
• Can be installed under the deck.
Overflow Installation Method 4. (Fig. 13)
• Vent line goes up through deck.
• Cut pipe at desired overflow level.
• Can be installed under the deck.
WARNING! Pipe must be straight
• There cannot be any place where the pipe rises
and falls possibly creating an air lock. (Fig. 14)
DOUBLE ELBOW
CUT AT DESIREDOVERFLOW LEVEL
REMOVE PLUG TO WINTERIZE
WATER SUPPLY1 1/2" OR 2"PVC PIPE
DO NOT GLUE
TO ALLOW FORFUTURE ADJUSTMENT
F.A. OR
THREADED WALL FITTING
NORMAL POOL
WATER LEVEL
DRILL 1/4" HOLEIF PIPE EXTENDSWITH NO AIR GAP
TO PREVENT SYPHONINGOVERFLOW INSTALLATION METHOD 2
FIG. 11
1/2" PIPE
VENT LINE
VENT LINE
FLUSH WITH TILE
F.A. OR
THREADED WALL FITTING
1 1/2" OR 2"PVC PIPE
ANGLE PIPE AT 45º SO VENT
LINE WILL MISS PARALEVEL
NORMAL
LEVEL
DESIRED OVERFLOW LEVEL
S
WATER SUPPLY
FIG. 12
VENT LINE
DESIRED OVERFLOW LEVEL
WATER SUPPLY
1 1/2" OR 2"PVC PIPE
F.A. ORTHREADED FITTING
NORMAL
LEVEL
S
FIG. 13
BAD
BAD
BAD
BAD
FIG. 14
DECK INSTALLATIONS
WARNING! Before pouring deck make sure the Paralevel main housing has not shifted during construction
• Minimum deck thickness is 2 1/8”. Deck thickness over 5” may require an extension kit
NEGATIVE EDGE, BASIN OR RAISED DECK INSTALLATION
Negative edge, basin or raised deck installations
with extension kit. (Fig. 15)
• If required an extension kit (005-252-1541-00) can
be purchased separately.
• The extension should be glued in place using PVC
primer and gray PVC glue
• Use 6 5/8” from normal water level to the center of
the balance line.
• A maximum of 19 3/4” is allowed from the top of
beam to the normal water level.
6 5
8 " TO CENTER
OF BALANCE LINE
19 3
4 " MAX
TO WATER LEVEL
LEVEL
F.A. OR
THREADED WALL FITTING
GLUE JOINT
SEE PREVIOUS
OVERFLOW DETAILS
WATER SUPPLY
1 1/2" OR 2"PVC PIPE
NORMAL
FIG. 15
7
For technical assistance call 1.800.621.5886 or contact your regional representative
Item Part Number Description
1 005-760-2901-XX LID
2 005-760-2915-XX DECK RING
3 HOUSING
4 005-760-2911-00 WINTERIZATION/PRESSURE TEST KIT
* 1 ½ NPT CAP
* MAIN SEAL
* CAP SEAL
* SEAL PLUG
* O-RING 2-020 EP70
8 005-252-1541-00** EXTENSION KIT
9 004-627-5452-00** TOOL
10 004-760-2929-00 START UP KIT B
11 * TOP LEVER
12 * LOWER LEVER
13 * LINK LEVER
14 * RISER TUBE
15 * SNAP RING
16 * O RING 2-011 VITON DUR 75
17 * FLOW PLUG
18 * O RING 2-020 EP70
19 * RETAINER NUT
20 * RETAINER RING
21 * ADJUSTER SLEEVE
22 * FLOAT BODY
23 004-762-2930-00** EXTENSION 1”
* Parts are not available separately
** not part of Paralevel order separately
PARALEVEL B PART NUMBERS
18
17
16
15
14
13
12
11 21
22
19
20
1
2
3
8
4
9
2310
004-760-2903-XX
8
For technical assistance call 1.800.621.5886 or contact your regional representative
PARALEVEL A PART NUMBERS
004-760-2900-XX
1
2
3
4 8
9
11
12
14
13
15
16
17
18
19
20
21
22
23
10
Item Part Number Description
1 005-760-2901-XX LID
2 DECK RING
3 HOUSING
4 005-760-2911-00 WINTERIZATION/PRESSURE TEST KIT
* 1 ½ NPT CAP
* MAIN SEAL
* CAP SEAL
* SEAL PLUG
* O-RING 2-020 EP70
8 005-252-1541-00** EXTENSION KIT
9 004-627-5452-00** TOOL
10 004-760-2919-00 START UP KIT
11 * TOP LEVER
12 * LOWER LEVER
13 * LINK LEVER
14 * RISER TUBE
15 * SNAP RING
16 * O RING 2-011 VITON DUR 75
17 * FLOW PLUG
18 * O RING 2-020 EP70
19 * RETAINER NUT
20 * RETAINER RING
21 * ADJUSTER SLEEVE
22 * FLOAT BODY
23 004-762-2930-00** EXTENSION 1”
* Parts are not available separately
** not part of Paralevel order separately