APPROVED ENERGY CALCS & MANUAL J - 6716 LILA
FORM R405-2020 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method ProjectName: GEMINI IMPACT BuilderName: WYNNE BUILDING CORP. Street: City, State, Zip: FT. PIERCE, FL, Permit Office: ST. LUCIE COUNTY PermitNumber: Owner: Jurisdiction: DesignLocation: FL, Fort Pierce County. St Lucie (Florida Climate Zone 2 ) 1. New construction or existing New (From Plans) 10. WallTypes(1763.8 sgft.) Insulation Area 2. Single family or multiple family Detached a. Concrete Block- Int Insul, Exterior R=4.1 1507.80 ft2 3. Numbero€units, if multiple family 1 b.Frame -Wood, Adjacent R=11.0 256.00ft' 4. Number of Bedrooms 2 c. NIA R= fP d. NIA 5. Is this a worst case? Yes R= ft2 11. Ceiling Types (1839.0 sgft.) Insulation Area 6. Conditioned floorareaabove grade (ft2) 1839 a. UnderAttic (Vented) R=30.0 1839,00 ft2 b. NIA Conditionedfloorareabelow grade (ft2) 0 R= ft2 c. NIA R= 7. Windows(155.3 sgft.) Description Area ft2 12. Ducts R ft2 a. U-Factor: Sgl, U=1.02 115.28 ft2 a. Sup: Attic, Ret: Attic, AH: Attic 6 125 SHGC: SHGC=0.27 b. U-Factor. Sgi, U=1.11 40.00 ft2 SHGC: SHGC=0.27 13. Cooling systems kBtulhr Efficiency c. U-Factor. NIA ft2 a. Central Unit 34.8 SEER:15.00 SHGC: Area Weighted Average Overhang Depth: 3.318 ft. 14. Heating systems kStulhr Efficiency Area Weighted Average SHGC: 0.270 a. Electric Heat Pump 34.8 HSPF:8.50 8. Skylights Area c. U-Factor:(AVG) NIA ft2 SHGC(AVG): N/A 15.Hot water systems 9. Floor Types (1839.0 sgft.) Insulation Area a. Electric Cap:40gallons a. Slab -On -Grade Edge Insulation R=0.0 1839.00 ft2 b. Conservation features EF: 0.950 b. NIA R= ft2 None c. NIA R= ft2 16. Credits None Glass/Floor Area: 0.084 Total Proposed Modified Loads. 51.52 PASS Total Baseline Loads: 52.96 I hereby certify that the plans and specifications covered by this Review of the plans and 'fikEST,g� calculation are in compliance with the Florida Energy specifications covered by this Code calculation indicates compliance _,,.-y 10 the Florida �p PREPARED BY: with Energy Code. +` rrr �� ; �•;y Before DATE:-� -2 211 construction is completed this building will be inspected for Nl- compliance with Section 553,908 I hereby certify that this building, as designed, is in compliance with the Florida Energy Coder+Q�` Florida Statutes. WS OWNER/ - BUILDING OFFICIAL: DATE: DATE: - Compliance requires certification by the air handler unit manufacturer that the air handler certified factory -sealed in accordance with R403.3.2.1. enclosure qualifies as - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402.4.1.2). 1113/2021 7:44 AM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT PROJECT Title: GEMINI IMPACT Bedrooms: 2 Address Type: StreetAddress Building Type: User ConditionedArea: 1839 Lot# OwnerName: Total Stories: 1 Block/Subdivision: #of Units: 1 Worst Case: Yes PlatBook: BuilderName: WYNNE BUILDING CORP. RotateAngle: 270 Street: Permit Office: ST. LUCIE COUNTY CrossVentilation: No County: St. Lucie Jurisdiction: Whole House Fan: No City, State, Zip: FT. PIERCE, FamilyType: Detached FL, New/Ewsting: New(From Plans) Comment: CLIMATE V Design Temp Int Design Temp Heating Design DailyTemp DesignLocation TMY Site 97.5% 2.5% Winter Summer Degree Days Moisture Range FL, Fort Pierce FL_VERO_BEACH_MUNI 39 90 70 75 299 62 Low BLOCKS Number Name Area Volume 1 Entire House 1839 14712 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated 1 BEDROOM 343 2744 No 0 1 1 Yes Yes Yes 2 WIC 63 504 No 0 1 No Yes Yes 3 M. BATH 56 448 No 0 1 Yes Yes Yes 4 KITCHEN 172 1376 Yes 0 1 No Yes Yes 5 MASTER BEDROO 256 2048 No 0 1 1 Yes Yes Yes 6 ENTRY 83 664 No 0 1 Yes Yes Yes 7 LAUNDRY 42 336 No 0 1 Yes Yes Yes 8 GREAT/DINING 568 4544 No 0 1 Yes Yes Yes 9 CLOSET2 56 448 No 0 1 No Yes Yes 10 BATH 2 48 384 No 0 1 Yes Yes Yes 11 POWDER 42 336 No 0 1 No Yes Yes 12 SITTING ROOM 110 880 No 0 1 Yes Yes Yes FLOORS # FloorType Space Perimeter PerimeterR-Value Area JoistR-Value Tile Wood Carpet 1 Slab -On -Grade Edge Insulation BEDROOM 43 It 0 343 ft' ---_ 0 1 0 2 Slab-On-GradeEdge Insulation WIC tft 0 63W __-- 0 1 0 3 Slab -On -Grade Edge Insulation M.BATH 8ft 0 56 ft2 --__ 0 1 0 4Slab-On-Grade Edge Insulation KITCHEN 1 ft 0 172 ft' __-- 0 1 0 5 Slab -On -Grade Edge Insulation MASTERBEDRO 51ft 0 256W ---- 0 1 0 1/13/2021 7:44 AM 7.0.00-FlaRes2020 FSC 7th Edition (2020) Compliant Software Page 2 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT FLOORS # FloorType Space Perimeter PerimeterR-Value Area JoistR-Value Tile Wood Carpet 6 Slab-On-GradeEdge Insulation ENTRY 7ft 0 83 ft' ____ 0 1 0 7 Slab -On -Grade Edge Insulation LAUNDRY Eft 0 42 ft2 ____ 0 1 0 8 Slab -On -Grade Edge Insulation GREAT/DINING 39It 0 568 ft2 ___ 0 1 0 9 Slab -On -Grade Edge Insulation CLOSET2 1 ft 0 56 ft2 ____ 0 1 0 10SIab-On-GmdeEdgelnsulation BATH 2 8 ft 0 48 ft2 0 1 0 11SIab-On-Grade Edge Insulation POWDER 1 it 0 42 ft2 ____ 0 1 0 12SIab-On-GradeEdge Insulation SITTING ROOM 22ft 0 110 fF ____ 0 1 0 ROOF _ / Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg) 1 Hip Metal 1938IV O R2 Light N 0.6 No 0.7 No 0 18.43 ATTIC / `� # Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 Fullattic Vented 150 1839 ft2 N N CEILING # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type _ 1 UnderAttic(Vented) BEDROOM 30 Blown 343 ft2 0.1 Wood 2 UnderAttic(Vented) WIC 30 Blown 63ft 0.1 Wood 3 UnderAttic(Vented) M.BATH 30 Blown 56 fF 0.1 Wood 4 UnderAttiC(Vented) KITCHEN 30 Blown 172 ft2 0A Wood 5 UnderAttic(Vented) MASTER BEDRO 30 Blown 256 fF 0.1 Wood 6 UnderAttic(Vented) ENTRY 30 Blown 83 fF 0.1 Wood 7 UnderAtfic(Vented) LAUNDRY 30 Blown 42ft 0.1 Wood 8 UnderAtfic(Vented) GREAT/DINING 30 Blown 568 fF 0.1 Wood 9 UnderAtGc(Vented) CLOSET2 30 Blown 56 fF 0.1 Wood 10 UnderAttiC(Vented) BATH 30 Blown 48ft2 0.1 Wood 11 UnderAttic(Vented) POWDER 30 Blown 42 ft2 0.1 Wood 12 UnderAttic(Vented) SITTING ROOM 30 Blown 110fF 0.1 Wood WALLS Adjacent Space Cavity Width Height Sheathing Framing Solar Below _ 1 S=>E Exterior Concrete Black- Int Insul BEDROOM 4.1 29 0 8 0 232.0 ft2 0 0 0.4 0 _2 W=>S Exterior Concrete Block- Int Insult BEDROOM 4.1 14 0 S 0 112.Oft2 0 0 0.4 0 _ 3 S=>E Exterior Concrete Block- Int Insul M. BATH 4.1 8 0 8 0 64.0 fF 0 0 0.4 0 4 N=>W Exterior Concrete Block- Int lnsuMASTER BE 4.1 24 0 8 0 192.0 fF 0 0 0.4 0 1/13/2021 7:44 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT WALLS Adjacent S Space Cavity Width Height Sheathing Framing Solar Below o 5 E=>N Exterior Concrete Block- Int InsuMASTER BE 4.1 13 0 8 0 104.0 ft- 0 0 0.4 0 6 S=>E Exterior Concrete Block- Int InsuMASTER BE 4.1 14 0 8 0 112.Oft' 0 0 0.4 0 _7 E=>N Exterior Concrete Block -Int lnsul ENTRY 4.1 6 0 8 0 48.0 ft' 0 0 0.4 0 8 S=>E Exterior Concrete Block-Int lnsul ENTRY 4.1 1 0 8 0 8.0 ft' 0 0 0.4 0 _9 S=>E Exterior Concrete Block- Int lnsul LAUNDRY 4.1 6 0 8 0 48.0W 0 0 0.4 0 10 N=>W Exterior Concrete Block- Int lnsulGREATIDINI 4.1 30 0 8 11 267.5 ft- 0 0 0.4 0 11 W=>S Exterior Concrete Block-Int lnsuGREAT/DINI 4.1 9 0 8 11 80.3W 0 0 0.4 0 12 N=>W Exterior Concrete Block -Int lnsul BATH2 4.1 8 0 8 0 64.0 ft' 0 0 0.4 0 13 N=>W Exterior Concrete Block- Int InsuBITTING RO 4.1 10 0 8 0 80.0 ft` 0 0 0.4 0 14 S=>E Exterior Concrete Block- Int InsuBITTING RO 4.1 1 0 8 0 8.0 fP 0 0 0.4 0 15 W=>S Exterior Concrete Block- Int InsuBITTING RO 4.1 11 0 8 0 88.0 ft' 0 0 0.4 0 16 N=>W Garage Frame -Wood KITCHEN 11 32 8 256.0 ft2 0.23 0.4 0 DOORS # Omt DoorType Space Storms U-Value Width Height Area Ft In R In 1 E=>N Insulated ENTRY None .32 3 6 8 20ft WINDOWS Orientation shown is the entered orientation => changed to Worst Case. Wall Overhang V # Dint ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation IntShade Screening 1 W=>S 2 Metal Low-ESingle Yes 1.02 027 Y 32A ft= 1 It 0 in 1 ft4 in Drapes/blinds Exteriors 2 S=>E 3 Metal Low-ESingle Yes 1.02 027 Y 6.9ft2 ft0 in 1ft4in None None 3 E=>N 5 Metal Low-ESingle Yes 1.02 027 Y 32A ft' 1 ft0 in 1 ft4 in None None 4 N=>W 10 Metal Low-ESingle Yes 1.02 027 Y 18.4 ft' 1 ft 0 in 1 ft 4 in None None 5 W=>S 11 Metal Low-ESingle Yes 1.11 0.27 Y 40.0 ft' 10 ft0 in Ift4 in None None 6 N=>W 12 Metal Low-ESingle Yes 1.02 027 Y 6.9 ft2 1 8 0 in 1 ft4 in None None 7 W=>S 15 Metal Low-ESingle Yes 1.02 0.27 Y 18.4 ft2 1ft0in 1ft4in None None GARAGE # FloorArea CeilingArea Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 320 112 320 ft' 32 ft 8It 11 INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse ProposedACH(50) .000254 1226 67.26 12628 .0902 5 1/13/2021 7:44 AM 7.0.00-FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPnRT HEATING SYSTEM # System Type Subtype Speed Efficiency Capacity Block Ducts 1 Electric Heat Pump/ Split Single HSPF:8.5 34.8 kBtu/hr 1 sys#1 COOLING SYSTEM # System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 CentralUnit/ Split Single SEER: 15 34.8 kBtu/hr ofm 0.85 1 sys#1 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Electric None Garage 0.95 40 gal 60.9gal 120deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Can # CompanyName System Model# CollectorModel# Area Volume FEF None None ft' DUCTS / —Supply— --Return— Air CFM 25 CFM25 HVAC# V # Location R-Value Area Location Area LeakageType Handler TOT OUT QN RLF Heat Cool i Attic 6 125 ft' Attic 40 W DefaultLeakage Attic (Default) c(Default) c 1 1 TEMPERATURES Prog2mabler[T,]hermostat::x1)JN Ceiling Fans:Cooli rr ar Heating [X]Jan Feb [X]Mar �Ap�(JJ00 Apr € Me May [ jJun [ jJul (X� [ ]Aug ([JJ0C� [ ]Sepoct ([X�] ([X�] VeDec nting [[ lj Jan [ r Feb I[J�(1] Mar l l [ ] Jun [[ ]] Jul [ j Aug l[ 1] Sep [ ]X Nov [ jDDec ec ThermostatSchedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 88 68 as Heating(WEH) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 MASS Mass Type Area Thickness FumitureFraction Space Default(8lbs/sq.ft. oft? 0 ft 0.3 BEDROOM Default(8lbs/sq.ft. W ft 0.3 WIC Default(B lbs/sq.ft. ft� ft 0.3 M. BATH Default(81bs/sq.ft. ft' ft 0.3 KITCHEN Default(8 lbs/sq.ft. ft' ft 0.3 MASTER BEDROO Default(81bs/sq.ft. W ft 0.3 ENTRY Default(81bs/sq.ft. ft- ft 0.3 LAUNDRY Default(81bs/sq.ft. ft' ft 0.3 GREAT/DINING Ill312021 7:44 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT MASS Mass Type Area Thickness FunnitureFracfion Space Default(8lbs/sqft ft' ft 0.3 CLOSET 2 Default(81bs/sq.ft. ft' ft 0.3 BATH 2 Default(8lbs/sq.ft ft' ft 0.3 POWDER Default 8lbs/ .fL ft' ft 0.3 SITTING ROOM 1/13/2021 7:44 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 6 of 6 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: GEMINI IMPACT Builder Name: WYNNE BUILDING CORP. Street: Permit Office: ST. LUCIE COUNTY City, State, Zip: FT. PIERCE, FL, Permit Number: U Owner: Jurisdiction: w Design Location: FL, Fort Pierce z COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior themlal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped soffit pP ceilin 9/ the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking,or floor framing cavity 9 ty insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace wall . Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spa s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be airtight and IC rated. Plumbing and wiring Batt insulation shall be out neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. I Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover plates and walls or cell nas a. in addition, inspection of log wails shall be in accordance with me provisions of IGC'-400. 1/13/2021 7:45 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of i FORM R405-2020 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 97 The lower the EnergyPerformance Index, the more efficient the home. FT. PIERCE, FL, 1. New construction or existing New (From Plans) 10. Wall Type and Insulation 2. Single family or multiple family Detached a. Concrete Block - Int Insul, Exterior b. Frame - Wood, Adjacent 3. Number of units, if multiple family 1 c. N/A 4. Number of Bedrooms 2 d. N/A 5. Is this a worst case? Yes 11. Calling Type and insulation level a. Under Attic (Vented) 6. Conditioned floor area (W) 1839 b. N/A 7. Windows" Description Area c. N/A a. U-Factor. Sgl, U=1.02 115.28 ft- 12. Ducts, location & insulation level a. Sup: Attic, Rat: Attic, AH: Attic SHGC: SHGC=0.27 b. U-Factor. Sgl, U=1.11 40.00 ft' SHGC: SHGC=0.27 13. Cooling systems c. U-Factor. WA ft' a. Central Unit SHGC: d. U-Factor: N/A ft2 14. Heating g systems Area Weighted Average Overhang Depth: 3.318 ft. a. Electric Heat Pump Area Weighted Average SHGC: 0270 8. Skylights Description Area 15. Hot water systems a. U-Factor(AVG): N/A W a. Electric SHGC(AVG): N/A b. Conservation features 9. Floor Types Insulation Area None a. Slab -On -Grade Edge Insulation R=0.0 1839.00 ft' Credits (Performance method) b. N/A R= tt' c. N/A R= ft- I certify that this home has complied with the Florida Energy Efficiency Code for Building Construction through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL Display Card will be completed based on installed Code co�atures. Builder Signature: Date: Address of New Home: LQ \ �� City/FL Zip: QS Insulation Area R=4.1 1507.80 ft' R=11.0 256.00 fF R= ft- R= ft' Insulation Area R=30.0 1839.00 ft- R= ft' R= if R fF 6 125 kBtu/hr Efficiency 34.8 SEER:15.00 kBtu/hr Efficiency 34.8 HSPF:8.50 Cap: 40 gallons EF: 0.95 None 'Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 1/13/2021 7:45 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Project SummaryJob'.wrightsoft® Entire House Da ` QUICK CALCS, INC. 317 ST. LUCIE LN., Fr. PIERCE, FL 34946 Pt re: T 2-466-6799 F. M-466-6796 Emil: OUICKCALCS@AOL.COM Project• • For. THE GEMINI WYNNE DEV., FT. PIERCE, FL Notes: Design Information Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure 21011 Btuh Structure 19448 Btuh Ducts 6289 Central vent (0 cfm) 0 Btuh Btuh Ducts Central vent (0 cfm) 9502 0 Btuh Btuh none e ) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipmentload 27300 Btuh Use manufacturer's data n Infiltration Rate/swingg multiplier Equipmeniload 0.95 sensible 27502 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2170 Btuh DCuenntral 2590 vent (0 cfm) BBtuh Heatingg Area(tt2) Coolingg (none) 1839 1At Equipment latent load 4768 Btuh Volume (fP) 15582 15582 Airchanges/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 32271 Btuh Equiv AVF (dm) 99 52 Req. total capacity at 0.70 SHR 3.3 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Trade CARRIERAIR CONDITIONING Model 25HBC536A*030 AHRI ref 7914585 Efficiency Heating input Heating output Temperature rise Actual airflow Airflowfactor Static pressure Space thermostat Capacity balance point = 36 OF 8.5 HSPF 34600 Btuh@47°F 27 OF 1160 cirn 0.042 cIm/Btuh 0.50 in H2O Bacicup: Input=7kW, Output= 23009 Btuh, 100 AFUE Make Carrier Trade CARRIERAIR CONDITIONING Cond 25HBC536MO30 Coil FX4DN(B,F)037 AHRI ref 7914585 Efficiency 12.0 EER,15 SEER Sensible cooling 24360 Btuh Latentcooling 10440 Btuh Total cooling 34800 Btuh Actual air flow 1160 cfin Airflowfactor 0.040 cm/Btuh Static pressure 0.50 in H2O Load sensible heat ratio 0.86 Calculations approved byACCAto meet all requirements of Manual J 8th Ed wr.2#2t oft- 2021JaM307:44A9 •"^'-' RigFPSute®Uriversal 201919.021 RSU08101 Page 1 ...UICK1Doctm kWrigF oitFNACIWYNNE-GEMINInp Gaic=MIB Frm¢Ccorfzces: N F� wrightsoft° Right-M Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FL PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: OUICKC4LCS@AOL.COM 1 Room name EnfireHour MASTER BEDROOM 2 EVos:dvall 212.0 ft 43.0 ft 3 Room height 8.5 ft d 8.0 ft heaVmol 4 Room dimensom' - 1.0 x 343.0 ft 5 Roomarea 1839.0 fF 343.0 fR Ty Construclion U-value Or HTM Area W) Load Loud number (BWhAtx*q (BWW or penmetar (ft) (Btuh) or�pen m (ft) (BWh) Heat Cool Gross NIPS Heat Cool Gros NIPIS Heat Cool 6 13A-0os 0.143 n 4.00 235 628 602 2412 1533 0 0 0 0 1Aolom 1270 n 3556 34.77 7 0 247 241 0 0 0 0 4A5-2om 0.770 n 2156 1931 19 0 407 365 0 0 0 0 13A4ors 0.143 a 4.00 2.55 152 98 394 250 0 0 0 0 11 1Ac1om 1270 a 35.56 8729 33 2 1162 2853 0 0 0 0 11DO 0390 a 1022 1131 21 21 229 238 0 0 0 0 t13A-4os 0.143 s 4A0 255 473 466 1868 1187 232 232 929 591 —C 1Ac1on 1270 s 35.56 34.77 7 7 247 241 0 0 0 0 13A-0os 0.143 w 4.00 2.55 295 203 813 517 112 79 318 202 1A-dom 1270 w 3556 5525 33 2 1162 1808 33 2 1162 1806 4A5-2om 0.770 w 2156 44.72 19 2 407 945 0 0 0 0 4A5-2ovd 0.470 w 13.16 35.61 41 2 537 1453 0 0 0 0 P 12C-09v 0.091 255 128 224 224 571 287 0 0 0 0 C 16A-30md 0032 - 0A0 2.32 1839 1839 1648 42% 343 343 307 7% F 2ZA-ml 0.989 - 27.69 0.00 1839 212 5871 0 343 43 1191 0 6 c)AEDe=mon 508 618 Envelopelos4gain 17975 16592 3907 4012 12 a) Inflbafion 3037 856 674 190 b) Room venfilafion 0 0 0 0 13 Intemalgainst O=pants@ 230 0 0 0 0 Applianw4other 20M 0 Sub=I (lines6to 13) 21011 19448 4581 4202 Lesexmai load 0 0 0 0 Lestwsler 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 21011 19448 4581 4202 15 Ductloads 30% 49% 6289 9502 30% 49% 1371 2053 ToW room load 27300 28950 5952 6255 Air required (dm) 1160 1160 253 251 Calculations approved bvACCAtO meet all reouirements of Manual J 8th Ed -rw 2021-Jan-1307:44A9 'A RigYfSute81-riversal 201919.021 RSU08101 Page 1 ...UICK1DoamerMWngtboft HVAQWYNNE-GEMINIAP CaIc=MJ6 RorlDoorfaces: N F wrghtsoft- Right-l® Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466.6799 Fax 772466-6796 Emil: OUICKCALCS@AOL.COM 1 Room name WIC MBATH 2 Bposedwall 0 it 8.0 ft 3 Room height 8.0 It heaV=l 8.0 it heatlmol 4 Room dimensions 7.0 x 9A ft 7.0 x &0 ft 5 Room area 63.0 IF 56.0 T Ty Construction U-Wlue Or HTM Area Load Arm number (B1uh4F--F) (BtuhAF) or perimeter (ft) (Bluh) a penmeetar M (Biuh) Heat Cool Gross NIPS Heat Cool Gross NIPS Heat Cool 6 y/ 13A-4= 0.143 n 4.00 2.55 0 0 0 0 0 0 0 0 IL---G 1Aclom 1270 n 35.56 34.77 0 0 0 0 0 0 0 0 4A5-2om 0.770 n 21.56 19.31 0 0 0 0 0 0 0 0 13AAos 0.143 a 4.00 2.55 0 0 0 0 0 0 0 0 11 1Aclom 1270 a 3556 8729 0 0 0 0 0 0 0 0 11DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0 MI 13k4o s 0.143 s 4.00 255 0 0 0 0 64 57 228 145 -G 1Ac1am 1270 s 35.56 34.77 0 0 0 0 7 7 247 241 13A-0as 0.143 w 4.00 25.5 0 0 0 0 0 0 0 0 1Ac1om 1270 w 3555 5525 0 0 0 0 0 0 0 0 4A5-2om 0.770 w 21.56 44.72 0 0 0 0 0 0 0 0 4A5-2oW 0.470 w 13.16 35.61 0 0 0 0 0 0 0 0 P 12C-Ow 0.091 2.55 128 0 0 0 0 0 0 0 0 C 16A-30md 0.032 - 0.90 2.32 63 63 56 146 56 56 50 130 F 22A-tpl 0989 - 27.69 0.00 03 0 0 0 55 a 222 0 6 c)AED e=rsion .12 -47 Envelope loss(gain 56 134 747 469 12 a) Infiltration 0 0 125 35 b) Room%erNlation 0 0 0 0 13 Internal gains: Omrpants(Qo 230 0 0 0 0 Applianoeslolher 0 0 Subtofal(lines64113) 56 134 872 505 Lessexemalload 0 0 0 Lesstransfer 0 0 0 Redistribution 0 0 0 14 Sublolal 56 134 ]261 505 15 Ductloads 30% 49A 17 66 30 0 49% 247 Total room load 73 199 751 Air required(dm) 38 30 Calculations approved byACCAto meet all requirements of Manual J 8th Ed -rid- wrlghof[ ts- 2021-Jan1307:4499 �A MgttStits@Uriwrml20l9l9.021RSW8101 Page2 ...UICMDoa r6lWngftsotHVAC%WVNNE-GEMINIxW Calc=tvll8 Fnont Worfaces:N I wrghtsofr Right-JO Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., F.. PIERCE, FL 34946 Ptom:772-466-6799 Fax:772-466.6796 Email:OUICKCALCS AOL.COM 1 Room name KrrCHEN WSTER BEDROOM2 2 EVosdwail 8.0 ft 51.0 R 3 Room height 8.0 ft heaU000l 8.0 ft heV1bool 4 Room dlme 1.0 x 1M.0 it 7.0 x 256.0 Itnsons Room area 172.0 T 256.0 IF Ty Construction U-value Or HTM Area Lobe number (BiuhW' q or perimeer (ft) (BWh) or perimeter(fl) (BWh) Heat Cool Gros N/P/5 Heat Cool Gras N/P/S Heat Cool 6 V(/`�!G' 13A-4= 0.143 n 4.00 2.55 0 0 0 0 192 192 769 489 1Ac1orn 1270 n 35.56 34.77 0 0 0 0 0 0 0 0 4A5.2om 0.770 n 2156 1931 0 0 0 0 0 0 0 0 13A-4= 0.143 a 4.00 255 0 0 0 0 104 71 286 182 11 1Aclom 1270 a 35.56 87Z 0 0 0 0 33 2 1162 2853 D 11DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0 Vt_G13A-4= 0.143 s 4.00 255 0 0 0 0 112 112 448 285 1Aclom 1270 s 3556 34.77 0 0 0 0 0 0 0 0 13A-4= 0.143 w 4.00 255 0 0 0 0 0 0 0 0 1Aclom 1270 w 35M 5525 0 0 0 0 0 0 0 0 4A5-2om 0.770 w 21.56 44.72 0 0 0 0 0 0 0 0 4A5-2oW 0.470 w 13.16 35.61 0 0 0 0 0 0 0 0 P 12C-Ow 0.091 2.55 128 64 64 163 82 0 0 0 0 C 16A30md 0.032 - 0.90 222 172 172 154 399 256 256 229 594 F 22A-tp] 0989 27.69 0.00 172 8 222 0 256 51 1412 0 6 c)AEDe=Hsion -211 -176 Envelope losdgain 539 270 4307 4227 12 a) Infiltration 0 0 800 226 b) Rcomeentlation 0 0 0 0 13 Internal gains: Occupant@ 230 0 0 0 0 Appliaroaslolher 2000 0 Subtotal (lines 6 to 13) 539 2270 5106 4452 Less external load 0 0 0 0 Lestransfer 0 0 0 0 Redistibution 0 0 0 0 14 Subli 539 2270 5106 4452 15 Ductloads 30% 49% 161 1109 30% 49% 1528 2175 Total room bad 700 3380 6635 6627 Air required(dm) 30 135 282 --- Calculations approved bvACCAto meet all requirements of Manual J 8th Ed wrfi9ti�o�' 2021Jan-1307.44A9 �`WK PogH-Sdte®llrivers1201919.021 RSU08101 Page 3 ...UICKU)o ris\Wdgtmoft HVAaWYNNE-GEMINI.np Calc=MI8 Front Doorfaws: N wrightsoft° Right-J® Worksheet Job° Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCE LN.. Fr. PIERCE, FL 349Q Phore:772466-6799Fa 772-466b796 ErrafI:QU1CKrALCS@AO1-.COM 1 Room name ENTRY LAUNDRY 2 3 Evowdwall Room heir[ 20D t 8D It heaVmol 13.0 ft 8D t heatlmoi 4 5 Raom dimrlvvons Room area 1D x 63A ft 83.0 if 74 z 6.0 ft 42.0 tF Ty Conduction number U-value (BUiAFL'9 Or HTM (BWh Area or perim� (ft) Load (BWh) AM (fe) a pEarneeter (ft) Load (Bmh) Hea[ Cool Gros NIPS Heal Cool Gros WPS Heat Cool 6 %p 13A4os tAcian 4AS,2om 0.143 1270 0.770 n n n 4D0 35.56 21M 2S5 34.77 1931 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 11--GG 11 13A M 1Ad= 0.143 1270 a a 4D0 3556 255 9729 48 0 27 0 108 0 69 0 0 0 0 0 0 0 0 0 W Y--a 11D0 1344o s +Aclw 13A4= 1Aclw 4A&2am 4A&2oW 12C-WN 16A Sand 22A4P1 0390 0.143 1270 0.143 1270 0.770 0.470 0.091 0.032 0989 a s s w w w w - - - 1092 4D0 351% 4DD 3556 21M 13.16 2S5 090 2759 1131 255 34.77 2S5 5525 44.72 35.61 128 232 a00 21 8 0 0 0 0 0 104 83 83 21 8 0 0 0 0 0 104 83 20 229 32 0 0 0 0 0 265 74 554 238 20 0 0 0 0 0 133 193 0 0 48 0 0 0 0 0 66 42 42 0 48 0 0 0 0 0 56 42 13 0 192 0 0 0 0 0 143 38 360 0 - -- 122 0 0 0 0 0 - 72 97 0 p C F 6 c)AEDe rson fib -27 Envelope bsslgain 1263 595 733 264 12 a) Wftgon b) Roomvenfilafion 110 0 31 0 94 0 27 0 13 Irftnalgairs: O=pants@ 230 0 0 0 0 Applianosbbher 0 0 Subbtal(lines6b13) 1372 625 827 291 bme&Milload 0 0 0 0 14 Lmransier Redidibudon SubbW 0 0 1372 0 0 625 0 0 827 0 0 291 15 Durtloads 30% 49% 411 306 30% 49% 247 142 ToW mom bad Air requimd(dm) 1783 76 931 37 1074 46 433 17 Calculations approved byACCAto meet all requirements of Manual J 8th Ed 7&-pw wrzohtsoft- 2021-J n1307:4499 A R9NSulaVUnvarsa1201919D21 RSU08101 Page _.UICK1Dc rtAWdg%oftWAC1WYNNE-GEMMinp CaIc=MR FrortDoorboss: N wrightsoft Right-J@ Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN, Fr. PIERCE, FL 34946 PF re: 772-466-6799 F.72-4666796 Emil: GUICKCALCSmUOL.00M 1 Room name GREAT/DINING CLOSET2 2 Exposed wall 3910 ft 0 ft 3 Room height 8.9 ft heatcool 9.4 ft heaV000l 4 Room dimensions 1.0 x 568.0 ft 7.0 x 8.0 ft 5 Room area 568.0 ft' 56.0 T Ty Construction U-value Or HTM Area Load number (BtulMl;`E) (atuh" or perimeter (ft) (Btuh) or�perim�r (ft) (B�) Heat Cool Gross WAS Heat Cool Gross NIPS Heat Cool 6 VL13A4o s 0.143 n 4.00 2.55 267 248 993 632 0 0 0 0 1Ac1om 1270 n 3556 34.77 0 0 0 0 0 0 0 0 06,2om 0.770 n 21.56 19.31 19 0 407 365 0 0 0 0 W �G 13A4= 0.143 a 4.00 255 0 0 0 0 0 0 0 0 11 1Ac1om 1270 a 3556 8729 0 0 0 0 0 0 0 0 �D 11DO 0.390 a 10,92 1131 0 0 0 0 0 0 0 0 1/y 13A4ars 0.143 s 4A0 2.55 0 0 0 0 0 0 0 0 1Aciom 1270 s 3556 34.77 0 0 0 0 0 0 0 0 13A-0acs 0.143 w 4.00 2.55 80 39 157 100 0 0 0 0 1Actom 1270 w 35.56 5525 0 0 0 0 0 0 0 0 4A5-2om 0770 w 2156 44.72 0 0 0 0 0 0 0 0 4A5-2oW 0.470 w 13.16 35.61 41 2 537 1453 0 0 0 0 P 12C-Ow 0.091 - 2S5 128 0 0 0 0 0 0 0 0 C 16A30md 0.032 - 0.90 232 568 568 509 1318 56 56 50 130 I 22A-tpi 0989 - 27.69 0.00 568 39 1080 0 56 0 0 0 6 c)AED e i aon 256 -11 Envelope lossEain 36M 4123 50 119 12 a) Irlfiltraton 680 192 0 0 b) Roomvenfilafon 0 0 0 0 13 Internal gains: Cmrpans@ 230 0 0 0 0 Appliancasbther 1 0 0 Subhrhl(lines6to 13) 4364 4315 50 119 Lesexamalload 0 0 0 0 Lestransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 4364 4315 50 119 15 Ductloads 30% 49% 1306 2108 30% 49. 15 58 Total room load 5671 6423 65 177 Air required(Cm) 241 257 1 3 7 Calculations approved byACCAto meet all requirements of Manual J 8th Ed 2021-Jarv1307:44.09 AC�h ggftSUL Urivml20l9l9.021RSUb8101 Pages ...UICIDoc rtslWdgtts tWACIWVNNE-GEMINinp GIc=W8 Fror¢CoorfamEN wrightsoftRight-JO Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST.. LLICIE LN., F .. PIERCE, FL 34946 Phore: 772-4666799 Fax: 7724666796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 2 POWDER 8.0 ft p g 3 Roomheight 9.4 ft heai/mol 9.4 ft t>e 4 Roomdimerisions 6.0 x 8.0 ft 7.0 x 6.0 ft It 5 Room area 48.0 IF 42.0 IF Ty Coroltuction U-value Or HTM Area in Load Area (ft0 Load number I (BNWF) (BWhaI or perimeter (ft) (BWh) or perimeter (ft) (BWh) Heat FC.1 Gross NIPS Heat T Cool Gross N/P)S Heat Cool 6 4U 1SA4= 0.143 n 4.00 2.55 75 68 273 174 0 0 0 0 1Aclom 1270 n 3556 34.77 7 0 247 241 0 0 0 0 II--GG 4A5-2om 0.770 n 21.56 19.31 0 0 0 0 0 0 0 0 W 13A-4ots 0.143 a 4.00 2S5 0 0 0 0 0 0 0 0 11 I-G 1Ac1om 1270 a 3556 8729 0 0 0 0 0 0 0 0 �D 11DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0 13A-4ocs 0.143 s 4.00 2.55 0 0 0 0 0 0 0 0 1Aclom 1270 s 35.56 34.77 0 0 0 0 0 0 0 0 13A-0ocs 0.143 w 4.00 2.55 0 0 0 0 0 0 0 0 tActom 1270 w 3556 5525 0 0 0 0 0 0 0 0 4A5-2om 0.770 w 2156 44.72 0 0 0 0 0 0 0 0 4P5-2ovd 0.470 w 13.16 35.61 0 0 0 0 0 0 0 0 P 12C-09v 0A91 - 2.55 128 0 0 0 0 0 0 0 0 C 16A30md 0A32 - 0.90 2.32 48 48 43 111 42 42 38 97 F 22A-tpl 0.989 - 27.69 0.00 48 8 222 0 42 0 0 0 6 c)AEDe=rdw -08 Ernelopeloss/gain 784 478 38 89 12 a) Infiltration 147 42 0 0 b) Roomeentilation 0 0 0 0 13 Internal gains O=pants@ 230 0 0 0 0 Applianc other 0 0 Subbtal(lirus6to13) 932 520 38 89 Leasexbmalload 0 0 0 0 tesstrarsfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 932 520 38 89 15 Duo:loads 30% 49% 279 254 30% 49% 11 44 Total room bad 1211 773 49 133 Air required(dm) 51 31 2 5 Calculations approved byACCAto meet all requirements of Manual J 8th Ed -Fw wr19t+>Gsoft' -- 2021-Jan-1307:4499 A&h RigFt-SdbE&Uriversa1201919.021 RSUDS101 Page6 ...UICKDow rbirt Wdgoft HVAOWVNNE-GEMINInp Calc=W8 FrorQWorfaces N I wrighUoft° Right-M Worksheet Jab: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN.,FT. PIERCE, FL 34946 Prone: 772-466-6799 Fax 772-466-6796 Emil: OUICKCALCS@AOL.COM 1 Room name DEN 2 Fxposdwall 22.0 It 3 Room height 9.4 It heaVmol 4 Room dimensons 11.0 x 10.0 ft 5 Room area 110.0 ff Ty Constuction U-value Cr HTM Area (11� Load Area Load number (BtirhAF--°F) (Blih" or perimeter (ft) (BWh) or perimeter Heat Cool Gross N1P/S Heat Cool Gross N,PIS Heat Cool 6 13A4«s 0.143 n 4.00 255 94 94 376 239 1A-dw 127C n 3556 34.77 0 0 0 0 4A5-2om 0.770 n 2156 1931 0 0 0 0 W 13A4ars 0.143 a 4DO 2S5 0 0 0 0 11 �—G 1Actorn 1270 a 3556 8729 0 0 0 0 �D 11DO 0.390 a 10.92 11.31 0 0 0 0 V 13A4= 0.143 s 4.00 255 9 9 38 24 �f 1Ac1om 1270 s 3556 34.77 0 0 0 0 13A4o¢ 0.143 w 4.00 255 103 84 338 215 1A-dom 1270 w 35M 5525 0 0 0 0 4A5-2om 0.770 w 2156 44.72 19 2 407 845 4A5-2oW 0.470 w 13.16 35.61 0 0 0 0 P 12C-Om 0.091 - 2,55 128 0 0 0 0 C 16A-30md 0.032 - 0.90 232 110 110 99 255 F 22Artpl 0-%9 - 27.69 - ODO 110 22 609 0 6 c)AED exalrson 233 En\A lope lossigain 1868 1811 12 a) Infiltration 405 114 b) Roomsentilation 0 0 13 Internal gainer C=pante@ 230 0 0 Applianoesolher 0 Subtotal (lines6 te 13) 2273 1926 Lesextemal load 0 0 Les transfer 0 0 Redistribution 0 0 14 Subhrtal 2273 1926 15 Ductloads 30A 49%1 680 941 Total room load 2953 2867 Air required (cfm) 125 115 Calculations approved bvACCAto meet all requirements of Manual J 8th Ed Aft-rl+- wrlgbtsolt- 2021-Jarv1307:44.09 Riglt-Sdte@Uriwrsa12O1919.021 RSU08101 Page ...UICK1Downerts\Whg%Dft HVAMWVNNE-GEMINI.np Calc=WB Front Doortams N wrightsoft° Duct System SummaryDate: Entire House By. QUICK CALCS, INC. 317 ST.LUCE•:LN.,Fr.. PIERCE, FL 34946 Phone; 772AW-6799 Fa 772-466-6796 Email: QUICKCALCS@AOLCOM Project• • For. THEGEMINI WYNNE DEV., FT. PIERCE, FL Bdemal static pressure Pressure losses Available static pressure Supply/retum available pressure Lowest friction rate Actual airflow Total elective length (TEL) Heating 0.50 in H2O 0 in H2O 0.50 in H2O 0250 / 0250 in H2O 0286 in/100ft 1160 dm 175 Supply Branch Detail Table Cooling 0.50 in H2O 0 in H2O 0.50 in H2O 0250 / 0250 in H2O 0286 in/100ft 1160 dim Name Design (Bhth) Hg (cim) ag (dm) Design FR Diam (in) H x W (in) Dud Matt AcW Ln (ft) Ftg.Egv Ln (ft) Trunk BATH2 In 1211 51 31 0.368 4.0 OxO VIFx 21.0 115.0 st1 CLOSET2 c 177 3 7 0.363 4.0 Ox0 VIFx 22.6 115.0 st1 DEN h 2953 125 115 0.289 7.0 0x0 VIFx 38.1 135.0 st2 ENTRY h 1783 76 37 0.485 4.0 OxO VIFx 8.1 95.0 GREAT/DINING-A c 3211 120 129 0.300 6.0 OxO VIFx 31.7 135.0 st2 GREATMINING-B c 3211 120 129 0.308 6.0 OxO VIFx 27.3 135.0 st2 KITCHEN c 3380 30 135 0.376 7.0 0x0 MFx 18.1 115.0 st1 LAUNDRY In 1074 46 17 0.369 6.0 Ox0 VIFx 20.4 115.0 st1 M BATH h 1133 48 30 0.366 4.0 Ox 0 VIFx 21.6 115.0 st1 MASTER BEDROOM h 2976 126 125 0286 6.0 OXO VIFX 40.1 135.0 st2 MASTER BEDROOM h 6635 282 266 0.352 7.0 OxO VIFx 272 115.0 st1 MASTERBEDROO" h 2976 126 125 0297 6.0 OxO VIFx 33.1 135.0 st2 POWDER c 133 2 5 0.379 4.0 OxO VIFx 17.1 115.0 st1 WIC c 199 3 8 1 0.309 4.0 Ox0 MFX 26.6 135.0 st2 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 PeakAVF 622 631 0286 803 12.0 0 x 0 VinIFIX st1 st1 PeakAVF 1084 1123 0.286 804 16.0 0 x 0 VInlFIX Wrightsoftm 20214ar 1307:44:09 i1 .W..., .•-.v*M. MgttSURes+Unwa 1201919.021 R5U08101 Page 1 ...UICKIDow rl6AWnghsot HVAQWYNJE-GEMMInp Calc=M18 Fro Doorta N Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) HxW (in) Stud/Joist Opening (in) Dud Mat Trunk rb1 Ox0 1160 1160 0 0 0 0 Ox 0 MR -Fk wrightsoft- 2021Ja 1307A499 Pigit-SUL-8 Urwersal 201919.021 RSU08101 Page 2 UICK ...OoomeNs\WrigFEnitFNAGiWYNNE-GEMINInp Ca1c=M18 FrorR Doorfaces N