HomeMy WebLinkAboutEvaluation Report - Roofing Underlayments CREEK Certificate of Authorization bur 29824
17520 Edinburgh Drive
Tampa, FL 33647
Ij TECHNICAL SERVICES, LLC (813)480-3421
EVALUATION REPORT FLORIDA BUILDING CODE 7T"EDITION(2020)
Manufacturer: BEACON SALES ACQUISITIONS, INC. Issued October 18, 2020
c/o OWENS CORNING ROOFING AND ASPHALT LLC
1 Owens Corning Parkway
Toledo, OH 43657
(800)438-7465
Quality Assurance: Intertek Testing Services NA, Inc. (QUA1673)
SCOPE
Category: Roofing
Subcategory: Underlayments
Code Edition: Florida Building Code, 7"' Edition (2020)including High-Velocity Hurricane Zones (HVHZ)
Code Sections: 1507.1.1, 1518.4
Properties: Physical properties
REFERENCES
Entity Report No. Standard Year
Intertek Testing Services NA Ltd.(TST1509) 102389161 COQ-002A AC 188 2012
Intertek Testing Services NA Ltd.(TST1509) 102389161 COQ-004 ASTM D 226 2009
PRI Construction Materials Technologies(TST5878) OCR-259-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies(TST5878) 1378TO127 ASTM D 4533 2015
ASTM D 5035 2011(2019)
ASTM D 751 2019
PRODUCT DESCRIPTION
Beacon Tri-Built A mechanically attached, synthetic underlayment for use in steep slope roofing
applications as an alternative to ASTM D 226, Type I or Type II felt that has
demonstrated a minimum tear strength per ASTM D 4533 of 15 pounds, a minimum
tensile strength per ASTM D 5035 of 20 pounds/inch, and meets liquid water
transmission test of Section 8.6 of ASTM D 4869.
OCR17002.3 FL22259-R3 Page 1 of 3
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
0 G R E E K OWENS CORNING ROOFING AND ASPHALT LLC
Beacon Tri-Built
TECHNICAL SERVICES, LLC
APPLICATION
Unless otherwise noted, the following application details shall be followed for New and Existing construction.
See manufacturer's installation instructions for further detail.
Roof Deck: The roof deck shall be constructed of closely fitted wood sheathing for new or existing
construction. Plywood deck shall be installed in accordance with FBC requirements.
Roof decks shall have no more than '/8"gap at abutting joints.
Attachment method Underlayment shall be attached in accordance with the FBC Section 1507.1.1,
(Non-HVHZ): Table 1507.1.1.1 and manufacturer's installation instructions.
Attachment method Underlayment shall be installed with a minimum 4-inch head lap and minimum 6-inch
(HVHZ): end lap and be fastened as specified in FBC Section 1518.2.
Allowable roof coverings Mechanically attached roof systems as prescribed in FBC Table 1507.1.1.1.
(Non-HVHZ):
Allowable roof coverings Underlayment shall be used with mechanically attached asphalt shingles.
(HVHZ):
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) Wind uplift resistance in not within scope of this evaluation.
3) Installation of the evaluated product shall comply with this report,the FBC, and the manufacturer's published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
4) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
5) Roof slope limitations shall be in accordance with FBC requirements.
6) The underlayment may be used as described in other current FBC product approval documents.
7) Roof coverings shall not be adhered directly to the underlayment. Roof coverings shall be mechanically
fastened through the underlayment to the roof deck.
8) The underlayment shall not be installed over existing roof coverings.
9) The underlayment shall be installed starting at the eave in horizontal layers such that the laps shed water
from the deck. The first layer shall cover the entire bottom edge of the deck. End laps shall be staggered a
minimum of 72-inches from the preceding course.
10) The underlayment shall be exposed on the roof deck for a maximum duration of 30 days.
11) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
OCR17002.3 FL22259-R3 Page 2 of 3
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
0 G R E E K OWENS CORNING ROOFING AND ASPHALT LLC
Beacon Tri-Built
TECHNICAL SERVICES, LLC
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code 7`h Edition (2020) including High-Velocity Hurricane Zones (HVHZ) as evidenced in the referenced documents
submitted by the named manufacturer.
11%JYIIR��11���, 2020. 10.18
�,. �.••. �ENs� . s •,: �� 11 :45:25
ti. . � ,
No 74021
_� � Digitally signetl by ZecM1ary R.Prieat
= -04'00'
�-33' STATE OF 1JJ
'��'�•'•A, p?:•'�� � Zachary R. Priest, P.E.
R `• G��� Florida Registration No. 74021
4'���S�ONA�� ``� Organization No.ANE9641
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned,operated,or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R. Priest,P.E.does not have, nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT
OCR17002.3 FL22259-R3 Page 3 of 3
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.