FPS Electric Service Standards
PREPARED BY SUBJECT SECTION: PAGE
Delivery uran - IV. SERVICE and METER CONNECTIONS IV: 6 of 24
Design u pport
FIGURE E IV 1
Temporary/Construction Service - from Overhead System (typical )
101
Direction of FPL pal
For prompt electric service, set
temporary pole as d etaEl d
Service Drop
4�' Pole Cable
Brace Attachment Point of attachment shall provide clearances
as shown in Fig. I -
Meter
1U 0 Disconnec in
Min ' Means
an
t i n ' Min (Weatherproof
' Max rith )
T
1 " Min ,
' Min
Ground Wire enclosed in I r
PVC conduit where required ' J
Ground lid
Driven minimum of 8
Notes :
1 . Before servi a n be run , Company must have an electrical inspection ;
necessary tree trimming shall be done by the customer; and the deposit and
non-refundable temporary service charge shall be paid.
. Service pole shall not be within 25 ft. of swimming pool and must provide
clearances shown ire Fig. l w .
. Unspliced timbers are required (minimum length of 12 ft. for 2x4 braces and 1
ft. for 4x4 posts. Use ten penny 1 Od nails (3" long ).
4. Special arrangements scull be made with FFL if service drop exceeds 80 ft. or
is larger than 00-amp capacity.
5. Minimum typical requirements are shown . If local code requirements are more
stringent, they shall be adhered to.
. The surface the meter o I t is mounted on shall be plumb so the meter
socket jaws are truly vertical . The meter enclosure must be on FPL's approved
list.
. Where acceptable to the inspecting authority, an 18 ft. treated pole t' rain .
diameter t the top may be substituted for the 4 4 timber and braces,
provided the pole is set 5 ft. deep and well tamped . All other requirements
remain the same.
O 2021 , Florida Poorer & Light Company Page 6 of 24