HomeMy WebLinkAboutNEW Manual J UpdatedCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 10:57:49 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Load Short Form 4/29/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Cooper Residence, NisAir Air ConditioningFor: 7702 Hibiscus Rd, Ft. Pierce, FL 34951 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1-041-230A** AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259425 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW7.9 Sensible cooling Btuh26950 Heating output Btuh27037 Latent cooling Btuh11550 Temperature rise °F19 Total cooling Btuh38500 Actual air flow cfm1283 Actual air flow cfm1283 Air flow factor cfm/Btuh0.050 Air flow factor cfm/Btuh0.052 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.75 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Laundry 39 436 882 22 46 Bed 2 137 2422 1863 121 98 Bath 39 54 103 3 5 Bath 2 51 766 582 38 31 Hall 30 0 0 0 0 Bed 3 153 3225 2407 161 126 Bed 4 157 2507 1814 126 95 Foyer GR 426 5261 6235 263 327 Pantry 14 0 0 0 0 Kitchen DR 411 4674 6610 234 347 Master Bath 95 2084 955 104 50 Hers 20 409 167 20 9 His 9 12 22 1 1 Master Bed 222 3779 2820 189 148 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 10:57:49 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW House 1801 25629 24461 1283 1283 Other equip loads 2917 1549 Equip. @ 0.95 RSM 24813 Latent cooling 8775 TOTALS 1801 28546 33588 1283 1283 2021-Nov-12 10:57:49 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Building Analysis 4/29/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Cooper Residence, NisAir Air ConditioningFor: 7702 Hibiscus Rd, Ft. Pierce, FL 34951 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 16.346513.1Walls 13.2377117.4Glazing 000Doors 6.317851.0Ceilings 20.157343.23.2Floors 11.231842.2Infiltration 22.86504Ducts 00Piping 00Humidification 10.22917Ventilation0Adjustments 100.028546Total Cooling Walls Glazing Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 11.028631.9Walls 18.1470621.8Glazing 000Doors 12.532501.8Ceilings 000Floors 3.48900.6Infiltration 27.97252Ducts 6.01549Ventilation 21.15500Internal gains 00Blower 0Adjustments 100.026010Total Latent Cooling Load = 8775 Btuh Overall U-value = 0.103 Btuh/ft²-°F Data entries checked. 2021-Nov-12 10:57:49 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Component Constructions 4/29/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Cooper Residence, NisAir Air ConditioningFor: 7702 Hibiscus Rd, Ft. Pierce, FL 34951 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 12203.155.10.109387ne 7802.02 7482.0211693.155.10.109371se 5062.027913.155.10.109251sw 4602.027193.155.10.109228nw 24932.0238983.155.10.1091237all Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud 3421.466892.9411.00.101235 Frm Wall, 1/2" Gyp Bd Frm Wall, R-11, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" O.C. Stud 281.26652.9411.00.10122 Windows Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2.17 ft window ht, 1 ft sep.); 6.8 ft head ht 10622.67916.800.5805ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 70622.652516.800.58031ne 70622.652516.800.58031nw 141322.6105016.800.58062all Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 8 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 35322.626216.800.58016ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 8 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht 88622.075818.800.65040ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 100121.484118.000.62047sw 2021-Nov-12 10:57:49 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 4.7 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht 40510.167616.800.58040sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2.08 ft window ht, 1 ft sep.); 6.8 ft head ht 14222.610516.800.5806nw Doors (none) Ceilings Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0341801 32501.8017850.9930.0 Floors On Grade Depth, Tile Flr Fnsh 00573428.700.989200 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 10:57:49 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Project Summary 4/29/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Cooper Residence, NisAir Air ConditioningFor:7702 Hibiscus Rd, Ft. Pierce, FL 34951 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh19125 Structure Btuh17209 Ducts Btuh6504 Ducts Btuh7252Central vent (92 cfm) 2917 Btuh Central vent (92 cfm) Btuh1549 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh28546 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh24813 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh3032 Ducts Btuh2206Central vent (92 cfm) Btuh3537 CoolingHeating Outside air18011801Area (ft²) Equipment latent load Btuh8775 1577215772Volume (ft³)Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh33588 Equiv. AVF (cfm) 53100 Req. total capacity at 0.70 SHR ton3.0 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond ML14XC1-041-230A**AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259425Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW7.9 Sensible cooling Btuh26950Heating output Btuh27037 Latent cooling Btuh11550 Temperature rise °F19 Total cooling Btuh38500Actual air flow cfm1283 Actual air flow cfm1283 Air flow factor cfm/Btuh0.050 Air flow factor cfm/Btuh0.052Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.75 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 10:57:49Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Right-J® Worksheet 4/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House Laundry 2 Exposed wall 199.9 ft 5.5 ft 3 Room height 8.8 ft 8.0 heat/coolft 4 Room dimensions ft7.0x5.5 5 Room area 1800.8 ft²38.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 479 387 1220 780 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 5 0 79 106 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 31 0 525 706 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 22.0422.04 40 0 758 886 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 371 371 1169 748 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 338 251 791 506 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 swsw 17.9817.98 21.3921.39 47 6 841 1001 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 10.0710.07 40 40 676 405 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 266 228 719 460 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 6 0 105 142 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 31 0 525 706 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 235 235 689 342 44 44 129 64 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.261.26 22 22 65 28 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 1801 1801 1785 3250 39 39 38 69 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1801 200 5734 0 39 6 158 0 6 c) AED excursion 400 -13 Envelope loss/gain 15942 10819 325 120 12 a) Infiltration 3184 890 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 5 1150 0 0 Appliances/other 4350 500 Subtotal (lines 6 to 13)19125 17209 325 620 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 19125 17209 325 620 15 Duct loads 34%42%6504 7252 34%42%111 261 Total room load 25629 24461 436 882 Air required (cfm)Air required (cfm)1283 1283 22 46 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 10:57:49Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Right-J® Worksheet 4/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 2 Bath 2 Exposed wall 24.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft136.5x1.0 ft5.5x7.0 5 Room area 136.5 ft²38.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 swsw 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 84 68 216 138 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 108 108 317 158 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.261.26 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 137 137 135 246 39 39 38 69 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 137 24 688 0 39 0 0 0 6 c) AED excursion 107 -1 Envelope loss/gain 1619 1002 38 68 12 a) Infiltration 184 51 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)1803 1303 38 68 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 4 8 2 4 14 Subtotal 1807 1311 41 72 15 Duct loads 34%42%615 552 34%42%14 31 Total room load 2422 1863 54 103 Air required (cfm)Air required (cfm)121 98 3 5 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 10:57:49Right-Suite® Universal 2021 21.0.10 RSU29066 Page 3...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Right-J® Worksheet 4/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bath 2 Hall 2 Exposed wall 6.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x8.5 ft8.5x3.5 5 Room area 51.0 ft²29.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 swsw 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 48 42 132 84 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 6 0 105 142 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.261.26 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 51 51 51 92 30 30 29 54 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 51 6 172 0 30 0 0 0 6 c) AED excursion 49 -1 Envelope loss/gain 459 367 29 53 12 a) Infiltration 105 29 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)564 397 29 53 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 7 13 -29 -53 14 Subtotal 572 410 0 0 15 Duct loads 34%42%194 173 34%42%0 0 Total room load 766 582 0 0 Air required (cfm)Air required (cfm)38 31 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 10:57:49Right-Suite® Universal 2021 21.0.10 RSU29066 Page 4...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Right-J® Worksheet 4/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 3 Bed 4 2 Exposed wall 25.5 ft 21.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft153.3x1.0 ft157.0x1.0 5 Room area 153.3 ft²157.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 96 80 253 162 104 88 279 178 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 16 0 262 353 16 0 262 353 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 64 64 202 129 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 swsw 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 108 92 291 186 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.261.26 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 153 153 152 277 157 157 156 283 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 153 26 731 0 157 21 602 0 6 c) AED excursion -26 -25 Envelope loss/gain 1953 1306 1501 919 12 a) Infiltration 447 125 368 103 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 250 Subtotal (lines 6 to 13)2399 1681 1869 1272 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 7 13 2 4 14 Subtotal 2407 1694 1871 1276 15 Duct loads 34%42%818 714 34%42%636 538 Total room load 3225 2407 2507 1814 Air required (cfm)Air required (cfm)161 126 126 95 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 10:57:49Right-Suite® Universal 2021 21.0.10 RSU29066 Page 5...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Right-J® Worksheet 4/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Foyer GR Pantry 2 Exposed wall 34.5 ft 0 ft 3 Room height 9.5 heat/coolft 8.0 heat/coolft 4 Room dimensions ft426.3x1.0 ft5.5x2.5 5 Room area 426.3 ft²13.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 223 152 478 306 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 swsw 17.9817.98 21.3921.39 31 4 561 668 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 10.0710.07 40 40 676 405 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 83 83 242 120 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.261.26 22 22 65 28 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 426 426 423 769 14 14 14 25 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 426 35 989 0 14 0 0 0 6 c) AED excursion 360 -1 Envelope loss/gain 3435 2656 14 24 12 a) Infiltration 489 137 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 3 690 0 0 Appliances/other 900 0 Subtotal (lines 6 to 13)3924 4383 14 24 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 2 4 -14 -24 14 Subtotal 3926 4386 0 0 15 Duct loads 34%42%1335 1848 34%42%0 0 Total room load 5261 6235 0 0 Air required (cfm)Air required (cfm)263 327 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 10:57:49Right-Suite® Universal 2021 21.0.10 RSU29066 Page 6...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Right-J® Worksheet 4/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Kitchen DR Master Bath 2 Exposed wall 28.0 ft 19.5 ft 3 Room height 9.5 heat/coolft 8.0 heat/coolft 4 Room dimensions ft410.5x1.0 ft9.0x10.5 5 Room area 410.5 ft²94.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 195 139 438 280 84 79 250 160 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 5 0 79 106 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 22.0422.04 40 0 758 886 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 71 71 224 144 72 72 227 145 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 swsw 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.261.26 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 411 411 407 741 95 95 94 171 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 411 28 803 0 95 20 559 0 6 c) AED excursion -98 -14 Envelope loss/gain 2892 2305 1209 568 12 a) Infiltration 583 163 342 96 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 1700 0 Subtotal (lines 6 to 13)3475 4628 1550 663 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 12 22 5 8 14 Subtotal 3487 4650 1555 672 15 Duct loads 34%42%1186 1960 34%42%529 283 Total room load 4674 6610 2084 955 Air required (cfm)Air required (cfm)234 347 104 50 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 10:57:49Right-Suite® Universal 2021 21.0.10 RSU29066 Page 7...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Right-J® Worksheet 4/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Hers His 2 Exposed wall 4.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft4.0x5.0 ft8.9x1.0 5 Room area 20.0 ft²8.9 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 11 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 nene 18.8518.85 22.0422.04 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 32 32 101 64 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 swsw 17.9817.98 21.3921.39 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 10.0710.07 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.261.26 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 20 20 20 36 9 9 9 16 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 20 4 115 0 9 0 0 0 6 c) AED excursion -2 0 Envelope loss/gain 235 98 9 16 12 a) Infiltration 70 20 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)305 118 9 16 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 305 118 9 16 15 Duct loads 34%42%104 50 34%42%3 7 Total room load 409 167 12 22 Air required (cfm)Air required (cfm)20 9 1 1 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Nov-12 10:57:49Right-Suite® Universal 2021 21.0.10 RSU29066 Page 8...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Right-J® Worksheet 4/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Master Bed 2 Exposed wall 31.9 ft 3 Room height 8.5 heat/coolft 4 Room dimensions ft222.4x1.0 5 Room area 222.4 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall, Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 .G Impact, Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 .G Impact, Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 .G Impact, Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 11 G Impact, Clear Low-e 0.650 ne 18.85 22.04 0 0 0 0 W Blk Wall, Stucco Ext 0.109 se 3.15 2.02 132 132 415 266 W Blk Wall, Stucco Ext 0.109 sw 3.15 2.02 115 99 312 200 G Impact, Clear Low-e 0.620 sw 17.98 21.39 16 2 280 334 G Impact, Clear Low-e 0.580 sw 16.82 10.07 0 0 0 0 W Blk Wall, Stucco Ext 0.109 nw 3.15 2.02 26 26 80 51 G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 P Frm Wall, 1/2" Gyp B 0.101 -2.94 1.46 0 0 0 0 P Frm Wall, 1/2" Gyp B 0.101 -2.94 1.26 0 0 0 0 C Attic, Shngl Roof, R 0.034 -0.99 1.80 222 222 220 401 F On Grade Depth, Tile 0.989 -28.68 0.00 222 32 915 0 6 c) AED excursion 66 Envelope loss/gain 2224 1318 12 a) Infiltration 596 167 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 500 Subtotal (lines 6 to 13)2820 1984 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 2820 1984 15 Duct loads 34%42%959 836 Total room load 3779 2820 Air required (cfm)189 148 2021-Nov-12 10:57:50 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Duct System Summary 4/29/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Cooper Residence, NisAir Air ConditioningFor: 7702 Hibiscus Rd, Ft. Pierce, FL 34951 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.529 / 0.171 in H2O in H2O0.529 / 0.171 Lowest friction rate in/100ft0.213in/100ft0.213 Actual air flow cfm1283cfm1283 Total effective length (TEL) ft329 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st195.012.9VlFx0x04.00.49063103cBath st3120.026.0VlFx0x04.00.3623746766hBath 2 st195.012.2VlFx0x06.00.4941171462422hBed 2 st3120.029.6VlFx0x07.00.3541521943225hBed 3 st3120.024.9VlFx0x06.00.3651141512507hBed 4 st2100.032.6VlFx0x07.00.3991961583117cFoyer GR st2100.032.9VlFx0x07.00.3981961583117cFoyer GR-A st4200.048.9VlFx0x04.00.2131125409hHers st4195.044.4VlFx0x04.00.2211122cHis st2100.032.6VlFx0x07.00.3992081403305cKitchen DR-A st2100.032.4VlFx0x07.00.4002081403305cKitchen DR-B st195.013.1VlFx0x04.00.4905626882cLaundry st4195.053.2VlFx0x07.00.213601252084hMaster Bath st4195.048.5VlFx0x06.00.217891141890hMaster Bed st4195.044.1VlFx0x06.00.221891141890hMaster Bed-A Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 378 250 0.213 692 10.0 0x0 VinlFlx st2 st3 Peak AVF 391 302 0.354 884 9.0 0x0 VinlFlx st1 st1 Peak AVF 565 482 0.354 720 12.0 0x0 VinlFlx st2 Peak AVF 975 1058 0.213 758 16.0 0x0 VinlFlx Bold/italic values have been manually overridden 2021-Nov-12 10:57:50 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 2 ...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb5 0x 1510 114 78.8 0.217 564 7.0 x0 0 VlFx rt1 rb6 0x 1940 152 80.4 0.213 555 8.0 x0 0 VlFx rt1 rb7 0x 1460 117 66.1 0.259 545 7.0 x0 0 VlFx rt1 rb1 0x 7980 967 66.8 0.256 547 18.0 x0 0 VlFx rt1 rb8 0x 2520 190 0 0 0 0 x0 0 VlFx Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 1288 1350 0.213 764 18.0 0x0 VinlFlx 2021-Nov-12 10:57:50 Right-Suite® Universal 2021 21.0.10 RSU29066 Page 1 ...s\Wrightsoft HVAC\7702 Hibiscus Rd PSL Prop.rup Calc = MJ8 Front Door faces: SW 1481Job:Manual S Compliance Report 4/29/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Cooper Residence, NisAir Air ConditioningFor: 7702 Hibiscus Rd, Ft. Pierce, FL 34951 Cooling Equipment Design Conditions °F77.2Entering coil DB:Btuh26010Sensible gain:°F90.4Outdoor design DB: °F64.4Entering coil WB:Btuh8775Latent gain:°F77.4Outdoor design WB: Btuh34784Total gain:°F75.0Indoor design DB: cfm1283Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: ML14XC1-041-230A**+CBA27UHE-048-230*++TDRModel:LennoxManufacturer: cfm1283Actual airflow: % of load104Btuh26950Sensible capacity: % of load132Btuh11550Latent capacity: %70SHR:% of load111Btuh38500Total capacity: Heating Equipment Design Conditions °F67.4Entering coil DB:Btuh28546Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm1283Actual airflow: °F50Temp. rise:% of load95kW7.9Output capacity: Meets all requirements of ACCA Manual S.