HomeMy WebLinkAboutBIRCH DR- MANUAL J (1) (1) L wrigni project Summary Date: SEPT.21,2021 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM Project • • For: BIRCH DRIVE PROJECT, SOUTHERN CITY DEVELOPMENT 5109 BIRCH DRIVE, FORT PIERCE, FL 34982 Notes: Design Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 28 °F Design TD 15 °F Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 20804 Btuh Structure 18094 Btuh Ducts 5681 Btuh Ducts 8144 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 26485 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipmenf sensible load 24926 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 4220 Btuh Ducts 2209 Btuh Central vent (0 cfm) 0 Btuh Heating Coolingg (none) Area (ft2) 1866 1866 Equipment latent load 6429 Btuh Volume (ft3) 15939 15939 Air changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 31355 Btuh Equiv.AVF (cfm) 101 53 Req. total capacity at 0.70 SHR 3.0 ton Heating Equipment Summary Cooling Equipment Summary Make Make Goodman Mfg. Trade Trade GOODMAN Model Cond GSX160371A AHRI ref Coil AVPTC37D14B AHRI ref 202544189 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 6.8 kW Sensible cooling 24920 Btuh Heating output 23286 Btuh Latent cooling 10680 Btuh Temperature rise 18 °F Total cooling 35600 Btuh Actual air flow 1187 cfm Actual air flow 1187 cfm Air flow factor 0.045 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.80 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. )Oft—rk- ww•-igl 2021-Sep-21 16:43:11 Right-SuiteO Universal 2021 21.0.02 RSU08101 Page 1 = ...htsoft HVAC\SOUTHERN CITY-BIRCH DR PROJECT.rup Calc=MJ8 Front Door faces: E IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: SEPT.21,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name Entire House MASTER BEDROOM 2 Exposed wall 180.0 ft 31.0 ft 3 Room height 8.7 ft 9.3 ft heat/cool 4 Room dimensions 1.0 x 227.0 ft 5 Room area 1840.0 ft2 227.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 VLG13A-4ocs 0.143 n 4.00 2.19 278 199 797 436 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 55 0 1001 825 0 0 0 0 D 11DO 0.390 n 10.92 10.34 24 24 262 248 0 0 0 0 V�J 13A-40 cs 0.143 e 4.00 2.19 413 401 1604 876 158 158 633 346 11 l G� 2 glazing,clr low-e 0.650 a 18.20 33.77 12 0 218 405 0 0 0 0 V�/ 13A-40cs 0.143 s 4.00 2.19 476 365 1463 799 130 100 401 219 G 2 glazing,clr low-e 0.650 s 18.20 16.03 111 0 2013 1772 30 0 546 481 13A-40cs 0.143 w 4.00 2.19 376 352 1409 770 0 0 0 0 2 alazina,clr low-e 0.650 w 18.20 33.77 24 0 437 811 0 0 0 0 C 16B-30ad 0.032 0.90 1.60 1840 1840 1649 2944 227 227 203 363 F 22A-tph 1.358 38.02 0.00 1840 180 6844 0 227 31 1179 0 6 c)AED excursion 32 -24 Envelope loss/gain 17698 9918 2962 1385 12 a) Infiltration 3106 876 581 164 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 7300 1400 Subtotal(lines 6 to 13) 20804 18094 3543 2949 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 20804 18094 3543 2949 15 Duct loads 27% 45% 5681 8144 27% 45% 967 1327 Total room load T26485 26238 4510 4276 Air required(cfm) 11871 1187 202 193 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k —r"- wrigl 2021-Sep-21 16:43:11 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 1 htsoft HVAC\SOUTHERN CITY-BIRCH DR PROJECT.rup Calc=MJ8 Front Door faces: E IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: SEPT.21,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name M BATH M WIC 1 2 Exposed wall 13.0 ft 0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 9.0 x 13.0 ft 6.0 x 6.0 ft 5 Room area 117.0 ft2 36.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 D 11DO 0.390 n 10.92 10.34 0 0 0 0 0 0 0 0 V�J 13A-40 cs 0.143 e 4.00 2.19 104 92 368 201 0 0 0 0 11 l G� 2 glazing,clr low-e 0.650 a 18.20 33.77 12 0 218 405 0 0 0 0 V�/ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 G 2 glazing,clr low-e 0.650 s 18.20 16.03 0 0 0 0 0 0 0 0 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 alazina,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 C 16B-30ad 0.032 0.90 1.60 117 117 105 187 36 36 32 58 F 22A-tph 1.358 38.02 0.00 117 13 494 0 36 0 0 0 6 c)AED excursion -6 -12 Envelope loss/gain 1186 788 32 46 12 a) Infiltration 209 59 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 300 Subtotal(lines 6 to 13) 1395 847 32 346 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1395 847 32 346 15 Duct loads 27% 45% 381 381 27% 45% 9 156 Total room load T1776 1228 41 502 Air required(cfm) 80 56 12 23 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Sep-21 16:43:11 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 2 htsoft HVAC\SOUTHERN CITY-BIRCH DR PROJECT.rup Calc=MJ8 Front Door faces: E IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: SEPT.21,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name M WIC 2 KITCHEN 2 Exposed wall 0 ft 13.0 ft 3 Room height 8.0 ft heat/cool 9.3 ft heat/cool 4 Room dimensions 6.0 x 7.0 ft 13.0 x 17.0 ft 5 Room area 42.0 ft2 221.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 D 11DO 0.390 n 10.92 10.34 0 0 0 0 0 0 0 0 V�J 13A-40 cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 11 l G� 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 V�/ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 121 109 436 238 G 2 glazing,clr low-e 0.650 s 18.20 16.03 0 0 0 0 12 0 218 192 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 alazina,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 C 16B-30ad 0.032 0.90 1.60 42 42 38 67 221 221 198 354 F 22A-tph 1.358 38.02 0.00 42 0 0 0 221 13 494 0 6 c)AED excursion -12 -51 Envelope loss/gain 38 55 1347 733 12 a) Infiltration 0 0 243 69 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 300 1600 Subtotal(lines 6 to 13) 38 355 1590 2402 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 38 355 1590 2402 15 Duct loads 27% 45% 10 160 27% 45% 434 1081 Total room load 48 515 2024 3483 Air required(cfm) 2 23 91 158 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Sep-21 16:43:11 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 3 htsoft HVAC\SOUTHERN CITY-BIRCH DR PROJECT.rup Calc=MJ8 Front Door faces: E IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: SEPT.21,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name LAUNDRY FOYER 2 Exposed wall 2.0 ft 17.0 ft 3 Room height 8.0 ft heat/cool 9.3 ft heat/cool 4 Room dimensions 8.0 x 12.0 ft 17.0 x 12.0 ft 5 Room area 96.0 ft2 204.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 VLG13A-4ocs 0.143 n 4.00 2.19 16 16 64 35 158 104 417 228 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 30 0 546 450 D 11DO 0.390 n 10.92 10.34 0 0 0 0 24 24 262 248 V�J 13A-40 cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 11 l G� 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 V�/ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 G 2 glazing,clr low-e 0.650 s 18.20 16.03 0 0 0 0 0 0 0 0 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 alazina,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 C 16B-30ad 0.032 0.90 1.60 96 96 86 154 204 204 183 326 F 22A-tph 1.358 38.02 0.00 96 2 76 0 204 17 646 0 6 c)AED excursion -23 -93 Envelope loss/gain 226 166 2054 1159 12 a) Infiltration 32 9 318 90 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 500 1500 Subtotal(lines 6 to 13) 258 675 2372 2749 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 5 9 14 Subtotal 258 675 2378 2758 15 Duct loads 27% 45% 71 304 27% 45% 649 1241 Total room load 329 979 3027 3999 Air required(cfm) 15 44 136 181 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Sep-21 16:43:11 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 4 htsoft HVAC\SOUTHERN CITY-BIRCH DR PROJECT.rup Calc=MJ8 Front Door faces: E IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: SEPT.21,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name GREAT RM BEDROOM 4 2 Exposed wall 18.0 ft 33.0 ft 3 Room height 9.3 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 13.0 x 22.0 ft 1.0 x 151.0 ft 5 Room area 286.0 ft2 151.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 D 11DO 0.390 n 10.92 10.34 0 0 0 0 0 0 0 0 V�J 13A-40 cs 0.143 e 4.00 2.19 47 47 186 102 72 72 288 158 11 l G� 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 V�/ 13A-40cs 0.143 s 4.00 2.19 121 67 269 147 104 89 356 195 G 2 glazing,clr low-e 0.650 s 18.20 16.03 54 0 976 859 15 0 273 240 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 88 88 352 193 2 alazina,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 C 16B-30ad 0.032 0.90 1.60 286 286 256 458 151 151 135 242 F 22A-tph 1.358 38.02 0.00 286 18 684 0 151 33 1255 0 6 c)AED excursion 40 -9 Envelope loss/gain 2372 1606 2660 1018 12 a) Infiltration 337 95 532 150 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 1100 200 Subtotal(lines 6 to 13) 2709 2801 3192 1368 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 5 9 104 39 14 Subtotal 2714 2810 3295 1407 15 Duct loads 27% 45% 741 1265 27% 45% 900 633 Total room load 3455 4074 4195 2040 Air required(cfm) 155 184 188 92 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Sep-21 16:43:11 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 5 htsoft HVAC\SOUTHERN CITY-BIRCH DR PROJECT.rup Calc=MJ8 Front Door faces: E IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: SEPT.21,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name CLST 4 BEROOM 3 2 Exposed wall 2.0 ft 12.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 9.0 x 2.0 ft 1.0 x 164.0 ft 5 Room area 18.0 ft2 164.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 D 11DO 0.390 n 10.92 10.34 0 0 0 0 0 0 0 0 V�J 13A-40 cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 11 l G� 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 V�/ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 G 2 glazing,clr low-e 0.650 s 18.20 16.03 0 0 0 0 0 0 0 0 13A-40cs 0.143 w 4.00 2.19 16 16 64 35 96 81 324 177 2 alazina,clr low-e 0.650 w 18.20 33.77 0 0 0 0 15 0 273 507 C 16B-30ad 0.032 0.90 1.60 18 18 16 29 164 164 147 262 F 22A-tph 1.358 38.02 0.00 18 2 76 0 164 12 456 0 6 c)AED excursion -2 168 Envelope loss/gain 156 61 1201 1114 12 a) Infiltration 32 9 193 55 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 200 Subtotal(lines 6 to 13) 188 71 1394 1368 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -188 -71 194 80 14 Subtotal 0 0 1588 1448 15 Duct loads 27% 45% 0 0 27% 45% 434 652 Total room load 0 0 2021 2099 Air required(cfm) 0 0 91 95 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Sep-21 16:43:11 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 6 htsoft HVAC\SOUTHERN CITY-BIRCH DR PROJECT.rup Calc=MJ8 Front Door faces: E IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: SEPT.21,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name CLST 3 BATH 2 2 Exposed wall 2.0 ft 6.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 9.0 x 2.0 ft 9.0 x 6.0 ft 5 Room area 18.0 ft2 54.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 D 11DO 0.390 n 10.92 10.34 0 0 0 0 0 0 0 0 V�J 13A-40 cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 11 l G� 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 V�/ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 G 2 glazing,clr low-e 0.650 s 18.20 16.03 0 0 0 0 0 0 0 0 13A-40cs 0.143 w 4.00 2.19 16 16 64 35 48 39 156 85 2 alazina,clr low-e 0.650 w 18.20 33.77 0 0 0 0 9 0 164 304 C 16B-30ad 0.032 0.90 1.60 18 18 16 29 54 54 48 86 F 22A-tph 1.358 38.02 0.00 18 2 76 0 54 6 228 0 6 c)AED excursion -2 108 Envelope loss/gain 156 61 596 583 12 a) Infiltration 32 9 97 27 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 188 71 693 611 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -188 -71 187 80 14 Subtotal 0 0 880 691 15 Duct loads 27% 45% 0 0 27% 45% 240 311 Total room load 0 0 1120 1002 Air required(cfm) 0 0 50 45 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Sep-21 16:43:11 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 7 htsoft HVAC\SOUTHERN CITY-BIRCH DR PROJECT.rup Calc=MJ8 Front Door faces: E IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: SEPT.21,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name CLST 2 BEDROOM 2 2 Exposed wall 2.0 ft 29.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 9.0 x 2.0 ft 13.0 x 12.0 ft 5 Room area 18.0 ft2 156.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 VLG13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 104 79 316 173 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 25 0 455 375 D 11DO 0.390 n 10.92 10.34 0 0 0 0 0 0 0 0 V�J 13A-40 cs 0.143 e 4.00 2.19 0 0 0 0 32 32 128 70 11 l G� 2 glazing,clr low-e 0.650 a 18.20 33.77 0 0 0 0 0 0 0 0 V�/ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 G 2 glazing,clr low-e 0.650 s 18.20 16.03 0 0 0 0 0 0 0 0 13A-40cs 0.143 w 4.00 2.19 16 16 64 35 96 96 384 210 2 alazina,clr low-e 0.650 w 18.20 33.77 0 0 0 0 0 0 0 0 C 16B-30ad 0.032 0.90 1.60 18 18 16 29 156 156 140 250 F 22A-tph 1.358 38.02 0.00 18 2 76 0 156 29 1103 0 6 c)AED excursion -2 -46 Envelope loss/gain 156 61 2526 1031 12 a) Infiltration 32 9 467 132 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 200 Subtotal(lines 6 to 13) 188 71 2993 1363 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -188 -71 99 44 14 Subtotal 0 0 3093 1407 15 Duct loads 27% 45% 0 0 27% 45% 845 633 Total room load 0 0 3938 2041 Air required(cfm) 0 0 176 92 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Sep-21 16:43:11 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 8 htsoft HVAC\SOUTHERN CITY-BIRCH DR PROJECT.rup Calc=MJ8 Front Door faces: E IL : W I Nyl l Right-J®Worksheet Job: Entire House Date: SEPT.21,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name HALL 2 Exposed wall 0 ft 3 Room height 8.0 ft heat/cool 4 Room dimensions 4.0 x 8.0 ft 5 Room area 32.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V)/ 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 I!—�3 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 D 11DO 0.390 n 10.92 10.34 0 0 0 0 V�/ 13A-4ocs 0.143 e 4.00 2.19 0 0 0 0 11 l C 2 glazing,clr low-e 0.650 e 18.20 33.77 0 0 0 0 V�✓ 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 G 2 glazing,clr low-e 0.650 s 18.20 16.03 0 0 0 0 �/�/ 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 C' 2 glazinq,clr low-e 0.650 w 18.20 33.77 0 0 0 0 C 16B-30ad 0.032 0.90 1.60 32 32 29 51 F 22A-tph 1.358 38.02 0.00 32 0 0 0 6 c)AED excursion -2 Envelope loss/gain 29 50 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 0 Subtotal(lines 6 to 13) 29 50 Less external load 0 0 Less transfer 0 0 Redistribution -29 -50 14 Subtotal 0 0 15 Duct loads 27% 45% 0 0 Total room load 0 0 Air required(cfm) 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2021-Sep-21 16:43:11 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 9 htsoft HVAC\SOUTHERN CITY-BIRCH DR PROJECT.rup Calc=MJ8 Front Door faces: E L-7 wrignI Duct System Summary Job: Date: SEPT.21,2021 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM Project • • For: BIRCH DRIVE PROJECT, SOUTHERN CITY DEVELOPMENT 5109 BIRCH DRIVE, FORT PIERCE, FL 34982 Heating Cooling External static pressure 1.00 in H2O 1.00 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 1.00 in H2O 1.00 in H2O Supply/ return available pressure 0.500/ 0.500 in H2O 0.500/0.500 in H2O Lowest friction rate 1.000 in/100ft 1.000 in/100ft Actual air flow 1187 cfm 1187 cfm Total effective length (TEL) 179 ft Supply Branch DetailTable Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk BATH 2 h 1120 50 45 1.000 6.0 Ox 0 VIFx 34.5 135.0 st3 BEDROOM 2 h 3938 176 92 1.000 7.0 Ox0 VIFx 41.4 135.0 st3 BEDROOM 4 h 4195 188 92 1.000 7.0 Ox0 VIFx 44.0 135.0 st3 BEROOM 3 c 2099 91 95 1.000 7.0 Ox0 VIFx 32.5 135.0 st3 FOYER c 3999 136 181 1.000 8.0 Ox0 VIFx 23.8 115.0 st1 GREATRM c 4074 155 184 1.000 8.0 Ox0 VIFx 26.5 115.0 st1 KITCHEN c 3483 91 158 1.000 8.0 Ox0 VIFx 19.7 115.0 st1 LAUNDRY c 979 15 44 1.000 6.0 Ox0 VIFx 28.5 115.0 st1 M BATH h 1776 80 56 1.000 6.0 Ox0 VIFx 17.8 115.0 st2 M WIC 1 c 502 2 23 1.000 5.0 Ox 0 VIFx 15.0 115.0 st2 MWIC2 c 515 2 23 1.000 5.0 Ox0 VIFx 18.2 115.0 st2 MASTER BEDROOM h 4510 202 193 1.000 8.0 Ox0 VIFx 17.3 115.0 st2 • • Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st1 Peak AVF 901 892 1.000 843 14.0 0 x 0 VinlFlx st3 Peak AVF 505 325 1.000 926 10.0 0 x 0 VinlFlx st1 st2 Peak AVF 286 295 1.000 668 9.0 0 x 0 VinlFlx - --eft° # - wrigl 2021-Sep-21 16:43:15 Right-SuiteO Universal 2021 21.0.02 RSU08101 Page 1 �L u ...htsoft HVAC\SOUTHERN CITY-BIRCH DR PROJECT.rup Calc=MJ8 Front Door faces: E TableReturn Branch Detail Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb1 Ox0 1187 1187 0 0 0 0 Ox 0 VIFx -- — --eft° # F wrigl 2021-Sep-21 16:43:15 . -m..., M .,a... Right-SuiteO Universal 2021 21.0.02 RSU08101 Page 2 �L u ...htsoft HVAC\SOUTHERN CITY-BIRCH DR PROJECT.rup Calc=MJ8 Front Door faces: E This document was created with Win2PDF available at http://www.win2pdf.com. The unregistered version of Win2PDF is for evaluation or non-commercial use only. This page will not be added after purchasing Win2PDF.