HomeMy WebLinkAbout5380-F85FB-v20.0 - Sheet - M1 - HVAC FLOOR PLAN1 2 3 7 7.8 8
F
E
D
ASSOCIATE
VESTIBULE
OFFICE
STAGING
C
TH
TH
WOMEN'S RESTROOM
TH
6"ø
12x12EF-2
REMOTE SMOKE DETECTOR TEST STATIONS FOR RTU-1, 2, & 3 PROVIDED BY RTU
MANUFACTURER. TEST STATIONS TO BE MOUNTED ON THE MANAGER'S OFFICE WALL.
COORDINATE LOCATIONS WITH ARCHITECTURAL PLANS. SECURITY CONTRACTOR
SHALL WIRE RTU FACTORY MOUNTED SMOKE DETECTORS TO SECURITY/FIRE ALARM
PANEL. MECHANICAL CONTRACTOR SHALL PROVIDE WIRING BETWEEN COMPONENTS
AS WELL AS WIRING TO SHUT DOWN THE A/C FAN UPON ACTIVATION OF THE SMOKE
DETECTOR. G.C. TO TEST THE SMOKE DETECTOR FUNCTIONS WITH THE WAWA
PROJECT MANAGER.
OWNER SHALL PROVIDE WALL MOUNTED SENSOR(S) FOR EACH MECHANICAL UNIT PER
ROOFTOP UNIT SCHEDULE ON SHEET M3. G.C. SHALL PROVIDE AND INSTALL JUNCTION
BOX, CONDUIT, AND WIRE FROM JUNCTION BOX TO RTU (REFER TO ELECTRICAL PLANS).
G.C. SHALL INSTALL SENSORS. G.C. SHALL CONNECT WIRE TO SENSORS AND TO RTU,
BAS CONTRACTOR SHALL CONNECT TO RTU ONLY.
COORDINATE EXACT LOCATION OF EXHAUST FAN PENETRATION WITH ARCHITECTURAL
ROOF PLAN. INSTALL GALVANIZED DUCT WORK DOWN FROM FAN, INTO CEILING/JOIST
SPACE, AND CONNECT TO CEILING GRILLES.
REFER TO TYPICAL PLENUM DETAIL ON SHEET M3.
UNDERCUT DOOR 1" TO ALLOW FOR TRANSFER OF AIR.
COORDINATE DUCT WITH STRUCTURE IN THIS LOCATION. COORDINATE TAKEOFF
LOCATIONS WITH TRUSS WEB OPENINGS.
PROVIDE SURFACE MOUNT ADAPTER FRAME TO ALLOW ACCESS TO CEILING ABOVE
THROUGH DIFFUSER OPENING. SEE AIR DEVICE SCHEDULE
ROUTE DUCT UNDER STRUCTURAL MEMBERS AT THIS LOCATION.
COORDINATE AND ROUTE MAIN DUCT HIGH IN JOIST SPACE. AVOID CONFLICTS WITH
UTILITIES.
DUCT TAKEOFF WITH DAMPER FROM BOTTOM OF MAIN DUCT.
INSTALL EXHAUST FAN PER DETAIL SHEET M3. FAN SHALL BE WIRED TO EMERGENCY
SHUTOFF SWITCH PROVIDED BY OTHERS. REFERENCE ARCHITECTURAL AND
ELECTRICAL DRAWINGS.
EMERGENCY SHUTOFF SWITCH AND WALL PLACARD INDICATING VENTILATION SYSTEM
EMERGENCY SHUTOFF PROVIDED BY OTHERS. REFERENCE ELECTRICAL AND
ARCHITECTURAL DRAWINGS.
MOUNT CENTER OF EXHAUST GRILLE AT 12" ABOVE FINISHED FLOOR. ROUTE DUCT
SIZED AS SHOWN FROM GRILLE, UP IN WALL CAVITY TO ABOVE CEILING, THEN TO
EXHAUST FAN AND OUT TO EXTERIOR WALL LOUVER. COORDINATE DUCT ROUTING
WITH ALL OTHER TRADES.
12"X12" EXTERIOR WALL LOUVER MODEL EHH-601 AS MANUFACTURED BY GREENHECK.
INSTALL PER MANUFACTURER'S RECOMMENDED INSTALLATION INSTRUCTIONS.
FLORIDA PRODUCT APPROVAL #10088.1. PROVIDE WITH BIRD SCREEN, 1-1/2" FLANGE,
AND ALUMINUM MILL FINISH.
TRANSFER AIR ASSEMBLY
1
2
3
4
5
6
7
8
9
10
11
13
14
DN.
FROM
RTU-3
UP TO
RTU-3
DN. FROM
RTU-1
UP TO
RTU-1
UP TO
EF-1
TO RTU-1
TO RTU-3
TO RTU-2
UP TO
RTU-2
28x20
10"ø
28x2024x27
AC-1
A. MECHANICAL CONTRACTOR SHALL ADJUST ALL LINEAR SLOT
DIFFUSERS TO A GENERALLY VERTICAL FLOW. ADJUSTMENT
SHALL BE MADE SO AS TO AVOID AIRFLOWS ON SENSORS,
REFRIGERATION CASES, OR OPEN FOOD REFRIGERATION
EQUIPMENT.
C
B
A
3.5 4 5 6
KEY NOTES:
SHEET GENERAL NOTE:
12
WATER SERVICE
ROOM
24x27
DN. FROM
RTU-2
28x20
27x24
AC-2
UP TO
EF-3
WALK-IN FREEZER
WALK-IN REFRIG.
COFFEE
RETAIL AREA
RETAILAREASELFSERVICE
WALK-IN REFRIG.
RETAIL WALK-IN
REFRIG.
REAR VESTIBULE
MEN'S RESTROOM
ELECTRICAL ROOM
WASH ROOM
FOOD SERVICE
DELIVERY VESTIBULE
CD-4
70 CFM
CD-4
70 CFM
CD-3
100 CFM
CD-3
40 CFM
CD-3
40 CFM
CD-1
200 CFM
LD-1
315 CFM LD-1
325 CFM
LD-1
315 CFM
LD-1
325 CFM
LD-1
315 CFM
LD-1
315 CFM
8"ø
20x1610"ø 10"ø
10"ø14x1612x1212"ø
6"ø
6"ø
8"ø6"
ø 6"ø 6"
ø 8"
ø6"
ø8"ø18x1616"
ø12"ø10"
ø14"ø
12"ø
10"ø
12"ø
10"ø
10"ø
10"ø
10"ø
10x1210"ø18x1812"
ø14"ø
12"ø
12"ø 14"ø
12"ø
12"ø
12"ø12"
ø24x2210"ø
10"ø10"
ø 10"
ø 10"
ø 10"
ø 8"
ø LD-
1 315
CFMLD-
1315
CFM 8"
ø 14"
ø14"ø10"
ø10"ø10"
ø 14"ø 14"
ø 22x2014"
ø 14"
ø 14"
ø 14"
ø LD-
1 315
CFM 12"
ø 12"
øG-1
720 CFM
G-1
720 CFM
G-1
720 CFM
G-1
720 CFM
LD-2
440 CFM
LD-2
440 CFM
LD-2
440CFMLD-2
440 CFM
LD-2
440 CFM16"
øLD-2
445 CFM
LD-2
445 CFM
LD-2
445 CFM
LD-2
445 CFM
16"ø
12"ø
12"ø
LD-1 270 CFM
CD-1
550 CFM
12"ø14"
ø18"
ø
10"
ø
10"
ø
12"
ø DROP
1010
1010 9
6
6 12"
ø 12"ø12"ø10"
ø 9
18"ø
14"ø
14"ø
10 10
G-1
770 CFM G-
1 770
CFM G-1
770 CFM 10
14"ø
28x2414"ø
6 6
14"ø
G-1
770 CFM
14"ø
G-1
765 CFM
2 TYP.)
14"ø
14"ø
G-1
550 CFM
G-1
550 CFM
LD-1
270 CFM
LD-1
300 CFM
CD-3
45 CFM
LD-1
365 CFM
LD-1
365 CFM
LD-1
365 CFM
LD-1
200
CFM LD-
1 200
CFM 6"
ø 6"
øDROP
10"
ø
6"ø
10"ø
10"ø
6 66
6 14"
øDROPDROPCD-2
590 CFM
14"ø
14"øG-
1 765
CFM 3
TYP.)14"
ø 3
TYP.)14"ø G-
2 590
CFM G-
1 590
CFM
6"ø10"ø
10"ø
14"ø
14"ø14"
ø 14"
ø14x1214"ø
1 8"
ø8"ø
8"
ø
8"
øG-
1
70
CFM
G-
1 70
CFM G-
1 140
CFM
2
2
2
3
3
4
4
4
5
5
6
6
6
6
6
6 6
6
6
6
6
6
10
7
8 8
8 8 8 9
9 9
9 9
9 20x1828x20
13 14
12 G-
3 60
CFM
G-
4100CFM
G-4
100
CFM
8"
ø
10"ø8"
ø DN.
TO GRILLE
8 8"
øG-4
100
CFM
11
6"
ø8
8
10 G-
1 60
CFM G-5 60 CFM
8"ø
15 15 15 15 15 G
20x18HVAC LEGEND SYMBOL DESCRIPTION NEW RECTANGULAR
OR ROUND DUCT FLEXIBLE DUCT SUPPLY
AIR DUCTWORK UP THROUGH PLAN
RETURN AIR DUCTWORK UP THROUGH
PLAN EXHAUST AIR DUCTWORK
UP THROUGH PLAN 90°
ELBOW WITH TURNING VANES MANUAL
AIR VOLUME CONTROL
DAMPER 4 WAY
SUPPLY DIFFUSER
3 WAY SUPPLY
DIFFUSER 2
WAY OPPOSED
SUPPLY
DIFFUSER
RETURN AIR
DEVICE EXHAUST AIRDEVICE
CO2 SENSOR MECHANICAL EQUIPMENT TAG
CONDENSATEPIPINGXXX
CFM A
C RTU-10
COMBINATION TEMPERATURE/
HUMIDITY SENSORTH LINEARSLOTDIFFUSER
WITH PLENUM AIR CURTAINAC-
X LD-X 10x8 8"
ø 12"ø PACKAGED ROOFTOP
AIR CONDITIONERRTU-
X
ROOF MOUNTED
EXHAUSTFAN
EF-
X INLINE EXHAUST
FAN 2 WAY CORNERSUPPLY
DIFFUSER EF-X CFM