HomeMy WebLinkAboutLightingCOMcheck Software Version 4.1.2.1
Interior Lighting Compliance Certificate
Project Title:
2017 Florida Building Code, Energy Conservation
Project Type:New Construction
Construction Site:
Orange Ave. & Kings Hwy.
Ft. Pierce, FL 34945
Owner/Agent:
Cuhaci & Peterson Architects
Engineers and Planners
1925 Prospect Ave.
Orlando, FL 32814
407-661-9100
Designer/Contractor:
Cuhaci & Peterson Architects
Engineers and Planners
1925 Prospect Ave.
Orlando, FL 32814
407-661-9100
Project Information
Energy Code:
Wawa - ORN - F85FB - 2180719
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations.
Additional Efficiency Package(s)
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
B X C)
1-Retail 5831 1.13 6612
6612TotalAllowedWatts =
Proposed Interior Lighting Power
E
C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
of
Fixtures
1-Retail
DL1/DL1E: DL1/DL1E: Recessed 6" LED Downlight: LED Other Fixture Unit 28W:1 15 30 450
DL3/DL3E: DL3/DL3E: Recessed 4" LED Downlight: LED Other Fixture Unit 28W:1 23 30 690
GL1/GL1E: GL1/GL1E: Recessed 2x2 LED: LED Other Fixture Unit 36W:1 55 37 2035
GL3/GL3E: GL3/GL3E: Recessed 2x4 LED: LED Other Fixture Unit 40W:1 14 35 490
GL5/GL5E: GL5/GL5E: Recessed 2x6 LED: LED Other Fixture Unit 46W:1 1 44 44
HL: HL: Vapor Tight LED Sfc. Mnt.: LED Other Fixture Unit 28W:1 2 27 54
LL1: LL1: 4' Rec. linear LED wallwasher: LED Other Fixture Unit 36W:1 1 38 38
LL2: LL2: Linear LED per foot: LED A Lamp 2.5W:1 26 2 57
PL1: PL1: Pendant LED Lamp: LED Other Fixture Unit 16W:1 9 18 162
SH/SHE: SH/SHE: 4' Vaportight linear LED: LED Linear 33W:1 7 38 266
SL1: SL1: 4' LED Wall Grazer: LED Other Fixture Unit 6.5W:4 3 28 84
4370TotalProposedWatts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2017 Florida Building Code, Energy Conservation requirements in COMcheck Version 4.1.2.1 and to comply
with any applicable mandatory requirements listed in the Inspection Checklist.
Interior Lighting PASSES: Design 34% better than code
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Reportdate:
101ofPage
Jaison P. Moras, P.E.
Name - Title Signature Date
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Reportdate:
102ofPage
04/17/2020
COMcheck Software Version 4.1.2.1
Exterior Lighting Compliance Certificate
Project Title:
2017 Florida Building Code, Energy Conservation
Project Type:New Construction
Construction Site:
Orange Ave. & Kings Hwy.
Ft. Pierce, FL 34945
Owner/Agent:
Cuhaci & Peterson Architects
Engineers and Planners
1925 Prospect Ave.
Orlando, FL 32814
407-661-9100
Designer/Contractor:
Cuhaci & Peterson Architects
Engineers and Planners
1925 Prospect Ave.
Orlando, FL 32814
407-661-9100
Project Information
Energy Code:
Wawa - ORN - F85FB - 2180719
4 (High activity metropolitan commercial district)Exterior Lighting Zone
Allowed Exterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable
Wattage
E
Allowed Watts
B X C)
Overhangs at entry doors and seating area (Entry canopy)1136 ft2 0.4 Yes 454
Exterior wall lighting (Illuminated area of facade wall or surface)2463 ft2 0.2 No 493
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
454
947
1300
a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
b)A supplemental allowance equal to 1300 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
E
C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
of
Fixtures
Overhangs at entry doors and seating area ( Entry canopy 1136 ft2): Tradable Wattage
DL2/DL2E: DL2/DL2E: Recessed 4.5" LED Downlight: LED PAR 20W:1 6 16 96
DL7/DL7E: DL7/DL7E: Wet Loc. Rec. 6" LED Downlight: LED Other Fixture Unit 28W:1 22 30 660
Exterior wall lighting ( Illuminated area of facade wall or surface 2463 ft2): Non-tradable Wattage
EL2: EL2: Wet Loc. LED Strip: LED Other Fixture Unit 6.5W:1 6 8 45
EL3: EL3: Wet Loc. LED Strip: LED Other Fixture Unit 6.5W:1 14 8 105
RF: RF: Wet Loc.LED Area Light: LED Other Fixture Unit 6.5W:1 4 27 108
REM2: REM2: Twin Remote Head Emer. Light: LED PAR 12W:2 3 18 54
WC1: WC1: Decorative LED Wall Sconce: LED Other Fixture Unit 13W:1 4 23 92
Z1: Z1: Wall Mtd. Ext. Area LED: Other:1 6 50 300
756TotalTradableProposedWatts =
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 2017 Florida Building Code, Energy Conservation requirements in COMcheck Version 4.1.2.1 and to comply
with any applicable mandatory requirements listed in the Inspection Checklist.
Exterior Lighting PASSES: Design 51% better than code
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Reportdate:
103ofPage
Jaison P. Moras, P.E.
Name - Title Signature Date
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Reportdate:
104ofPage
04/17/2020
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.2.1
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2017 Florida Building Code, Energy Conservation
Section
Req.ID
Plan Review Complies?Comments/Assumptions
C405.6
PR17]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the electrical systems
and equipment and document where
exceptions are claimed. Provisions are
made for metering individual tenant
units. Feeder connectors (for feeder
and branch circuits) sized in
accordance with approved plans with
maximum drop of 5% voltage drop
total.
Complies
Does Not
Not Observable
Not Applicable
C103.2
PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
C103.2
PR8]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the exterior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
C406
PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Reportdate:
105ofPage
Section
Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C402.2.6
FO12]3
Radiant heating systems panels
insulated to >=R-3.5 on face opposite
space being heated.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Reportdate:
106ofPage
Section
Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.1
EL15]1
Lighting controls installed to uniformly
reduce the lighting load by at least
50%.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1
EL18]1
Occupancy sensors installed in
required spaces.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1,
C405.2.2.
3
EL23]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
C405.2.2.
1
EL22]2
Automatic controls to shut off all
building lighting installed in all
buildings.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3
EL16]2
Daylight zones provided with
individual controls that control the
lights independent of general area
lighting.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3,
C405.2.3.
1,
C405.2.3.
2
EL20]1
Primary sidelighted areas are
equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3,
C405.2.3.
1,
C405.2.3.
3
EL21]1
Enclosed spaces with daylight area
under skylights and rooftop monitors
are equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
C405.2.5
EL25]null
Automatic lighting controls for exterior
lighting installed. Controls will be
daylight controlled, set based on
business operation time-of-day, or
reduce connected lighting > 30%.
Complies
Does Not
Not Observable
Not Applicable
C405.3
EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Reportdate:
107ofPage
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Reportdate:
108ofPage
Section
Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
2
FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
C405.4.1
FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
C405.5.1
FI19]1
Exterior lighting power is consistent
with what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
Complies
Does Not
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values.
C408.2.5.
1
FI16]3
Furnished as-built drawings for
electric power systems within 90 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.3
FI33]1
Lighting systems have been tested to
ensure proper calibration, adjustment,
programming, and operation.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Reportdate:
109ofPage
Project Title:
Data filename:
Wawa - ORN - F85FB - 2180719
W:\2018\2180719\HVAC Calcs\Energy Calcs\F85-FB-v2020.00-(FL)_2017 IECC.cck
04/16/20Reportdate:
1010ofPage