FORM R405-2020
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: WATSON RESIDENCE Builder Name:
Street: 1305 LONE PINE DRIVE Permit Office: ST LUCIE COUNTY
City,State,Zip: FORT PIERCE,FL, Permit Number:
Owner. MARVIN WATSON Jurisdiction: ST LUCIE COUNTY
Design Location: FL,Fort Pierce County: St.Lucie(Florida Climate Zone 2)
1. New construction or ebsting New(From Plans) 10. Wall Types(2744.0 sqft.) Insulation Area
2. Single family or multiple family Detached a.Concrete Block-Polystyrene Bead AggrcR=0.0 2529.30 ftz
b.Frame-Wood,Adjacent R=11.0 214.67 ft
. Number of units,if multiple family 1 c.N/A R= ftZ
4. Number of Bedrooms 3 d.N/A R= ft2
5. Is this a worst case? No 11.Ceiling Types (3243.0 sqft.) Insulation Area a.Roof Deck(Unvented) R=20.0 3243.00 ftz
6. Conditioned floor area above grade(ftz) 3243 b.N/A R= ftZ
Conditioned floor area below grade(ftZ) 0 c.N/A R= ftZ
7. Windows(327.8 sqft.) Description Area 12.Ducts R ftZ
a.Sup:Attic,Ret:Attic,AH:AHU 1 CLST 6 140
a. U-Factor: Sgl,U=0.65 327.83 ftZ b.Sup: Attic,Ret:Attic,AH:AHU 2 CLST 6 120
SHGC: SHGC=0.25
b. U-Factor: N/A ftZ 13.Cooling systems kBtu/hr Efficiency
SHGC: a.Central Unit 35.2 SEER:16.00
c. U-Factor: N/A ftZ b.Central Unit 18.8 SEER:16.00
SHGC:
Area Weighted Average Overhang Depth: 7.954 ft. 14.Heating systems kBtu/hr Efficiency
Area Weighted Average SHGC: 0.250 a.Electric Strip Heat 17.0 COP:1.00
b.Electric Strip Heat 7.0 COP:1.00
8. Skylights Area
c. U-Factor:(AVG) N/A ftZ 15.Hot water systems
SHGC(AVG): N/A a.Electric Tankless Cap:1 gallons
9. Floor Types (3243.0 sqft.) Insulation Area EF:0.990
a.Slab-On-Grade Edge Insulation R=0.0 3243.00 ftZ b. Conservation features
b.N/A R= ftz None
c.N/A R= ftZ 16.Credits None
Total Proposed Modified Loads: 88.46
lass/Floor Area: 0.101 PASS
Total Baseline Loads: 88.73
I hereby certify that the plans and specifications covered by Review of the plans and 0�11JE ST
ATF
this calculation are in compliance with the Florida Energy specifications covered by this
Code calculation indicates compliance ���i„��''' �•�+
with the Florida Energy Code.
PREPARED BY: k&;2QijyQBefore construction is completed
DATE: 11-22 202H this building will be inspected for
compliance with Section 553.908 * Q
hereby certify that this building, as des igne , is in compliance Florida Statutes.
ith the Florida Energy Cod�o e. COD y� �
OWNER/AGENT-- BUILDING OFFICIAL:
DATE: /h 2 Z'ZOZf DATE:
Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifi ss
certified factory-sealed in accordance with R403.3.2.1.
Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 an s project requires
an envelope leakage test report with envelope leakage no greater than 5.00 ACH50(R402.4.1.2).
11/17/2021 3:21 PM EnergyGaugeO USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 1 of 8
i
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title: WATSON RESIDENCE Bedrooms: 3 Address Type: Street Address
Building Type. User Conditioned Area: 3243 Lot#
Owner Name: MARVIN WATSON Total Stories: 1 Block/Subdivision:
#of Units: 1 Worst Case: No PlatBook:
Builder Name: Rotate Angle: 0 Street: 1305 LONE PINE DRIV
Permit Office: ST LUCIE COUNTY Cross Ventilation: No County: St.Lucie
Jurisdiction: ST LUCIE COUNTY Whole House Fan: No City,State,Zip: FORT PIERCE,
Family Type: Detached FL,
New/Ebsting: New(From Plans)
Comment:
CLIMATE
Design Temp Int Design Temp Heating Design Daily Temp
V Design Location TMY Site 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,Fort Pierce FL VERO_BEACH_MUNI 39 90 70 75 299 62 Low
i
BLOCKS
Number Name Area Volume
1 AHU 1 2211 20562.3
2 AHU 2 1032 9597.6
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated
1 GREAT RM 420 3906 No 0 1 Yes Yes Yes
2 LIVING RM 130 1209 No 0 1 Yes Yes Yes
3 FOYER 72 669.6 No 0 1 Yes Yes Yes
4 BEDROOM 2 156 1450.8 No 0 1 1 Yes Yes Yes
5 BEDROOM 3 144 1339.2 No 0 1 1 Yes Yes Yes
6 HALL 96 892.8 No 0 1 No Yes Yes
7 BATH 3 72 669.6 No 0 1 Yes Yes Yes
8 CLST 3 24 223.2 No 0 1 Yes Yes Yes
9 OFFICE 274 2548.2 No 0 1 Yes Yes Yes
10 CLST 2 18 167.4 No 0 1 No Yes Yes
11 OFFICE CLST 30 279 No 0 1 Yes Yes Yes
12 LAUNDRY 68 632.4 No 0 1 Yes Yes Yes
13 KITCHEN 288 2678.4 Yes 0 1 No Yes Yes
14 AHU 1 CLST 9 83.7 No 0 1 No Yes Yes
15 DINING RM 190 1767 No 0 1 Yes Yes Yes
16 NOOK 220 2046 No 0 11 Yes Yes Yes
17 BATH 2 65 604.5 No 0 1 Yes Yes Yes
18 M W IC 2 75 697.5 No 0 1 Yes Yes Yes
19 AHU 2 CLST 9 83.7 No 0 1 No Yes Yes
20 M W IC 3 84 781.2 No 0 1 No Yes Yes
21 M BATH 154 1432.2 No 0 1 Yes Yes Yes
11/17/2021 3:21 PM EnergyGauge®USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 2 of 8
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated
22 M W IC 1 112 1041.6 No 0 1 Yes Yes Yes
23 M TOILET 36 334.8 No 0 1 Yes Yes Yes
24 STORAGE 91 846.3 No 0 1 Yes Yes Yes
25 MASTER BEDROO 406 3775.8 No 0 1 1 Yes Yes Yes
FLOORS
# Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
1 Slab-On-Grade Edge Insulation GREAT RM 21 ft 420 ft2 ---- 1 0 0
2 Slab-On-Grade Edge Insulation LIVING RM lift 130 ft2 ___ 1 0 0
3 Slab-On-Grade Edge Insulation FOYER 8ft 72 ft2 1 0 0
4 Slab-On-Grade Edge Insulation BEDROOM 2 10 ft 156 ft2 __e 1 0 0
5 Slab-On-Grade Edge Insulation BEDROOM 3 10 ft 144 ft2 1 0 0
6 Slab-On-Grade Edge Insulation HALL 1 ft 96 ft2 1 0 0
7 Slab-On-Grade Edge Insulation BATH 3 6ft 72 ft2 __e 1 0 0
8 Slab-On-Grade Edge Insulation CLST 3 2ft 24 ft2 __e 1 0 0
9 Slab-On-Grade Edge Insulation OFFICE 17 ft 274 ft2 ___ 1 0 0
10SIab-On-Grade Edge Insulation CLST 2 1 ft 18 ft2 __e 1 0 0
11Slab-On-Grade Edge Insulation OFFICE CLST 2ft 30 ft2 ___ 1 0 0
12SIab-On-Grade Edge Insulation LAUNDRY 1 ft 68 ft2 1 0 0
13SIab-On-Grade Edge Insulation KITCHEN 1 ft 288 ft2 __e 1 0 0
14SIab-On-Grade Edge Insulation AHU 1 CLST 1 ft 9 ft2 1 0 0
15SIab-On-Grade Edge Insulation DINING RM 12 ft 190 ft2 ____ 1 0 0
16SIab-On-Grade Edge Insulation NOOK 6ft 220 ft2 1 0 0
17SIab-On-Grade Edge Insulation BATH 2 8ft 65 ft2 1 0 0
18SIab-On-Grade Edge Insulation M W IC 2 12 ft 75 ft2 ___- 1 0 0
19SIab-On-Grade Edge Insulation AHU 2 CLST 1 ft 9 ft2 1 0 0
20SIab-On-Grade Edge Insulation M W IC 3 1 ft 84 ft2 -_-- 1 0 0
21SIab-On-Grade Edge Insulation M BATH 16 ft 154 ft2 1 0 0
22SIab-On-Grade Edge Insulation M W IC 1 7 ft 112 ft2 __e 1 0 0
23SIab-On-Grade Edge Insulation M TOILET 12 ft 36 ft2 ___- 1 0 0
24SIab-On-Grade Edge Insulation STORAGE 16 ft 91 ft2 ____ 1 0 0
11/17/2021 3:21 PM EnergyGauge®USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 3 of 8
3
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
FLOORS
# Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
25SIab-On-Grade Edge Insulation MASTER BEDRO 22 ft 406 ft2 ___ 1 0 0
I
ROOF
/ Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch
V # Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg)
1 Hip Metal 3513 ft2 0 ft2 Light N 0.1 No 0.9 No 20 22.62
ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Unvented 0 3243 ft2 N N
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
1 Under Attic(Unvented) GREAT RM 0 Blown 420 ft2 0.1 Wood
2 Under Attic(Unvented) LIVING RM 0 Blown 130 ft2 0.1 Wood
3 Under Attic(Unvented) FOYER 0 Blown 72 ft2 0.1 Wood
4 Under Attic(Unvented) BEDROOM 2 0 Blown 156 ft2 0.1 Wood
5 Under Attic(Unvented) BEDROOM 3 0 Blown 144 ft2 0.1 Wood
6 Under Attic(Unvented) HALL 0 Blown 96 ft2 0.1 Wood
7 Under Attic(Unvented) BATH 3 0 Blown 72 ft2 0.1 Wood
8 Under Attic(Unvented) CLST 3 0 Blown 24 ft2 0.1 Wood
9 Under Attic(Unvented) OFFICE 0 Blown 274 ft2 0.1 Wood
10 Under Attic(Unvented) CLST 2 0 Blown 18 ft2 0.1 Wood
11 Under Attic(Unvented) OFFICE CLST 0 Blown 30 ft2 0.1 Wood
12 Under Attic(Unvented) LAUNDRY 0 Blown 68 ft2 0.1 Wood
13 Under Attic(Unvented) KITCHEN 0 Blown 288 ft2 0.1 Wood
14 Under Attic(Unvented) AHU 1 CLST 0 Blown 9 ft2 0.1 Wood
15 Under Attic(Unvented) DINING RM 0 Blown 190 ft2 0.1 Wood
16 Under Attic(Unvented) NOOK 0 Blown 220 ft2 0.1 Wood
17 Under Attic(Unvented) BATH 2 0 Blown 65 ft2 0.1 Wood
18 Under Attic(Unvented) M W IC 2 0 Blown 75 ft2 0.1 Wood
19 Under Attic(Unvented) AHU 2 CLST 0 Blown 9 ft2 0.1 Wood
20 Under Attic(Unvented) M WIC 3 0 Blown 84 ft2 0.1 Wood
21 Under Attic(Unvented) M BATH 0 Blown 154 ft2 0.1 Wood
22 Under Attic(Unvented) M WIC 1 0 Blown 112 ft2 0.1 Wood
23 Under Attic(Unvented) M TOILET 0 Blown 36 ft2 0.1 Wood
24 Under Attic(U nvented) STORAGE 0 Blown 91 ft2 0.1 Wood
25 Under Attic(Unvented) MASTER BEDRO 0 Blown 406 ft2 0.1 Wood
I
11/17/2021 3:21 PM EnergyGauge®USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 4 of 8
I
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
WALLS
j Adjacent Space Cavity Width Height Sheathing Framing Solar Below
13-1/al,le Ft In Et In Area R-%/Aile Erqrtffinn Ahqnr Grarfp%
1 E Exterior Concrete Block-Polystyr&REAT RM 0 20 0 9 4 186.7 ftZ 0 0 0.1 0
2 S Exterior Concrete Block-PolystyrGREAT RM 0 21 0 9 4 196.0 ftZ 0 0 0.1 0
3 N Exterior Concrete Block-PolystyrddVING RM 0 10 0 9 4 93.3 ftZ 0 0 0.1 0
4 W Exterior Concrete Block-Polystyr&AVING RM 0 4 0 9 4 37.3 ftZ 0 0 0.1 0
5 N Exterior Concrete Block-Polystyren€DYER 0 8 0 9 4 74.7 ftZ 0 0 0.1 0
6 W Exterior Concrete Block-PolystyMI)ROOM 2 0 13 0 9 4 121.3 ftZ 0 0 0.1 0
7 N Garage Frame-Wood BEDROOM 2 11 12 0 9 4 112.0 ftZ 0 0.1 0.1 0
8 W Exterior Concrete Block-Polysty&EOROOM 3 0 12 0 9 4 112.0 ftZ 0 0 0.1 0
9 W Exterior Concrete Block-PolystyrenSATH 3 0 6 0 9 4 56.0 ftZ 0 0 0.1 0
10 W Exterior Concrete Block-PolystyrenCLST 3 0 2 0 9 4 18.7 ftZ 0 0 0.1 0
11 S Exterior Concrete Block-Polystyrer@FFICE 0 14 0 9 4 130.7 ftZ 0 0 0.1 0
i
12 W Exterior Concrete Block-PolystyrerOFFICE 0 19 0 9 4 177.3 ftZ 0 0 0.1 0
_13 N Garage Frame-Wood CLST 2 11 2 0 9 4 18.7 ft2 0 0.1 0.1 0
14 S Exterior Concrete Block-Polysty fflCE CLS 0 2 0 9 4 18.7 ftZ 0 0 0.1 0
15 E Exterior Concrete Block-PolystyrdiAUNDRY 0 1 0 9 4 9.3 ftZ 0 0 0.1 0
16 N Garage Frame-Wood LAUNDRY 11 7 0 9 4 65.3 ftZ 0 0.1 0.1 0
17 W Garage Frame-Wood LAUNDRY 11 2 0 9 4 18.7 ftZ 0 0.1 0.1 0
18 N Exterior Concrete Block-PolystyrEHNING RM 0 11 0 9 4 102.7 ftZ 0 0 0.1 0
19 E Exterior Concrete Block-PolystyrEHNING RM 0 4 0 9 4 37.3 ftZ 0 0 0.1 0
20 S Exterior Concrete Block-Polystyren&OOK 0 6 0 9 4 56.0 ftZ 0 0 0.1 0
21 E Exterior Concrete Block-PolystyrenSATH 2 0 5 0 9 4 46.7 ftZ 0 0 0.1 0
22 W Exterior Concrete Block-PolystyrenSATH 2 0 3 0 9 4 28.0 ftZ 0 0 0.1 0
23 E Exterior Concrete Block-PolystyrerM WIC 2 0 12 0 9 4 112.0 ftZ 0 0 0.1 0
24 N Exterior Concrete Block-PolystyrerM BATH 0 11 0 9 4 102.7 ftZ 0 0 0.1 0
25 E Exterior Concrete Block-Polystyrerfd BATH 0 11 0 9 4 102.7 ftZ 0 0 0.1 0
26 W Exterior Concrete Block-PolystyreM BATH 0 4 0 9 4 37.3 ftZ 0 0 0.1 0
27 S Exterior Concrete Block-PolystyrerM W IC 1 0 7 0 9 4 65.3 ftZ 0 0 0.1 0
28 N Exterior Concrete Block-PolystyrdabTOILET 0 6 0 9 4 56.0 ftZ 0 0 0.1 0
29 W Exterior Concrete Block-Polystyrefold-TOILET 0 6 0 9 4 56.0 ftZ 0 0 0.1 0
_ Z 0 0 0.1 0
30 E Exterior Concrete Block-Polystyr�'�ORAGE 0 7 0 9 4 65.3 ft
31 S Exterior Concrete Block-PolystyrEKORAGE 0 13 0 9 4 121.3 ftZ 0 0 0.1 0
32 W Exterior Concrete Block-PolystyrE&'EORAGE 0 7 0 9 4 65.3 ftZ 0 0 0.1 0
33 N Exterior Concrete Block-Polys~TER BE 0 2 0 9 4 18.7 ftZ 0 0 0.1 0
34 E Exterior Concrete Block-PolystyrUASTER BE 0 18 0 9 4 168.0 ftZ 0 0 0.1 0
35 S Exterior Concrete Block-PolystyTER BE 0 6 0 9 4 56.0 ftZ 0 0 0.1 0
I
DOORS
# Ornt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 N Insulated FOYER None .14 3 8 24 ftZ
2 W Insulated STORAGE None .14 2 8 8 21.3 ftZ
I
11/17/2021 3:21 PM EnergyGauge®USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 5 of 8
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
WINDOWS
Orientation shown is the entered,Proposed orientation.
Wall Overhang
# Omt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening
1 E 1 Metal Low-E Single Yes 0.65 0.25 Y 48.0 ft2 22 ft 0 in 1 ft 4 in Drapes/blinds None
2 S 2 Metal Low-E Single Yes 0.65 0.25 Y 30.0 ft2 2 ft 0 in 1 ft 4 in None None
3 S 2 Metal Low-E Single Yes 0.65 0.25 Y 30.0 ft2 2 ft 0 in 1 ft 4 in None None
4 N 3 Metal Low-E Single Yes 0.65 0.25 Y 30.0 ft2 10 ft 0 in 1 ft 4 in None None
5 N 5 Metal Low-E Single Yes 0.65 0.25 Y 16.0 ft2 14 ft 0 in 1 ft 4 in None None
6 W 6 Metal Low-E Single Yes 0.65 0.25 Y 30.0 ft2 2 ft 0 in 1 ft 4 in None None
7 W 8 Metal Low-E Single Yes 0.65 0.25 Y 15.0 ft2 2 ft 0 in 1 ft 4 in None None
8 W 9 Metal Low-E Single Yes 0.65 0.25 Y 9.0 ft2 2 ft 0 in 1 ft 4 in None None
9 W 12 Metal Low-E Single Yes 0.65 0.25 Y 30.0 ft2 2 ft 0 in 1 ft 4 in Drapes/blinds None
10 N 18 Metal Low-E Single Yes 0.65 0.25 Y 30.0 ft2 10 ft 0 in 1 ft 4 in None None
11 S 20 Metal Low-E Single Yes 0.65 0.25 Y 16.0 ft2 22 ft 0 in 1 ft 4 in None None
12 E 25 Metal Low-E Single Yes 0.65 0.25 Y 12.0 ft2 2 ft 0 in 1 ft 4 in None None
13 E 34 Metal Low-E Single Yes 0.65 0.25 Y 11.8 ft2 2 ft 0 in 1 ft 4 in None None
14 E 34 Metal Low-E Single Yes 0.65 0.25 Y 20.0 ft2 2 ft 0 in 1 ft 4 in None None
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 504 ft2 504 ft2 23 ft 9 ft 11
I
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
i
11
Wholehouse ProposedACH(50) .000295 2513.3 137.89 258.87 .0958 5
HEATING SYSTEM
# System Type Subtype Speed Efficiency Capacity Black Ducts
1 Electric Strip Heat/ None COP:1 27 kBtu/hr 1 sys#1
2 Electric Strip Heat/ None COP:1 17 kBtu/hr 2 sys#2
I
COOLING SYSTEM
# System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit/ Split Single SEER:16 35.2 kBtu/hr 1056 cfm 0.8 1 sys#1
2 Central Unit/ Split Single SEER:16 18.8 kBtu/hr 564 cfm 0.8 2 sys#2
I
HOT WATER SYSTEM
# System Type SubType Location EF Cap Use SetPnt Conservation
1 Electric Tankless Exterior 0.99 1 gal 55.1 gal 120 deg None
I
11/17/2021 3:21 PM Ener Gau e® -
gy g USA 7.0.00 FlaRes2020 FBC 7th Edition(2020) Compliant Software Page 6 of 8
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ft2
I
DUCTS
—Supply— —Return— Air CFM 25 CFM25 HVAC#
V # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 Attic 6 140 ft2 Attic 14 ftz Default Leakage AHU 1 CLS (Default)c(Default)c 1 1
2 Attic 6 120 ft' Attic 12 ft2 Default Leakage AHU 2 CLS (Default)c(Default)c 2 2
TEMPERATURES
Programable Thermostat: N Ceiling Fans:
Cooling [ ]Jan Feb Mar Apr [ ]May Jun Jul [X]Auge [ ]Oct [ ]Nov Dec
Heatin [X]Jan Feb Mar f Apr [ ]May 4 Jun Jul [ ]Au4 SeP [ ]Oct [X]Nov Dec
Vent in [ ]Jan Feb Mar [X]Apr [ ]May [ Jun Jul [ ]Aug [ Se [X]Oct [X]Nov Dec
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(W D) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 80 80 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 80 80 78 78 78 78 78 78 78 78
Heating(WD) AM 65 65 65 65 65 65 65 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 68 68
Heating(WEH) AM 65 65 65 65 65 65 65 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 68 68
MASS
Mass Type Area Thickness Furniture Fraction Space
Default(8 Ibs/sq.ft. 0 ft2 0 ft 0.3 GREAT RM
Default(8lbs/sq.ft. ft2 ft 0.3 LIVING RM
Default(8 Ibs/sq.ft. ft2 ft 0.3 FOYER
Default(8 lbs/sq.ft. ft2 ft 0.3 BEDROOM 2
Default(8 Ibs/sq.ft. ft2 ft 0.3 BEDROOM 3
Default(8 Ibs/sq.ft. ft2 ft 0.3 HALL
Default(8 Ibs/sq.ft. ft2 ft 0.3 BATH 3
Default(8 Ibs/sq.ft. ft2 ft 0.3 CLST 3
Default(8 Ibs/sq.ft. ft2 ft 0.3 OFFICE
Default(8 Ibs/sq.ft. ft2 ft 0.3 CLST 2
Default(8 Ibs/sq.ft. ft2 ft 0.3 OFFICE CLST
Default(8 Ibs/sq.ft. ft2 ft 0.3 LAUNDRY
Default(8 Ibs/sq.ft. ft2 ft 0.3 KITCHEN
Default(8lbs/sq.ft. ft2 ft 0.3 AHU 1 CLST
Default(81bs/sq.ft. ft2 ft 0.3 DINING RM
Default(8 Ibs/sq.ft. ft2 ft 0.3 NOOK
Default(8 Ibs/sq.ft. ft2 ft 0.3 BATH 2
Default(8 Ibs/sq.ft. ft2 ft 0.3 M W IC 2
Default(8 Ibs/sq.ft. ft2 ft 0.3 AHU 2 CLST
11/17/2021 3:21 PM EnergyGauge®USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 7 of 8
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
MASS
Mass Type Area Thickness Furniture Fraction Space
Default(8 Ibs/sq.ft. ft2 ft 0.3 M W IC 3
Default(8 Ibs/sq.ft. ft2 ft 0.3 M BATH
Default(8 Ibs/sq.ft. ft2 ft 0.3 M W IC 1
Default(8 Ibs/sq.ft. ft2 ft 0.3 M TOILET
Default(8 Ibs/sq.ft. ft2 ft 0.3 STORAGE
Default(8 Ibs/s .ft. ft2 ft 0.3 MASTER BEDROO
11/17/2021 3:21 PM EnergyGauge®USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 8 of 8
I
I '
' 2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1 a
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: WATSON RESIDENCE Builder Name:
Street: 1305 LONE PINE DRIVE Permit Office: ST LUCIE COUNTY
City,State,Zip: FORT PIERCE,FL, Permit Number: Y
U
Owner: MARVIN WATSON Jurisdiction: ST LUCIE COUNTY W
2
Design Location: FL,Fort Pierce U
COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA
General A continuous air barrier shall be installed in the building envelope. Air-permeable insulation shall
The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material.
requirements Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with the The insulation in any dropped ceiling/soffit
Ceiling/attic insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier.
Access openings,drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls The junction of the foundation and sill plate shall be sealed. Cavities within comers and headers of frame walls
The junction of the top plate and the top of exterior walls shall be sealed. shall be insulated by completely filling the cavity with a
Knee walls shall be sealed. material having a thermal resistance of R-3 per inch
minimum.
Exterior thermal envelope insulation for framed walls
shall be installed in substantial contact and continuous
alignment with the air barrier.
Windows,skylights The space between window/doorjambs and framing,and
and doors skylights and framing shall be sealed.
Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated.
Floors The air barrier shall be installed at any exposed edge of insulation. Floor framing cavity insulation shall be installed to
(including maintain permanent contact with the underside of
above-garage subfloor decking,or floor framing cavity insulation shall
and cantilevered floors) be permitted to be in contact with the top side of
sheathing,or continuous insulation installed on the
underside of floor framing and extends from the bottom
to the top of all perimeter floor framing members.
Crawl space walls Exposed earth in unvented crawl spaces shall be covered with a Where provided instead of floor insulation,insulation
Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls.
Shafts,penetrations Duct shafts,utility penetrations,and flue shafts opening to exterior
or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit,or narrow
Narrow cavities cavities shall be filled by insulation that on installation
readily conforms to the available cavity spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spaces.
Recessed lighting Recessed light fixtures installed in the building thermal envelope shall Recessed light fixtures installed in the building
be sealed to the finished surface. thermal envelope shall be air tight and IC rated.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring an
plumbing in exterior walls,or insulation that on
installation readily conforms to available space shall
extend behind piping and Wring.
Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall be
on exterior wall tubs shall separate them from the showers and tubs. insulated.
Electrical/phone box on The air barrier shall be installed behind electrical or communication
exterior walls boxes or air-sealed boxes shall be installed.
HVAC register boots HVAC supply and return register boots that penetrate building thermal
envelope shall be sealed to the sub-floor,wall covering or ceiling
Concealed When required to be sealed,concealed fire sprinklers shall only be sealed
sprinklers in a manner that is recommended by the manufacturer.Caulking or other
adhesive sealants shall not be used to fill voids between fire sprinkler
cover plates and walls or ceilin s.
a.In addition,inspection of log walls shall be in accordance with the provisions of ICC-400.
11/17/2021 3:21 PM EnergyGauge®USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 1 of 1
FORM R405-2020
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
i
ESTIMATED ENERGY PERFORMANCE INDEX` = 100
The lower the EnergyPerformance Index, the more efficient the home.
1305 LONE PINE DRIVE, FORT PIERCE, FL,
1. New construction or existing New(From Plans) 10. Wall Type and Insulation Insulation Area
2. Single family or multiple family Detached a.Concrete Block-Polystyrene Bead AggrER=0.0 2529.30 ft2
I b.Frame-Wood,Adjacent R=11.0 214.67 ft
3. Number of units,if multiple family 1 c.N/A R= ft2
4. Number of Bedrooms 3 d.N/A R= ft2
1 11.Ceiling Type and insulation level Insulation Area
5. Is this a worst case? No a.Roof Deck(Unvented) R=20.0 3243.00 ft2
6. Conditioned floor area(ft2) 3243 b.N/A R= ft2
2
7. W ftindows- Description Area c.N/A R= 2
a. U-Factor: S I,U=0.65 327.83 ft2 12.Ducts,location&insulation level R ft
g a.Sup:Attic,Ret:Attic,AH:AHU 1 CLST 6 140
SHGC: SHGC=0.25 b.Sup: Attic,Ret:Attic,AH:AHU 2 CLST 6 120
b. U-Factor: N/A ft2
SHGC: 13.Cooling systems kBtu/hr Efficiency
c. U-Factor: N/A ft2 a.Central Unit 35.2 SEER:16.00
SHGC: b.Central Unit 18.8 SEER:16.00
d. U-Factor: N/A ft2 14.Heating systems kBtu/hr Efficiency
SHGC: a.Electric Strip Heat 27.0 COP:1.00
Area Weighted Average Overhang Depth: 7.954 ft. b.Electric Strip Heat 17.0 COP:1.00
Area Weighted Average SHGC: 0.250
8. Skylights Description Area 15.Hot water systems
a.Electric Cap:1 gallons
a. U-Factor(AVG): N/A ft2EF:0.99
SHGC(AVG): N/A
b. Conservation features
9. Floor Types Insulation Area None
a.Slab-On-Grade Edge Insulation R=0.0 3243.00 ft2 Credits(Performance method) None
b.N/A R= ft2
c.N/A R= ft2
I certify that this home has complied with the Florida Energy Efficiency Code for Building o&zgE sT.grF
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code compliant fe tures.
Builder Signature: AWAS Date: I��22-Ztf�/ �*✓ K`I �.
Address of New Home: JDjOs Lane �,1Q `�,�-��L, City/FL Zip: rr(?m,•Y- pc 3�rg,,s 'co
D wig
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage(EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code,
Energy Conservation, contact the Florida Building Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
11/17/2021 3:21 PM EnergyGauge®USA 7.0.00-FlaRes202O FBC 7th Edition(2020) Compliant Software Page 1 of 1