HomeMy WebLinkAboutNEW Prop Manual J Updated 9 @ Load Short Form Job: 1525 wri htsoft Date: 6/9/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project Information For: Talbot Residence,NisAirAir Conditioning 6901 Fort Walton Ave,Fort Pierce,FL 34951 Design Information Htg Clg Infiltration Outside db(°F) 41 90 Method Simplified Inside db(°F) 70 75 Construction quality Average Design TD(°F) 29 15 Fireplaces 0 Daily range - L Inside humidity(%) 30 50 Moisture difference(gr/Ib) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1-041-230A** AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259425 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 8.2 kW Sensible cooling 26950 Btuh Heating output 28002 Btuh Latent cooling 11550 Btuh Temperature rise 20 °F Total cooling 38500 Btuh Actual airflow 1283 cfm Actual airflow 1283 cfm Air flow factor 0.049 cfm/Btuh Air flow factor 0.052 cfim/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.74 ROOM NAME Area Htg load Clg load Htg AVF CIg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) Bed 2 164 2883 1650 141 86 Bath 50 675 326 33 17 Linen 6 0 0 0 0 Hall 28 0 0 0 0 Bed 3 173 3199 2023 156 106 Laundry 46 866 955 42 50 Kitchen 205 291 3305 14 173 Family Room 194 3346 2710 163 142 Dining/Foyer 240 3660 2433 179 127 WIC 51 976 339 48 18 Master Bath 121 1716 1005 84 53 Living Room 288 2681 5005 131 261 Pan 6 0 0 0 0 Master Bed 260 4608 4199 225 219 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Nov-12 13:03:40 A- AM.1-11-•", _ -.-pP . Right-Sute®Urrversa12021 21.0.10 RSU29066 Page 1 ACCP. ...ightsoft HVAC\6901 Fort Walton Ave PSL Prop.rup Calc=MJ8 Front Door faces: N Lin 8 0 0 0 0 Wtr Clst 30 1365 620 67 32 M Hall 12 0 0 0 0 House 1880 26266 24570 1283 1283 Other equip loads 2992 1589 Equip.@ 0.95 RSM 24955 Latent cooling 9072 TOTALS 1880 29258 34027 1283 1283 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Nov-12 13:03:40 A AM.T-I1-•", _ -.-,, Right-Sute®Urrversa12021 21.0.10 RSU29066 Page 2 ACCP. ...ightsoft HVAC\6901 Fort Walton Ave PSL Prop.rup Calc=MJ8 Front Door faces: N Building Analysis Job: 1525 +� wrightsoft° gna Date: 6/9/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Talbot Residence,NisAirAir Conditioning 6901 Fort Walton Ave,Fort Pierce,FL 34951 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(°F) 70 75 Elevation: 26 ft Design TD(°F) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 2.4 56.9 Dry bulb(°F) 41 90 Infiltration: Daily range(°F) - 15 ( L ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 amme Component Btuh/ft2 Btuh %of load Walls 3.1 4481 15.3 Walls ventilation Glazing 17.2 4027 13.8 Doors 3.7 148 0.5 Ceilings 1.0 1863 6.4 Floors 3.0 5650 19.3 Glazing/ Ducts Infiltration 2.3 3446 11.8 Ducts 6650 22.7 Piping 0 0 Other Humidification 0 0 Ceilings Ventilation 2992 10.2 Infiltration Adjustments 0 Total 29258 100.0 Floors • • • Component Btuh/ftz Btuh %of load Walls 1.9 2766 10.6 Walls Ventilation Glazing 24.3 5678 21.7 Doors 2.4 95 0.4 Internal Gains Ceilings 0.6 1203 4.6 Floors 0 0 0 Glazing Infiltration 0.7 963 3.7 Ducts 8364 32.0 Ventilation 1589 6.1 Internal gains 5500 21.0 Other Blower 0 0 Ceilings Adjustments 0 Infiltration Ducts Total 1 1261591 100.0 Latent Cooling Load=9072 Btuh Overall U-value=0.102 Btuh/ft2--°F Data entries checked. wrightsoft° 2021-Nov-1 2 13:03:40 ^., k-I-rII °^a,I I..,.I. °r I I Right-SuiteO Urrversal2021 21.0.10 RSU29066 Page 1 ightsoft HVAC\6901 Fort Walton Ave PSL Prop.rup Calc=MJ8 Front Door faces: N Component Constructions Job: 1525 +� wrightsoft C p C i Date: 6/9/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Talbot Residence,NisAirAir Conditioning 6901 Fort Walton Ave,Fort Pierce,FL 34951 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(°F) 70 75 Elevation: 26 ft Design TD(°F) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(grAb) 2.4 56.9 Dry bulb(°F) 41 90 Infiltration: Daily range(°F) - 15 ( L ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ftUF ft2-7/Btuh Btuh/ft' Btuh Btuh/ft' Btuh Walls Blk Wall,Stucco Ext,R-4.1 Ext Bd inl,8"Thk, 1/2"Gyp Bd Int Fnsh ne 288 0.109 5.1 3.15 907 2.02 580 se 32 0.109 5.1 3.15 101 2.02 64 se 173 0.109 5.1 3.15 546 2.02 349 sw 69 0.109 5.1 3.15 218 2.02 139 sw 272 0.109 5.1 3.15 857 2.02 548 nw 366 0.109 5.1 3.15 1153 2.02 737 all 1200 0.109 5.1 3.15 3782 2.02 2419 Partitions Fnn Wall, 1/2"Gyp Bd Ext,R-11 Cav Ins, 1/2"Gyp Bd Int Fnsh,2"A", 16" 238 0.101 11.0 2.94 699 1.46 347 OC Stud Windows Impact,Clear Low-e: Impact,Clear Low-e;NFRC rated(SHGC=0.18); ne 5 0.450 0 13.1 61 17.7 83 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(1.17 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.24); ne 16 0.580 0 16.8 262 22.6 353 50%blinds 45°,medium;50%outdoor insect screen;foreground=green sw 31 0.580 0 16.8 525 21.8 681 grass(0.23); 1 ft overhang(5.2 ft window ht, 1 ft sep.);6.8 ft head ht nw 47 0.580 0 16.8 787 22.6 1060 all 94 0.580 0 16.8 1574 22.4 2094 Impact,Clear Lowe: Impact,Clear Low-e;NFRC rated(SHGC=0.16); se 8 0.490 0 14.2 107 14.2 107 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(1.25 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Low-e;NFRC rated(SHGC=0.16); se 8 0.490 0 14.2 107 11.1 83 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23);6.8 ft overhang(1.25 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.22); se 13 0.620 0 18.0 225 21.1 264 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(4.17 ft window ht, 1 ft sep.);6.8 ft head ht wrightsoft"' 2021-Nov-1213:03:40 --k=de-•,.ea«a-a. ,P=. Right-Sute®Universal 202121.0.10RSU29066 Pagel ACCA ightsoft HVAC\6901 Fort Walton Ave PSL Prop.n p Calc=MJ8 Front Door faces: N Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.22); se 31 0.620 0 18.0 557 21.4 663 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(5.17 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Low-e: Impact,Clear Low-e;NFRC rated(SHGC=0.24); sw 7 0.580 0 16.8 115 21.1 145 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23); 1 ft overhang(3.17 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.24); nw 22 0.580 0 16.8 377 22.6 507 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23);7 ft overhang(5.17 ft window ht, 1 ft sep.);6.8 ft head ht Impact,Clear Lowe: Impact,Clear Lowe;NFRC rated(SHGC=0.21); nw 48 0.650 0 18.8 905 22.0 1058 50%blinds 45°,medium;50%outdoor insect screen;foreground=green grass(0.23);7 ft overhang(8 ft window ht, 1 ft sep.);6.8 ft head ht Doors Fbrgls Door se 40 0.127 7.0 3.69 148 2.37 95 Ceilings Attic,Metal Roof,R-30 Roof Ins, 1/2"Gyp Bd Int Fnsh 50 0.034 30.0 0.99 50 1.80 90 1830 0.034 30.0 0.99 1814 0.61 1113 all 1880 0.034 30.0 0.99 1863 0.64 1203 Floors On Grade Depth,Tile Flr Fnsh 197 0.989 0 28.7 5650 0 0 wrightsoft- 2021-Nov-12 13:03:40 --1-de-•,.e a«a-a. ,P=. Right-Site®Urrversal 2021 21.0.10 RSU29066 Page 2 ACCA ightsoft HVAC\6901 Fort Walton Ave PSL Prop.rup Calc=MJ8 Front Door faces: N Pro S Job: 1525 +� wrightsoft° Project Date: 6/9/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Talbot Residence,NisAirAir Conditioning 6901 Fort Walton Ave,Fort Pierce,FL 34951 Notes: Design Information Weather: St Lucie Co Intl,FL,US Winter Design Conditions Summer Design Conditions Outside db 41 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 29 °F Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 19616 Btuh Structure 16206 Btuh Ducts 6650 Btuh Ducts 8364 Btuh Central vent(94 cfm) 2992 Btuh Central vent(94 cfm) 1589 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 29258 Btuh Use manufacturer's data n Rate/swin multiplier 0.95 Infiltration Equipmen�sensible load 24955 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3199 Btuh Ducts 2244 Btuh Central vent(94 cfm) 3628 Btuh Heating Cooling Outside air Area(ft�) 1880 1880 Equipment latent load 9072 Btuh Volume(ft3) 17073 17073 Air changes/hour 0.38 0.20 Equipment Total Load(Sen+Lat) 34027 Btuh Equiv.AVF(cfm) 108 57 Req.total capacity at 0.70 SHR 3.0 ton Heating Equipment Summary Cooling Equipment Summary Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1-041-230A** AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259425 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 8.2 kW Sensible cooling 26950 Btuh Heating output 28002 Btuh Latent cooling 11550 Btuh Temperature rise 20 °F Total cooling 38500 Btuh Actual airflow 1283 cfm Actual airflow 1283 cfrn Air flow factor 0.049 cfm/Btuh Air flow factor 0.052 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.74 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft- 2021-Nov-1213:03:40 ^M�oksI°�k,�„.I"---,1.o,or,, Right-Sute®Urrversal202121.0.10RSU29066 Pagel ACCA ightsoft HVAC\6901 Fort Walton Ave PSL Prop.rup Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1525 House Date: 6/9/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name House Bed 2 2 E)posed wal l 197.0 It 28.5 it 3 Room height 9.1 ft 8.0 it heat/000l 4 Room dimensions 1.0 x 164.0 it 5 Room area 1879.8 fF 164.0 fF Ty Consh'ucton U-value Or HTM Area (ft) Load Area (ft) Load number (Btuh/ft2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 308 288 907 580 112 96 304 194 T-jImpact,Clear Lowe 0.450 ne 13.05 17.69 5 0 61 83 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 16 0 262 353 16 0 262 353 W Blk Wall,Stucco Ext 0.109 se 3.15 2.02 32 32 101 64 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 272 173 546 349 0 0 0 0 Impaa Clear Low-e 0.490 se 14.21 14.22 8 4 107 107 0 0 0 0 G Impaa Clear Low-e 0.490 se 14.21 11.08 8 8 107 83 0 0 0 0 G Impaa Clear Low-e 0.620 se 17.98 21.13 13 2 225 264 0 0 0 0 Impact,ClearLow-e 0.620 se 17.98 21.39 31 4 557 663 0 0 0 0 D Fbrgls Door 0.127 se 3.69 2.37 40 40 148 95 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 76 69 218 139 0 0 0 0 Impact,Clear Lowe 0.580 sw 16.82 21.08 7 1 115 145 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 303 272 857 548 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.82 31 4 525 681 0 0 0 0 W Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 483 366 1153 737 0 0 0 0 Impact,ClearLow-e 0.580 nw 16.82 22.64 22 0 377 507 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 47 0 787 1060 0 0 0 0 Impact,Clear Lowe 0,650 nw 18.85 22,04 48 0 905 1058 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.46 238 238 699 347 116 116 341 169 C Attic,Metal Roof,R 0.034 0.99 1.80 50 50 50 90 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 0.61 1830 1830 1814 1113 164 164 163 100 F On Grade Depth,Tile 0.989 28.68 0.00 1880 197 5650 0 164 29 817 0 6 c)AED excursion 675 -59 Envelope loss/gain 16170 9743 1887 757 12 a) Infiltration 3446 963 262 73 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 5 1150 0 0 Appliances/other 4350 250 Subtotal(lines 6 to 13) 19616 16206 2149 1081 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 5 3 14 Subtotal 19616 16206 2153 1083 15 Dud loads 34% 52% 66501 8364 34% 52% 730 566 FFTotal room load 26266 24570 2883 1650 Air required(dm) 1283 1283 141 86 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1213:03:40 �� ..i htsoft HVAC\69 Right-Sate@ Uriversal 2021 2l.O.10 RSU29066 Page 1 g 01FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1525 House Date: 6/9/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Bath Linen 2 E)posed wal I 5.5 ft O ft 3 Room height 8.0 it heat/000l 8.0 it heat/000l 4 Room dimensions 9.0 x 5.5 it 2.5 x 2.5 it 5 Room area 49.5 ft' 6.3 ft Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Bilk Wall,Stucco Ext 0.109 ne 3.15 2.02 44 39 124 79 0 0 0 0 T-jImpact,Clear Lowe 0.450 ne 13.05 17.69 5 0 61 83 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 W Bilk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 11 BilkWall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 2.37 0 0 0 0 0 0 0 0 Bilk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.580 sw 16.82 21.08 0 0 0 0 0 0 0 0 Bilk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.82 0 0 0 0 0 0 0 0 WI - Bilk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 I; CCI Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0,650 nw 18.85 22,04 0 0 0 0 0 0 0 0 P Frm Wall,IQ"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 0.61 50 50 49 30 61 6 6 4 F On Grade Depth,Tile 0.989 28.68 0.00 50 6 158 0 6 0 0 0 6 c)AED excursion -12 0 Envelope loss/gain 392 180 6 4 12 a) Infiltration 103 29 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 494 209 6 4 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 10 6 -6 -4 14 Subtotal 504 214 0 0 15 Dud loads 34% 52%1 171 112 34% 52%1 0 0 Total room load 675 326 0 0 Air required(dm) 33 17 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1213:03:40 ACCP. .. htsoft HVAC\69 Right-Sute®Urrversal 2021 21.0.10 RSU29066 Page 2 i g 01FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1525 House Date: 6/9/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Hall Bed 3 2 E)posed wal I O ft 27.5 ft 3 Room height 8.0 It heat/000l 8.0 It heat/cool 4 Room dimensions 3.5 x 8.0 It 1.0 x 172.5 ft 5 Room area 28.0 ft' 172.5 fF Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 120 120 378 242 T-jImpact,Clear Lowe 0.450 ne 13.05 17.69 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 2.37 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.580 sw 16.82 21.08 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.82 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 100 84 266 170 Impact,ClearLow-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 16 0 262 353 Impaa Clear Low-e 0,650 nw 18.85 22,04 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 0.61 28 28 28 17 173 173 171 105 F On Grade Depth,Tile 0.989 28.68 0.00 28 0 0 0 173 28 789 0 6 c)AED excursion -1 59 Envelope loss/gain 28 16 1866 929 12 a) Infiltration 0 0 514 144 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 250 Subtotal(lines 6 to 13) 28 16 2380 1323 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution -28 -16 9 5 14 Subtotal 0 0 2389 1328 15 Dud loads 34% 52% 01 0 34% 52% 810 694 FFTotal room load 0 0 3199 2023 Airrequired(dm) 0 0 156 106 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1213:03:40 �� ..i htsoft HVAC\69 Right-Sate@ Uriversal 2021 2l.O.10 RSU29066 Page 3 g 01FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1525 House Date: 6/9/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Laundry Kitchen 2 E)posed wal I 11.5 ft 0 ft 3 Room height 8.0 ft heat/000l 10.0 ft heat/000l 4 Room dimensions 7.0 x 6.5 ft 1.0 x 205.0 ft 5 Room area 45.5 ft2 205.0 fF Ty Conshvcton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.450 ne 13.05 17.69 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 2.37 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.580 sw 16.82 21.08 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 sw 16.82 21.82 0 0 0 0 0 0 0 0 WI - Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 I; CCI Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0,650 nw 18.85 22,04 0 0 0 0 0 0 0 0 P Frm Wall,12"Gyp B 0.101 2.94 1.46 92 92 270 134 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 0.61 46 46 45 28 205 205 203 125 F On Grade Depth,Tile 0.989 28.68 0.00 46 12 330 0 205 0 0 0 6 c)AED excursion -36 -123 Envelope loss/gain 645 126 203 2 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 2 460 Appliances/other 500 1700 Subtotal(lines 6 to 13) 645 626 203 2162 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 2 1 14 8 14 Subtotal 647 627 217 2170 15 Dud loads 34% 52% 219 328 34% 52% 74 1135 qT.0, tal room load 866 955 291 3305 quired(dm) 42 50 14 173 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1213:03:40 �� ..i htsoft HVAC\69 Right-Sate@ Uriversal 2021 2l.O.10 RSU29066 Page 4 g 01FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1525 House Date: 6/9/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Family Room Dining/Foyer 2 E)posed wal l 22.5 it 23.0 it 3 Room height 10.0 it heat/000l 10.0 it heat/000l 4 Room dimensions 15.5 x 12.5 it 20.0 x 12.0 it 5 Room area 193.8 fF 240.0 fF Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.450 ne 13.05 17.69 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 200 114 359 229 Impaa Clear Low-e 0.490 se 14.21 14.22 0 0 0 0 8 4 107 107 G Impaa Clear Low-e 0.490 se 14.21 11.08 0 0 0 0 8 8 107 83 G Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.620 se 17.98 21.39 0 0 0 0 31 4 557 663 D Fbrgls Door 0.127 se 3.69 2.37 0 0 0 0 40 40 148 95 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.580 sw 16.82 21.08 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 70 70 221 141 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.82 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 155 124 390 250 0 0 0 0 Impact,ClearLow-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 31 0 525 706 0 0 0 0 Impaa Clear Low-e 0.650 nw 18.85 22.04 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 30 30 88 44 C Attic,Metal Roof,R 0.034 0.99 1.80 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 0.61 194 194 192 118 240 240 238 146 F On Grade Depth,Tile 0.989 28.68 0.00 194 23 645 0 240 23 660 0 6 c)AED excursion 168 97 Envelope loss/gain 1973 1383 2263 1464 12 a) Infiltration 526 147 467 131 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 250 0 Subtotal(lines 6 to 13) 2499 1780 2731 1595 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 3 3 14 Subtotal 2499 1780 2733 1598 15 Dud loads 34% 52% 8471 930 34% 52% 927 835 FFTotal room load 3346 2710 3660 2433 Air required(dm) 163 142 179 127 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1213:03:40 �� ..i htsoft HVAC\69 Right-Sate@ Uriversal 2021 2l.O.10 RSU29066 Page 5 g 01FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1525 House Date: 6/9/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name WIC Master Bath 2 E)posed wal l 8.5 ft 13.0 it 3 Room height 8.0 it heat/000l 8.0 it heat/000l 4 Room dimensions 6.0 x 8.5 it 1.0 x 120.5 it 5 Room area 51.0 ft2 120.5 ft Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 32 32 101 64 T-jImpact,Clear Lowe 0.450 ne 13.05 17.69 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 72 60 187 120 Impaa Clear Low-e 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 13 2 225 264 Impact,ClearLow-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 2.37 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.580 sw 16.82 21.08 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 68 68 214 137 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.82 0 0 0 0 0 0 0 0 WI - Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 I; CCI Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0,650 nw 18.85 22,04 0 0 0 0 0 0 0 0 P Frm Wall,1/2"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 0.61 51 51 51 31 121 121 119 73 F On Grade Depth,Tile 0.989 28.68 0.00 51 9 244 0 121 13 373 0 6 c)AED excursion -11 55 Envelope loss/gain 509 157 1005 577 12 a) Infiltration 159 44 243 68 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 668 201 1248 645 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 61 22 33 15 14 Subtotal 729 223 1282 660 15 Dud loads 34% 52% 2471 116 34% 52% 434 345 FFTotal room load 976 339 1716 1005 Airrequired(dm) 48 18 84 53 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigFrtsoft° 2021-Nov-1213:03:40 �� ..i htsoft HVAC\69 Right-Suite@ Universal 2021 21.0.10 RSU29066 Page 6 g 01FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1525 House Date: 6/9/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Living Room Pan 2 E)posed wal I 11.5 It 0 ft 3 Room height 10.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 1.0 x 288.0 It 2.5 x 2.5 It 5 Room area 288.0 fF 6.3 ft Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.450 ne 13.05 17.69 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 G Impact,Clear Lowe 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 G Impact,Clear Lowe 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 2.37 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.08 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.82 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 115 67 211 135 0 0 0 0 Impact,ClearLow-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impact,Clear Lowe 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0,650 nw 18.85 22,04 48 0 905 10511 0 0 0 0 P Frm Wall,12"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 0 0 0 0 0 0 0 0 C Aftic,Metal Roof,R 0.034 0.99 0.61 288 288 285 175 6 6 6 4 F On Grade Depth,Tile 0.989 28.68 0.00 288 12 330 0 6 0 0 0 6 c)AED excursion 249 0 Envelope loss/gain 1731 1618 6 4 12 a) Infiltration 269 75 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 3 690 0 0 Appliances/other 900 0 Subtotal(lines 6 to 13) 2000 3283 6 4 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 2 4 -6 -4 14 Subtotal 2002 3286 0 0 15 Dud loads 34% 52%1 6791 1718 34% 46%1 0 0 Total room load 2681 5005 0 0 Air required(dm) 131 261 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigFrtsoft° 2021-Nov-1213:03:40 �� ..i htsoft HVAC\69 Right-Suite@ Universal 2021 21.0.10 RSU29066 Page 7 g 01FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1525 House Date: 6/9/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Master Bed Lin 2 E)q)osed wal l 32.0 it 2.0 ft 3 Room height 8.7 it heat/000l 8.0 it heat/000l 4 Room dimensions 1.0 x 259.5 it 4.0 x 2.0 it 5 Room area 259.5 fF 8.0 ft2 Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Bilk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.450 ne 13.05 17.69 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 W Bilk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 11 BilkWall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 2.37 0 0 0 0 0 0 0 0 Bilk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 16 16 50 32 Impact,Clear Lowe 0.580 sw 16.82 21.08 0 0 0 0 0 0 0 0 Bilk Wall,Stucco Ext 0.109 sw 3.15 2.02 165 134 423 270 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.82 31 4 525 681 0 0 0 0 W Bilk Wall,Stucco Ext 0.109 nw 3.15 2.02 113 91 286 183 0 0 0 0 Impact,ClearLow-e 0.580 nw 16.82 22.64 22 0 377 507 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0,650 nw 18.85 22,04 0 0 0 0 0 0 0 0 P Frm Wall,IQ"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 0 0 0 0 8 8 8 14 C Attic,Metal Roof,R 0.034 0.99 0.61 260 260 257 158 0 0 0 0 F On Grade Depth,Tile 0.989 28.68 0.00 260 32 918 0 8 2 57 0 6 c)AED excursion 267 -3 Envelope loss/gain 2785 2065 116 44 12 a) Infiltration 651 182 37 10 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 500 0 Subtotal(lines 6 to 13) 3435 2747 153 54 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 6 10 -153 -54 14 Subtotal 3441 2758 0 0 15 Dud loads 34% 52% 11671 1442 34% 29% 0 0 FFTotal room load 4608 4199 0 0 Airrequired(dm) 225 219 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1213:03:40 ACCP. .. htsoft HVAC\69 Right-Sute®Urrversal 2021 21.0.10 RSU29066 Page 8 i g 01FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft°° Right-J®Worksheet Job: 1525 House Date: 6/9/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name WtrClst MHall 2 E)posed wal l 11.5 it 0 It 3 Room height 8.0 it heat/000l 8.0 it heat/000l 4 Room dimensions 4.0 x 7.5 it 3.0 x 4.0 it 5 Room area 30.0 it' 12.0 ft2 Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall,Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact,Clear Lowe 0.450 ne 13.05 17.69 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 ne 16.82 22.64 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 se 3.15 2.02 32 32 101 64 0 0 0 0 11 Blk Wall,Stucco Ext 0.109 se 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.490 se 14.21 14.22 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.490 se 14.21 11.08 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.620 se 17.98 21.13 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.620 se 17.98 21.39 0 0 0 0 0 0 0 0 D Fbrgls Door 0.127 se 3.69 2.37 0 0 0 0 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 60 53 167 107 0 0 0 0 Impact,Clear Lowe 0.580 sw 16.82 21.08 7 1 115 145 0 0 0 0 Blk Wall,Stucco Ext 0.109 sw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 sw 16.82 21.82 0 0 0 0 0 0 0 0 W Blk Wall,Stucco Ext 0.109 nw 3.15 2.02 0 0 0 0 0 0 0 0 Impact,ClearLow-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0,650 nw 18.85 22,04 0 0 0 0 0 0 0 0 P Frm Wall,12"Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic,Metal Roof,R 0.034 0.99 1.80 30 30 30 54 12 12 12 22 C Attic,Metal Roof,R 0.034 0.99 0.61 0 0 0 0 0 0 0 0 F On Grade Depth,Tile 0.989 28.68 0.00 30 12 330 0 12 0 0 0 6 c)AED excursion 26 -1 Envelope loss/gain 743 397 12 20 12 a) Infiltration 215 60 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 958 457 12 20 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 61 22 -12 -20 14 Subtotal 1020 479 0 0 15 Dud loads 34% 29%1 3461 141 34% 29%1 0 0 Total room load 1365 620 0 0 Air required(dm) 67 32 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Nov-1213:03:40 �� ..i htsoft HVAC\69 Right-Sate@ Uriversal 2021 2l.O.10 RSU29066 Page 9 g 01FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N Duct System Summary Job: 1525 +� wrightsoft D S S Date: 6/9/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.mm Project Information For: Talbot Residence,NisAirAir Conditioning 6901 Fort Walton Ave,Fort Pierce,FL 34951 Heating Cooling External static pressure 0.70 in H2O 0.70 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0.70 in H2O 0.70 in H2O Supply/return available pressure 0.498/0.202 in H2O 0.498/0.202 in H2O Lowest friction rate 0.263 in/100ft 0.263 in/100ft Actual airflow 1283 cfm 1283 cfm Total effective length(TEL) 266 ft SupplyDetail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FIR (in) (in) Matl Ln(ft) Ln(ft) Trunk Bat, h 675 40 20 0.400 4.0 Ox0 VIFx 24.4 100.0 st1 Bed 2 h 2883 169 103 0.393 7.0 Ox 0 VI Fx 26.7 100.0 st1 Bed 3 h 2023 188 127 0 0 Ox 0 VI Fx 0 0 Dining/Foyer h 1830 107 76 0.349 6.0 Ox0 VIFx 32.5 110.0 st4 Dining/Foyer-A h 1830 107 76 0.457 6.0 Ox0 VIFx 14.1 95.0 st2 Family Room h 3346 196 170 0.368 7.0 Ox 0 VI Fx 35.2 100.0 st1 Kitchen-A c 3305 17 207 0.436 7.0 Ox0 VI Fx 19.3 95.0 st2 Laundry c 955 51 60 0.454 5.0 Ox0 VI Fx 14.7 95.0 st2 Living Room c 2502 79 157 0.264 7.0 Ox 0 VI Fx 53.3 135.0 st5 Living Room-A c 2502 79 157 0.263 7.0 Ox 0 VI Fx 54.0 135.0 st5 Master Bath h 1716 101 63 0.328 6.0 Ox 0 VI Fx 36.9 115.0 st4 Master Bed h 2304 135 132 0.264 7.0 Ox 0 VI Fx 53.6 135.0 st5 Master Bed-A h 2304 135 132 0.264 7.0 Ox 0 VI Fx 53.8 135.0 st5 WIC h 976 57 21 0.326 5.0 Ox 0 VI Fx 37.8 115.0 st4 Wdr Clst h 1365 80 39 0.316 5.0 Ox 0 VI Fx 42.6 115.0 st4 SupplyDetail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st1 PeakAVF 405 294 0.368 742 10.0 0 x 0 VinlFlx st4 PeakAVF 773 776 0.263 726 14.0 0 x 0 VinlFlx st2 st5 PeakAVF 427 577 0.263 735 12.0 0 x 0 VinlFlx st4 st2 PeakAVF 948 1119 0.263 802 16.0 0 x 0 VinlFlx wrightsoft® 2021-Nov-1213:03:41 AM,,-I „",H,11aw.,1-P-1 Right-Sute®Uriversal2021 21.0.10 RSU29066 Page 1 ACCP. ...ightsoft HVAC\6901 Fort Walton Ave PSL Prop.n p Calc=MJ8 Front Door faces: N TableReturn Branch Detail Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening(in) Matl Trunk rb7 Ox0 196 170 75.8 0.266 444 9.0 Ox 0 VIFx rt1 rb2 Ox0 188 127 76.7 0.263 425 9.0 Ox 0 VIFx rt1 rb3 Ox0 169 103 66.9 0.302 383 9.0 Ox 0 VIFx rt1 rb1 Ox0 660 855 38.1 0.530 484 18.0 Ox 0 VIFx rt1 rb4 Ox0 327 284 0 0 0 0 Ox 0 VIFx TableReturn Trunk Detail Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk rt1 PeakAVF 1213 1256 0.263 710 1&0 0 x 0 VInIFIX Bolditalic values have been manually overridden wrightsOft® 2021-Nov-1213:03:41 A AM.=—I1 ,I,.«awa.C—p,. Right-Sute®Uriversal 2021 21.0.10 RSU29066 Page 2 ACCP. ...ightsoft HVAC\6901 Fort Walton Ave PSL Prop.n p Calc=MJ8 Front Door faces: N Manual S Compliance Report Job: 1525 +� wrightsoft° p Date: 6/9/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project Information For: Talbot Residence,NisAirAir Conditioning 6901 Fort Walton Ave,Fort Pierce,FL 34951 Cooling Equipment Design Conditions Outdoor design DB: 90.4°F Sensible gain: 26159 Btuh Entering coil DB: 77.4°F Outdoor design WB: 77.4°F Latent gain: 9072 Btuh Entering coil WB: 64.5°F Indoor design DB: 75.0°F Total gain: 35231 Btuh Indoor RH: 50% Estimated airflow: 1283 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Lennox Model: ML14XC1-041-230A**+CBA27UHE-048-230*++TDR Actual airflow: 1283 cfm Sensible capacity: 26950 Btuh 103%of load Latent capacity: 11550 Btuh 127%of load Total capacity: 38500 Btuh 109%of load SHR: 70% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 29258 Btuh Entering coil DB: 67.4°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elecstrip Manufacturer: Model: Actual airflow: 1283 cfm Output capacity: 8.2 kW 96%of load Temp.rise: 50 °F Meets all requirements ofACCA Manual S. wrightsoft, 2021-Nov-12 13:03:41 AM,,—I „l,,,�.,nawa,—,�, Right-Sute®Urrversa12021 21.0.10 RSU29066 Page 1 ACCk ightsoft HVAC\6901 Fort Walton Ave PSL Prop.rup Calc=MJ8 Front Door faces: N