HomeMy WebLinkAboutProject Information1 , DEL -AIR Manual S Compliance Report°b:°t"96l°°k5waterst°•.. Date: HEATING • AIO CONnmONOIO Entire House By: DCs DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Project• • For: ADAMS HOMES 5338 San Bendetto Place, Fort Pierce, FL 34951 Cooling Equipment Design Conditions Outdoor design DB: 90.4°F Sensible gain: 25531 Btuh Outdoor design WB: 77.4°F Latent gain: 4767 Btuh Indoor design DB: 75.0°F Total gain: 30297 Btuh Indoor RH: 50% Estimated airflow: 1167 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: 25HBC537A0030+FX4DNB037L Actual airflow: 1167 cfm Sensible capacity: 28355 Btuh 111% of load Latent capacity: 5078 Btuh 107% of load Total capacity: 33433 Btuh 110% of load SHR: 85% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 27195 Btuh Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: 25HBC537A0030+FX4DNB037L Actual airflow: 1167 cfm Output capacity: 31730 Btuh 117% of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1167 cfm Output capacity: 7.6 kW 95% of load Temp. rise: 20 OF Meets all requirements of ACCA Manual S. Entering coil DB: 76.8°F Entering coil WB: 63.4°F Entering coil DB: 69.3°F Capacity balance: 35 IF Economic balance: -99 IF WYightsaft- 2020-Mar-10 09:20:16 ACC r,•�• m a- �mwM Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1 ttWaterstone182OBGL.rup Calc = MJ8 Front Door faces: NW DEL -AIR Component Constructions Job: Lot 119 Block 5 Watersto... Date: HEATING-AINCONOmONINC Entire House By: DCS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM NWG•ject Information For: ADAMS HOMES 5338 San Bendetto Place, Fort Pierce, FL 34951 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (OF) 70 75 Elevation: 26 ft Design TD (OF) 29 15 Latitude: 280N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 2.4 56.9 Dry bulb (OF) 41 90 Infiltration: Daily range (OF) - 15 (L ) Method Simplified Wet bulb (OF) - Wind speed (mph) 15.0 77 7.5 Construction quality Fireplaces Average 0 Construction descriptions Or Area lJ-value Insul R Htg HTM Loss Clg HTM Gain ft� BtuhM T ft'-°F/Btuh BtuhM Btu BtuhM Btuh Walls Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh Partitions 12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud ne 534 0.143 4.1 4.15 2215 2.59 1382 se 317 0.143 4.1 4.15 1314 2.59 820 sw 611 0.143 4.1 4.15 2534 2.59 1581 nw 126 0.143 4.1 4.15 524 2.59 327 all 1588 0.143 4.1 4.15 6586 2.59 4110 270 0.091 13.0 2.64 713 1.31 354 Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, ne 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (3.2 ft window ht, 0.83 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, ne 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft Be overhang (5.3 ft window ht, 0.83 ft sep.); 6.67 ft head ht sw all 1 OC-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, se 1/8" thk; NFRC rated (SHGC=0.70); 11.5 ft overhang (6.7 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, se 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 11.5 ft overhang (5.3 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, sw 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, nw 1/8" thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.33 ft overhang (5.3 ft window ht, 3.9 ft sep.); 6.67 ft head ht 7 0.330 0 9.57 66 17.7 123 49 0.330 0 9.57 469 17.7 868 33 0.330 0 9.57 313 15.6 511 33 0.330 0 9.57 313 15.6 511 114 0.330 0 9.57 1095 16.5 1889 18 0.550 0 16.0 285 16.2 289 33 0.330 0 9.57 313 8.52 279 16 0.330 0 9.57 156 15.6 254 16 0.330 0 9.57 156 16.6 271 � � wrightsoft® 2020-Mar-10 09:20:16 �11 Right -Suite@ Universal 2019 19.0.12 RSU23828 Page 1 ...terstonel820BGL\Lotll9Blk5Waterstonel820BGL.rup Calc = MJ8 Front Door faces: NW 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, nw 16 0.330 0 9.57 156 16.6 271 1/8" thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.33 ft overhang (5.3 ft window ht, 5.3 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, nw 7 0.330 0 9.57 67 26.3 184 1/8" thk; NFRC rated (SHGC=0.31); 9 ft overhang (1.4 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, nw 14 0.330 0 9.57 130 22.1 300 1/8" thk; NFRC rated (SHGC=0.31); 50% drapes, medium; 9 ft overhang (6.8 ft window ht, 2 ft sep.); 6.67 ft head ht Doors 11JO: Door, mtl fbrgl type nw 20 0.600 6.3 17.4 355 17.6 359 Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" 1835 0.032 30.0 0.93 1703 1.69 3100 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 185 0.989 0 28.7 5306 0 0 wrightsOft- 2020-Mar-10 09:20:16 14C3:�% n .,•t•, Chu., w ., Right -Suite® Universal 2019 19.0.12 RSU23828 Page 2 ... terstone1820BGL\Lot119Blk5Waterstone1820BGL.rup Calc = MJ8 Front Door faces: NW `WProject Summary Job: Lot 119 Block Watersto DEL -AIR ... Date: HEAnNO•AIR CONDITIONING Entire House By: DCS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM For: ADAMS HOMES 5338 San Bendetto Place, Fort Pierce, FL 34951 Notes: JA 8-18-15 Change to 3.0 ton 2116/16 S. Finch L. S. 3-10-20 VWK Design Information Weather: Winter Design Conditions Outside db 41 OF Inside db 70 OF Design TD 29 OF Heating Summary Structure 20791 Btuh Ducts 6404 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 27195 Btuh Infiltration Method Construction quality Fireplaces Area (ft2 Volume ()ft3) Air changes/hour Equiv. AVF (cfm) St Lucie Co Intl, FL, US Simplified Average 0 Heating Cooling 1820 1820 18350 18350 0.38 0.20 116 61 Heating Equipment Summary Make Carrier Trade CARRIER Model 25H BC537AO030 AH R I ref 10487322 Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat Capacity balance point = 35 OF Backup: 8.5 HSPF 34600 Btuh @ 470F 27 OF 1167 cfm 0.043 cfm/Btuh 0.30 in H2O Input = 8 kW, Output = 25920 Btuh, 100 AFUE Summer Design Conditions Outside db 90 OF Inside db 75 OF Design TD 15 OF Daily range . L Relative humidity 50 % Moisture difference 57 ar/lb Sensible Cooling Equipment Load Sizing Structure 18043 Btuh Ducts 7488 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Equipment sensible load 25531 Btuh Latent Cooling Equipment Load Sizing Structure 3364 Btuh Ducts 1403 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 4767 Btuh Equipment Total Load (Sen+Lat) 30297 Btuh Req. total capacity at 0.75 SHR 2.8 ton Cooling Equipment Summary Make Carrier Trade CARRIER Cond 25HBC537AO030 Coil FX4DNB037L AHRI ref 10487322 Efficiency 12.5 EER, 15.5 SEER Sensible cooling 26250 Btuh Latent cooling 8750 Btuh Total cooling 35000 Btuh Actual air flow 1167 cfm Air flow factor 0.046 cfm/Btuh Static pressure 0.30 in H2O Load sensible heat ratio 0.84 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsof - 2020-Mar-10 09:20:16 A .. .­ Right -Suite® Universal 2019 19.0.12 RSU23828 Page 1 ... tersfone1820BGL\Lot119BIk5Waterstone1820BGL.rup Calc = MJ8 Front Door faces: NW ! DEL -AIR Right-M Worksheet Job: Lot 119 Block Waterstone... rumrxo•euncosomnraeo Entire House Date: DEL AIR HTG, A/C & REFRIG. INC By: DCS 531 CODISCO WAY, SANFORD, FL32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Entire House 185.0 ft 10.0 ft d 1835.0 ft2 BDRM 2 36.0 ft 10.0 It heat/cool 13.0 x 13.0 It 169.0 ft2 Ty Construction number U-value (Btuh/ftz-°F) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 �B*Wall, D P A.-- C F., stucco ext " 2A-2ov _2A-2ov-._,_ .__,__:_ Blk wall, stucco ext 10C-v 2A-2ov -2A 2ov Blk vial! ' all, stucco ext 2A 2ov 2A.2ov_-___..---_ �- Blk wall, stucco ext 2A-2ov 2A-2ov 26-2fv 2B-2fv 11J0.. -__ 12C Osw. __ . _ . -•-- 168 30ad 22Atpl__',_ .__ _ 4 0 143 0.330 ___-_ 0.330 0.143 0.550 0.330 _ 0.330 _. 0 143 0.330 _ _._0.330 0.143 0.330 0.330 0.330 0.330 0.600, .... _ _0.091 0.032 _.___0.989_,_:._-28.680.00 r 6 ne _ne. se se se se , ' sw sw _ sw nw nw nw nw nw nw _ . -- 4.15 9.57 _-_9.57. 4.15 15.95 9.57 _ 9.57. 4.15 9.57 ., _9.57, 4.15 9.57 9.57 9.57 9.57 . _ 17.40 . • .. 2.64. 0.93 2.59 1,7.70 17.70 2.59 16.20 15.62 _8.52 2.59 15.63 -:._ 15.57 2.59 16.61 16.61 26.32 22.09 17.58 __ .1.31 1.69 ----- ' 590 7 49 400 18 33 __ 33 v 660 33 ,: 16 200 16 16 7 14 - _20 270 1835 1835, - _-534 0 '0 317 18 8 _ 33 611 8 °--... 4 126 0 0 0 0 .__ 20 . __.-.. _ 270 1835 __..JBS - 2215 66 469 1314 285 313 _ 313 _ 2534 313 ___-.156 524 156 156 67 130 355 . ._ _713 1703 ------- ,5306._.____0_._. - - 1982 123 _ _-868 820 289 511 279 _ 1581 511 .._254 327 271 271 184 300 359 _ _ 354 3100 - - 100 0 _ 0 130 0 16 0 0 1339 0 -- .- _-0 0 0 0 0 0 0 _ _0 169 .169__ 166 0 0 114 0 4 _ _ __ _ 0 130 0 --_--_---_0 0 0 0 0 0 0 .- . - -- -0 169 a__36 --- -- 415 0 0 471 0 156 _ _ 0 5 .0 _0 0 0 0 0 0 0 - 0 157 " - 269 0 0 V - 294 0 255 336 0 ---... 0 0 0 0 0 0 _ 0 -_ . , __ 0 286 6 c) AED excursion 172 30 Envelope loss/gain 17087 11958 2771 1461 12 a) Infiltration b) Room ventilation 3704 0 1035 0 721 0 201 0 13 Internal gains: Occupants @ 230 Appliances/other 5 1150 3900 0 0 300 Subtotal (lines 6 to 13) 20791 18043 3492 1962 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 31 % 41 % 0 0 0 20791 6404 0 0 0 18043 7488 31 % 41 % 0 0 0 3492 1075 0 0 0 1962 814 Total room load Air required (cfm) 27195 1167 25531 11671 4567 196 2776 127 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed ~-*- wrYg!-rtt3-.3c" - A. Right -Suite® Universal 2019 19.0.12 RSU23828 2020-Mar-10 09:20:16 AeC ...terstone1820BGL\Lot119Blk5Waterstone1820BGL.rup Calc = MJ8 Front Door faces: NW Page 1 QDEL--AIR Right-M Worksheet Job: Lot 119 Block Waterstone... r¢amic•ameonamoMO Entire House Date: DEL AIR HTG, A/C & REFRIG. INC By: DCS 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM 1 Room name BATH 2 BDRM 3 2 3 4 5 Exposed wall Room height Room dimensions Room area 6.0 ft 10.0 ft heat/cool 13.0 x 6.0 It 78.0 ftz 13.0 It 10.0 It heat/cool 13.0 x 13.0 ft 169.0 ftz Ty Construction number U-value (Btuh/ftz-OF) Or HTM (Btuh/ftz) Area (ftz) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 - G Blk wall, stucco exf 2A 2ov 2A--2ov Blk wall, stucco ext 10C-v 2A-2ov 2A 2ov Blk wall, stucco ext 2A 2ov 2A:2ov__�_ _ _-. _-- Blk wall, stucco ext 2A-2ov 2A-2ov 2B-2fv 2B-2fv -11J0 --.__. __-- -- - 12CGOsw . _ _- _ - - 16B-30ad 0143 0.330 0330._ne9.57 - 0.143 0.550 0.330 0.330 0.143 0.330 0:330 0.143 0.330 0.330 0.330 0.330 __.-.0.600 .._ .. _ 0.091 0.032 6e _ ne se se se se_ sw sw .aw_ nw nw nw nw nw _ nw_ - _- - 115 9.67 4.15 15.95 9.57 9.57_0 4.15 9.57 --- 9.57 4.15 9.57 9.57 9.57 9.57 __ 17.40 -- 2,64 0.93 2.59 17.70 N17.70.---__ 2.59 16.20 15.62 2.59 15.0 __. 15.57 2.59 16.61 16.61 26.32 22.09 _,._17.58 1.31.. 1.69 0 0 0 0 0 60 0 - -,_. 0 0 0 0 0 0 0 _ _ __. 0 78 _...__78 o 0 0 0 0 60 0 - 0 0 0 0 0 0 0 _ _ _0 78 ._--.. - 6 ..-- -- ,o 0 0 0. 0 249 0 ____ 0 0 0 0 0 0 -0 -- --. _0 72 _ - _, �172 -- - _.0 0 M - -- 0 0 0 155 0`. _ _. _ -__0 0 0 0 0 0 _._ . q . _ ,.. _ _0 132 ._ . _. 0 ,-- -: 0 0 - - 0 0 0 __0 130 0 _-. _- ...15 0 0 0 0 0 _ ._. -_, ..0 169 - .. '..._ 169 _- -- -0 0 0 0 0 ____ _ 0 114 0 __:_.---_4 0 0 0 0 0 ._0 169 _ 13 _ ..._ B 0 ' --- 0 0 0 _ _ 0 41- -0 .- --. _156. 0 0 0 0 0 __..._..- 0 0.- 157 _-- -- -- 0 0 0 0 0 _ __ 0 - 294 1 0 _ _ 254 0 0 0 0 0 -._ 0 __'____0 286 !--G D P_ _.._. C 6 c) AED excursion -18 56 Envelope loss/gain 493 269 1157 890 12 a) Infiltration b) Room ventilation 120 0 34 0 260 0 73 0 13 Internal gains: Occupants Qa 230 0 0 0 0 Appliances/other 0 300 Subtotal (lines 6 to 13) 613 303 1418 1262 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 31 % 41% 0 0 0 613 189 0 0 0 303 126 31 % 41 % 0 0 0 1418 437 0 0 0 1262 524 Total room load Air required (cfm) 802 34 429 20 1 1854 80 1786 82 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. -� wrigf�tsoft ^ Right -Suite® Universal 2019 19.0.12 RSU23828 2020-Mar-10 09:20:16 .ZUKPage 2 ...terstone1820BGL\Lot119Blk5Waterstone1820BGL.rup Calc = MJ8 Front Door faces: NW RDEL-AIR Right-J® Worksheet xFmxtc • wa coxomoxms Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot 119 Block 5 Waterstone ... Date: By: DCS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area DINING/FOYER 18.0 It 10.0 It heat/cool 1.0 x 276.0 It 276.0 ft2 DEN/BDRM 4 31.0 ft 10.0 It heat/cool 13.0 x 13.0 It 169.0 ftz Ty Construction number U-value (Btuh/ftZ°F) Or HTM (Btuh/ftz) Area (ftz) or perimeter ft () Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 -__-- _ D f?-,.. C Blk wall, stucco,ext 2A-2ov 2A2wallov___---.___ Blk , stucco ext 10C-v 2A-2ov 2A 2ov _ BIk wall stucco ext - 2A2ov 2A 2ov_ ..__. __._. Blk wall, stucco ext 2A-2ov 2A-2ov 2B-2fv 213-2fv 11J0 12C0sw :- - - 166 30ad - 0 143 0.330, 0330-.ne 0.143 0.550 0.330 0.330 6.143 0.336 _� - 0.330 0.143 0.330 0,330 0.330 0.330 0.600 ---0.091 0.032 ne ne- se se se _ se sw "sw _ sw nw nw nw nw nw hw . 4.15 9.57 957 4.15 15.95 9.57 9 57. 4.15 9.57; .. _ _ 9.57. 4.15 9.57 9.57 9.57 9.57 17.40 2.64 0.93 _,.28.68 _ 2.59 . 17.70 .,17.70_ 2.59 16.20 15.62 8.52 2.59 15.68 _-_ 15.57 2.59 16.61 16.61 26.32 22.09 17.58 . _ 1.81.. 1.69 0.00 0 0 0 - - `-"8 0 0 0 -- 110 33 - ---._ ._0 70 0 0 7 14 20 _ _ 70. 276 --276 _ 0 0 _'0 _ _. _ 0 0 0 0 - _� 8 _ ___.... 0 29 0 0 0 0 _ -_ 20 _. ---70 276 .-- _ _18 0 0 _ 0 0 0 _ _ _ 0 _ ,321 313 _.__-_ .__0 120 0 0 67 130 _ - ,. 355 _ __.185 256 515 0 0 _.__ _ _._O._._.O 0 0 _ _ 0 200 511 -_---- __0 75 0 0 184 300 - __.- , 359 __.-_...92 466 .-_,_ __. Q 0 0 0 0 0 130 0 -- _ ______0 130 16 16 0 0 _._.......-0 ._- ._0 169 _..._-.169.,=- _ _ _.. 0 _0 0 0 0 0 130 0 ID 97 0 0 0 0 _._...__. __0 - -----.._0 169 31 . _.207 0 0 _ _ 0 0 0 _ _ _ _ 0 539 0 ____-.... _0, 404 156 156 0 0 _ . __0 _ _. _.0--_0 157 ,_ 889. - - 129 0 0 _ _ 0 0 0 _ _ 0 336 0 ----'_--__0 252 271 271 0 0 0 286 0. 6 c) AED excursion 365 145 Envelope loss/gain 2263 2553 2509 1691 12 a) Infiltration b) Room ventilation 360 0 101 0 621 0 173 0 13 Internal gains: Occupants @ 230 Appliances/other 1 230 0 0 0 300 Subtotal (lines 6 to 13) 2623 2883 3129 2164 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 31 % 41 % 0 0 0 2623 808 0 0 0 2883 1197 31 % 41 % 0 0 0 3129 964 0 0 0 2164 898 Total room load Air required (cfm) 3431 147 4080 186 4093 176 3062 140 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. A -+ wr➢ghtso�R Right -Suite® Universal 2019 19.0.12 RSU23828 2020-Mar-10 09:20:16Page 3 ...terstone1820BGL\Lot119Blk5Waterstone1820BGL.rup Calc = MJ8 Front Door faces: NW PDEL--AIR Right-M Worksheet Job: Lot 119 Block 5 Waterstone ... I MG-AMCONMmorpNG Entire House Date: DEL AIR HTG, A/C & REFRIG. INC By: DCS 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area FAMILY RM 13.0 It 10.0 It heat/cool 13.0 x 22.0 ft 286.0 ftz MSTR BDRM 41.0 It 10.0 ft heat/cool 14.0 x 17.0 It 238.0 ft2 Ty Construction number U-value (Btuh/ftZ°F) Or HTM (Btuh/ftz) Area (ftz) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 y/ - Blk wall, stucco exf 2A 2ov ,. 2A2ov Blk wall, stucco ext 1GC-v 2A-2ov 2A 2ov__ _ Blk wall, _, stucco ext 2A 2ov 2A2ov_-------�,_. Blk wall, stucco ext 2A-2ov 2A-2ov 2B-2fv 2B-2fv' _ _.. 92C-0sw.__ 16B-30ad 22A_tph__' __ .__. ... ................. y..... _. 0.143 0.330 - __0330 0.143 0.550 0.330 0.330 0 143 0.330 _ _0.330_.sw,. 0.143 0.330 0.330 0.330 0.330 0,600 _ ., 0.091 0.032 _ ...0989 .. .,,_ .. .4 rie ne -no . se se se _se_ sw sw, nw nw nw nw nw -nw- ...__ - -.:._ .._. ,, .,.. 4.15 9.57 ___9_57, 4.15 15.95 9.57 9_57 4.15 . 9.57 __9.57 4.15 9.57 9.57 9.57 9.57 17.40 _. ,2.64 0.93 _ 26,68 ..._... .� - 259 17.70 1770 2.59 16.20 15.62 8.52 -2:69 15:63 __.15.57,_. 2.59 16.61 16.61 26,32 22.09 17.58 ..1.31. 1.69 ,. _ 0.00 ..... 0 0 _ _ 0 - 130 18 0 _ _ 0 0 _. _- 0.._-.._.._ 0 0 0 0 0 _ -0 ._ _.....0 286 286 .... _e.., µ' 0 0 79 18 0 _33 6 0 -0 0 0 0 0 0 ._ _- 0 , ..._ _._0 286 .- : 13 _.. .. _.. ..... - 0 0 - 329 285 0 _._ _ _ 313 0 0 -0 0 0 0 0 0 _ .. _... 0 __._____.0.__-.._. 265 .._373 .._..._. - -' p 0 206 289 0 _ 279 0 0 0 0 0 0 0 _ 0 _0._.. 483 , -- ____0 ._._._ _-...._. -170 0 16 • 140 0 16 _ _ , 0 lob 0 0 0 0 0 0 0 _ 0 238 238 .-.. _. 154 0 0 124 0 4 - 0 - 100 0 0 0 0 0 0 _ .-0 .__. __ 0 238 ._ .. _ _41 ._._..... .... - 637 0 513 0 156 0 415 0 0 0 0 0 0 _ .. t] _. -_0 221 1176 _ _ .. _ 398 0 320 0 255 _ _ 0 _ 259 0 0 0 0 0 0 -0 . .__ .__0 4.02 0 _..-.. „ GG _ D_11J0 Ti' ---. _ C F_ _ : ... .. _.. 6 c) AED excursion -145 -554 Envelope loss/gain 1565 1112 3274 1869 12 a) Infiltration b) Room ventilation 260 0 73 0 821 0 229 0 13 Internal gains: Occupants @ 230 Appliances/other 3 690 600 1 230 600 Subtotal (lines 6 to 13) 1826 2475 4095 2929 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 31 % 41 % 0 0 0 1826 562 0 0 0 2475 1027 31 % 41 % 0 0 0 4095 1261 0 0 0 2929 1215 Total room load Air required (cfm) 2388 102 3502 160 5356 230 4144 189 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. -+'�.F- wr➢gF�tsoft^ �A 2020-Mar-10 09:20:16 Right -Suite® Universal 2019 19.0.12 RSU23828 Page 4 ...terstone1820BGL\Lot119BIk5Waterstone18206GL.rup Cale = MJ8 Front Door faces: NW ;DEL --AIR Right-JO Worksheet Job: Lot 119 Block Waterstone... NE MQ-nmcoxnmuMNc Entire House Date: DEL AIR HTG, A/C & REFRIG. INC By: DCS 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM 1 Room name M. BATH M. WIC 2 Exposed wall 12.0 it 0 it 3 4 Room height Room dimareensions 10.0 it heat/cool 10.0 it heat/cool 5 Room 1.0 x 119.0 ft 119.0 ftz 7.0 x 7.0 ft 49.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ft2) Load number (Btuh/ft2-OF) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 _.. - 'Blk @I' stucco ezt... 2A 2ov ..._ 0143 0.330 rie ne 4.75 9.51 2.59 ' 17.70 _ 120 `; - 113 7 0 ._ .- _469 66 _------- 293 0 .. 0 --- ---- --0 ���---GGG 123 0 0 0 0 _2A-2ov_ _ _ 0330 _ ne _ _ 9:5.7 - -_ _1, 7_70 -------- 0 0 --- ----�-_ 0 0 0 0 0 0 11 Blk wall, stucco ext~ 10C-v 0.143 0.550 se se 4.15 15.95 2.59 16.20 0 0 0 0 ----- ._'- 0 0 - ..- _-- 0 0 _ . -- - -- 0 0 - - 0 0 - 6 0 ---- 0 0 2A-2ov 0.330 se 9.57 15.62 0 0 0 0 0 0 0 0 2A-2ov 0.330 se 9.57 0 0 Blk wall stucco ext 2A 2ov 0143 0 330 sw sw 4.15 9.57 2.59 15.63 0 0 0 0 0 � -0 0 0 --- - 0 0 - ` - 0 p 0 - -0 - 0 LL--GG 2A 2ov .. - ...... - 0 330 sw. 9.57 . . _15.63 _ 0 _ _ .:0 - - 0 0 0 0 0 Blk wall, stucco ext 2A-2ov 0.143 0.330 nw nw 4.15 9.57 2.59 16.61 0 0 0 0 0 0 - 0 0 _ -0 0 0 .__.. -- _0 0 0 _._._. _ _ _ 0 0 _---------0 0 0 2A-2ov 0.330 nw 9.57 16.61 0 0 0 0 0 0 0 0 2B-2fv 0.330 nw 9.57 26.32 0 0 0 0 0 0 0 0 2B-2fv 0.330 nw 9.57 22.09 0 0 0 0 0 0 0 0 - ..-_ 1 - .--- ...... .... .. .-.I-__ nw:.._.1 ...._1 __ � 0 0 0 P C CJ .12 _0sw '._._-.- 168 30ad 0091 _r... _....2.64 ... :_..J.31 - -.1 . ..__..0 - -._.., ._...._ _ 0 _._.� . .-.._- 0 ._ ..0. ._._.__._0__. __..._-.0. .0 ... 0 �0 _ :. ...:-0. F _ -.. 22A tpl _ _ . ,_ 0.032 ' 0.989 0.93 28.68 1.69 119 119 119 12 110 201 0 49 49 45 83 _ __. .- _ .0.00 _ - -- _._ _... _ _344 __ - _ . _49 0 . -_ . _ _0 . _0 6 c) AED excursion -38 -5 Envelope loss/gain 990 579 45 78 12 a) Infiltration 240 67 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 Appliances/other 0 0 0 Subtotal (lines 6 to 13) 1230 646 45 78 Less external load 0 0 0 Less transfer 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1230 646 0 45 0 78 15 Duct loads 31 % 41% 379 268 31% 41 % 14 32 Total room load Air required ad 1609 914 �13 111 69 42 5 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed - wrogF�tsoft" Right -Suite® 2020-Mar-10 09:20:16 Universal 2019 19.0.12 RSU23828 Page 5 ... terstone1820BGL\Lot119Blk5Waterstonel820BGL.rup Cato = MJ8 Front Door faces: NW QDEL AIR Right-M Worksheet Job: Lot 119 Blocks Waterstone... euzmIc•maconnmoxwc Entire House Date: DEL AIR HTG, A/C & REFRIG. INC By: DCS 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area KITCHEN/NOOK 15.0 ft 10.0 It heat/cool 1.0 x 246.0 ft 246.0 ftz LAUNDRY 0 ft 10.0 ft heat/cool 6.0 x 6.0 ft 36.0 ft2 Ty Construction number U-value (Btuh/ft--F) Or HTM (Btuh/ft2) Area (ftz) or perimeter (ft) Load (Btuh ) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool 'Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 --G D C Blk wall, stucco ezt 2A 2oy 2A26v__-=.. Blk wall, stucco ext 1OC-v 2A-2ov 2A-2ov__ _ __ -___ _ Blk wall, stucco ext 2A 2ov 2A 2ov- - --...._. Blk wall, stucco ext 2A-2ov 2A-2ov 2B-2fv 213-2fv 11J0 _ _._ _. .__. .. 12C.Osw. __- 16B-30ad 22ArtPl . ... _ ---- . 0.143ne 0.330 .__.._0330 0.143 0.550 0.330 -_ 0.330 0,143 0.330 0.330 0.143 0.330 0.330 0.330 0.330 .. _ ,0.600 _ __-0.091 0.032 ,.. 0 989 ne ne- se se se se , sw sw . sw. nw nw nw nw nw nw . - .. -. 4.15 ., 9:57 --__9_57 4.15 15.95 9.57 9.57 _ 4.15 9.57 - -. _ -9,57 4.15 9.57 9.57 9.57 9.57 17.40 -_:2.64. 0.93 ._,28.68, 2.59 17 70 _ 17_70.--.,. 2.59 16.20 15.62 8.52 f89 15.63 15.57 2.59 16.61 16.61 26.32 22.09 17.58 - .-.1:31- 1.69 --- Or00 __-.. 150 0 --- 330 0 0 0 0 - -0 0 .. - -0 0 0 0 0 0 -- ._ -y - 0 -__-1.46 246 .. _ .246 '-117 0 0 0 0 0 • -0 - ' 0 - -- 0 0 0 0 0 0 _--.--- 0 _140 246 _ _. ___ 15 - -- �- 481 0 _.---_ 313 0 0 0 0 -` " 0 0 _. 0 0 0 0 0 0 ..•_,__...0 _._.__ 369 228 :'' 430 -' 304 0• 57 0 0 0 0 - 0 0 :0 0 0 0 0 0 0 -- . 183 416 :. _ _0 "0 0 _ _ 0 0 0 0 _. _ _'. 0 0 - 0 0 0 0 0 0 -- .__. , _ 60 36 ..� ._..36 D 0 0 0 0 0 0 -_ _ -6, 0 0 0 0 0 0 0 - - 0 ._.__. - 60 36 _. _' - _ 0 - --- ---6 0 0 _ -0 0 0 0 ..... 6 .0 .- 0 0 0 0 0 0 _ 0 _ .. 158 33 0 0 0 6 0 0 0 6 0 - - - 0 0 0 0 0 0 - 0 79 61 __ __ 6 c) AED excursion -123 -41 Envelope loss/gain 1827 1358 192 99 12 a) Infiltration b) Room ventilation 300 0 84 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 1200 0 0 600 Subtotal (lines 6 to 13) 2128 2642 192 699 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 31 % 41 % 0 0 0 2128 655 0 0 0 2642 1096 31 % 41 % 0 0 0 192 59 0 0 0 699 290 Total room load Air required (cfm) 2783 119 3738 171 251 11 988 45 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed . - -I-wr7gl�tso4ftA 2020-Mar-10 09:20:16 Right -Suite® Universal 2019 19.0.12 RSU23828 Page 6 terstone1820BGL\Lot119Blk5Waterstone1820BGL.rup Calc = MJ8 Front Door faces: NW DEL -AIR Duct System Summary Job: Lot 119 Block 5 WaterstoQ... Date: HFAIING•AIR CONDmONING Entire House By: DCS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM •lect Intormation For: ADAMS HOMES 5338 San Bendetto Place, Fort Pierce, FL 34951 External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120 / 0.120 in H2O 0.212 in/100ft 1167 cfm Cooling 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120 / 0.120 in H 20 0.212 in/100ft 1167 cfm 113 ft Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 802 34 20 0.278 4.0 Ox 0 V I Fx 16.3 70.0 BDRM 2 h 4567 196 127 0.258 8.0 Ox 0 VIFx 22.9 70.0 BDRM 3 c 1786 80 82 0.305 6.0 Ox 0 VIFx 8.6 70.0 DEN/BDRM 4 h 4093 176 140 0.288 7.0 Ox 0 VIFx 13.2 70.0 DINING/FOYER c 4080 147 186 0.314 7.0 Ox 0 VIFx 6.5 70.0 FAMILY RM c 3502 102 160 0.233 8.0 Ox 0 VIFx 17.9 85.0 Sti KITCHEN/NOOK c 3738 119 171 0.228 8.0 Ox 0 VIFX 20.1 85.0 St1 LAUNDRY c 988 11 45 0.223 4.0 Ox 0 VIFx 22.7 85.0 Sti M. BATH h 1609 69 42 0.224 5.0 Ox 0 VIFx 22.2 85.0 st1 M. WIC c 111 3 5 0.225 4.0 Ox 0 VIFx 21.9 85.0 sti MSTR BDRM h 5356 230 189 0.212 8.0 Ox 0 VIFx 28.2 85.0 St1 Supply Trunk Detail Table Name Trunk Type Htg (cfm) Clg (Cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk St1 Peak AVF 534 612 0.212 573 14.0 0 x 0 VinlFlx * wrightso, CA _ -• ••. = ftm Right-SuiteO Universal 2019 19.0.12 RSU23828 ..terstane1820BGL\Lot119Blk5Waterstone1820BGL.rup Calc = MJ8 Front Door faces: NW 2020-Mar-10 09:20:17 Page 1 Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rbi Ox 0 1167 1167 0 0 0 0 Ox 0 VIFx t; wri�ghtsoftm 2020-Mar-10 09:20:17 � �M•t•� ••�«•.a.�=gym Right -Suite® Universal 2019 19.0.12 RSU23828 ..terstonel820BGL\Lotll9Blk5Waterstonel820BGL.rup Calc = MJ8 Front Door faces: NW Page 2 2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 119 Block 5 Waterstone 1820 BGL Builder Name: ADAMS HOMES Street: 5338 San Bendetto Place Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 w Design Location: FL, ST LUCIE_CO_INTL 2 U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. 9 Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in an Y dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within comers and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial -contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac 3s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the drywall. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub -floor or drywall. Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. _1 Caulking or other adhesive sealants shall not be used to fill voids be.tween.fire.sprinkler cover nlates and walls or ceilings. a. in addition, inspection or log walls snail be in accordance with the provisions of ICC-400. 3/10/2020 9:32 AM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 FORM' R405-2017 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2017 Florida Building Code, Energy Conservation via the residential Simulated Performance Method shall include: ❑ This checklist ❑ A Form R405 report that documents that the Proposed Design complies with Section R405.3 of the Florida Energy Code. This form shall include a summary page indicating home address, a -ratio and the pass or fail status along with summary areas and types of components, whether the home was simulated as a worst -case orientation, name and version of the compliance software tool, name of individual completing the compliance report (one page) and an input summary checklist that can be used for field verification (usually four pages/may be greater). ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO for the Performance Method: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed Envelope Leakage Test Report (usually one page) ❑ If Form R405 duct leakage type indicates anything other than "default leakage" then a completed Form R405 Duct Leakage Test Report.(usually one page) . 3/10/2020 9:31:39 AM EnergyGauge® USA 6.0.02 (Rev. 1) - RaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1