HomeMy WebLinkAboutProject Information1 -- wrightsoft® Load Short Form House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vicldlynrie@aircalcs.com f-roject intormation For: Rosa Residnece, NisAirAir Conditioning 1565 Bennett Rd., Fort Pierce, FL 34947 Job: 1368 Date: Nov05, 2020 By. Chris Bateman Design Information Htg Clg Infiltration Outside db (°F) 41 90 Method Simplified Inside db (°F) 70 75 Construction quality Average Design TD (°F) 29 15 Fireplaces 0 Daily range - L Inside humidity (%) 30 50 Moisture difference (grAb) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S030-230A** AHRI ref Coil CBA27UHE-030-230*++TDR AHRI ref 10259437 Efficiency 100 EFF Efficiency 13.0 EER,16 SEER Heating input 6.9 kW Sensible cooling 20300 Btuh Heating output 23474 Btuh Latentcooling 8700 Btuh Temperature rise 22 °F Total cooling 29000 Btuh Actual airflow 967 cfm Actual airflow 967 cfm Airflowfactor 0.043 cfm/Btuh Airflowfactor 0.048 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.77 ROOM NAME Area (ft2) Htg load (Btuh) CIg load (Btuh) HtgAVF (cfm) CIgAVF (cfm) Laundry 72 1000 1068 43 51 M.Bath 66 1704 688 73 33 M. Hall 26 0 0 0 0 WIC 63 1724 676 73 32 Master Bed 255 2199 2598 94 124 Great Room/Foyer 345 4103 4509 175 215 Pantry 15 0 0 0 0 Kltchen/Nook 273 3589 5501 153 262 Bed 3 168 3191 1829 136 87 Bath 54 833 460 35 22 Linen 8 0 0 0 0 Bed 2 182 4344 2978 185 142 Li n QO n n n n Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -*- wrightsoft0 0%op 2021-Nov 1210:age ItightStite®Uriversal 202121.0.10 RSU29066Page ACCA...is\wrightsoftHVACU565BemeftRdPSLProp.np Calc=MJ8 Front Door faces: E House 1558 22687 20306 967 967 Other equip loads 1453 771 Equip. @ 0.95 RSM 20108 Latent cooling 6121 T/1TA1 Q 4 rrQ 7A 4 40 7R790 OP7 OG27 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrigh' tsoftm Rigtt-Sate® Uriversal 2021 21.0.10 RSU29066 ACC...ts\WrightsoftHVAC\1565BemettRdPSLProp.rlp Cale =MJ8 Frord Door faces: E 2021-Nov1210:32:03 Page 2 a Building Analysis Job: 1368 - - wrightsoft® Date: Nov05, 2020 House By. Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: viddlyme@aircalcs.com For: Rosa Residnece, NisAirAirConditioning 1565 Bennett Rd., Fort Pierce, FL 34947 Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature ff) 70 75 Elevation: 26 ft Design TD (°F) 29 15 Latitude: 28ON Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (grAb) 2.4 56.9 Dry bulb (°F) 41 90 Infiltration: Daily range (°F) - 15 (L ) Method Simplified Wet bulb (°F) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Component Btuh/ft2 Btuh % of load Walls 3.1 4958 20.5 Glazing 17.3 2850 11.8 Doors 3.7 89 0.4 Ceilings 1.0 1544 6.4 Floors 3.4 5306 22.0 Infiltration 1.9 3010 12.5 Ducts 4930 20.4 Piping 0 0 Humidification 0 0 Ventilation 1453 6.0 Adjustments 0 Total 1 1 24139 100.0 Cooling Component Btuh/ftz Btuh % of load Walls 1.9 3089 14.7 Glazing 17.7 2906 13.8 Doors 3.7 89 0.4 Ceilings 1.8 2811 13.3 Floors 0 0 0 Infiltration 0.5 841 4.0 Ducts 5549 26.3 Ventilation 771 3.7 Internal gains 5020 23.8 Blower 0 0 Adjustments 0 Total 1 1 21078 100.0 Latent Cooling Load = 6121 Btuh Overall U-value = 0.104 Btuh/ft2--°F Data entries checked. Intlltratlon Vontilatinn Gains -Of&- =Ightsoft- 2021-Nov-1210:32:03 = •���­�-Right-Sate® Universal 202121.0.10 RSU29066 Page1 A ...fs\WrightsoftFNAC\1565BemettRdPSLProp.r� Cale Front E 1 ' Component Constructions Job: 1368 wrightsoft® p Date: Nov05, 2020 House By. Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beads, FL32966 Phone: 772.800.8413 Email: viddlyrne@aircalcs.com Project For: Rosa Residnece, NisAirAir Conditioning 1565 Bennett Rd., Fort Pierce, FL 34947 Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (OF) 70 75 Elevation: 26 ft Design TD (OF) 29 15 Latitude: 280N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (grAb) 2.4 56.9 Dry bulb (°F) 41 90 Infiltration: Daily range (OF) - 15 (L ) Method Simplified Wet bulb (°F) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U value Insul R Htg HTM Loss Clg HTM Gain ft' Bt1h1ti°F ftMFBtuh Btuh/R' Btuh BtuhV Btuh Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd inl, 8" Thk, 1/2" Gyp Bd Int Fnsh n 310 0.109 5.1 3.15 976 2.02 624 e 269 0.109 5.1 3.15 846 2.02 541 s 312 0.109 5.1 3.15 985 2.02 630 w 501 0.109 5.1 3.15 1577 2.02 1009 all 1391 0.109 5.1 3.15 4384 2.02 2804 Partitions Fmn Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2N4", 16" OC Stud Windows Impact, Clear Low-e: Impact, Clear Lowe; NFRC rated (SHGC=0.24); n 50% blinds 45', medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (3.17 ft window ht, 1 ft sep.); 8 ft head ht Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); n 50% blinds 45', medium; 50% outdoor insect screen; foreground = green e grass (0.23); 1 ft overhang (5.25 ft window ht, 1 ft sep.); 8 ft head ht w all Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); e 50% blinds 45', medium; 50% outdoor insect screen; foreground = green grass (0.23); 6 ft overhang (5.25 ft window ht, 1 ft sep.); 8 ft head ht Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); s 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2.17 ft window ht, 1 ft sep.); 8 ft head ht Impact, Clear Low-e: Impact, Clear Lowe; NFRC rated (SHGC=0.21); w foreground = green grass (0.23); 12 ft overhang (8 ft window ht, 1 ft sep.); 8 ft head ht Doors Fbrgls Door 195 0.101 11.0 2.94 574 1.46 285 10 0.580 0 16.8 164 11.5 112 16 0.580 0 16.8 272 11.5 186 23 0.580 0 16.8 390 28.1 652 16 0.580 0 16.8 272 28.1 455 56 0.580 0 16.8 935 23.3 1294 46 0.580 0 16.8 780 17.0 789 5 0.490 0 14.2 67 12.2 57 48 0.650 0 18.8 905 12.1 580 e 24 0.127 7.0 3.69 89 3.73 89 : -F- Wrightsoft® 2021-Nov-1210:32:03 .N,.� .WU .,� . , Right Stite®Uriversal 2021 21.0.10 RSU29066 Page 1 ��...ts\WrightsoftHVAC\1565BemettRdPSLProp.np Calc=MJ8 FrontDoorfaoes: E Cbilings Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 1558 0.034 30.0 0.99 1544 1.80 2811 Floors On Grade Depth, Tile Flr Fnsh 185 0.989 0 28.7 5306 .0 0 . A -rk wrightsaft® 2021-Nov-1210:32:03 z�Mgt3-Sute8Uriversa1202121.0.10RSU29066 Paget tsUrightsoft M/AC11565 Bemett Rd PSL Prop.np Calc= MJB From Door faces: E Project Summary Job: 1368 - - wrightsofte Date: Nov05, 2020 House By. Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vicdlyme@aircalcs.com Project Information For: Rosa Residnece, NisAirAir Conditioningg 1565 Bennett Rd., Fort Pierce, FL 34947 Notes: Design Information Weather: St Lucie Cc Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure 17756 Btuh Structure 14757 Btuh Ducts 4930 Btuh Ducts 5549 Btuh Central vent (46 cfm) 1453 Btuh Central vent (46 cfm) 771 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 24139 Btuh Use manufacturer's data n Rate/swin multipplier 0.95 Infiltration Equipmenisensibleload 20108 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2721 Btuh Ducts 1639 Btuh Central vent (46 cfm) 1761 Btuh Heating Cooling Outside air Area (ft�) 1558 1558 Equipment latent load 6121 Btuh Volume (fN) 14911 14911 Airchanges/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 26229 Btuh Equiv. AVF (cfm) 94 50 Req. total capacity at 0.70 SHR 2.4 ton Heating Equipment Summary Cooling Equipment Summary Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S030-230A** AHRI ref Coil CBA27UHE-030-230*++TDR AHRI ref 10259437 Efficiency 100 EFF Efficiency 13.0 EER,16 SEER Heating input 6.9 kW Sensible cooling 20300 Btuh Heating output 23474 Btuh Latentcooling 8700 Btuh Temperature rise 22 OF Total cooling 29000 Btuh Actual airflow 967 cfm Actual airflow 967 cfm Airflowfactor 0.043 cfrnBtuh Airflowfactor 0.048 cfmBtuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.77 Calculations approved byACCAto meet all requirements of Man t iJ 8th Eq\rt\ ' - wrightsoi�t- Righ-Sute@Uriversal2021 21.0.10 RSU29066 OV �OJ�N 2021-Nov 121 Page 1 ts\Wdgt1soft HVAQ1 565 Bennett Rd PSL Prop.rup Calc=MJB Front Door faces: E cJl' Qe� - wrightsoft" Right-JO Worksheet House Air Calm, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email:,Addlyrrie@aircalcs.com Job: 1368 Date: Nov05, 2020 By: Chris Bateman 1 2 3 4 5 Room name Exposed tell Room height Room dimensions Room area House 185.0 ft 9.6 It 1557.8 It' Laundry 11.0 ft 9.3 It heat/mol 11.0 x 6.5 ft 71.5 fN Ty Construction number U-value (Btuh/t;°F) Or HTM (BtuhAtl Area or perimeter (ft) Load (BWh) Area or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross NiP/S Heat Cool 6 11 Blk Wall, SU000 E d Impact ClearLow-e, Impact, Clear Lowe Blk Wall, Stu000 Fact Impact, ClearLow-e Impact Clear Low-e Fbrgls Door __ Blk Wall, Stuoao Etd- -Impad,.Clear.Lowe Blk Wall, Strom Ext Impact Clear Low-e mpact, Clear LowLe FrmWa11,1/2GypB Attig Shngl Roof, R On Grade Depth, Tile 0109 0580 _.. O580 0.109 0.580 0.580 _ _ 0.127 0.109 -0.490 0.109 0.580 0.650 n n .__ n ' e ' a a _ e s -s-- w w w 3.15 16.82' 16.82 2.02 11:48 11.48 836 10 _ 1B, 310 0 0 976 164 272 624 112 0 0 0 0 0 0 0 0, _ - __ 0 0 ^ 0 0 0 0 ^-0 ----0. 0 0 3.15 16.82 16.82 3.69 3.15 -14211. 3.15 16.82 18.85 2.02 28.13 17.02 3.73 2.02 -----I 23 2.02 28.13 12.09 _ __ - 362 23 46 __ 24 317 _____' `5 565 16 48 _- 269 0 35 _ 24 312 _ -- �`5 501 0 48 ___ 846 390 780 _ 89 965 67. _ _T�186 541 652 789 _ 89 630 57. _ _ T 0 0 0 __ 0 -'--0 �0 _ - 0 0 0 ___ 0 ------0 -_____0 0 0 0 0 '0 _ W L-G WI _ 1577 272 905 1544 5306 1009 455 - i 580 _ 2811• _ 0 __� 0 0 0 0 ---Q 0 0 h--c� 0101,-�: 0.034 ._ . _� - - � _?94 _ 0.99 _- 1.46_ 1.80 _ _ 0.00 _v.195..__.__ _ _ 1558 1558 195,_-.--574---_-.-265102.._..___102__- -y_ 1558 185 ---0 _ -,_ 72 72 --.0 72 �11 --0,---0 301._�149_ 71 129 _ v 315 _ _-__0.989 _28.68 .__ _-_ _ 6 c) AED exarsion 73 -39 Enwlopelosslgain 1 14747 8896 687 239 12 a) Infiltration b) Roomventilation 3010 0 841 01 0 0 0 0 13 Intemal gains: Occupants @ 230 Applianoes/other 4 920 4100 0 0 500 Subtotal (lines6 to 13) 17756 14757 687 739 14 15 Less edemal load Less transfer Redistribution Subtotal Ductloads 28% 38% 0 0 0 17756 4930 0 0 0 14757 5549 28%11111 38% 0 0 96 782 217 0 0 37 776 292 Total room load Air required (dm) 22687 967 20306 967 1000 43 1068 51 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. 't"I't" 2021-Nov1210:32:03 .4CCA Right-Sute@)Unlversa12021 21.0.10 RSU29066 Page 1 ts\WdghtsoftWAC11565.BemeftRdPSLProp.rup Calc=MJ6 FrontDoorfaces: E + wrightsoft° Right-JO Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beads, FL32966 Phone: 772.800.8413 Email: vidjlyrm@aircalcs.com Job: 1368 Date: Nov05, 2020 By: Chris Bateman 1 2 3 4 5. Room name Fposed tell Room height Room dimensions Room area M. Bath 17.5 It 9.3 It heaV000l 5.5 x 12.0 ft 66.0 1>? M Hall 4.0 It 9.3 It heat/000l 4.0 x 6.5 ft 26.0 Ty Construction number U-value (BtuhAt;°F) Or HTM (Btuh/M Area or perimeter (ft) Load (Btuh) Area or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 Blk Wall, Stucco E)d Impact,ClearLowe Impact Clear Low-e---Y Blk Wall, Stumo Ext Impact Clear Low-e Impact Clear Lowe Fbrpls Door _ - 0109 0.580 -- - 0.580 0.109 0.580 0.580 0.127 _ n n n -- a a a a _.�3.15 16.82 - 16682 3.15 16.82 16.82 3.69 2A2 11A8 ._ 11A 2.02 28.13 17.02 _ 3.73 0 0 _ � 0 0 0 0 0 �.112 _w 0 0 � ^ 0 0 0 0 0 _-._. 0 0 _- -- � 0 0 0 0 _. O 0 -� - 0 0 0 0 _ 0 .- 0 0 °--- 0 0 0 0 0 O 0 ------ 0 0 0 0 y� _ 0 - .0 0 . -0 0 0 0 _ 0 '^ .�. ..- - 0 _ - __.. 0 0 0 0 _ 0 - y _ ��1111 _ W ' -G Blk Wall, Stucoo Est-" ' .Impact;.Clear.Lowe.. Blk Wall, Stucco Ext Impact Clear Low-e -Impact Clear Lowe FrrnWall,1C::%pB -- AmG Shnpl Raof On G- ra-d-e D-e R_- pthTile- 0.109 __.._;0.490 0.109 0.580 _-_-0.650 s -s_ w w w 3 f 5 .__:I.4.21. 3.15 16.82 -a 18.85 --2g4 Q 28.686._. 2.02 _ .-.1223 2.02 28.13 -__ 12.09 80 _- �--1 5 107 0 0 -y_ _.. 0 _ 5� 337 0 0 -__ �.__ 0 _..- 150 __65__19 502 215 0 0 0 0 0 0 _.. 109 _ 6 - - 115 0 0 0 . _� 0 ----___.._54 __4_9 - 0 WI - y 0 0 0 _._ 51: - - 66 .--57 0 0 ----�_0 __.. _.-75 . -_ - 0 0 �..�_ 0 __.._..._ 37. __-26 26 0 0 ____ __0 --.-3� __--26 I--c� --_G- C _- F_„r - --0101 0.034 - -- - .0:989__ va____.66 - 4 6 c) AED exarsion -26 -5 Envelope loss/gain 1121 440 12501 96 12 a) Infiltration b) Room ventilation 213 0 59 0 0 0 0 0 13 Internal gains Occupants@ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 1334 500 250 96 14 15 Less mdemal load Lessiransfer Redistribution Subtotal Dud loads 28% 38% 0 0 0 1334 370 0 0 0 500 188 28% 38% 0 0 -250 0 01 0 0 -96 0 0 Total room load Airrequired (kim) 1704 73 688 33 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wr7gF�tsofte 2021-Now1210:32:03 & .. -^- Right Suite®Universal 2021 21.0.10 RSU29066 Page 2 tsNwdghtsoft HVAC11565 Bennett Rd PSL Prop.rap Calc = MJ8 Front Door faces: E + wrightsoft" Right-JO Worksheet House Air Calm, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: viddlyme@aircalcs.com Job: 1368 Date: Nov05, 2020 By: Chris Bateman 1 2 3 4 5 Room name Exposed v all Room height Room dimensions Room area WIC 17.0 It 9.3 ft heat/000l 5.5 x 11.5 ft 63.3 1? Master Bed 15.0 ft 10.0 It heat/cool 15.0 x 17.0 ft 255.0 it' Ty Construdion number U-value (BtihAt;-°F) Or HTM (BtuhAt� Area (M or perimeter (ft) Load (Btuh) Area (ft� or perimeter (ft) Load (Btuh) Heat Cool Gross NP)S Heat Cool Gross NSS Heat Cool 6 11 G Blk Wall, Stuoio Eikt-' Impack Clear Lowe Impact Clear Lowe _ 0109 0 580 _--_: 0.580 0.109 0.580 0.580 v 0.127 ,n3.15 n . n a a a e_ _ 16.82 __ 16.82' 3.15 16.82 16.82 3.69 2.02-�B 11.48 _ 11:48 2.02 28.13 17.02 3.73 1;0 _ 0 - 0 0 0 0 0 0 '_ 0 -J 0 0 0 0 " _M o 0 ,_ 'o _ --0 0 0 0 0 0 __ 0 - _ _ 0 0 0 0 . _ 0 0 __ _ 0 , - 0 0 0 0 0 0 ��_ 0 -- _ 0 0 _ 0 0 0 _____,__ 0 Blk Wall, Stucco Ext Impact, Clear Lowe Impact Clear Low-e Fbrqls Door 0 0 0 0 0 0 0 0 0 0 0 0 ,W ! Blk Wall; Stucoo E)d _Impact.Clearl-owe= Blk Wall, Stu000 Ext Impact, ClearLm*e lmpaci Clear Lowe - Fnn Wall, ll22 Gyp�B _._ A#M hngl Roof, R •0109 ._.0490 0.109 0.580 _ _ 0.650 ._ __.._ 010]: _- 0.034 s • _.s_- w w w 3.15 .=1421. 3.15 16.82 -18.85 _ _2_ 0.99 .2.02 -_,1223 2.02 28.13 12.09 �'46 1.80 0.00 _ 107 _0 51 0 -0 0 63 ._. _ � 63 107 .�_ 0 51 0 0 .e _ __. 4 , 63 _- 17 337 _ _ 0 161 0 216 0--- 103 0 0 6 :_-.0 150 16 0 0 ; 0 0' 0 0 _,�0 270 455 . IW - 134 0 0-0-0 422 272 A - _ --0' a4 _m _ , 63 . _ 488 - _ 6 _,- 114 _ 0 _ ^__._ 255 ;255 -- T 255 _ �15 253 M` 430 0 _ _ 460_ ,_ '-0. 6 c) AED exarsi.n -26 100 Envelope loss/gain 1048 407 1377 1286 12 a) Infiltration b) Room venfilation 301 0 84 0 286 0 80 0 13 Internal gain& Occupants@ 230 Appliancesrother 0 0 0 0 0 500 Subtotal( lines6to13) 1350 491 1663 1865 14 15 Less e)demal load Less transfer Redistribution Subtotal Duct loads 28% 38% 0 0 0 1350 375 0 0 0 491 185 28% 38% 0 0 59 1721 478 0 0 23 1888 710 Total room load Air required (cfm) 173 1724 676 32 2199 94 2598 124 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. *- Rht wrigF�tsotFt^ 2021-Nov-1210:32:03 .4CC- P. g-SUte®Urrversal 2021 2110 RSU29066 .0.Page 3 ts\WdghtsoftHVAC\1565BemeftRdPSLProp.rup Calc=MJ8 Front Door faces: E + wrightsoft' Right-J® Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyme@aircals.com Job: 1368 Date: Nov05, 2020 By. Chris Bateman 1 2 3 4 5 Room name Exposed till Room height Room dimensions Room area GreatRoomiFoyer 28.0 ft 9.3 It heaV000l 1.0 x 345.0 It 345.0 ft' Pantry 0 It 9.3 ft heat/cool 5.0 x 3.0 It 15.0 ft2 Ty Construction number U-value (BtiuhAt--F) Or HTM (BtuhAn Area (ft� or perimeter (ft) Load (Btuh) Area or perimeter (ft) Load (Btuh) Heat Cool Gross NrP/S Heat Cool Gross N/P/S Heat Cool 6 11 - 0 0 _. 0 0 0 y _ 0 W - 0 6 _ 0 0 0 0 ----0- - '~ 0 0 0 - 0 0 0 0 �-G BIk WaII,'Stu=E Impact, Clear Lowe ,Impac( Clear Lowe Blk Wall, Stucco E)d Impact Clear Lowe Impact Clear Lowe FbrglsDoor 0'109 '0580 _ 0580 0.109 0.580 0.580 __ 0.127 n n _n e - a a e 3.15 16.82 _ 16.82 3.15 16.82 16.82 3.69 202 1148 T_11.48 2.02 28.13 17.02 D 0 ' 0 _ 0 - 237 0 46 _.� 24 0 0 _ ._ �0 T 167 0 35 `24 --- - 0 0 _ 0 525 0 780 ._v 89 -- 0 0 __. 0 - 336 0 789 _ 89 - q 0 �0 0 0 0 _ _ 0 ! G 111���JJJ WI _ � G Blk Wall, Stucco E)d :Impact Clear.Low--e. Blk Wall, Stucco E)d Impact Clear Lowe Impact Clear Lowe Fmi Walli l2'.. �� _ z�pB__ AtbGShngl_Roof R -_ On Grade Depth, Tile _ 0.109 -0:490._s_ 0.109 0.580 0.650 s w w w 3.15 1.421. 3.15 16.82 18.85 2.02 -`12.23 2.02 28.13 12_09 19 _-__-1 0 0 19 --0 0 0 .,- 0 __ 345 ._ _-._. 2$ 59 w.�..._-_A 0 0 0 37 - 0 , 0 __-0 0 0 0 0 _-____0 0 0 0--- _____0. 0 0 0 0 -__0 0 0 0 W I - _ 0 0 0 _-_ P .' C F _ - _ �:__ 01Q1. .__ 0034, 0 989 _ _``- _� .__ _ ... 294, 0.99 28.68 _ _.__1._46 1.80 0.00 -_____ _0 _. _ .345 -__. _345 ____, 342 ..-_-.- 803 -_,_- 04 _. _-_. �_ 15 w.- -15 ._ -_ 15 -- _-- 15 ---0 _, __ 27 -- 0 iL 6 o) AED excursion -168 -1 Envelope loss/gain 2611 1714 15 26 12 a) Infiltration b) Room ventilation 487 0 136 0 0 0 0 0 13 Intemalgains: Occupants@ 230 Appliancestother 2 460 900 0 0 0 Subtotal (lines 6 to 13) 3099 3210 15 26 14 15 Less extemalload Less transfer Redistribution Subtotal Ductloads 28% 38% 0 0 113 3211 892 0 0 67 3277 1232 28% 38% 0 0 -15 0 0 0 0 -26 0 0 Total room load Air required (c-n) 4103 1751 4509 215 0 0 0 0 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -*- 2021-Nov-1210:32:03 .eA R1gft-Sute®Universal 2021 21.0.10 RSU29066 Page 4 ts\WrightsoftHVAC\1565Banned RdPSLProp.rup CaIc=MJ8 Front Door faces: E wrightsofte Right-JO Worksheet Job: 1368 House Date: Nov05, 2020 By: Chris Bateman Air Calks, LLC 7550 Hidden Hammock Ln, Vero Beads, FL32966 Phone: 772.800.8413 Email: viedlyrm@aircalcs.com 1 2 3 4 5 Room name Exposed v ell Room height Room dimensions Room area !, t en/Nook 23.5 it 9.3 ft heaV000l 1.0 x 273.0 ft 273.0 ft' Bed 3 26.5 It 10.0 It heaV000l 1.0 x 168.0 ft 168.0 ft Ty Construction number U-value (BtuhA;°F) Or HTM (B Area (ftF) or perimeter (ft) Load (Btuh) Area or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 Blk Wall,Stiu¢o Ext - ImpactClearLowe : Impact, Clear Lowe- _ Blk Wall, StucoD EA Impact Clear Lowe Impact ClearLow-e Fbrgls Door 0.109 0.580 --�_�0.580 0.109 0.580 0.580 0.127 n n _ n _ a a a e M 3,15 16.82 16.82 3.15 16.82 16.82 3.69 _ 2.02 11AB 11 A8 2.02 28.13 17.02 3.73 .� 0 0 _-;_ 0 0 0 0 0 _ 0 - 0 . 0 0 0 0 0 -^ 0 0 ;. 1.�__w_. 0 0 0 0 ---0 0 0 0 0 0 0 -- 120 0 _ 16 0 0 0 0 404 0 0 0 0 0 0 -' 327 0 _ - 272 0 0 0 0 209 0 , _ .186. 0 0 0 0 ��1111 IL-G-p IWI � G _ Blk Wall, Stucbo Ext .Impaa:ClearLovve._� Bilk Wall, Stucno EA Impact, Clear Lowe ImpactClearLowe -Frm Wall,1_/2.' GyP B Atkq Shngl Roof R _ On_Grade Depth, Tile _ _ 0.109 ._-o.490 0.109 0.580 0.650 _, '0.1'o OA34 s ---s, w w _w _ _ 3.15 - 1421. 3.15 16.82 18.85 0.99 20.68 2.02 ___12.23 2.02 28.13 12.09 - 1.80 0.00 ~ 0 :�___ 0 219 0 - _ 48 273 i p-273 J 0 �0 171 0 _ _ 48 _ _ 0 _ __ 0 -______0 344 0 .�T 580 -_ 493 0 �- 0 ----0 145 0 0 0 0 _ A 457 0 0 _ __.-_--.0. 292 0 0, IW - --0 537 0 _ _ 905 271, 674 145 0 0 I--ci _ P -_---- C _ .y F ___-__ _- _ _ 168 _' 168 168 _27 167. _ 303 0 _- �0.989 _ _ . ` _273 -� `'24 -�, 760 -. m - _ 6 d) AED excursion 295 -69 Envelopeloss(gain 2387 1712 1983 922 12 a) Infiltration b) Roomventilation 416 0 116 0 505 0 141 0 13 Internal gains: Occupants@ 230 Applianoask her 2 460 1700 0 0 250 Subtotal (lines 6 to 13) 2803 3988 2488 1313 14 151 Less extemalload Lesstransfer Redistribution Subtotal Duct loads 28% 38% 0 0 6 2809 780 0 0 10 3998 1503 28% 38% 0 0 10 2497 693 0 0 17 1329 500 Total room load Airrequired(dm) 3589 153 5501 262 3191 136 1829 87 Calculations approved WACCAto meetall requirements of Manual J 8th Ed. i.F wri" c irt- 2021-Nov-1210:32:03 Right-SuteO Universal 2021 21.0.10 RSU29066 Page 5 tsm ghtsoftHVAGY1565Bennett RdPSLProp.nQ Calc=MJ8 Front Door faces: E -i{�- wrightsoft Right-J® Worksheet Job: 1368 House Date: Nov05, 2020 By: Chris Bateman Air Calks, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: %icidlyme@aircalcs.com 1 2 3 4 5 Room name ENposed Hell Room height Room dimensions Room area Bath 6.0 ft 9.3 It heat/000l 9.0 x 6.0 ft 54.0 ft' Linen 0 ft 9.3 ft heaUcool 2.5 x 3.0 ft 7.5 ft' Ty Construction number U-value (BWhAt�-°F) Or HTM (Btuhfin Area (M or perimeter (ft) Load (Btuh) Area (n or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 \�--G Blk Wall, Stump FAQ Impact, ClearLow-e .Impac�ClearLowe. Blk Wall, Stucco Ext Impact Clear Low-e Impact, Clear Lowe FbrglsDoor Blk Well, Stucco E)d .Impad.Clearl-owe_ Blk Wall, Stucoo Ext Impad ClearLawe Impact Clear Lowe .- At ci Shngl Roof, R _-- Grade Depth, Tile - 0.109 0.580 0.580 0.109 0.580 0.580 0.127 n n -n . a a a a 3.15 16.82 2.02 11.48 56 10 0 - 46 0 0 0 0 0 0 _-._---0 0 0 0 -- _ -- 54 _ �. 6 - - 164 0 0 0 0 0 _--0 0 0 0 - _54 - --172 -- 93 112 0 0 0 0 _ 0 ,-_0 0 0 0 --- 0 0 0 0 0 0 0 0 ---- - p 0 0 0 0 0 - 0 _.--__0 0 0 0 - O 0 0 0 0 0 0 _.-_-0 0 0 -__0 -_-- 7 - -- .. _--___ 0 0 0 0 0 0 - 0 _______A 0 0 ._ 0 _0. _ --_- -14 - - -- T.16.82 3.15 16.82 16.82 315 ---1.4.21. 3.15 16.82 - 18:85 _- 0_99.._ 28.68 .-__41A48 2.02 28.13 17.02 2.02 _..12.23 2.02 28.13 12.09 1.80 __ 0 0 0 ___ 0, _- _-0 0 0 0 54 _ WII � L_G __- 0.109 _-__0.490 0.109 0.580 _. 0.650 . _ _ -- 0.034 0.989 u _s_ w w _w_ ___. _, _ W I--G 0 0 0 � C- F _. _.._..On ,. _ _ 97 -- - __- --_-.__ 8 --- = 8 _-_ 0.00 . __- -_. _ . 54 - - --0 ----- _ .-. 6 c) AED exarsion -17 -1 Envelope losstgain 535 286 7 13 12 a) Infiltration b) Room ventilation 106 0 30 01 0 0 0 0 13 Internal gams: Occupants@ 230 Appliancestother 0 0 0 0 0 0 Subtotal (lines6 to 13) 641 315 7 13 14 15 Less extemalload Less transfer Redistribution Subtotal Duct loads 28% 380/. 0 0 11 652 181 0 0 19 334 126 28%1 380/0 0 0 -7 0 0 0 0 -13 0 0 Total room load Air required (dm) 1 135 833 460 22 0 0 0 0 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. - wrYgF�tsot- 2021-Nov-1210:32:03 ACCP. Rigk-Sute®U iversal 2021 21.0.10 RSU290fifi Page 6 ts\WrightsoftHVAC\1565BemettRdPSLProp.nQ Calc=MJ8 Front Door faces: E -- wrightsoft" Right-J® Worksheet Job: 1368 House Date: Nov05, 2020 By. Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beadt, FL32966 Phone: 772.800.8413 Email: v ddlyrne@aircalcs.00m 1 2 3 4 5 Room name Exposed well Room height Room dimensions Room area Bed 2 36.5 ft 10.0 ft heaUmol 1.0 x 1820 ft 182.0 fF Hall 0 ft 9.3 ft heat/000l 3.5 x 9.0 ft 31.5 f 2 Ty Construction number U-value (BtuhAt;°h) Or HTM (B Area (T) or perimeter (ft) Load (Btuh) Area or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 - 3.15 16.82 ^- 16_82 3.15 16.82 16.82 3.69 - 2.02 11.4E _ 11A8 2.02 28.13 17.02 3.73 -- 160 0 0.,---0 125 23 0 0_ i _ 160 0 102 0 0 0 -�0 -~ 0 0 0 0 0 0 Blk Wall, Stu000 Eid Impact, Clear Lowe Impact ClearLow_e_---- Blk Wall, Stucoo Ext Impact Clear Lowe Impact Clear Lowe FbrglsDoor _ B I k WalI, SWcoo E)d .Impact CIear.Lowe-._-, Blk Wall, Stucoo Ext Impac,ClearLowe ImpactClearLawe--_ FrrrtW_all,1/2`-Gyp Bw_ AtbgShngl Roof, R__- _. On Grade Depth,Tile--- - 0.109 0.580 --------0;580 0.109 0.580 0.580 n n ^n a a a e -504 0 --- 0 321 390 0 0 '322 0 --.----0 205 652 0 _ 0 -,----0 0 0 -_ 0 ----- 328 ------0 0 0 -_ _--_-0 0 0 0 0 0 0 0 0 0 0 ' 0 0 0 0 0 ----- _ W� L--G0 �0.127 0.909 __.T_ 0.490 0.109 0.580 _ 0.650 0.034 _ s -s_ w w _ w �- 3.15 _-i_4.21: 3.15 16.82 _ 18.85 _-� 0.99 2.02 1223 - 80 - _ 80 ___-_0 0 0 _ 0 -_-__182 7 252 ___ __0 0 0 -__ _ 0 _...._-_-32 _____0 0 0 _- __. 32 _. 0 0 ___---0 0 0 ---, 57 --------0 W 2.02 28.13 - 12A9 1.80 -' -0 0 0 ____. _ 0 -^---182 _ _. , 182, _0 0 0 _---_ 0 180 -----1047 0 0 _.. --_- 31 ^_ P _� F -_-- -_,0.00 --•-3z ---.----0 -----_-_.'0 6 c) AED excursion 32 -3 Envelope loss(gain 2694 1702 31 54 12 a) Infiltration b) Roomventilation 695 0 194 0 0 0 0 0 13 Internal gains Occupants@ 230 Appliancesrother 0 0 250 0 0 0 Subtotal (lines 6 to 13) 3390 2146 31 54 14 15 Less extemalload Less transfer Redistribution Subtotal Dudloads I281/o 38% 0 0 10 3400 944 0 0 17 2164 814 28% 38% 0 0 -31 0 0 0 0 -54 0 0 Total room load Airrequired(dm) 4344 1851142 2978 0 101 0 0 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -1rt- wrigtitsotFt- 2021-Nov-1210:32:03 Right-SuteO Universal 2021 21.0.10 RSU29066 Page 7 ts\WdghtsoftWADI 565 Berried Rd PSL Prop.r p Calc= MJ8 Front Door faces: E Duct System Summary Job: 1368 - - wrightsoft® Date: Nov05, 2020 House By. Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vicidlyme@aircalcs.com For: Rosa Residnece, NisAirAirConditioning 1565 Bennett Rd., Fort Pierce, FL 34947 External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.70 in H2O 0 in H2O 0.70 in H2O 0.576 / 0.124 in H2O 0.300 in/100ft 967 cfm 233 Cooling 0.70 in H2O 0 in H2O 0.70 in H2O 0.576 / 0.124 in H2O 0.300 in/100ft 967 cfrn Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Bath h 833 43 26 0.312 4.0 Ox0 VIFx 54.4 130.0 st3 Bed 2 h 4344 222 170 0.300 8.0 Ox 0 VIFx 62.0 130.0 st3 Bed 3 h 3191 163 105 0.327 7.0 Ox 0 VIFx 51.2 125.0 st3 GreatRoom/Foyer c 2254 105 129 0.397 6.0 Ox0 VIFx 40.2 105.0 st1 GreatRoom/Foyer--A c 2254 105 129 0.398 6.0 Ox0 VIFx 39.8 105.0 st1 Kitchen/Nook c 2750 92 157 0.401 6.0 Ox 0 VIFx 38.6 105.0 st1 KitchenNook A c 2750 92 157 0.401 6.0 Ox 0 VIFx 38.5 105.0 st1 Lary c 1068 51 61 0.456 5.0 Ox0 VIFx 26.3 100.0 st2 M. Bath h 1704 87 39 0.473 5.0 Ox 0 VIFx 21.7 100.0 st2 Master Bed c 1299 56 74 0.473 5.0 Ox 0 VIFx 21.9 100.0 St2 Master Bed -A c 1299 56 74 0.479 5.0 Ox 0 VIFx 20.3 100.0 st2 WIC h 1724 88 39 0.481 5.0 Ox 0 VIFx 19.6 100.0 St2 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) Orn) FR (fpm) (in) (in) Material Trunk st3 PeakAVF 428 301 0.300 784 10.0 0 x 0 UnlFlx st1 st1 PeakAVF 821 873 0.300 816 14.0 0 x 0 VinlFlx st2 PeakAVF 339 287 0.456 767 9.0 0 x 0 VinlFlx wrightsoft® 2021-Nov-1210:32:04 �_ Rigft Sute® Universal 2021 21.0.10 RSU29066 Page 1 �+M...ts\WdgtisoftWAC\1565BemettRdPSLProp.np Calc=MJ8 FrortDoorfaces: E Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) . FR (fpm) (in) (in) Opening (in) Mat Trunk rb4 Ox 0 201 187 41.4 0.300 575 8.0 Ox 0 VIFx rb1 Ox 0 574 698 0 0 0 0 Ox 0 Wx rb6 Ox0 222 170 0 0 0 0 Ox 0 MFx rb3 Ox0 163 105 0 0 0 0 Ox 0 MFx -*- wrightsoft® 2021-Nov 1210:32:04 A—r—� RighFSriteOUriversal202121.0.10RSU29066 Page 44CCk ...ts\WrightsoftWAQ1565BemettRdPSLProp.np Calc=MJ8 FrordDoor faoes: E -- wrightsoft° Manual S Compliance Report House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vickilyrm@aircalcs.com For. Rosa Residnece, NisAirAir Conditioning 1565 Bennett Rd., Fort Pierce, FL 34947 Design Conditions Job: 1368 Date: Nov05, 2020 By. Chris Bateman Outdoor design DB: 90.4°F Sensible gain: 21078 Btuh Entering coil DB: 76.8°F Outdoor design WB: 77.4°F Latent gain: 6121 Btuh Entering coil WB: 64.0°F Indoor design DB: 75.0°F Total gain: 27199 Btuh Indoor RH: 50% Estimated airflow: 967 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Lennox Model: ML14XC1S030-230A**+CBA27UHE-030-230*++TDR Actual airflow. 967 cfrrt Sensible capacity: 20300 Btuh 96% of load Latent capacity: 8700 Btuh 142% of load Total capacity: 29000 Btuh 107%of load SHR: 70% Design Conditions Outdoor design DB: 41.0°F Heat loss: 24139 Btuh Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elecstrip Manufacturer: Model: Actual airflow: 967 cfrn Output capacity: 6.9 kW 97% of load Meets all requirements ofACCA Manual S. Entering coil DB: 68.1 °F Temp. rise: 50 °F -�- wrightsoft® 2021-Nov-1210:32:04 �� AU -/ -..��, Right Sute®Uriversal 2021 21.0.10 RSU29066 Page 1 A...tsUrigttsoftHVACt1565Bennett RdPSLProp.np Cale =MJB Front Door faces: E a Job M 1368 Performed by Chris Bateman for: Rosa Residnece 1565 Bennett Rd. Fort Pierce, FL 34947 Air Calcs, LLC 7550 Hidden Hammock Ln Vero Beach, FL 32966 Phone: 772.800.8413 vicki[ynne@aircalcs.com Scale: 1 :104 Page 1 Right -Suite® Universal 2021 21.0.10 RSU29066 2021-Nov-1210:36:45 VAC\1565 Bennett Rd PSL Prop.rup