-- wrightsoft® Load Short Form
House
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vicldlynrie@aircalcs.com
f-roject intormation
For: Rosa Residnece, NisAirAir Conditioning
1565 Bennett Rd., Fort Pierce, FL 34947
Job: 1368
Date: Nov05, 2020
By. Chris Bateman
Design
Information
Htg
Clg
Infiltration
Outside db (°F)
41
90
Method
Simplified
Inside db (°F)
70
75
Construction quality
Average
Design TD (°F)
29
15
Fireplaces
0
Daily range
-
L
Inside humidity (%)
30
50
Moisture difference (grAb)
2
57
HEATING EQUIPMENT
COOLING EQUIPMENT
Make
Make Lennox
Trade
Trade LENNOX
Model
Cond ML14XC1S030-230A**
AHRI ref
Coil CBA27UHE-030-230*++TDR
AHRI ref 10259437
Efficiency
100 EFF
Efficiency
13.0 EER,16 SEER
Heating input
6.9
kW
Sensible cooling
20300
Btuh
Heating output
23474
Btuh
Latentcooling
8700
Btuh
Temperature rise
22
°F
Total cooling
29000
Btuh
Actual airflow
967
cfm
Actual airflow
967
cfm
Airflowfactor
0.043
cfm/Btuh
Airflowfactor
0.048
cfm/Btuh
Static pressure
0.70
in H2O
Static pressure
0.70
in H2O
Space thermostat
Load sensible heat ratio
0.77
ROOM NAME
Area
(ft2)
Htg load
(Btuh)
CIg load
(Btuh)
HtgAVF
(cfm)
CIgAVF
(cfm)
Laundry
72
1000
1068
43
51
M.Bath
66
1704
688
73
33
M. Hall
26
0
0
0
0
WIC
63
1724
676
73
32
Master Bed
255
2199
2598
94
124
Great Room/Foyer
345
4103
4509
175
215
Pantry
15
0
0
0
0
Kltchen/Nook
273
3589
5501
153
262
Bed 3
168
3191
1829
136
87
Bath
54
833
460
35
22
Linen
8
0
0
0
0
Bed 2
182
4344
2978
185
142
Li n
QO
n
n
n
n
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
-*- wrightsoft0 0%op 2021-Nov 1210:age ItightStite®Uriversal 202121.0.10 RSU29066Page
ACCA...is\wrightsoftHVACU565BemeftRdPSLProp.np Calc=MJ8 Front Door faces: E
House
1558
22687
20306
967
967
Other equip loads
1453
771
Equip. @ 0.95 RSM
20108
Latent cooling
6121
T/1TA1 Q
4 rrQ
7A 4 40
7R790
OP7
OG27
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
wrigh' tsoftm
Rigtt-Sate® Uriversal 2021 21.0.10 RSU29066
ACC...ts\WrightsoftHVAC\1565BemettRdPSLProp.rlp Cale =MJ8 Frord Door faces: E
2021-Nov1210:32:03
Page 2
a
Building Analysis Job: 1368
- - wrightsoft® Date: Nov05, 2020
House By. Chris Bateman
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: viddlyme@aircalcs.com
For: Rosa Residnece, NisAirAirConditioning
1565 Bennett Rd., Fort Pierce, FL 34947
Location:
Indoor:
Heating
Cooling
St Lucie Co Intl, FL, US
Indoor temperature ff)
70
75
Elevation: 26 ft
Design TD (°F)
29
15
Latitude: 28ON
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (grAb)
2.4
56.9
Dry bulb (°F) 41
90
Infiltration:
Daily range (°F) -
15 (L )
Method
Simplified
Wet bulb (°F) -
77
Construction quality
Average
Wind speed (mph) 15.0
7.5
Fireplaces
0
Component
Btuh/ft2
Btuh
% of load
Walls
3.1
4958
20.5
Glazing
17.3
2850
11.8
Doors
3.7
89
0.4
Ceilings
1.0
1544
6.4
Floors
3.4
5306
22.0
Infiltration
1.9
3010
12.5
Ducts
4930
20.4
Piping
0
0
Humidification
0
0
Ventilation
1453
6.0
Adjustments
0
Total
1
1 24139
100.0
Cooling
Component
Btuh/ftz
Btuh
% of load
Walls
1.9
3089
14.7
Glazing
17.7
2906
13.8
Doors
3.7
89
0.4
Ceilings
1.8
2811
13.3
Floors
0
0
0
Infiltration
0.5
841
4.0
Ducts
5549
26.3
Ventilation
771
3.7
Internal gains
5020
23.8
Blower
0
0
Adjustments
0
Total
1
1 21078
100.0
Latent Cooling Load = 6121 Btuh
Overall U-value = 0.104 Btuh/ft2--°F
Data entries checked.
Intlltratlon
Vontilatinn
Gains
-Of&- =Ightsoft- 2021-Nov-1210:32:03
= •����-Right-Sate® Universal 202121.0.10 RSU29066 Page1
A
...fs\WrightsoftFNAC\1565BemettRdPSLProp.r� Cale Front E
1 '
Component Constructions Job: 1368
wrightsoft® p Date: Nov05, 2020
House By. Chris Bateman
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beads, FL32966 Phone: 772.800.8413 Email: viddlyrne@aircalcs.com
Project
For: Rosa Residnece, NisAirAir Conditioning
1565 Bennett Rd., Fort Pierce, FL 34947
Location:
Indoor:
Heating
Cooling
St Lucie Co Intl, FL, US
Indoor temperature (OF)
70
75
Elevation: 26 ft
Design TD (OF)
29
15
Latitude: 280N
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (grAb)
2.4
56.9
Dry bulb (°F) 41
90
Infiltration:
Daily range (OF) -
15 (L )
Method
Simplified
Wet bulb (°F) -
77
Construction quality
Average
Wind speed (mph) 15.0
7.5
Fireplaces
0
Construction descriptions
Or
Area
U value
Insul R
Htg HTM
Loss Clg HTM
Gain
ft'
Bt1h1ti°F
ftMFBtuh
Btuh/R'
Btuh BtuhV
Btuh
Walls
Blk Wall, Stucco Ext, R-4.1 Ext Bd inl, 8" Thk, 1/2" Gyp Bd Int Fnsh
n
310
0.109
5.1
3.15
976 2.02
624
e
269
0.109
5.1
3.15
846 2.02
541
s
312
0.109
5.1
3.15
985 2.02
630
w
501
0.109
5.1
3.15
1577 2.02
1009
all
1391
0.109
5.1
3.15
4384 2.02
2804
Partitions
Fmn Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2N4", 16"
OC Stud
Windows
Impact, Clear Low-e: Impact, Clear Lowe; NFRC rated (SHGC=0.24); n
50% blinds 45', medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (3.17 ft window ht, 1 ft sep.); 8 ft head ht
Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); n
50% blinds 45', medium; 50% outdoor insect screen; foreground = green e
grass (0.23); 1 ft overhang (5.25 ft window ht, 1 ft sep.); 8 ft head ht w
all
Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); e
50% blinds 45', medium; 50% outdoor insect screen; foreground = green
grass (0.23); 6 ft overhang (5.25 ft window ht, 1 ft sep.); 8 ft head ht
Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); s
50% blinds 45°, medium; 50% outdoor insect screen; foreground = green
grass (0.23); 1 ft overhang (2.17 ft window ht, 1 ft sep.); 8 ft head ht
Impact, Clear Low-e: Impact, Clear Lowe; NFRC rated (SHGC=0.21); w
foreground = green grass (0.23); 12 ft overhang (8 ft window ht, 1 ft sep.);
8 ft head ht
Doors
Fbrgls Door
195
0.101
11.0
2.94
574
1.46
285
10
0.580
0
16.8
164
11.5
112
16
0.580
0
16.8
272
11.5
186
23
0.580
0
16.8
390
28.1
652
16
0.580
0
16.8
272
28.1
455
56
0.580
0
16.8
935
23.3
1294
46
0.580
0
16.8
780
17.0
789
5
0.490
0
14.2
67
12.2
57
48
0.650
0
18.8
905
12.1
580
e 24 0.127
7.0 3.69 89 3.73 89
: -F- Wrightsoft® 2021-Nov-1210:32:03
.N,.� .WU .,� . , Right Stite®Uriversal 2021 21.0.10 RSU29066 Page 1
��...ts\WrightsoftHVAC\1565BemettRdPSLProp.np Calc=MJ8 FrontDoorfaoes: E
Cbilings
Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 1558 0.034 30.0 0.99 1544 1.80 2811
Floors
On Grade Depth, Tile Flr Fnsh 185 0.989 0 28.7 5306 .0 0 .
A -rk wrightsaft® 2021-Nov-1210:32:03
z�Mgt3-Sute8Uriversa1202121.0.10RSU29066 Paget
tsUrightsoft M/AC11565 Bemett Rd PSL Prop.np Calc= MJB From Door faces: E
Project Summary Job: 1368
- - wrightsofte Date: Nov05, 2020
House By. Chris Bateman
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vicdlyme@aircalcs.com
Project Information
For: Rosa Residnece, NisAirAir Conditioningg
1565 Bennett Rd., Fort Pierce, FL 34947
Notes:
Design
Information
Weather: St Lucie Cc Intl, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db
41
OF
Outside db
90
OF
Inside db
70
OF
Inside db
75
OF
Design TD
29
OF
Design TD
15
OF
Daily range
L
Relative humidity
50
%
Moisture difference
57
grAb
Heating Summary
Sensible Cooling Equipment Load Sizing
Structure
17756
Btuh
Structure
14757
Btuh
Ducts
4930
Btuh
Ducts
5549
Btuh
Central vent (46 cfm)
1453
Btuh
Central vent (46 cfm)
771
Btuh
Outside air
Outside air
Humidification
0
Btuh
Blower
0
Btuh
Piping
0
Btuh
Equipment load
24139
Btuh
Use manufacturer's data
n
Rate/swin multipplier
0.95
Infiltration
Equipmenisensibleload
20108
Btuh
Method
Simplified
Latent Cooling Equipment Load Sizing
Construction quality
Average
Fireplaces
0
Structure
2721
Btuh
Ducts
1639
Btuh
Central vent (46 cfm)
1761
Btuh
Heating
Cooling
Outside air
Area (ft�)
1558
1558
Equipment latent load
6121
Btuh
Volume (fN)
14911
14911
Airchanges/hour
0.38
0.20
Equipment Total Load (Sen+Lat)
26229
Btuh
Equiv. AVF (cfm)
94
50
Req. total capacity at 0.70 SHR
2.4
ton
Heating Equipment Summary
Cooling Equipment Summary
Make
Make Lennox
Trade
Trade LENNOX
Model
Cond ML14XC1S030-230A**
AHRI ref
Coil CBA27UHE-030-230*++TDR
AHRI ref 10259437
Efficiency
100 EFF
Efficiency 13.0 EER,16 SEER
Heating input
6.9
kW
Sensible cooling
20300
Btuh
Heating output
23474
Btuh
Latentcooling
8700
Btuh
Temperature rise
22
OF
Total cooling
29000
Btuh
Actual airflow
967
cfm
Actual airflow
967
cfm
Airflowfactor
0.043
cfrnBtuh
Airflowfactor
0.048
cfmBtuh
Static pressure
0.70
in H2O
Static pressure
0.70
in H2O
Space thermostat
Load sensible heat ratio
0.77
Calculations approved byACCAto meet all requirements of Man t iJ 8th Eq\rt\
' - wrightsoi�t- Righ-Sute@Uriversal2021 21.0.10 RSU29066 OV �OJ�N 2021-Nov 121 Page 1
ts\Wdgt1soft HVAQ1 565 Bennett Rd PSL Prop.rup Calc=MJB Front Door faces: E
cJl' Qe�
- wrightsoft"
Right-JO Worksheet
House
Air Calm, LLC
7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email:,Addlyrrie@aircalcs.com
Job: 1368
Date: Nov05, 2020
By: Chris Bateman
1
2
3
4
5
Room name
Exposed tell
Room height
Room dimensions
Room area
House
185.0 ft
9.6 It
1557.8 It'
Laundry
11.0 ft
9.3 It heat/mol
11.0 x 6.5 ft
71.5 fN
Ty
Construction
number
U-value
(Btuh/t;°F)
Or
HTM
(BtuhAtl
Area
or perimeter (ft)
Load
(BWh)
Area
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
NiP/S
Heat
Cool
6
11
Blk Wall, SU000 E d
Impact ClearLow-e,
Impact, Clear Lowe
Blk Wall, Stu000 Fact
Impact, ClearLow-e
Impact Clear Low-e
Fbrgls Door __
Blk Wall, Stuoao Etd-
-Impad,.Clear.Lowe
Blk Wall, Strom Ext
Impact Clear Low-e
mpact, Clear LowLe
FrmWa11,1/2GypB
Attig Shngl Roof, R
On Grade Depth, Tile
0109
0580
_.. O580
0.109
0.580
0.580
_ _ 0.127
0.109
-0.490
0.109
0.580
0.650
n
n
.__ n
' e '
a
a
_ e
s
-s--
w
w
w
3.15
16.82'
16.82
2.02
11:48
11.48
836
10
_ 1B,
310
0
0
976
164
272
624
112
0
0
0
0
0
0
0
0,
_ - __ 0
0
^ 0
0
0
0
^-0
----0.
0
0
3.15
16.82
16.82
3.69
3.15
-14211.
3.15
16.82
18.85
2.02
28.13
17.02
3.73
2.02
-----I 23
2.02
28.13
12.09
_ __
- 362
23
46
__ 24
317
_____' `5
565
16
48
_-
269
0
35
_ 24
312
_ -- �`5
501
0
48
___
846
390
780
_ 89
965
67.
_ _T�186
541
652
789
_ 89
630
57.
_ _
T 0
0
0
__ 0
-'--0
�0
_
- 0
0
0
___ 0
------0
-_____0
0
0
0
0
'0
_
W
L-G
WI _
1577
272
905
1544
5306
1009
455
- i 580
_ 2811•
_ 0
__�
0
0
0
0
---Q
0
0
h--c�
0101,-�:
0.034
._ .
_�
-
- �
_?94
_ 0.99
_-
1.46_
1.80
_ _ 0.00
_v.195..__.__
_ _ 1558
1558
195,_-.--574---_-.-265102.._..___102__-
-y_ 1558
185
---0
_ -,_ 72
72
--.0
72
�11
--0,---0
301._�149_
71
129
_
v 315
_
_-__0.989
_28.68
.__
_-_
_
6
c) AED exarsion
73
-39
Enwlopelosslgain
1
14747
8896
687
239
12
a) Infiltration
b) Roomventilation
3010
0
841
01
0
0
0
0
13
Intemal gains: Occupants @ 230
Applianoes/other
4
920
4100
0
0
500
Subtotal (lines6 to 13)
17756
14757
687
739
14
15
Less edemal load
Less transfer
Redistribution
Subtotal
Ductloads
28%
38%
0
0
0
17756
4930
0
0
0
14757
5549
28%11111
38%
0
0
96
782
217
0
0
37
776
292
Total room load
Air required (dm)
22687
967
20306
967
1000
43
1068
51
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
't"I't" 2021-Nov1210:32:03
.4CCA Right-Sute@)Unlversa12021 21.0.10 RSU29066 Page 1
ts\WdghtsoftWAC11565.BemeftRdPSLProp.rup Calc=MJ6 FrontDoorfaces: E
+ wrightsoft°
Right-JO Worksheet
House
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beads, FL32966 Phone: 772.800.8413 Email: vidjlyrm@aircalcs.com
Job: 1368
Date: Nov05, 2020
By: Chris Bateman
1
2
3
4
5.
Room name
Fposed tell
Room height
Room dimensions
Room area
M. Bath
17.5 It
9.3 It heaV000l
5.5 x 12.0 ft
66.0 1>?
M Hall
4.0 It
9.3 It heat/000l
4.0 x 6.5 ft
26.0
Ty
Construction
number
U-value
(BtuhAt;°F)
Or
HTM
(Btuh/M
Area
or perimeter (ft)
Load
(Btuh)
Area
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
Blk Wall, Stucco E)d
Impact,ClearLowe
Impact Clear Low-e---Y
Blk Wall, Stumo Ext
Impact Clear Low-e
Impact Clear Lowe
Fbrpls Door _
- 0109
0.580
-- - 0.580
0.109
0.580
0.580
0.127
_ n
n
n --
a
a
a
a
_.�3.15
16.82
- 16682
3.15
16.82
16.82
3.69
2A2
11A8
._ 11A
2.02
28.13
17.02
_ 3.73
0
0
_ � 0
0
0
0
0
�.112
_w 0
0
� ^ 0
0
0
0
0
_-._. 0
0
_- -- �
0
0
0
0
_. O
0
-� - 0
0
0
0
_ 0
.- 0
0
°--- 0
0
0
0
0
O
0
------ 0
0
0
0
y� _ 0
- .0
0
. -0
0
0
0
_ 0
'^
.�. ..- -
0
_ - __.. 0
0
0
0
_ 0
-
y _
��1111
_
W '
-G
Blk Wall, Stucoo Est-" '
.Impact;.Clear.Lowe..
Blk Wall, Stucco Ext
Impact Clear Low-e
-Impact Clear Lowe
FrrnWall,1C::%pB --
AmG Shnpl Raof
On G- ra-d-e D-e R_-
pthTile-
0.109
__.._;0.490
0.109
0.580
_-_-0.650
s
-s_
w
w
w
3 f 5
.__:I.4.21.
3.15
16.82
-a 18.85
--2g4
Q
28.686._.
2.02
_ .-.1223
2.02
28.13
-__ 12.09
80
_- �--1
5
107
0
0
-y_ _.. 0
_ 5�
337
0
0
-__ �.__ 0
_..- 150
__65__19
502
215
0
0
0
0
0
0
_.. 109
_ 6
- - 115
0
0
0
. _� 0
----___.._54
__4_9
- 0
WI -
y
0
0
0
_._ 51:
- - 66
.--57
0
0
----�_0
__.. _.-75
. -_ -
0
0
�..�_ 0
__.._..._ 37.
__-26
26
0
0
____ __0
--.-3�
__--26
I--c�
--_G-
C _-
F_„r
- --0101
0.034
-
-- - .0:989__
va____.66
- 4
6
c) AED exarsion
-26
-5
Envelope loss/gain
1121
440
12501
96
12
a) Infiltration
b) Room ventilation
213
0
59
0
0
0
0
0
13
Internal gains Occupants@ 230
Appliances/other
0
0
0
0
0
0
Subtotal (lines 6 to 13)
1334
500
250
96
14
15
Less mdemal load
Lessiransfer
Redistribution
Subtotal
Dud loads
28%
38%
0
0
0
1334
370
0
0
0
500
188
28%
38%
0
0
-250
0
01
0
0
-96
0
0
Total room load
Airrequired (kim)
1704
73
688
33
0
0
0
0
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
wr7gF�tsofte 2021-Now1210:32:03
& .. -^- Right Suite®Universal 2021 21.0.10 RSU29066 Page 2
tsNwdghtsoft HVAC11565 Bennett Rd PSL Prop.rap Calc = MJ8 Front Door faces: E
+ wrightsoft"
Right-JO Worksheet
House
Air Calm, LLC
7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: viddlyme@aircalcs.com
Job: 1368
Date: Nov05, 2020
By: Chris Bateman
1
2
3
4
5
Room name
Exposed v all
Room height
Room dimensions
Room area
WIC
17.0 It
9.3 ft heat/000l
5.5 x 11.5 ft
63.3 1?
Master Bed
15.0 ft
10.0 It heat/cool
15.0 x 17.0 ft
255.0 it'
Ty
Construdion
number
U-value
(BtihAt;-°F)
Or
HTM
(BtuhAt�
Area (M
or perimeter (ft)
Load
(Btuh)
Area (ft�
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
NP)S
Heat
Cool
Gross
NSS
Heat
Cool
6
11
G
Blk Wall, Stuoio Eikt-'
Impack Clear Lowe
Impact Clear Lowe _
0109
0 580
_--_: 0.580
0.109
0.580
0.580
v 0.127
,n3.15
n
. n
a
a
a
e_
_
16.82
__ 16.82'
3.15
16.82
16.82
3.69
2.02-�B
11.48
_ 11:48
2.02
28.13
17.02
3.73
1;0
_ 0
- 0
0
0
0
0
0
'_ 0
-J 0
0
0
0
" _M o
0
,_ 'o
_ --0
0
0
0
0
0
__ 0
- _ _ 0
0
0
0
. _ 0
0
__ _ 0
, - 0
0
0
0
0
0
��_ 0
-- _ 0
0
_ 0
0
0
_____,__ 0
Blk Wall, Stucco Ext
Impact, Clear Lowe
Impact Clear Low-e
Fbrqls Door
0
0
0
0
0
0
0
0
0
0
0
0
,W
!
Blk Wall; Stucoo E)d
_Impact.Clearl-owe=
Blk Wall, Stu000 Ext
Impact, ClearLm*e
lmpaci Clear Lowe -
Fnn Wall, ll22 Gyp�B _._
A#M hngl Roof, R
•0109
._.0490
0.109
0.580
_ _ 0.650
._ __.._ 010]:
_- 0.034
s •
_.s_-
w
w
w
3.15
.=1421.
3.15
16.82
-18.85
_ _2_
0.99
.2.02
-_,1223
2.02
28.13
12.09
�'46
1.80
0.00
_
107
_0
51
0
-0
0
63
._. _ � 63
107
.�_ 0
51
0
0
.e _ __. 4
, 63
_- 17
337
_ _ 0
161
0
216
0---
103
0
0
6
:_-.0
150
16
0
0
; 0
0'
0
0
_,�0
270
455
.
IW -
134
0
0-0-0
422
272
A
- _
--0'
a4
_m _ , 63
. _ 488
- _ 6
_,- 114
_ 0
_ ^__._
255
;255
--
T 255
_ �15
253
M` 430
0
_ _ 460_
,_ '-0.
6
c) AED exarsi.n
-26
100
Envelope loss/gain
1048
407
1377
1286
12
a) Infiltration
b) Room venfilation
301
0
84
0
286
0
80
0
13
Internal gain& Occupants@ 230
Appliancesrother
0
0
0
0
0
500
Subtotal( lines6to13)
1350
491
1663
1865
14
15
Less e)demal load
Less transfer
Redistribution
Subtotal
Duct loads
28%
38%
0
0
0
1350
375
0
0
0
491
185
28%
38%
0
0
59
1721
478
0
0
23
1888
710
Total room load
Air required (cfm) 173
1724
676
32
2199
94
2598
124
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
*- Rht
wrigF�tsotFt^ 2021-Nov-1210:32:03
.4CC-
P. g-SUte®Urrversal 2021 2110 RSU29066 .0.Page 3
ts\WdghtsoftHVAC\1565BemeftRdPSLProp.rup Calc=MJ8 Front Door faces: E
+ wrightsoft'
Right-J® Worksheet
House
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyme@aircals.com
Job: 1368
Date: Nov05, 2020
By. Chris Bateman
1
2
3
4
5
Room name
Exposed till
Room height
Room dimensions
Room area
GreatRoomiFoyer
28.0 ft
9.3 It heaV000l
1.0 x 345.0 It
345.0 ft'
Pantry
0 It
9.3 ft heat/cool
5.0 x 3.0 It
15.0 ft2
Ty
Construction
number
U-value
(BtiuhAt--F)
Or
HTM
(BtuhAn
Area (ft�
or perimeter (ft)
Load
(Btuh)
Area
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
NrP/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
- 0
0
_.
0
0
0
y _ 0
W - 0
6
_
0
0
0
0
----0-
- '~ 0
0
0
- 0
0
0
0
�-G
BIk WaII,'Stu=E
Impact, Clear Lowe
,Impac( Clear Lowe
Blk Wall, Stucco E)d
Impact Clear Lowe
Impact Clear Lowe
FbrglsDoor
0'109
'0580
_ 0580
0.109
0.580
0.580
__ 0.127
n
n
_n
e -
a
a
e
3.15
16.82
_ 16.82
3.15
16.82
16.82
3.69
202
1148
T_11.48
2.02
28.13
17.02
D
0
' 0
_ 0
- 237
0
46
_.� 24
0
0
_ ._ �0
T 167
0
35
`24
--- - 0
0
_ 0
525
0
780
._v 89
-- 0
0
__. 0
- 336
0
789
_ 89
- q
0
�0
0
0
0
_ _ 0
!
G
111���JJJ
WI _
� G
Blk Wall, Stucco E)d
:Impact Clear.Low--e.
Blk Wall, Stucco E)d
Impact Clear Lowe
Impact Clear Lowe
Fmi Walli l2'..
�� _ z�pB__
AtbGShngl_Roof R -_
On Grade Depth, Tile _
0.109
-0:490._s_
0.109
0.580
0.650
s
w
w
w
3.15
1.421.
3.15
16.82
18.85
2.02
-`12.23
2.02
28.13
12_09
19
_-__-1
0
0
19
--0
0
0
.,- 0
__ 345
._ _-._. 2$
59
w.�..._-_A
0
0
0
37
- 0
, 0
__-0
0
0
0
0
_-____0
0
0
0---
_____0.
0
0
0
0
-__0
0
0
0
W
I -
_
0
0
0
_-_
P .'
C
F _ -
_
�:__ 01Q1.
.__ 0034,
0 989
_
_``-
_�
.__
_ ... 294,
0.99
28.68
_
_.__1._46
1.80
0.00
-_____ _0
_. _
.345
-__. _345
____, 342
..-_-.- 803
-_,_-
04
_.
_-_. �_
15
w.- -15
._
-_ 15
-- _--
15
---0
_, __
27
-- 0
iL
6
o) AED excursion
-168
-1
Envelope loss/gain
2611
1714
15
26
12
a) Infiltration
b) Room ventilation
487
0
136
0
0
0
0
0
13
Intemalgains: Occupants@ 230
Appliancestother
2
460
900
0
0
0
Subtotal (lines 6 to 13)
3099
3210
15
26
14
15
Less extemalload
Less transfer
Redistribution
Subtotal
Ductloads
28%
38%
0
0
113
3211
892
0
0
67
3277
1232
28%
38%
0
0
-15
0
0
0
0
-26
0
0
Total room load
Air required (c-n)
4103
1751
4509
215
0
0
0
0
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
-*- 2021-Nov-1210:32:03
.eA R1gft-Sute®Universal 2021 21.0.10 RSU29066 Page 4
ts\WrightsoftHVAC\1565Banned RdPSLProp.rup CaIc=MJ8 Front Door faces: E
wrightsofte Right-JO Worksheet Job: 1368
House Date: Nov05, 2020
By: Chris Bateman
Air Calks, LLC
7550 Hidden Hammock Ln, Vero Beads, FL32966 Phone: 772.800.8413 Email: viedlyrm@aircalcs.com
1
2
3
4
5
Room name
Exposed v ell
Room height
Room dimensions
Room area
!, t en/Nook
23.5 it
9.3 ft heaV000l
1.0 x 273.0 ft
273.0 ft'
Bed 3
26.5 It
10.0 It heaV000l
1.0 x 168.0 ft
168.0 ft
Ty
Construction
number
U-value
(BtuhA;°F)
Or
HTM
(B
Area (ftF)
or perimeter (ft)
Load
(Btuh)
Area
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
Blk Wall,Stiu¢o Ext -
ImpactClearLowe :
Impact, Clear Lowe- _
Blk Wall, StucoD EA
Impact Clear Lowe
Impact ClearLow-e
Fbrgls Door
0.109
0.580
--�_�0.580
0.109
0.580
0.580
0.127
n
n
_ n _
a
a
a
e
M 3,15
16.82
16.82
3.15
16.82
16.82
3.69
_ 2.02
11AB
11 A8
2.02
28.13
17.02
3.73
.� 0
0
_-;_ 0
0
0
0
0
_ 0
- 0
. 0
0
0
0
0
-^ 0
0
;. 1.�__w_.
0
0
0
0
---0
0
0
0
0
0
0
-- 120
0
_ 16
0
0
0
0
404
0
0
0
0
0
0
-' 327
0
_ - 272
0
0
0
0
209
0
, _ .186.
0
0
0
0
��1111
IL-G-p
IWI �
G
_
Blk Wall, Stucbo Ext
.Impaa:ClearLovve._�
Bilk Wall, Stucno EA
Impact, Clear Lowe
ImpactClearLowe
-Frm Wall,1_/2.' GyP B
Atkq Shngl Roof R _
On_Grade Depth, Tile _
_
0.109
._-o.490
0.109
0.580
0.650
_, '0.1'o
OA34
s
---s,
w
w
_w
_
_ 3.15
- 1421.
3.15
16.82
18.85
0.99
20.68
2.02
___12.23
2.02
28.13
12.09
- 1.80
0.00
~ 0
:�___ 0
219
0
- _ 48
273
i p-273
J 0
�0
171
0
_ _ 48
_ _
0
_ __
0
-______0
344
0
.�T 580
-_ 493
0
�- 0
----0
145
0
0
0
0
_ A
457
0
0
_
__.-_--.0.
292
0
0,
IW -
--0
537
0
_ _ 905
271,
674
145
0
0
I--ci
_
P -_----
C _ .y
F ___-__
_- _
_ 168
_' 168
168
_27
167.
_ 303
0
_- �0.989
_ _
. `
_273
-� `'24
-�,
760
-.
m
-
_
6
d) AED excursion
295
-69
Envelopeloss(gain
2387
1712
1983
922
12
a) Infiltration
b) Roomventilation
416
0
116
0
505
0
141
0
13
Internal gains: Occupants@ 230
Applianoask her
2
460
1700
0
0
250
Subtotal (lines 6 to 13)
2803
3988
2488
1313
14
151
Less extemalload
Lesstransfer
Redistribution
Subtotal
Duct loads
28%
38%
0
0
6
2809
780
0
0
10
3998
1503
28%
38%
0
0
10
2497
693
0
0
17
1329
500
Total room load
Airrequired(dm)
3589
153
5501
262
3191
136
1829
87
Calculations approved WACCAto meetall requirements of Manual J 8th Ed.
i.F wri" c irt- 2021-Nov-1210:32:03
Right-SuteO Universal 2021 21.0.10 RSU29066 Page 5
tsm ghtsoftHVAGY1565Bennett RdPSLProp.nQ Calc=MJ8 Front Door faces: E
-i{�- wrightsoft Right-J® Worksheet Job: 1368
House Date: Nov05, 2020
By: Chris Bateman
Air Calks, LLC
7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: %icidlyme@aircalcs.com
1
2
3
4
5
Room name
ENposed Hell
Room height
Room dimensions
Room area
Bath
6.0 ft
9.3 It heat/000l
9.0 x 6.0 ft
54.0 ft'
Linen
0 ft
9.3 ft heaUcool
2.5 x 3.0 ft
7.5 ft'
Ty
Construction
number
U-value
(BWhAt�-°F)
Or
HTM
(Btuhfin
Area (M
or perimeter (ft)
Load
(Btuh)
Area (n
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
\�--G
Blk Wall, Stump FAQ
Impact, ClearLow-e
.Impac�ClearLowe.
Blk Wall, Stucco Ext
Impact Clear Low-e
Impact, Clear Lowe
FbrglsDoor
Blk Well, Stucco E)d
.Impad.Clearl-owe_
Blk Wall, Stucoo Ext
Impad ClearLawe
Impact Clear Lowe .-
At ci Shngl Roof, R _--
Grade Depth, Tile -
0.109
0.580
0.580
0.109
0.580
0.580
0.127
n
n
-n .
a
a
a
a
3.15
16.82
2.02
11.48
56
10
0
- 46
0
0
0
0
0
0
_-._---0
0
0
0
-- _ -- 54
_ �. 6
- -
164
0
0
0
0
0
_--0
0
0
0
- _54
- --172
-- 93
112
0
0
0
0
_ 0
,-_0
0
0
0
--- 0
0
0
0
0
0
0
0
---- - p
0
0
0
0
0
- 0
_.--__0
0
0
0
- O
0
0
0
0
0
0
_.-_-0
0
0
-__0
-_-- 7
- --
.. _--___ 0
0
0
0
0
0
- 0
_______A
0
0
._ 0
_0.
_ --_- -14
- - --
T.16.82
3.15
16.82
16.82
315
---1.4.21.
3.15
16.82
- 18:85
_- 0_99.._
28.68
.-__41A48
2.02
28.13
17.02
2.02
_..12.23
2.02
28.13
12.09
1.80
__
0
0
0
___
0,
_- _-0
0
0
0
54
_
WII �
L_G
__-
0.109
_-__0.490
0.109
0.580
_. 0.650
. _ _ -- 0.034
0.989
u
_s_
w
w
_w_
___.
_, _
W
I--G
0
0
0
� C-
F _. _.._..On
,. _ _ 97
-- -
__-
--_-.__ 8
--- =
8
_-_ 0.00
. __-
-_. _ . 54
- - --0
-----
_ .-.
6
c) AED exarsion
-17
-1
Envelope losstgain
535
286
7
13
12
a) Infiltration
b) Room ventilation
106
0
30
01
0
0
0
0
13
Internal gams: Occupants@ 230
Appliancestother
0
0
0
0
0
0
Subtotal (lines6 to 13)
641
315
7
13
14
15
Less extemalload
Less transfer
Redistribution
Subtotal
Duct loads
28%
380/.
0
0
11
652
181
0
0
19
334
126
28%1
380/0
0
0
-7
0
0
0
0
-13
0
0
Total room load
Air required (dm)
1
135
833
460
22
0
0
0
0
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
- wrYgF�tsot- 2021-Nov-1210:32:03
ACCP. Rigk-Sute®U iversal 2021 21.0.10 RSU290fifi Page 6
ts\WrightsoftHVAC\1565BemettRdPSLProp.nQ Calc=MJ8 Front Door faces: E
-- wrightsoft" Right-J® Worksheet Job: 1368
House Date: Nov05, 2020
By. Chris Bateman
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beadt, FL32966 Phone: 772.800.8413 Email: v ddlyrne@aircalcs.00m
1
2
3
4
5
Room name
Exposed well
Room height
Room dimensions
Room area
Bed 2
36.5 ft
10.0 ft heaUmol
1.0 x 1820 ft
182.0 fF
Hall
0 ft
9.3 ft heat/000l
3.5 x 9.0 ft
31.5 f 2
Ty
Construction
number
U-value
(BtuhAt;°h)
Or
HTM
(B
Area (T)
or perimeter (ft)
Load
(Btuh)
Area
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
- 3.15
16.82
^- 16_82
3.15
16.82
16.82
3.69
- 2.02
11.4E
_ 11A8
2.02
28.13
17.02
3.73
-- 160
0
0.,---0
125
23
0
0_
i _ 160
0
102
0
0
0
-�0
-~ 0
0
0
0
0
0
Blk Wall, Stu000 Eid
Impact, Clear Lowe
Impact ClearLow_e_----
Blk Wall, Stucoo Ext
Impact Clear Lowe
Impact Clear Lowe
FbrglsDoor _
B I k WalI, SWcoo E)d
.Impact CIear.Lowe-._-,
Blk Wall, Stucoo Ext
Impac,ClearLowe
ImpactClearLawe--_
FrrrtW_all,1/2`-Gyp Bw_
AtbgShngl Roof, R__- _.
On Grade Depth,Tile---
- 0.109
0.580
--------0;580
0.109
0.580
0.580
n
n
^n
a
a
a
e
-504
0
--- 0
321
390
0
0
'322
0
--.----0
205
652
0
_ 0
-,----0
0
0
-_ 0
----- 328
------0
0
0
-_ _--_-0
0
0
0
0
0
0
0
0
0
0
'
0
0
0
0
0
-----
_
W�
L--G0
�0.127
0.909
__.T_ 0.490
0.109
0.580
_ 0.650
0.034
_
s
-s_
w
w
_ w
�-
3.15
_-i_4.21:
3.15
16.82
_ 18.85
_-� 0.99
2.02
1223
- 80
- _
80
___-_0
0
0
_ 0
-_-__182
7
252
___ __0
0
0
-__ _ 0
_...._-_-32
_____0
0
0
_- __. 32
_.
0
0
___---0
0
0
---, 57
--------0
W
2.02
28.13
- 12A9
1.80
-' -0
0
0
____. _ 0
-^---182
_ _. , 182,
_0
0
0
_---_ 0
180
-----1047
0
0
_.. --_- 31
^_
P _�
F
-_--
-_,0.00
--•-3z
---.----0
-----_-_.'0
6
c) AED excursion
32
-3
Envelope loss(gain
2694
1702
31
54
12
a) Infiltration
b) Roomventilation
695
0
194
0
0
0
0
0
13
Internal gains Occupants@ 230
Appliancesrother
0
0
250
0
0
0
Subtotal (lines 6 to 13)
3390
2146
31
54
14
15
Less extemalload
Less transfer
Redistribution
Subtotal
Dudloads
I281/o
38%
0
0
10
3400
944
0
0
17
2164
814
28%
38%
0
0
-31
0
0
0
0
-54
0
0
Total room load
Airrequired(dm)
4344
1851142
2978
0
101
0
0
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
-1rt- wrigtitsotFt- 2021-Nov-1210:32:03
Right-SuteO Universal 2021 21.0.10 RSU29066 Page 7
ts\WdghtsoftWADI 565 Berried Rd PSL Prop.r p Calc= MJ8 Front Door faces: E
Duct System Summary Job: 1368
- - wrightsoft® Date: Nov05, 2020
House By. Chris Bateman
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vicidlyme@aircalcs.com
For: Rosa Residnece, NisAirAirConditioning
1565 Bennett Rd., Fort Pierce, FL 34947
External static pressure
Pressure losses
Available static pressure
Supply / return available pressure
Lowest friction rate
Actual airflow
Total effective length (TEL)
Heating
0.70
in H2O
0
in H2O
0.70
in H2O
0.576 / 0.124
in H2O
0.300
in/100ft
967
cfm
233
Cooling
0.70 in H2O
0 in H2O
0.70 in H2O
0.576 / 0.124 in H2O
0.300 in/100ft
967 cfrn
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FR
Diam
(in)
H x W
(in)
Duct
Mat
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
Bath
h 833
43
26
0.312
4.0
Ox0
VIFx
54.4
130.0
st3
Bed 2
h 4344
222
170
0.300
8.0
Ox 0
VIFx
62.0
130.0
st3
Bed 3
h 3191
163
105
0.327
7.0
Ox 0
VIFx
51.2
125.0
st3
GreatRoom/Foyer
c 2254
105
129
0.397
6.0
Ox0
VIFx
40.2
105.0
st1
GreatRoom/Foyer--A
c 2254
105
129
0.398
6.0
Ox0
VIFx
39.8
105.0
st1
Kitchen/Nook
c 2750
92
157
0.401
6.0
Ox 0
VIFx
38.6
105.0
st1
KitchenNook A
c 2750
92
157
0.401
6.0
Ox 0
VIFx
38.5
105.0
st1
Lary
c 1068
51
61
0.456
5.0
Ox0
VIFx
26.3
100.0
st2
M. Bath
h 1704
87
39
0.473
5.0
Ox 0
VIFx
21.7
100.0
st2
Master Bed
c 1299
56
74
0.473
5.0
Ox 0
VIFx
21.9
100.0
St2
Master Bed -A
c 1299
56
74
0.479
5.0
Ox 0
VIFx
20.3
100.0
st2
WIC
h 1724
88
39
0.481
5.0
Ox 0
VIFx
19.6
100.0
St2
Supply Trunk Detail Table
Trunk
Htg
Clg
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
Orn)
FR
(fpm)
(in)
(in)
Material
Trunk
st3
PeakAVF
428
301
0.300
784
10.0
0 x 0
UnlFlx
st1
st1
PeakAVF
821
873
0.300
816
14.0
0 x 0
VinlFlx
st2
PeakAVF
339
287
0.456
767
9.0
0 x 0
VinlFlx
wrightsoft® 2021-Nov-1210:32:04
�_ Rigft Sute® Universal 2021 21.0.10 RSU29066 Page 1
�+M...ts\WdgtisoftWAC\1565BemettRdPSLProp.np Calc=MJ8 FrortDoorfaces: E
Grille
Htg
Clg
TEL
Design
Veloc
Diam
H x W
Stud/Joist
Duct
Name
Size (in)
(cfm)
(cfm)
(ft)
.
FR
(fpm)
(in)
(in)
Opening (in)
Mat
Trunk
rb4
Ox 0
201
187
41.4
0.300
575
8.0
Ox 0
VIFx
rb1
Ox 0
574
698
0
0
0
0
Ox 0
Wx
rb6
Ox0
222
170
0
0
0
0
Ox 0
MFx
rb3
Ox0
163
105
0
0
0
0
Ox 0
MFx
-*- wrightsoft® 2021-Nov 1210:32:04
A—r—� RighFSriteOUriversal202121.0.10RSU29066 Page
44CCk ...ts\WrightsoftWAQ1565BemettRdPSLProp.np Calc=MJ8 FrordDoor faoes: E
-- wrightsoft° Manual S Compliance Report
House
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vickilyrm@aircalcs.com
For. Rosa Residnece, NisAirAir Conditioning
1565 Bennett Rd., Fort Pierce, FL 34947
Design Conditions
Job: 1368
Date: Nov05, 2020
By. Chris Bateman
Outdoor design DB:
90.4°F
Sensible gain: 21078
Btuh Entering coil DB: 76.8°F
Outdoor design WB:
77.4°F
Latent gain: 6121
Btuh Entering coil WB: 64.0°F
Indoor design DB:
75.0°F
Total gain: 27199
Btuh
Indoor RH:
50%
Estimated airflow: 967
cfm
Manufacturer's Performance Data
at Actual Design Conditions
Equipmenttype:
SplitAC
Manufacturer:
Lennox
Model: ML14XC1S030-230A**+CBA27UHE-030-230*++TDR
Actual airflow.
967
cfrrt
Sensible capacity:
20300
Btuh
96% of load
Latent capacity:
8700
Btuh
142% of load
Total capacity:
29000
Btuh
107%of load SHR: 70%
Design Conditions
Outdoor design DB: 41.0°F Heat loss: 24139 Btuh
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype: Elecstrip
Manufacturer: Model:
Actual airflow: 967 cfrn
Output capacity: 6.9 kW 97% of load
Meets all requirements ofACCA Manual S.
Entering coil DB: 68.1 °F
Temp. rise: 50 °F
-�- wrightsoft® 2021-Nov-1210:32:04
�� AU -/ -..��, Right Sute®Uriversal 2021 21.0.10 RSU29066 Page 1
A...tsUrigttsoftHVACt1565Bennett RdPSLProp.np Cale =MJB Front Door faces: E
a
Job M 1368
Performed by Chris Bateman for:
Rosa Residnece
1565 Bennett Rd.
Fort Pierce, FL 34947
Air Calcs, LLC
7550 Hidden Hammock Ln
Vero Beach, FL 32966
Phone: 772.800.8413
vicki[ynne@aircalcs.com
Scale: 1 :104
Page 1
Right -Suite® Universal 2021
21.0.10 RSU29066
2021-Nov-1210:36:45
VAC\1565 Bennett Rd PSL Prop.rup