HomeMy WebLinkAboutPanel Limits AHJ Introduction letter ri Panel Limits: A NEC 705.13 complaint Power Control System 07/12/2021 To whom it may concern: This letter is meant to describe and provide listing documentation for Panel Limits— a Powerwall and Powerwall+ integrated Power Control System for busbar protection. Panel Limits is a busbar protection method listed for use in compliance with 2020 NFPA 70 705.13 and UL1741 PCS. This packet will provide a functional understanding of Panel Limits, demonstration of code compliance, example configurations and listing documentation. Sample configuration: T3o{er w't: - Erie Meier 01 I I I Crld Con trOliqu SourcQ(2o Virtkiol Fl;�ngl- or Busbar Key Terms: Controlled sources —Tesla ACPW and Tesla Powerwall+ Uncontrolled sources—external solar inverters or similar power production sources connected to the virtual panel. Virtual Panel—a group of panelboards and conductors that are considered as one single panel with respect to Panel Limits. Tesla Panel Limits Power Control System monitors the amperage flowing into a virtual panel from the grid, controlled and uncontrolled power sources. As the measured current approaches the configured Panel Limit, the site controller will first reduce the power output of the energy storage system and then curtail controlled solar output. In accordance with the Powerwall+ UL1741 PCS listing all solar connected to the Powerwall+ solar assembly is classified as a controlled power source. The utilization of Tesla Panel Limits PCS ensures the virtual panel will never see a greater ampacity than its lowest ampacity busbar rating. T - 5 L n Panel Limits: A NEC 705.13 complaint Power Control System 07/12/2021 NFPA 70 705.13 (A)-(E) Compliance 705.13(A): Monitoring • Tesla Site Controller receives meter data from Backup Switch or Backup Gateway and or Neurio (W1/W2) meters. • Tesla site controller receives controlled current data of the AC output of the Powerwall+ and Powerwall • The summation of current is continuously monitored and compared with configured Panel Limit ampacity setting. This is true for both grid and on-site power production sources. • If communication from any meter is lost all controlled power production sources are curtailed to 0. NEC 705.13(B): Settings • Panel site limit setting is restricted to Tesla personnel. • Configured Panel Limit will never be greater than the rating of the smallest busbar within the virtual panel. • The default panel limit setting is 100A to align with minimum service requirements for single-family dwellings per NEC 230.79(c). Panel limit amperage value can be configured up to 200A. • Panel Limit amperage value is determined on a site-specific basis, ensuring all busbars and feeder conductors abide by 705.12 provisions either through traditional compliance means or the panel limits amperage setting as allowed by 705.13. NEC 705.13(C): Overcurrent Protection • Tesla Site Controller software is UL 1741 PCS certified as a secondary overcurrent device • Tesla Site Controller curtails the output of the ESS and solar as measured ampacity approaches the Panel Limit. Once ESS and solar have been curtailed, loads will be fed exclusively from the grid; thus, the main breaker or breaker in the upstream panel still acts as primary OCPD to provide busbar protection. NEC 705.13(D) Single Power Source Rating • Each Powerwall is connected to the virtual panel with the required 30A breaker and 50A breaker for each Powerwall+. o Breaker acts as primary OCPD ensuring ampacity of connected conductors does not exceed conductor ampacity rating. o Each unit by design is unable to exceed the busbar rating. NEC 705.13(E)Access to Settings • Panel Limits feature is only adjustable by Tesla personnel. • Non-Testa personal do not have the permissions needed to change panel limit settings. Changing Panel Limit setting to anything other than the default 100A setting requires contacting Tesla Tier 2 support to request Panel Limit ampacity setting change. T = 5 L n Panel Limits: A NEC 705.13 complaint Power Control System 07/12/2021 705.12 Compliance Per 705.12 the PCS controller configured setting shall be considered the power- source output circuit current in 705.12(A)through (E). • If no uncontrolled sources present, then by default panel complies with 705.12(B)(3)(1) i.e, the 100% rule. • If uncontrolled sources present, such as solar utilizing a traditional stand- alone PV inverter, then 705.12(B)(3)(2)compliance required equal to the sum of uncontrolled sources i.e., 120% rule 705.12 Load-Side So-uree Corms-e uEL& Thc 0UtpUL Of WL inLt•r- connected electric power source shall l-)e permitted to he connected to the load We of the ser%sire dir�connecting means of Ltlr oLhrr sUUft a(s) ;It any disuibution oq uipinrnl on dic premises, Where distribution equipment or feeders are fed simultaiwously by a primary source of electricity and mac or more other power source and are capable of suppl}61g muld- ple hrwjnr.h rirciiits nr Fe.Mcrs, nr both, the interconnecting V1LLipLatnL Shall comply WiLh 705� 12(A) throu6ji (E), WILCIZ a power control system (PCS) is installed in accordance with 705-13, the PwGting of the. PC'S rpntroller i�hall be considered the poWur—sOLtrce output circuit cwTenL iLn 705.1 (A) through (E). UL 1741 Power Control Systems Compliance Busbar labeling requirements PCS controlled current setting will be indicated on a field applied marking label that will be applied at all panelboards that are part of the virtual panel. PCS Controlled Current Setting:_A The maximum output current from this system towards the main panel is controlled electronically.Refer to manufacturer's instructions for more information (Ampacity to be marked by installer) CT Labeling requirements As required by the UL Standard, the following label appears on the dedicated CT's (if used)for the Panel Limits Power Control System WARNING: THIS SENSOR IS PART OF POWER CONTROL SYSTEM. DO NOT REMOVE. REPLACE ONLY WITH SAME TYPE AND RATING. T - 5 L n Panel Limits: A NFPA 70 705.13 complaint Power Control System 06/29/2021 Example Single Lines showing most common configurations by product type Powerwall+ and Gateway 2 for Whole Home Backup Virtual Panel Site Meter T N 0 - - * Solar Meter T S 5 L R Backup panel Backup Gateway 2 Meter socket panel Grid Powerwall+ F1 Optional System Shutdown Switch Powerwall+ and Gateway 2 for Partial Home backup Virtual Panel Site Meter Solar Meter Backup panel Backup Gateway 2 Main panel Meter socket panel Grid Powerwall+ Optional System Shutdown Switch T - 5 L n Panel Limits: A NFPA 70 705.13 complaint Power Control System 06/29/2021 Powerwall+ and Backup Switch for Whole Home Backup Virtual Panel Backup Switch Site Meter . . Meter Backup panel Service disconnect Meter socket panel Grid Powerwall+ El Optional System Shutdown Switch ACPW w/Uncontrolled Solar Inverter and Gateway 2 for Whole Home Backup Virtual Panel Site Meter Solar Meter Solar Inverter Backup panel Backup Gateway 2 Meter socket panel Grid Uncontrolled Source Powerwall F] Optional System Shutdown Switch ACPW and uncontrolled solar inverter and Gateway 2 for partial home back up Virt,al Panel Site Meter 0 Q Solar e o Meter O Solar Inverter Backup panel Backup Gateway 2 Main panel Meter socket panel Grid Uncontrolled Source Powerwall a Optional System Shutdown Switch Number: MS-0009914, Attacment I TOVRheinlan& Conformity Letter Revision: J Y Revision: 0 Effective date: 06/21/2019 Tesla Inc. 23rd June 3500 Deer Creek Road, 2021 Palo Alto, CA 94304 USA Report Number: 32195439.001 Project Number: 234171546 and 234173937 Product(s)tested: Grid Support Utility Interactive Inverter with Gateway 2 or Backup Switch. Model(s): Powerwall+(1850000-XX-Y) Dear Mr./Mrs.Jonathan McCormick/Viraj Andrabadu/Nirja Vakil, Based on the evaluations undertaken,the model(s) of the below product have been found to comply with the requirements of the referenced specifications at the time the tests were carried out. Nationally Recognized TUV Rheinland of North America, Inc. Testing Laboratory(NRTL) NRTL Issuing Office Address 1279 Quarry Lane, Suite A, Pleasanton, CA 94566 Applicant Name Tesla, Inc. Applicant Address 3500 Deer Creek Road, Palo Alto, CA 94304, USA Model Numbers Powerwall+(1850000-XX-Y)with Backup Switch TUV Rheinland of North America,Inc. • ACPW(1092170-XX-Y, 2012170-XX-Y, Pleasanton Office 3012170-XX-Y) 1279 Quarry Lane, • PVI (1538000-XX-Y) suite A,Pleasanton, • Backup Switch (1624171-XX-Y) CA 94566 Tel:(925)249-9123 Powerwall+(1850000-XX-Y)with Gateway 2 Fax:(925)249-9124 Web: • ACPW(1092170-XX-Y, 2012170-XX-Y, www.us.tuv.com 3012170-XX-Y) TUV Rheinland of • PVI (1538000-XX-Y) North America,Inc. • Gateway 2 (1232100-XX-Y) North American Headquarters 12 Commerce Road Software/Firmware Version 8586a41 c49c Newtown,CT 06470 Tel:+1(203)426- 0888 Standard(s)Tested UL 1741: Standard for Inverters, Converters, Fax:+1(203)426- Controllers and Interconnection System Equipment for 4009 Mail:info@tuv.com Use with Distributed Energy Resources, April 20, 2010. Web:www.tuv.com Edition 2 [(Supplement SA)+R:15Feb20181, Power Control Systems (PCS), Certification Requirement Decision 3/8/2019 Page 1 of 5 Number: MS-0009914, Attachment 1 TUVRheinland" Conformity Letter Revision: 0 Effective date: 06/21/2019 PCS limits defined by NFPA Compliant and tested on 22"d June 2021 2020 edition section 705.13 Testing period: 04/21/21—05/07/21, 06/22/21 Reference reports: This document should be read together with 32195440.001 and 32195440.002 Powerwall+ ratings Nominal Battery Energy 13.5 kWh Nominal Grid Voltage 240 VAC Voltage range 211.2-264 VAC Maximum continuous Power On Grid 5 kW input/7.6 kW output BESS Continuous Power 5 kW input/5 kW output Maximum continuous Power Off Grid 5 kW input/9.6kW output Frequency 60 Hz Phase 240 VAC: 2 wire+ neutral +ground Maximum continuous Power On Grid 32 A output BESS Continuous Power 24 A input Maximum continuous Power Off Grid 40 A output PV Maximum Input Voltage 600 VDC PV Operating DC Input Voltage range 60-550 VDC PV DC MPPT Voltage range 60-480 VDC Maximum Current per MPPT 13 A Maximum Short Circuit Current per MPPT 15 A Overcurrent Protection Device 50 A Software/Firmware version 8586a41c49c Enclosure Type Type 3R Rated ambient temperature [°C] -20°C to+50°C PCS ratings Maximum PCS controlled current 200 A Maximum Open Loop response time 9.09 seconds Average Open Loop response time 5.01 seconds Page 2 of 5 Number: MS-0009914, Attachment 1 TOVRheinland" Conformity Letter Revision: 0 Effective date: 06/21/2019 Attachments: 1. System Label for PCS TESLA POWERWALL+BATTERY ENERGY STORAGE SYSTEM GRID SUPPORT UTILITY INTERACTIVE INVERTER F WE art t M"Ft L_ Photovoltaic(PV)and Battery Energy Storage System{BESS)Power Conversion Equlpmant Prctamt Cla55 rass I Ennosum-Type type-M Operating Temperature Range -20-C to 50°C ❑elated Temperature Range 43aC to SVC PV Inverter Topology Nw Ndated am Inverter Topobgy L�bwdl Nominal Battery Energy 13.5 kw-hr n-:ey type upon M'55 15E k9 Photovoltaic(PV)and Battery Energy Storage System(BESS)Specifications Nominal Grid Voltage 209 VAC 340 VAC (Input/output) Grid Voltage Range lS.L229.8 VAC 211.2-2fA VAC Mahn m Continuous 6-6 kVA 7-6 WA Output Power On-ad Mminum Continuous 9.6 WA Output Power oR-Grid BESS 1,jwMm 5 k:A 5.Bl Cuntlnuous Input Power Frewency 60 Fla MmInnun Continuous Ouput 32 AAC current on-Grid Mmlman Continuous Ouput 4a AAC Current oi BE55 MW Im 24 AAC Contlnuous Input Current Pd AIIXInY.In Input Current 13 ADC woperatngDC Input voltagelavnge 6o-56ovnC Phase 20e VAC/240 VAC 2 W HH-PE Mulnlun Supply Fault current 10 IRA AC cmr=5 to 1151d ss40 the maximum operating current nN this systan may be controlled eledlm-ca v.ReW tothe wnuradurers Instruct.a�n i rror 1Jc-e--la•mvilj rt l f7\ A'\ �j-;SMinutes PHOTOVOLTAIC cPV)RAPID SH DTDO4VN SYSTEM EDIVITEENT [=ALRION:ais�t of F�Fcrai��ocrc.oa raoT CAI-r710N:eoiN Aconrdo'oC wLr-E �act-Ns L cA.Vn,:,m Z..THEw nm�Ar sEx PosEo to WARNING L—RIiC s Ck—A RD_THE DC MFNr POWQ2 FE6 FROM MORE THAN ONE SOD—. T T= SLIT — � Page 3 of 5 Number: MS-0009914, Attacment I TOVRheinlan& Conformity Letter Revision: J Y Revision: 0 Effective date: 06/21/2019 Thank you for the opportunity to service your product testing needs. Please do not hesitate to contact our engineering or sales team for any questions you may have. Evaluated by: Reviewed by: Himanshu Vaidya Howard Liu Test Engineer Manager,Power Electronics Segment —Americas Email:hvaidya@us.tuv.com Email:hliu@us.tuv.com Page 4 of 5 Number: MS-0009914, Attacment I TOVRheinlan& Conformity Letter Revision: J Y Revision: 0 Effective date: 06/21/2019 Revision History 6/22/21—Himanshu Vaidya - Added project number 234173937 — project to test and evaluate Overcurrent limitation feature as per UL 1741 PCS standard Clause 208.1, A with respect to NFPA 70 2020 edition section 705.13. - Added testing period date 6/22/21 - Added row in Description table for above feature mentioned. Page 5 of 5 rtek wntertek te 3933 US Route 11 C Cortlanlan d, NY 13045 Total Quality.Assured. Telephone:607-753-7311 www.inteilek.com Verification of Conformity On the basis of the evaluations undertaken, the sample(s) of the below product have been found to comply with the requirements of the referenced specifications at the time the tests were carried out. Applicant Name &Address Tesla Inc. 3500 Deer Creek Road, Palo Alto, CA 94304 Product(s) Tested AC Powerwall - Grid Support Utility Interactive Inverter Gateway Ratings and principal characteristics See Amendment 1 AC Powerwall Model(s) 1092170-xx-y, 2012170-xx-y, 3012170-xx-y Gateway Model(s) 1232100 -followed by two numbers; followed by one letter Brand name/ MD5 checksum Tesla/ b624638a90cf Relevant Standard(s)/Specification(s) Inverters, Converters, Controllers And Interconnection System Equipment For Use With Distributed Energy Resources [UL 1741:2010 Ed.2(Supplement SA)+R:15Feb2018] Power Control Systems (PCS) Certification Requirement Decision 3/8/2019 NFPA 70: 2020, 705.13 Verification Issuing Office Name & Intertek, 3933 US Route 11, Cortland, NY 13045, USA Address Gateway Date of Test(s) 11/4/2019-12/4/2019, 4/23/2020 to 5/13/2020, 6/23/2021 Verification/Report Number(s) 104267560CRT-001, 103879962CRT-003, 104709967CRT-001 NOTE:This verification is part of the full test report(s)and should be read in conjunction with it. This Verification is for the exclusive use of Intertek's client and is provided pursuant to the agreement between Intertek and its Client.Intertek's responsibility and liability are limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement for any loss,expense or damage occasioned by the use of this Verification.Only the Client is authorized to permit copying or distribution of this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material,product or service must first be approved in writing by Intertek. The observations and test/inspection results referenced in this Verification are relevant only to the sample tested/inspected. This Verification by itself does not imply that the material,product,or service is or has ever been under an Intertek certification program. Signature Name: Liyuan Liu Position: Sr. Project Engineer Date: June 24,2021 www.intertek.com GFT-OP-11e(7-March-2017) Amendment Backup Gateway North1 Nameplate gACICUP GATE�fAY� r_o„ra,.6 inc UL STdS 57,91E✓lBfiBwL PLACE TESLA PN f 6ARC�OE LA9EL HERE Cv-hTwd m: C54 STOfi QZ3�2�6 d a14 PROTE Tf4rE CLASS LLA55 I ENQOSUI�TYPE{UL 90} FFMA TYPE 3R,I7hNTIGHT OPERATING iEMPERIkTURE RANG �°F TQ 122°F J��I NPUT/OL1TPl1T i+{1LT/uC�RAFlC�(2$) 11i�2-0OVAC MAX CURREM 20dA MAX INaJT 51-IORT❑RCUIT QJRI�Ni 10kA• FRE4LENCY FAHz MAXIMLM P4WE]t A9kW 'W}EN RROTE{TEa 9Y 206 AMPERE F'A4%HJM CLJL55 J FUSE THIS PAHEL90AR6 5 SUIfAEILE FOR 4Jg OH A CIRCUIT CAPAELE OF�ELI5fE13� FIdT FIORE TF{4H 77kF,R.F75 SYMMETRIG4L AMPERES,�16 VOL TS M,47�AU7 SEE Cb4JfAEY{TATFG4 '�„�"I F4R A{OITICNAL SAFETY NFORht4T14H CAUTIO�'1: RI54{OF ELECTRIC SHOUC_MULTIPLE VOLTAGE 50lJRrF� TERMINATEd WITHIN_REFER SEF�fICINGTQ QUALJFE7} PERSONAfL dI5C.ONNECT E,4Cf-I CIR0.1ff 9EFORE SERVICING_ COMPARTMENT FOR SUPPLY AUTHORITY USE ONLY 4YARNING:ISOLATE A.T 9LIPPLY ALJTHORffY SOURCE BEFORE ENTERING THIS COMPARTMENT RI SC3LIE dE CHOC ELECTRIC3UE. PLUSIEURS SOURCES DE TENSION 50NT CDNNECT�ES a1 L'FTf�]TIEUR dE OET �OUIPMENT. CHAOUE CRCUIT Doff ETRE d�CONNECT� INdIVaUE1.LE�IENT A,Y,IWf INTERYEMION_ LA MAINTENkNOE dOIT ETRE EFFECTUr'E PAR dU PERSONNEL OUALIFI�. COMPARTMENT R�SERV�AU DISTRIBUTEUR DT�ECTRICITE lSVERTISSE)4ENT=ISOLER a�LA SOURCE d'ALIMENTATION ❑t.I dISTRIBiJTEUR AYIWT U'OUVRIR CE CDMPARTIMENT THE MA7CIMUM OPERIkTING CURRENT OF THIS 5Y5TE71 MIiY BE CONTROLLEd ELECTRONICALLY_REFER TO THE MANUFACTURER'S INSTRUCTIONS FOR MORE INFORMATION.MA7UMLIM PCS OdNTR10LLEd QJRRENT SETTING 2U0 AMPS SUITABLE FOR USE AS SERVICE EQUIPMENT CLASS CfL PANELJjOARi} T � SLn (7-March-2017) Additional Gatewa 2.0 NA PCS ratings Maximum PCS controlled current 200A Average Open loop response 0.96 seconds (60ms added for delay between 1st and 9th ACPW Maximum open loop response 1.76 seconds (60ms added for delay between 1st and 9th ACPW) AC Powerwall Ratings Protective Class Class I Enclosure Type Type 3R Ingress Protection Battery& Power IP 67/IP 56 Electron ics/M i ring Operating Temperature Range -200C to+50°C Derated Temperature Range +43°C to+50°C Inverter Topology Isolated Battery Energy 13.5 kWh Battery Type U.lon Weight 125 K AC Input/Output Nominal Voltage A.C. 100/120/200/208/220/230/240 Voltage Range&Max 90-110 V AC: 25A Continuous Current 114-126 V AC: 24A 180-220 V AC: 25A 198-220 V AC: 24A 198-242 V AC: 25A 207-253 V AC: 25A 228-252 V AC: 24A Frequent Range/Nominal Hz 50-60; 50/60 Max Continuous Power(kVA) 100 V AC: 2.5 kVA 120 V AC: 2.9 kVA(USA) 200 V AC: 5 kVA 208 V AC: 5 kVA(USA) 220 V AC: 5.5 kVA 230 V AC: 5.8 kVA 240 V AC: 5.8 kVA(USA) Power Factor Range -0.85 to+0.85 Max Output Fault Current 32 A AC 200V/208V/240V; 2W +N +PE; Phase 20; All Other Voltages; 1 W +N +PE; 10 Max Supply Fault Current 10 kA AC www.intertek.com GFT-OP-11e(7-March-2017) Lntertek k 3933 US Route 11 Cortland, Cortland, NY 13045 Total Quality.Assured. Telephone:607-753-7311 www.intertek.com Revision History Date Engineer/Reviewer Description of Change 6/3/2020 Dipesh Patel Changed Model number from "Backup Gateway North America 2.0"to "1232100—followed by two numbers;followed by one letter" 11/13/2020 Liyuan Liu Added new AC Powerwall model 3012170-XX-Y, G104505850CRT which using the alternate battery cell LG Chem IN21700M48F. 6/24/2021 Liyuan Liu Added Relevant Standard(s)/Specification(s) NFPA G104709967CRT 70: 2020, 705.13. www.intertek.com GFT-OP-11e(7-March-2017)