jb_349367_00_e_acad_b_01_EE
ABBREVIATIONS ELECTRICAL NOTES JURISDICTION NOTES A AMPERE AC ALTERNATING CURRENT BLDG 1. THIS SYSTEM IS GRID—INTERTIED VIA A UL—LISTED BUILDING CONC CONCRETE DC DIRECT CURRENT POWER—CONDITIONING INVERTER. EGC EQUIPMENT GROUNDING CONDUCTOR (E) 2. A NATIONALLY — RECOGNIZED TESTING EXISTING EMT ELECTRICAL METALLIC TUBING FSB LABORATORY SHALL LIST ALL EQUIPMENT IN FIRE SET—BACK GALV GALVANIZED GEC GROUNDING COMPLIANCE WITH ART. 110.3. ELECTRODE CONDUCTOR GND GROUND HDG HOT 3. WHERE ALL TERMINALS OF THE DISCONNECTING DIPPED GALVANIZED I CURRENT Imp CURRENT AT MEANS MAY BE ENERGIZED IN THE OPEN POSITION, MAX POWER Isc SHORT CIRCUIT CURRENT kVA A SIGN WILL BE PROVIDED WARNING OF THE KILOVOLT AMPERE kW KILOWATT LBW LOAD HAZARDS PER ART. 690.17. BEARING WALL MIN MINIMUM (N) NEW NEUT 4. EACH UNGROUNDED CONDUCTOR OF THE NEUTRAL NTS NOT TO SCALE OC ON CENTER PL MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED BY PROPERTY LINE POI POINT OF INTERCONNECTION PHASE AND SYSTEM PER ART. 210.5. PV PHOTOVOLTAIC SCH SCHEDULE S STAINLESS 5. CIRCUITS OVER 250V TO GROUND SHALL COMPLY STEEL STC STANDARD TESTING CONDITIONS TYP WITH ART. 250.97, 250.92(B). TYPICAL UPS UNINTERRUPTIBLE POWER SUPPLY V 6. DC CONDUCTORS EITHER DO NOT ENTER BUILDING VOLT Vmp VOLTAGE AT MAX POWER Voc VOLTAGE OR ARE RUN IN METALLIC RACEWAYS OR AT OPEN CIRCUIT W WATT 3R NEMA 3R, RAINTIGHT ENCLOSURES TO THE FIRST ACCESSIBLE DC DISCONNECTING MEANS PER ART. 690.31(E). 7. ALL WIRES SHALL BE PROVIDED WITH STRAIN RELIEF AT ALL ENTRY INTO BOXES AS REQUIRED BY UL LISTING. 8. MODULE FRAMES SHALL BE GROUNDED AT THE UL — LISTED LOCATION PROVIDED BY THE MANUFACTURER USING UL LISTED GROUNDING HARDWARE. 9. MODULE FRAMES, RAIL, AND POSTS SHALL BE BONDED WITH EQUIPMENT GROUND CONDUCTORS. VICINITY MAP INDEX Sheet 1 COVER SHEET Sheet 2 SITE PLAN Sheet 3 STRUCTURAL VIEWS Sheet 4 UPLIFT CALCULATIONS LICENSE GENERAL NOTES j Sheet 5 THREE LINE DIAGRAM Sheet 6 THREE LINE DIAGRAM CONT. 1. ALL WORK SHALL COMPLY WITH THE 2020 Cutsheets Attached FLORIDA BUILDING CODE (7TH EDITION), FLORIDA FIRE PREVENTION CODE (7TH EDITION). 2. ALL ELECTRICAL WORK SHALL COMPLY WITH THE ; 2014 NATIONAL ELECTRIC CODE. i MODULE GROUNDING METHOD: ZEP SOLAR AHJ: St. Lucie County REV BY DATE COMMENTS 9 REV A IF 1 7/7/2021 Decreased the system size and powerwall count. ' REV B JC 10/14/21 Changed modules to 425W s UTILITY: Florida Power and Light J B-3 4 9 3 6 7 O O CUSTOMER: DESCRIPTION: DESIGN: CONTAINED AL A THE INFORMATION HEREIN JOB NUMBER: Mario r i o D e Ol i ve i t 11.47 5 K W P V ARRAY p T = 5 L n CONTAINED SHALL NOT BE USED FOR THE Raul Ze ed0 Lastra SHALL IT BEBENEFIT OF ADISCLOSED IN MOLE NYONE EXCEPT AOR IN ZEP NOR MOUNTING SYSTEM: 7924 Saddlebrook Dr 27 KWH ENERGY STORAGE SYSTEM PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH MoouLEs:Mighty Hook Port St. Lucie, FL 34986 THE SALE AND USE OF THE RESPECTIVE (27) Tesla # T425S TESLA EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME: SHEET: REV: DATE: PERMISSION OF TESLA INC. 7.6 kW Tesla Inc 1538000-00—F 240V 9045635873 COVER SHEET 1 e 12/6/2021 PITCH: 231 (5:12) ARRAY PITCH:231 (5:12) MP1 AZIMUTH: 146 ARRAY AZIMUTH: 146 MATERIAL: Low Profile W-Tile STORY: 2 Stories PITCH: 23 ARRAY PITCH:23 MP2 AZIMUTH:236 ARRAY AZIMUTH: 236 MATERIAL: Low Profile W-Tile STORY: 2 Stories a6 PITCH: 23 ARRAY PITCH:23 00 (E)DRIVEWAY 1 MP3 AZIMUTH:326 ARRAY AZIMUTH: 326 61 MATERIAL: Low Profile W-Tile STORY: 2 Stories Chid Digitally signed by Chid Sekar S e ka r 118 16 34-08'00'2 LEGEND D (E) UTILITY METER & WARNING LABEL INVERTER W/ INTEGRATED DC DISCO & WARNING LABELS RELAY AUTOMATIC RELAY Front Of House 0 DC DC DISCONNECT & WARNING LABELS AC AC DISCONNECT & WARNING LABELS 0 DC JUNCTION/COMBINER BOX & LABELS Ess ENERGY STORAGE SYSTEM FOR STAND ALONE OPERATION OD DISTRIBUTION PANEL & LABELS Lc LOAD CENTER & WARNING LABELS — -=SB O DEDICATED PV SYSTEM METER r,_AQL Y 7 RSD RAPID SHUTDOWN / STANDOFF LOCATIONS N / O CONDUIT RUN ON EXTERIOR R� CONDUIT RUN ON INTERIOR / GATE/FENCE /�Fs HEAT PRODUCING VENTS ARE RED / �� '� INTERIOR EQUIPMENT IS DASHED / SV L=�J SITE PLAN N Scale:1/16" = 1' W E 01, 16' 32' 110 S CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER: J B-3 4 9 3 6 7 00 CUSTOMER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT BE USED FOR THE Mario De Oliveir 11.475 KW PV ARRAY Raul Zepeda Lastra - 5 L n BENEFIT OF ANYONE EXCEPT TESLA INC., NOR MOUNTING SYSTEM: SHALL IT BE DISCLOSED IN WHOLE OR IN ZEP Mighty Hook 7924 Saddlebrook Dr 27 KWH ENERGY STORAGE SYSTEM PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: Port St. Lucie, FL 34986 ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (27) Tesla # T425S TESLA EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME: SHEET: REV: DATE: PERMISSION OF TESLA INC. 7.6 kW Tesla Inc 1538000-00—F 240V 9045635873 SITE PLAN 2 e 12/6/2021 INSTALLATION NOTES: (N) STANDOFF SHALL LAG DIRECTLY 1. CUT (N) BLOCKING TO FIT TIGHT INTO (N) BLOCKING BETWEEN (E) TRUSSES AND KEEP FLUSH TO ROOF SHEATHING. ENSURE THERE ARE (N) 2x6 DF#2 OR SPF#2 BLOCKING. NO GAPS BETWEEN MEMBERS. 2. INSTALL (N) BLOCKING WITH TWO A34 CLIPS, ONE AT EACH END OF BLOCKING. 3. NAIL A34 CLIPS TO EXISTING RAFTERS WITH (8) 8D (0.131") X 1.5" NAILS, FILLING (E) JACK TRUSS OR RAFTER ALL HOLES. ENSURE ALL NAILS ARE (BLOCKING NOT REQUIRED DOWN HERE) LOCATED AWAY FROM EDGE OF MEMBERS TO AVOID SPLITTING WOOD. (N) SIMPSON A34 CLIPS (2 PER BLOCK) * INSTALL BLOCKING ONLY BELOW W/ (8) 8d (0.131 ) X 1-1/2 NAILS PER CLIP STANDOFF LOCATIONS. (E) SHORTEST BOX TRUSS (BLOCKING FROM (E) LBW HERE UP TO RIDGE AS NEEDED) SIDE VIEW OF MP1 NTS THIS STRUCTURE WILL RECEIVE L4 S A BLOCKING UPGRADE. 2 MPl TOP CHORD 2X4 @ 24"OC ROOF AZI 146 PITCH 23 STORIES:2 ARRAY AZI 146 PITCH 23 BOTTOM CHORD 2X4 @ 24"OC Low Profile W-Tile U1 NEW BLOCKING SIDE VIEW INSTALLATION ORDER ZEP SPANNER BAR LOCATE RAFTER, MARK RAFTER (6) LOCATION, AND REMOVE TILE. (1) PLACE STANDOFF BASE & DRILL -------------------- ------ ---- PILOT HOLES AT THE RAFTER -- ----- - ---- LOCATION. $" DIA BOLT & NUT (1) (2) (7) (3) (2) CLEAN PAPER AROUND PILOT HOLE. ZEP SPANNER BAR CLAMP q �� HEIGHT. AANDOFF TO BATTEN STANDOFF (E) TILE 34" MIN. SEAL PILOT HOLES AND BOTTOM _,I, (4) OF STANDOFF WITH POLYURETHANE (E) ROOF DECKING (5) (4) SEALANT. 5/16" DIA STAINLESS 5) LAG STANDOFF INTO RAFTER. STEEL LAG BOLT LOWEST MODULE SUBSEQUENT MODULES (6) NOTCH TILE WEATHERING TO FIT (E) RAFTER STANDOFF AROUND STANDOFF. S 1 Scale: 1 1/2" = 1' 7) REINSTALL TILE. CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER: J B-3 49 3 6 7 00 CUSTOMER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT BE USED FOR THE Mario De Oliveir 11.475 KW PV ARRAY Raul Zepeda Lastra - 5 L n BENEFIT OF ANYONE EXCEPT TESLA INC., NOR MOUNTING SYSTEM: SHALL IT BE DISCLOSED IN WHOLE OR IN ZEP Mighty Hook 7924 Saddlebrook Dr 27 KWH ENERGY STORAGE SYSTEM PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: Port St. Lucie, FL 34986 ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (27) Tesla # T425S TESLA EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME: SHEET: REV: DATE: PERMISSION OF TESLA INC. 7.6 kW Tesla Inc 1538000-00—F 240V 9045635873 STRUCTURAL VIEWS 3 e 12/6/2021 Jobsite Specific Design Criteria Design Code ASCE 7-16 Risk Category II Table 1.5-1 Ultimate Wind Speed V—Ult 160 Fig. 1609A Exposure Category C Section 26.7 Ground Snow Load pg 0 Table 7-1 Edge Zone Width a 10.1 ft Fig. 30.3-2A to I MP Specific Design Information MP Name MP1 Roofing Low Profile W—Tile Standoff ZEP Mighty Hook Pitch 23 SL/RLL: PV 0.0 SL/RLL: Non—PV 19.0 Standoff Spacing and Layout MP Name MP1 Landscape X—Spacing 24 Landscape 12 X—Cantilever Landscape Y—Spacing 52 Landscape 24 Y—Cantilever Portrait X—Spacing 24 Portrait X—Cantilever 12 Portrait Y—Spacing 52 Portrait Y—Cantilever 24 Layout Not Staggered X and Y are maximums that are always relative to the structure framing that supports the PV. X is across rafters and Y is along rafters. CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER: J B-3 49 3 6 7 00 CUSTOMER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT BE USED FOR THE Mario De Oliveir 11.475 KW PV ARRAY Raul Zepeda Lastra - 5 L n BENEFIT OF ANYONE EXCEPT TESLA INC., NOR MOUNTING SYSTEM: SHALL IT BE DISCLOSED IN WHOLE OR IN ZEP Mighty Hook 7924 Saddlebrook Dr 27 KWH ENERGY STORAGE SYSTEM PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: Port St. Lucie, FL 34986 ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (27) Tesla # T425S TESLA EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME: SHEET: REV: DATE: PERMISSION OF TESLA INC. 7.6 kW Tesla Inc 1538000-00—F 240V 9045635873 UPLIFT CALCULATIONS 4 e 12/6/2021 MAIN PANEL SPECS GENERAL NOTES LICENSE Panel Number: SC4-8M20OFTRH Meter Number:304 402 620 Underground Service Entrance E 200A MAIN SERVICE PANEL E 20OA/2P MAIN CIRCUIT BREAKER TESLA (N) 200A INTERNAL $ BACKUP GATEWAY LOAD CENTER 200A 2P Z 40Al2P TO NEW SOLAR IV B , i I 302P 7 L1 I L J I i i Lz y ENERGY I N STORAGE SUBFEED I i I EGC SYSTEM THROUGH LUGS N I l EGc L1 30Al2P 7 Z " EGC N Lz L1 Lz y ENERGY N STORAGE GEC i SYSTEM — —---� �-------- EGC TO 120/240V i Z SINGLE PHASE i UTILITY SERVICE , I (E) LOI p I • Panel Limit feature for Powerwall unit(s) • to be utilized • Field label to be at the point of interconnection: • "PCS Controlled Current Setting: 200A The maximum output current from this system towards the main panel is controlled electronically. Refer to (E) 200A manufacturer's instructions for more information." DISTRIBUTION PANEL POI (1)Gror r!d Rod 3 AWG #2 0, THWN-2, Black 58 x 8, Copper ©L-L(1)AWG #6, THWN-2, Green AC Z (1)Tesla #1232100-00—G I-L(1)Copduit Back—up Gateway 2.0 NA for AC PW 2.0 2 PVC; Schedule 80 —(1)CUTLER—HAMM�R #BR240 (1)AWG #10, THWN-2, Black Breaker; 40A 2P, 2 Spaces � —(2)CUTLER—HAMM�R #BR230 7 6F(1)AWG #10, THWN-2, Red Breaker; 30A 2P, 2 Spaces ILL�_L�L(1)AWG #10, THWN-2, White —(1)P200As asp Accessory Kit for j W 2.0 NA —(l)AWG #10, THWN-2, Green —(1)Conduit Kit; 1° EMT (3)AWG #2/0, THWN-2, Black Y (2)3012170-05—B ®1=L(1)AWG #6, THWN-2, Green ASY,AC POWERWALL2.1,5KW,13.5KWH,M48 I-L(1)Copduit 2 PVC; Schedule 80 CONFIDENTIAL — THE INFORMATION HEREIN JOB NUMBER: J B-3 4 9 3 6 7 O O CUSTOMER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT BE USED FOR THE Mario De Oliveir 11.475 KW PV ARRAY Raul Zepeda Lastra — 5 L n BENEFIT OF ANYONE EXCEPT TESLA INC., NOR MOUNTING SYSTEM: SHALL IT BE DISCLOSED IN WHOLE OR IN ZEP Mighty Hook 7924 Saddlebrook Dr 27 KWH ENERGY STORAGE SYSTEM PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: Port St. Lucie, FL 34986 ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (27) Tesla # T425S TESLA EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME: SHEET: REV: DATE: PERMISSION OF TESLA INC. 7.6 kW Tesla Inc 1538000-00—F 240V 9045635873 THREE LINE DIAGRAM 5 e 12/6/2021 GENERAL NOTES INVERTER SPECS MODULE SPECS LICENSE Inv 1: DC Ungrounded INV 1 — (1) 7.6 kW Tesla Inc 1538000-00—F(24OV) — (27) Tesla #T425S PV Module, 425W, 397 PTC, 40MM, Black Frame, MC4/MC4—EVO2, ZEP, 1000V INV 2 Voc: 48.65 Vpmax: 41.05 INV 3 Isc AND Imp ARE SHOWN IN THE DC STRINGS IDENTIFIER Inverter 1 IND T 1 7.6 kW Tesla Inc 1538000-00—F (240V) q 5 240V c+ MP 1: 1x7 DC+ ------------------------ EGC —————————————— ---� L1 DC r------------- 2 TO MAIN PANEL L2 DC+ I DC+ AND ENERGY STORAGE SYSTEM Dc- I 3 Dc- EGC DC+ DC+ MP 1: 2x10 I DC- DC- I GND EGC— ----————————————————————————————————— EGC —————————————————j (1)Conduit Kit; 3/4" EMT CONDUIT MATERIAL TYPE TBD IN FIELD TO 2017 NEC STANDARDS Voc* = MAX VOC AT MIN TEMP LG Please see MCI wiring detail page for more information AC ' ` —(1)EE-000550-000 MC4 Y—Connector, Pl cgeptacle DC PV (3)Tesla MCI, 60OV, 13A (1)AWG #8, THWN-2, Black (2)PV Wire, AWG 10, Black Voc* =518.12 VDC Isc =22.48 ADC (2)PV wre, AWG 10, Black Voc* =362,69VDC Isc =11,24 ADC O (1)AWG #8, THWN-2, Red O (1)AWG #10, Solid Bare Copper EGC Vmp =410.5 VDC Imp=20.72 ADC O (1)AWG #10, THHN/THWN-2, Green EGC Vmp =287.35 VDC Imp=10.36 ADC III--LLL(1)AWG #10, THWN-2, Green EGC Vmp =240 VAC Imp=32 AAC (1)Conduit Kit; 3/4" EMT (1)Conduit Kit; 3/4" EMT —(1)Conduit Kit; 3/4" EMT (2)PV Wire, AWG 10, Black Voc* =362.69VDC Isc =11,24 ADC (4)PV Wire, AWG 10, Black Voc* =518.12VDC Isc =11,24 ADC ®k (1)AWG #10, Solid Bare Copper EGC Vmp =287.35 VDC Imp=10.36 ADC O (1)AWG #10, THHN/THWN-2, Green EGC Vmp =410.5 VDC Imp=10.36 ADC (1)Conduit Kit; 3/4" EMT (1)Conduit Kit; 3/4" EMT CONFIDENTIAL — THE INFORMATION HEREIN JOB NUMBER: J B-3 4 9 3 6 7 O O CUSTOMER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT BE USED FOR THE Mario De Oliveir 11.475 KW PV ARRAY Raul Zepeda Lastra — 5 L n BENEFIT OF ANYONE EXCEPT TESLA INC., NOR MOUNTING SYSTEM: SHALL IT BE DISCLOSED IN WHOLE OR IN ZEP Mighty Hook 7924 Saddlebrook Dr 27 KWH ENERGY STORAGE SYSTEM PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: Port St. Lucie, FL 34986 ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (27) Tesla # T425S TESLA EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME: SHEET: REV: DATE: PERMISSION OF TESLA INC. 7.6 kW Tesla Inc 1538000-00—F 240V 9045635873 THREE LINE DIAGRAM CONT. 6 e 12/6/2021 SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY - Address: 7924 Saddlebrook Dr Battery storage utilized at this facility. INVERTER ENERGY STORAGE SYSTEM ENERGY STORAGE SYSTEM RAPID l SHUTDOWN j SWITCH 1 UTILITY j SERVICE 1 OPERATING VOLTAGE = 240V JB-349367-00 CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER: J B-3 49 3 6 7 00 CUSTOMER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT BE USED FOR THE Mario De Oliveir 11.475 KW PV ARRAY Raul Zepeda Lastra - 5 L n BENEFIT OF ANYONE EXCEPT TESLA INC., NOR MOUNTING SYSTEM: SHALL IT BE DISCLOSED IN WHOLE OR IN ZEP Mighty Hook 7924 Saddlebrook Dr 27 KWH ENERGY STORAGE SYSTEM PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: Port St. Lucie, FL 34986 ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (27) Tesla # T425S TESLA EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME: SHEET: REV: DATE: PERMISSION OF TESLA INC. 7.6 kW Tesla Inc 1538000-00—F 240V 9045635873 SITE PLAN PLACARD 7 e 12/6/2021 WARNING:PHOTOVOLTAIC POWER SOURCE Label Location: - ' WARNING Label • 'Location: WARNING Label Location: I ' Code:Per Code: NEC ELECTRIC SHOCK HAZARD • ELECTRIC SHOCK HAZARD 690.31.G.3 NEC 'DO NOT TOUCH TERMINALS 1 13 THE DC CONDUCTORS OF THIS LabelTERMINALS ON BOTH LINE AND PHOTOVOLTAIC SYSTEM ARE PHOTOVOLTAIC DC LOADN TH OPEN POS TIONIZED MAY BEOENERG ZED DISCONNECT Per NEC .•1 .113.13 Label Location: SOLAR . ..- 1 Location: Label Location: WARNING EQUIPPED ..- . . .- and,Telsa Inverter MAXIMUM POWER _A Code: INVERTER OUTPUT ••e: Per " POINT CURRENT(Imp) ._ • MAXIMUM POWER- CONNECTION 1 • ' 1 ' POINT VOLTAGE(Vmp)_V NEC 690.53 DO NOT RELOCATE F MAXIMUM SYSTEM THIS OVERCURRENTSitcom VOLTAGE(Voc)_V DEVICEswrCH SOLAR SHLITSHORT CIRCUITELECTRIC CURRENT(Isc)_A O Mla'1LtiELS AMME SHOCK HkZAAD Label Location: IN THE AR PHOTOVOLTAIC SYSTEM Label Location: EQUIPPED WITH RAPID ••" WARNING (DC) (INV) NEC 690.56.C.3 Per •.•- ELECTRIC SHOCK HAZARD 690.41.13 IF A GROUND FAULT IS INDICATED NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZEDLabel L• • CAUTION ' '•_ ••_ PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFEDNEC 690.64.13.4 Label • • WARNING Code:Per ELECTRICAL SHOCK HAZARD DO NOT TOUCH TERMINALSCEC 690.13.13 Label Location: TERMINALS ON BOTH LINE AND _ LOAD SIDES MAY BE ENERGIZED CAUTION • IN THE OPEN POSITION DUAL POWER SOURCEPer Code: DC VOLTAGE IS SECOND SOURCE IS NEC 705.12.13.3 ALWAYS PRESENT WHEN PHOTOVOLTAIC SYSTEM SOLAR MODULES ARE EXPOSED TO SUNLIGHT Label • • PHOTOVOLTAIC POINT OF �• •- • • INTERCONNECTION PHOTOVOLTAIC AC A P• WARNING: ELECTRIC SHOCKPer Code:• sconnec Per Code: HAZARD. CEC DO NOT TOUCH • 1 DISCONNECT TERMINALS.TERMINALS ON Conduit NEC ••1.13.B (CB): Combiner '• MAY BE ENERGIZED IN THE OPEN . Distribution (DC): DC Disconnect POSITION. FOR SERVICE DE-ENERGIZE BOTH SOURCE _ AND MAIN BREAKER. • • • Label PV POWER SOURCEIntegrated DC Disconnect MAXIMUM AC ' '• MAXIMUM AC A (LC): Load Center OPERATING CURRENT Per Code OPERATING CURRENT (M): Utility Meter MAXIMUM AC • ' MAXIMUM AC OPERATING VOLTAGE V • 1 OPERATING VOLTAGE V P• Point of • • Label Location: Label Location: BACKUP LOAD CENTER CAUTION Code:Per TRI POWER SOURCEPer Code: NEC 408.4 ,84 SECOND SOURCE IS PHOTOVOLTAIC SYSTEM ' THIRD SOURCE IS ENERGY STORAGE SYSTEM Label • • CAUTION DO NOT ADD NEW LOADSPer Code: .•- • • Per' WARNING ..- THIS EQUIPMENT FED BY NEC � _ on: MULTIPLE SOURCES.TOTAL CAUTION (MS-)RADEV COS,EXCOLUDRINGUMA NNT TH15 PANEL HAS SPLICED FEED Per • SUPPLY OVERCURRENT DEVICE, THROUGH CONDUCTORS. NEC 312.8.A(3) SHALL NOT EXCEED AMPACITY LOCATION OF DISCONNECT AT ENERGY OF BUSBAR. STORAGE BACKUP LOAD PANEL Label Label ... . NOMINAL ES5110LTAGE 1�Q��40V Location: CAUTION - MAX AVAILABLE SI IORT Per ..- DUAL POWER SOURCE Per ..- CIRCUIT FROM ESS= 32A Per 1•.7(D) label t• •- marked in field SECOND SOURCE IS ARC FAULTCLEARING ENERGY STORAGE SYSTEM 11ME FROM ESS: 67fT1S Label Location: (MS DATE OF CALcuLAT�aN: ENERGY STORAGE SYSTEM ON SITE - LOCATED WITHIN LINE OF SIGHT Per • - Label • • ENERGY STORAGE SYSTEM ON SITE LOCATED ON ADJACENT WALLPer Code: Label • • ENERGY STORAGE SYSTEM ON SITE LOCATED ON OPPOSITE WALLPer • " Label • • (MSENERGY STORAGE SYSTEM ON SITE - LOCATED INSIDE Per • - Disconnect Backup Load Center ROOFING SYSTEM SPECIFICATIONS 1-1 GROUND ZEP F-1 CAM FOOT V2 DESCRIPTION PV mounting solution for concrete tile roofs. Listed toUL2703 Listed toUL2703 Part#850-1511 Part#850-1564 Works with all Zep Compatible Modules. Auto bonding UL-listed hardware creates structural and electrical bond. Q��MPAT�6 rFA /0v �OMPp�v � SPECIFICATIONS Designed for pitched roofs. Installs in portrait and landscape orientations. DC WIRE CLIP HOME RUN CLIP Listed to UL 1565 Listed to UL 1565 Engineered for spans up to 72"and cantilevers up to 24". Part#850-1509 Part#850-1510 ZS Span has a UL 1703 Class"A" Fire Rating when installed using modules from any O manufacturer certified as"Type 1"or"Type 2". i Attachment method UL listed to UL 2582 for Wind Driven Rain. 50 psf(2400 Pa)front side and 85 psf(4070 Pa) rear side design load rating. Engineered for compliance with ASCE 7-05, 7-10, and 7-16 wind load requirements. ARRAY SKIRT END CAP Zep wire management products listed to UL 1565 for wire positioning devices. Listed to UL 2703 Listed to UL 2703 Part#850-1608 Part#850-1586(Left) ZS Span grounding products are listed to UL 2703 and UL 467. Part#850-1588(Right) ZS Span bonding products are listed to UL 2703. ` SPANNER CLAMP V2 MIGHTY HOOK V2 SKIRT GRIP INTERLOCK Listed to UL 2703 Listed to UL 2703&UL 2582 for Wind Driven Rain Listed to UL 2703 Listed to UL 2703 Part#850-1554 Part#850-1461 Part#850-1606 Part#850-1613 9P SPANNER BAR (VARYING LENGTHS) SPLICE ASSEMBLY KIT, SPAN HYBRID INTERLOCK Listed to UL 2703 Listed to UL 2703 Listed to UL 2703 Part#850-1627 Part#850-1625 Part#850-1281 T - 5 L n DOC-0065160 ZS SPAN DATASHEET 2 T - 5 L n DOC-0065160 ZS SPAN DATASHEET 3 POWERWALL TYPICAL SYSTEM LAYOUTS Tesla Powerwall is a fully-integrated AC battery system for T WHOLE HOME BACKUP residential or light commercial use. Its rechargeable lithium-ion battery pack provides energy storage for solar self-consumption, optional'' time-based control, and backup. Powerwall's electrical interface provides a simple connection to Solar any home or building. Its revolutionary compact design achieves market-leading energy density and is easy to install, enabling owners to quickly realize the benefits of reliable, clean power. O o O to Solar inverter ------------------------ Main panel Backup Gateway Utility meter Grid including service disconnect T=5 L n PERFORMANCE SPECIFICATIONS MECHANICAL SPECIFICATIONS AC Voltage(Nominal) 120/240 V Dimensions' 1150 mm x 753 mm x 147 mm Feed-In Type Split Phase (45.3 in x 29.6 in x 5.75 in) �^ Weight' 114 kg(251.3 Ibs) Grid Frequency 60 Hz Mounting options Floor or wall mount Total Energy' 14 kWh Powerwall Whole home - 'Dimensions and weight differ slightly if manufactured before March 2019. backup Usable Energy' 13.5 kWh Contact Tesla for additional information. 147 mm Real Power,max continuous 5 kW(charge and discharge) 753 mm ( (29.6 in) 5.75 in) Real Power,peak(10s,off-grid/backup) 7 kW(charge and discharge) Apparent Power,max continuous 5.8 kVA(charge and discharge) Apparent Power,peak(10s,off-grid/backup)7.2<VA(charge and discharge) T o 9 L n PARTIAL HOME BACKUP Load Start Capability 106 A LRA for each Powerwall Maximum Supply Fault Current 10 kA Optional 1150 mm I i Maximum Output Fault Current 32 A (45.3 in) Overcurrent Protection Device 30 A Imbalance for Split-Phase Loads 100% Solar Power Factor Output Range +/-1.0 adjustable Power Factor Range(full-rated power) +/-0.85 Internal Battery DC Voltage 50 V Round TripEfficiency'2 90% ENVIRONMENTAL SPECIFICATIONS O Warranty 10 years Solar Inverter Operating Temperature -200C to 500C(-4°F to 122°F) ------------------------- Sub panel Backup Gateway Main panel Utility meter Grid 'Values provided for 250C(770F),3.3 kW charge/discharge power. 'AC to battery to AC,at beginning of life. Recommended Temperature 0°C to 300C(32°F to 86°F) Operating Humidity(RH) Up to 100%,condensing T-s Storage Conditions -200C to 300C(-4°F to 86°F) COMPLIANCE INFORMATION Up to 95%RH,non-condensing State of Energy(SoE):25%initial Certifications UL 1642,UL 1741,UL 1973, Maximum Elevation 3000 m(9843 ft) UL 9540,IEEE 1547,UN 38.3 Environment Indoor and outdoor rated Grid Connection Worldwide Compatibility Powerwall Backup loads Home loads Enclosure Type NEMA 3R Emissions FCC Part 15 Class B,ICES 003 Ingress Rating IP67(Battery&Power Electronics) Environmental RoHS Directive 2011/65/EU IP56(Wiring Compartment) Seismic AC156,IEEE 693-2005(high) Wet Location Rating Yes Noise Level @ 1m < 40 dBA at 300C(86°F) T = 5 L Fi TESLA.COM/ENERGY NA-BACKUP-2021-06-01 TESLA.COM/ENERGY POWERWALL Backup Gateway 2 The Backup Gateway 2 for Tesla Powerwall provides energy management and monitoring for solar self-consumption,time-based control,and backup. The Backup Gateway 2 controls connection to the grid,automatically detecting outages and providing a seamless transition to backup power. When equipped with a main circuit breaker,the Backup Gateway 2 can be installed at the service entrance.When the optional internal panelboard is installed,the Backup Gateway 2 can also function as a load center. The Backup Gateway 2 communicates directly with Powerwall,allowing you to monitor energy use and manage backup energy reserves from any mobile device with the Tesla app. PERFORMANCE SPECIFICATIONS MECHANICAL SPECIFICATIONS Model Number 1232100-xx-y Dimensions 660 mm x 411 mm x 149 mm AC Voltage(Nominal) 120/240V (26 in x 16 in x 6 in) Weight 20.4 kg(45 lb) Feed-In Type Split Phase Mounting options Wall mount,Semi-flush mount Grid Frequency 60 Hz Current Rating 200 A Maximum Input Short Circuit Current 10 kA' Overcurrent Protection Device 100-200A;Service Entrance Rated' Overvoltage Category Category IV AC Meter Revenue accurate(+/-0.2%) 4 e S L R Primary Connectivity Ethernet,Wi-Fi Secondary Connectivity Cellular(3G,LTE/4G)2 User Interface Tesla App Operating Modes Support for solar self-consumption, o time-based control,and backup Backup Transition Automatic disconnect for seamless backup Modularity Supports up to 10 AC-coupled Powerwalls Optional Internal Panelboard 200A 6-space/12 circuit Eaton BR Circuit Breakers Warranty 10 years 'When protected by Class J fuses,Backup Gateway 2 is suitable for use in 411 149 circuits capable of delivering not more than 22kA symmetrical amperes. 2 The customer is expected to provide internet connectivity for Backup Gateway 2;cellular should not be used as the primary mode of connectivity.Cellular connectivity subject to network operator service coverage and signal strength. COMPLIANCE INFORMATION ENVIRONMENTAL SPECIFICATIONS Certifications UL 67,UL 869A,UL 916,UL 1741 PCS Operating Temperature -200C to 500C(-4°F to 122°F) CSA 22.2 0.19,CSA 22.2 205 Operating Humidity(RH) Up to 100%,condensing Emissions FCC Part 15,ICES 003 Maximum Elevation 3000 m(9843 ft) Environment Indoor and outdoor rated Enclosure Type NEMA 3R T = 5 L Fi NA 2020-09-16 TESLA.COM/ENERGY T = SLn GENERAL NOTES • DRAWING OF STANDARD MCI WIRING DETAIL FOR ANY GIVEN STRING LENGTH • IF INITIATED, RAPID SHUTDOWN OCCURS WITHIN 30 GD SECONDS OF ACTIVATION AND LIMITS VOLTAGE ON THE ROOF TO NO GREATER THAN 165V (690.12.B.2.1 ) • MID CIRCUIT INTERRUPTER (MCI) IS A UL 1741 PVRSE CERTIFIED RAPID SHUTDOWN DEVICE (RSD) DC+ J—BOX J—BOX J—BOX J—BOX J—BOX J—BOX MCI MCI RETRORT PV MODULES DC- 0 MCIS ARE LOCATED AT ROOF LEVEL, JUST UNDER THE PV MODULES IN ACCORDANCE WITH 690.12 REQUIREMENTS 1 • THE QUANTITY OF MCIS PER STRING IS DETERMINED BY STRING LENGTH — NUMBER OF MODULES BETWEEN MCI UNITS = 0-3 — MAXIMUM NUMBER OF MODULES PER MCI UNIT = 3 jJ—BOXj J—BOX J—BOX J—BOX — MINIMUM NUMBER MCI UNITS = MODULE COUNT/3 MCI *Exception: Tesla (Longi) modules installed in locations where the max Voc for 3 modules at low design temperature exceeds 165V shall be limited to 2 modules between MCIs. PLEASE REFER TO MCI CUTSHEET AND PVRSA INSERT FOR 1 (2)AWG, PV Wire, 600V, Black DC MORE INFORMATION T = SLM 1 � GENERAL NOTES • DRAWING OF STANDARD MCI WIRING DETAIL FOR ANY GIVEN STRING LENGTH • IF INITIATED, RAPID SHUTDOWN OCCURS WITHIN 30 SECONDS OF ACTIVATION AND LIMITS VOLTAGE ON THE ROOF TO NO GREATER THAN 165V (690.12.B.2.1) GD • MID CIRCUIT INTERRUPTER (MCI) IS A UL 1741 PVRSE CERTIFIED RAPID SHUTDOWN DEVICE (RSD) DC+ DIODE DIODE DIODE DIODE DIODE DIODE DIODE MCI SOLAR ROOF TLES DC- 0 MCIS ARE LOCATED AT DECK LEVEL, JUST UNDER THE 1 DIODE DIODE DIODE DIODE DIODE DIODE DIODE MCI TILES IN ACCORDANCE WITH 690.12 REQUIREMENTS • THE QUANTITY OF MCIS PER STRING IS DETERMINED BY STRING LENGTH — NUMBER OF TILES BETWEEN MCI UNITS = 0—10 DIODE DIODE DIODE DIODE DIODE DIODE DIODE — MAXIMUM NUMBER OF TILES PER MCI UNIT = 10 MCI — MINIMUM NUMBER MCI UNITS = TILE COUNT/10 DIODE DIODE DIODE DIODE PLEASE REFER TO MCI CUTSHEET AND PVRSA INSERT FOR 1 (2)AWG, PV Wire, 600V, Black DC MORE INFORMATION SOLAR INVERTER Tesla Solar Inverter provides DC to AC conversion and integrates with the Tesla ecosystem, including Solar Panels,Solar Roof,Powerwall,and vehicle charging,to provide a seamless T = s sustainable energy experience. KEY FEATURES to Integrated rapid shutdown,arc 2x the standard number of MPPTs for fault,and ground fault protection high production on complex roofs • No neutral wire simplifies installation I ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS MODEL NUMBER 1534000-xx-y 1538000-xx-y Dimensions 660 mm x 411 mm x 158 mm(26 in x 16 in x 6 in) OUTPUT(AC) 3.8 kW 7.6 kW Weight 52 lb Nominal Power 3,800 W 7,600 W Mounting options Wall mount(bracket) y Maximum Apparent Power 3,328 VA at 208 V 6,656 VA at 208 V Door and bracket can be removed for a mounting weight of 37 lb. 3,840 VA at 240 V 7,680 VA at 240 V Maximum Continuous Current 16 A 32 A o0 - o0 00 ' Breaker(Overcurrent Protection) 20 A 40 A o0 T o 2 L w o0 Nominal Power Factor 1 -0.9(leading/lagging) o0 00 THD(at Nominal Power) <5% o0 •oo INPUT(DC) 660 mm o0 MPPT 2 4 °o0 ,j o0 Input Connectors per MPPT 1-2 1-2-1-2 Maximum Input Voltage 600 VDC DC Input Voltage Range 60-550 VDC DC MPPT Voltage Range 60-480 VDC' Maximum Current per MPPT(I..) 13 A �Mm� 158 411 mm�Maximum Short Circuit 15A Current per MPPT(Is,) ENVIRONMENTAL SPECIFICATIONS PERFORMANCE SPECIFICATIONS Operating Temperature -300Cto450C(-220Fto1130F)4 Peak Efficiency 98%at 208 V 98.4%at 208 V Operating Humidity(RH) Up to 100%,condensing 98.1%at 240 V 98.6%at 240 V Storage Temperature -30°C to 70°C<-22°F to 158°F) SOLAR INVERTER CEC Efficiency 97.5%at 208 V 97.5%at 208 V 97.5%at 240 V 98.0%at 240 V Maximum Elevation 3000 m(9843 ft) Allowable DC/AC Ratio 1.7 Environment Indoor and outdoor rated 3.8 kW 17.6 kW Customer Interface Tesla Mobile App Enclosure Rating Type 3R Tesla Solar Inverter completes the Tesla home solar system,converting DC power from solar to AC power for home consumption.Tesla's Internet Connectivity Wi-Fi(2.4 GHz,802.11 b/g/n), Ingress Rating IP55(Wiring compartment)Ethernet,Cellular(LTE/4G)2 renowned expertise in power electronics has been combined with robust safety features and a simple installation process to produce an Pollution Rating PD2 for power electronics and terminal wiring AC Remote Metering Support Wi-Fi(2.4 GHz,802.11 b/g/n), compartment,PD3 for all other components outstanding solar inverter that is compatible with both Solar Roof and traditional solar panels.Once installed,homeowners use the Tesla RS-485 mobile app to manage their solar system and monitor energy consumption, resulting in a truly unique ecosystem experience. Operating Noise @ 1 m <40 db(A)nominal,<50 db(A)maximum Protections Integrated arc fault circuit interrupter (AFCI),Rapid Shutdown "For the 7.6 kW Solar Inverter,performance may be de-rated to 6.2 kW at KEY FEATURES 240 V or 5.37 kW at 208 V when operating at temperatures greater than Supported Grid Types 60 Hz,240 V Split Phase 45°C. • Built on Powerwall 2 technology for Designed to integrate with Tesla Powerwall and Tesla App 60 Hz,208 V Wye exceptional efficiency and reliability 3.8 kW and 7.6 kW models available COMPLIANCE INFORMATION Maximum current. • WI-Fi, Ethernet,and cellular Connectivity 2Cellular connectivity subject to network operator service coverage and signal Grid Certifications UL 1741,UL 1741 SA,IEEE 1547,IEEE 1547.1 with easy over-the-air updates strength. Safety Certifications UL 1741 PVRSS,UL 169913,UL 1998(US),UL 3741 Emissions EN 61000-6-3(Residential),FCC 47CFR15.109(a) T = 5 L Fi NA 2021-09-02 TESLA.COM/ENERGY SOLAR SHUTDOWN DEVICE The Tesla Solar Shutdown Device is part of the PV system rapid shutdown(RSD)function in accordance with Article 690 of the applicable NEC.When paired with the Tesla Solar Inverter,solar array shutdown is initiated by any loss of AC power. o� ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS Nominal Input DC Current Rating(IM,) 12 A Electrical Connections MC4 Connector Maximum Input Short Circuit Current(I5c) 15 A Housing Plastic Maximum System Voltage 600 V DC Dimensions 125 mm x 150 mm x 22 mm (5inx6inxI in) Weight 350 g(0.77 lb) RSD MODULE PERFORMANCE Mounting options ZEP Home Run Clip M4 Screw(#10) Maximum Number of Devices per String 5 M8 Bolt(5/16") Nail/Wood screw Control Power Line Excitation Passive State Normally open Maximum Power Consumption 7 W Warranty 25 years _ 250 mm o a COMPLIANCE INFORMATION M4 Screw 650 mm T150 mm M8 Bolt Certifications UL 1741 PVRSE,UL 3741, PVRSA(Photovoltaic Rapid e Shutdown Array) >11 Nail/ RSD Initiation Method PV System AC Breaker or Switch Wood Screw Compatible Equipment See Compatibility Table below ENVIRONMENTAL SPECIFICATIONS 22 mm 125 mm Ambient Temperature -400C to 500C(-40°F to 122°F) Storage Temperature -300C to 700C(-220F to 158°F) Enclosure Rating NEMA 4/IP65 UL 3741 PV HAZARD CONTROL (AND PVRSA) COMPATIBILITY Tesla Solar Roof and Tesla/Zep ZS Arrays using the following modules are certified to UL 3741 and UL 1741 PVRSA when installed with the Tesla Solar Inverter and Solar Shutdown Devices.See the Tesla Solar Inverter Installation Manual for detailed instructions and for guidance on installing Tesla Solar Inverter and Solar Shutdown Devices with other modules. Brand Model Required Solar Shutdown Devices Tesla Solar Roof V3 1 Solar Shutdown Device per 10 modules Tesla Tesla TxxxS(where xxx=405 to 450 W,increments of 5) 1 Solar Shutdown Device per 3 modules' Hanwha Q.PEAK DUO BLK-G5 1 Solar Shutdown Device per 3 modules Hanwha Q.PEAK DUO BLK-G6+ 1 Solar Shutdown Device per 3 modules 'Exception:Tesla solar modules installed in locations where the max Voc for three modules at low design temperatures exceeds 165 V shall be limited to two modules between MCIs. T - S L ri NA 2021-09-02 TESLA.COM/ENERGY POWERWALL+ PHOTOVOLTAIC (PV) AND BATTERY ENERGY STORAGE SYSTEM (BESS) SPECIFICATIONS MECHANICAL SPECIFICATIONS Powerwall+Model Number 1850000-xx-y Dimensions 1596 x 755 x 160 mm(62.8 x 29.7 x 6.3 in) Solar Assembly Model Number 1538000-xx-y Total Weight 140 kg(310 Ib)^ Nominal Battery Energy 13.5 kWh Battery Assembly 118 kg(261 lb) Nominal Grid Voltage(Input/Output) 120/240 VAC Solar Assembly 22 kg(49 lb) Grid Voltage Range 211.2-264 VAC Mounting options Floor or wall mount Frequency 60 Hz 755 mm 160 mm Phase 240 VAC:2W+N+GND Maximum Continuous Power On-Grid 7.6 kW full sun/5.8 kW no sun' Maximum Continuous Power Off-Grid 9.6 kW full sun/7 kW no sun' Peak Off-Grid Power(10 s) 22 kW full sun/10 kW no sun' T Maximum Continuous Current On-Grid 32 A output Maximum Continuous Current Off-Grid 40 A output Load Start Capability 118 A LRA PV Maximum Input Voltage 600 VDC PV DC Input Voltage Range 60-550 VDC T = 5 L n PV DC MPPT Voltage Range 60-480 VDC 1596 mm MPPTs 4(or 2 combined strings) Input Connectors per MPPT 1-2-1-2 Maximum Current per MPPT(I.P) 13 A(26 A for combined strings) Maximum Short Circuit 15 A Current per MPPT(IJ Allowable DC/AC Ratio 1.7 Overcurrent Protection Device 50 A breaker Maximum Supply Fault Current 10 kA Output Power Factor Rating +/-0.9 to 1 Round Trip Efficiency 90%2 ENVIRONMENTAL SPECIFICATIONS Solar Generation CEC Efficiency 97.5%at 208 V 98.0%at 240 V Operating Temperature -200C to 500C(-4°F to 1220F)5 Customer Interface Tesla Mobile App Recommended Temperature 0°C to 30°C(32°F to 86°F) P O W E R W A L L+ Internet Connectivity Wi-Fi,Ethernet,Cellular LTE/4G)3 Operating Humidity(RH) Up to 100%,condensing PV AC Metering Revenue grade(+/-0.5%) Storage Conditions -200C to 300C(-4°F to 86°F) Protections Integrated arc fault Up to 95%RH,non-condensing circuit interrupter(AFCI), State of Energy(SoE):25%initial Powerwall+ is an integrated solar battery system that stores energy from solar production. Its integrated design and PV Rapid Shutdown Maximum Elevation 3000 m(9843 ft) streamlined installation allow for simple connection to any home, and improved surge power capability brings whole Warranty 10 years Environment Indoor and outdoor rated home backup in a smaller package. Smart system controls enable owners to customize system behavior to suit their Enclosure Type Type 3R renewable energy needs. COMPLIANCE INFORMATION Solar Assembly Ingress Rating P55(Wiring Compartment) Battery Assembly Ingress Rating IP56(Wiring Compartment) KEY FEATURES PV Certifications UL 1699B,UL 1741,UL 3741,UL 1741 SA,UL IP67(Battery&Power Electronics) 1998(US),IEEE 1547,IEEE 1547.1 Noise Level @ 1 m < 40 db(A)optimal, • Integrated battery, inverter, and system controller for a more compact install Battery Energy Storage UL 1642,UL 1741,UL 1741 PCs,UL 1741 SA,UL <50 db(A)maximum • A suite of application modes, including self-powered, time-based control, and backup modes System Certifications 1973,UL 9540,IEEE 1547,IEEE 1547.1,UN 38.3 'Values provided for 250C(770F). • Wi-Fi, Ethernet, and LTE connectivity with easy over-the-air updates Grid Connection United States 2AC to battery to AC,at beginning of life. Emissions FCC Part 15 Class B 3Cellular connectivity subject to network service coverage and signal strength. The total weight does not include the Powerwall+bracket,which weighs an Environmental RoHS Directive 2011/65/EU additional 9 kg(20 lb). Seismic AC156,IEEE 693-2005(high) 5Performance may be de-rated at operating temperatures below 100C(50°F) or greater than 430C(1090F). NA2021-11-12 T = 5 L Fi NA2021-11-12 TESLA.COM/ENERGY SOLAR SHUTDOWN DEVICE SYSTEM LAYOUTS The Tesla Solar Shutdown Device is part of the PV Powerwall+with Backup Switch for Whole Home Backup system rapid shutdown (RSD)function in accordance % , with Article 690 of the applicable NEC. When paired X—) with Powerwall+, solar array shutdown is initiated by ' turning the Powerwall+ Enable switch off, or by pushing Solar Backup Switch the System Shutdown Switch if one is present. L_ — r ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS -s L_ Meter (t Load center Meter socket panel Grid Nominal Input DC Current Rating(IM,) 12 A Electrical Connections MC4 Connector Maximum Input Short Circuit Current(I5c) 15 A n Housing Plastic \/ Maximum System Voltage 600 V DC - Dimensions 125 mm x 150 mm x 22 mm Powerwall+ Backup loads (5 in x 6 in x 1 in) W RSD MODULE PERFORMANCE eight 350 g(0.77 lb) Mounting Options ZEP Home Run Clip Powerwall+with Backup Gateway 2 for Whole Home Backup Maximum Number of Devices per String 5 M4 Screw(#10) M8 Bolt(5/16") Control Power Line Excitation Nail/Wood screw � Passive State Normally open Solar Maximum Power Consumption 7 W Warranty 25 years -- -- --------- -- /1 250 mm r COMPLIANCE INFORMATION X M4 Screw Load center BackupGateway2 Meter socket panel Grid I o e Certifications UL 1741 PVRSE,UL 3741, PVRSA(Photovoltaic Rapid Shutdown Array) 650 mm 150 mm M8 Bolt RSD Initiation Method External System Shutdown Switch Powerwall+ Backup loads e o Compatible Equipment See Compatibility Table below Nail/ Wood Screw Powerwall+with Backup Gateway 2 for Partial Home Backup ENVIRONMENTAL SPECIFICATIONS Ambient Temperature -400C to 500C(-40°F to 122°F) Storage Temperature -300C to 600C(-220F to 140°F) Enclosure Rating NEMA 4/IP65 22 m 125 mm Solar mm T T=5 L^ Meter UL 3741 PV HAZARD CONTROL (AND PVRSA) COMPATIBILITY Backup panel Backup Gateway 2 Meter socket panel Grid I Tesla Solar Roof and Tesla/Zep ZS Arrays using the following modules are certified to UL 3741 and UL 1741 PVRSA when installed with the Powerwall+and Solar Shutdown Devices.See the Powerwall+Installation Manual for detailed instructions and for guidance on installing Powerwall+and Solar Shutdown Devices with other modules. Brand Model Required Solar Shutdown Devices Powerwall+ Backup loads =_ Tesla Solar Roof V3 1 Solar Shutdown Device per 10 modules Non-backup panel Tesla Tesla TxxxS(where xxx=405 to 450 W,increments of 5) 1 Solar Shutdown Device per 3 modules' Hanwha Q.PEAK DUO BLK-G5 1 Solar Shutdown Device per 3 modules O Hanwha Q.PEAK DUO BLK-G6+ 1 Solar Shutdown Device per 3 modules SSS 'Exception:Tesla solar modules installed in locations where the max Voc for three modules at low design temperatures exceeds 165 V shall be limited to Non-essential loads two modules between MCIs. T = 5 L n NA 2021-11-12 TESLA.COM/ENERGY l TESLA.COM/ENERGY Tesla Module Specifications N n o t o v o l t a i c Module Electrical Characteristics Power Class T4205 T42SS T4305 T420S, T425S, and T430S Test Method STC NOCT STC NOCT STC NOCT Max Power,Pm_(W) 420 313.7 425 317.4 430 321.1 Open Circuit Voltage,Vo<(V) 48.5 45.47 48.65 45.61 48.8 45.75 Short Circuit Current,Ise(A) 11.16 9.02 11.24 9.09 11.32 9.15 Max Power Voltage,V_(V) 40.90 38.08 41.05 38.22 41.20 38.36 Max Power Current,Imp(A) 10.27 6.24 10.36 8.3 10.44 8.37 Maximum Power The Tesla module is one of the most powerful Module Efficiency(%) 19.3 19.6 19.8 residential photovoltaic modules available. STC 1000 W/m�,25°C,AM1.5 Our system requires up to 20 percent fewer modules NOCT 800 W/m2,20°C,AM1.5,wind speed lm/s to achieve the same power as a standard system. The module boasts a high conversion efficiency Mechanical Loading Temperature Rating(STC) and a half cell architecture that improves shade Front Side Test Load 6120 Pa 1128lb/ft2 Temperature Coefficient of Isc +0.040%/°C tolerance. Rear Side Test Load 5190 Pa 1108 lb/ft' Temperature Coefficient of Von -0.260%/°C E E Beautiful Solar Front Side Design Load 4080 Pa 185 Ib/ft2 Temperature Coefficient of P_(W) -0.331%/°C o Featuring our proprietary Zep Groove design, Rear Side Design Load 3460 Pa 1 721b/ftz 35 mm/1.378 in the all-black module connects easily with Tesla ZS Hailstone Test 25 mm Hailstone at 23 m/s components to keep panels close to your 40+/-0.5 mm 1038+/-2 mm 40.9+/-0.08 in roof and close to each other for a blended aesthetic Mechanical Parameters 1.57+/-0.020in with simple drop-in and precision quarter-turn connections. Cell Orientation 144(6 x 24) Junction Box IP68,3 diodes ❑ Reliability Cable 4 mm2 112 AWG,1400 mm 155.1 in.Length e Tesla modules are subject to automotive-grade Connector Staubli MC4 or EV02 engineering scrutiny and quality assurance, far exceeding industry standards. Glass 3.2 mm ARC Glass Modules are certified to IEC/UL 61730-1, Frame Black Anodized Aluminum Alloy IEC/UL 61730 2 and IEC 61215. Weight 25.3 kg 155.8 lb d 2094 mm x 1038 mm x 40 mm * e Dimension ? o; 82.4 in x 40.9 in x 1.57 in m E E E O E E Operation Parameters a Operational Temperature -40'C up to+85°C o Power Output Tolerance -0/+5 W V_&Is,Tolerance +/-3% 984mm 38.7 in Max System Voltage DC 1000 V(IEC/UL) Max Series Fuse Rating 20 A NOCT 45.7+/-2'C Safety Class Class II Fire Rating UL Type 1 or 2 Limited Warranty Linear Power Warranty Current vs.Voltage Power vs.Voltage Current vs.Voltage Materials and Processing 25 years t00% 12 Cell Temp=25-C 500 Cell Temp=25°C 12 Incident Irradiance= 1000Wim= 95% 98% 0 -1000 W/m= 400 -1000 W/m2 O -1000 Wpm= Extra Linear Power Output 25 years E e -Soo W/m= -800 W/m2 8 -BOO W/m2 90% G -600 W/m2 300- -600 W/m2 ¢ -600 W/m2 6 -400 W/m2 -W/m2 « 6 -40°W/m2 The maximum Pmax degradation is 2% in the 85% 85% , -Zoo wrm= ;200 -200 wim= 4 -Zoo wrm= o 1st year and 0.54%annually from the 2nd to 3 80% V 2 a,00 U 2 25th year. 75% y o , is zo zs ol 0 0 10 20 30 40 50 0 10 20 30 40 50 0 10 20 30 40 50 voltage(V) voltage(v) Voltage(V) Tesla Module Datasheet T = 5 L n Tesla Module Datasheet T = 5 L n (TEPV-DS-0001-21) (TEPV-DS-0001-21)