HomeMy WebLinkAboutCombined_MechDAMPER SCHEDULE & DATADWG TAGQTYMNF. OR EQUALMODEL OR EQUALSERVICEMNT. POSITION/ AIRFLOW DIRECTIONFAN STATIC(IN. W.G.)DUCTCONNECTSIZEELECTRICREMARKSV/PH/HZFLACD 1-11GREENHECKRBDR-50NAT AIRHORIZ./ VERT. UP0.01"TBD"120/1/60-SUPPLY W/ 1" FLG. ON DISHARGE SIDENOTES:1) CONTRACTOR TO ADJUST SPRING TO SUIT AIR PRESSURE.AC EQUIPMENT SCHEDULEDWG TAGNOM. TON.QTYMNF. OR EQUALMODEL OR EQUALBTU/HHEAT TYPESYSTEMSEERCFMFAN STATIC (IN.W.G.)VAPOR/LIQUID PIPECONNECT SIZE(IN. ACR)V/PH/HZCOMPRESSORCONDENSER FANINDOOR FANELECT.HEATLOAD(KW)CONDENSING UNITAIR HANDER UNITTOTAL COOLSENSIBLECOOLHEATSUPPLYAIRRETURNAIROUTDOORAIRQTYFLALRAQTYFLAHPFLAMCAMAX FUSEMCAMAX FUSEAHU 1-011.01MITSUBISHIPVA-A12AA12,0009,24019,000HEAT PUMP21.4/13.4400400-0.801/2" & 1/4"208-230/1/601712.010.5121W2.4-11.0283.0(4)CU 1-011"PUZ-A12NKAAHU 2-015.01CARRIERFE4ANB00659,30044,00034,210ELEC. STRIP16200019001001.001-1/8" & 3/8"208-230/1/60125.6118.012.83/46.81034.85058.560CU 2-011"24VNA960A30AHU 2-025.01CARRIERFE4ANB00659,30044,00034,210ELEC. STRIP16200019001001.001-1/8" & 3/8"208-230/1/60125.6118.012.83/46.81034.85058.560CU 2-021"24VNA960A30AHU 3-015.01CARRIERFE4ANB00659,30044,00034,210ELEC. STRIP16200019001001.001-1/8" & 3/8"208-230/1/60125.6118.012.83/46.81034.85058.560CU 3-011"24VNA960A30AHU 3-024.01CARRIERFE4ANB00649,34037,05034,210ELEC. STRIP17.3160015001001.007/8" & 3/8"208-230/1/60121.296.012.23/46.81028.74058.560CU 3-021"24VNA948A30NOTES:1) CAPACITY IS MEASURED BY MANUFACTURE TESTITNG WHEN PAIRED WITH CORRESPONDING CONDENSING UNIT (SEE CONDENSING UNIT SCHEDULE).2) CONTRACTOR SHALL SUPPLY HUMIDITY SENSORS AND CONTROLS TO SUIT DEHUMIDIFCIATION CYCLE WITHIN EACH SPACE.3) COOLING CAPACITY DATA IS BASED ON 95 DEG F OUTDOOR CONDITIONS AND 67 DEG F EADB.FAN SCHEDULE & DATADWG TAGQTYMNF. OR EQUALMODEL OR EQUALSERVICECFMFAN STATIC(IN. W.G.)DUCTCONNECTSIZEELECTRICREMARKSV/PH/HZFLAEF01ARPANASONICFV-05-11VKS1TOILET EXH.50/80/1000.14"120/1/600.1-EF01ARPANASONICFV-05-11VQ3TOILET EXH.110/1500.14"120/1/600.1-NOTES:1) SUPPLY ALL FANS WITH NON-RETURN DAMPERS.WATER HEATER COMBUSTION CALCS (FBCFG 304.5.1)TOTAL CONSUMPTION199kBTUHREQ'D ROOM VOLUME9950CU FT.ACTUAL ROOM VOLUME14920CU FT.COMPLIANCE METYESTRANSFER DUCT REQUIRED:POOL EQUIPMENT COMBUSTION CALCS (FBCFG 304.5.1)TOTAL CONSUMPTION400kBTUHREQ'D ROOM VOLUME20000CU FT.ACTUAL ROOM VOLUME13296CU FT.COMPLIANCE METNOTRANSFER DUCT REQUIRED:MIN VENT SIZE400CU INMIN VENT SIZE DIAMETER23INFIREPLACE (CLUB RM.) COMBUSTION CALCS (FBCFG 304.5.1)TOTAL CONSUMPTION40kBTUHREQ'D ROOM VOLUME2000CU FT.ACTUAL ROOM VOLUME5104CU FT.COMPLIANCE METYESTRANSFER DUCT REQUIRED:FIREPLACE (DINNING, GREAT RM.) COMBUSTION CALCS (FBCFG304.5.1)TOTAL CONSUMPTION40kBTUHREQ'D ROOM VOLUME2000CU FT.ACTUAL ROOM VOLUME14399CU FT.COMPLIANCE METYESTRANSFER DUCT REQUIRED:FIREPLACE (MASTER SUITE) COMBUSTION CALCS (FBCFG 304.5.1)TOTAL CONSUMPTION40kBTUHREQ'D ROOM VOLUME2000CU FT.ACTUAL ROOM VOLUME5650CU FT.COMPLIANCE METYESTRANSFER DUCT REQUIRED:RANGE HOOD COMBUSTION CALCS (FBCFG 304.5.1)TOTAL CONSUMPTION65kBTUHREQ'D ROOM VOLUME3250CU FT.ACTUAL ROOM VOLUME14399CU FT.COMPLIANCE METYESTRANSFER DUCT REQUIRED:DRYER LVL.01 COMBUSTION CALCS (FBCFG 304.5.1)TOTAL CONSUMPTION35kBTUHREQ'D ROOM VOLUME1750CU FT.ACTUAL ROOM VOLUME680CU FT.COMPLIANCE METNOTRANSFER DUCT REQUIRED:MIN VENT SIZE35CU INMIN VENT SIZE DIAMETER12INDRYER LVL.02 COMBUSTION CALCS (FBCFG 304.5.1)TOTAL CONSUMPTION35kBTUHREQ'D ROOM VOLUME1750CU FT.ACTUAL ROOM VOLUME459CU FT.COMPLIANCE METNOTRANSFER DUCT REQUIRED:MIN VENT SIZE35CU INMIN VENT SIZE DIAMETER12INMECHANICAL SHEET INDEXARCHSHT NOJWLESHT NODESCRIPTIONM10101HVAC NOTES, EQUIPMENT & CALCSM10202HVAC PLAN - DETAILSM20103HVAC PLAN - FIRST FLOORM20204HVAC PLAN - SECOND FLOORM20305HVAC PLAN - THIRD FLOORM30106HVAC PLAN - REFRIGERANT & CONDENSATE PIPINGPLANBLDG VENTILATION (REF.: FBCM 403)SPACENO. OFBEDROOMSAC SQ.FT.MIN. O/ARATE (CFM)ALTERNATEREFERENCEDERATINGVALUEALT MIN O/ARATE (CFM)HOUSE3650195NO--GARAGE VENTILATION (REF.: FBCM 402)SPACEFLOOR AREAOPERABLE OPENINGAREAPERCENT OPERABLE PERFLOOR AREAMINIMUMINFILTRATIONREQUIREMENTSMET6 CAR GARAGE149216211%YESMEP EQUIPMENT SHALL BE LOCATED ABOVE THE BASE FLOODELEVATION +1 FOOT, EXCEPT AS REQUIRED TO ADDRESS LIFESAFETY REQUIREMENTS.DEHUMIDIFIER SCHEDULEDWGTAGQTYMNF. OREQUALMODEL OREQUALSERVICEWATER REMOVAL(PINTS PER DAY)CFMFAN STATIC(IN. W.G.)REMARKSDH 1-11APRIL AIRE1870MAIN FLOOR1301780.6DUCT KITNotes:1. ALL DEHUMIDIFIERS SHALL BE EQUIPPED W/ AN INTEGRAL MOTOIZED DAMPER OR OUTFIT W/ ACCESSORY MOTORIZED DAMPER(GREENHECK VCD OR EQUAL) THAT SHALL CLOSE 100% UPON UNIT DEACTIVATION.2. ALL DEHUMIDIFIERS SHALL BE PROVIDED INTEGRAL CONTROLS ENSURING ALL OFFCOIL CONDITIONS ARE TEMPEARTURE AND HUMIDITYNUETRAL.MECHANICAL SPECIFICATIONSNO.DESCRIPTIONA)AIR CONDITIONING SPECIFICATION1.DRAWINGS ARE DIAGRAMMATIC AND SHALL NOT BE SCALED FOR THE EXACT LOCATION OF EQUIPMENT, PIPING, DUCTWORK, OR OTHER ITEMS.2.DRAWINGS DO NOT SHOW EVERY DETAIL OF CONSTRUCTION OR INSTALLATION. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL ITEMS REQUIRED FOR A COMPLETE AND WORKING SYSTEM.3.ALL WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR IN A FIRST CLASS, WORKMAN-LIKE MANNER. THE COMPLETED SYSTEM SHALL BE OPERATIVE AND ACCEPTANCE BY ENGINEER/ARCHITECT SHALL BE ACONDITION OF THE SUB-CONTRACT.4.THE CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS, AND TESTS.5.THE CONTRACTOR SHALL THOROUGHLY FAMILIARIZE HIMSELF WITH ALL ASPECTS OF THE PROJECT AND SHALL VERIFY ALL CONDITIONS PRIOR TO CONSTRUCTION.6.ALL INSTALLATION SHALL BE COORDINATED BY THE CONTRACTOR WITH OTHER TRADES TO AVOID IMPACTS.7.ALL REQUIRED CONSTRUCTION INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK SHALL BE PROVIDED BY THE CONTRACTOR.8.ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH APPLICABLE NATIONAL, STATE AND LOCAL CODES, RULES, AND ORDINANCES.THE CODES IN EFFECT FOR THIS PROJECT SHALL THE 2020 EDITION OF FBC WITH REVISIONS AND ALL ASSOCIATED INDUSTRY CODES BY REFRENCE.9.ALL MATERIALS SHALL BE NEW AND SHALL BEAR UNDERWRITERS LABEL WHERE APPLICABLE.10.EQUIPMENT SHALL BE U.L. APPROVED.11.THE MECHANICAL CONTRACTOR SHALL PROVIDE A WRITTEN WARRANTY THAT SHALL GUARANTEE ALL WORKMANSHIP AND MATERIALS FOR ONE YEAR FROM THE DATE OF FINAL WORK ACCEPTANCE BY THE OWNEROR OWNERS REPRESENTITIVE.12.ARCHITECTURAL AND/OR ENGINEERING EXPENSES THAT ARE INCURRED DUE TO REVISIONS OR SUBSTITUTIONS REQUESTED FOLLOWING THE ISSUE OF APPROVED DRAWINGS SHALL BE PAID FOR BY THECONTRACTOR.B)INSTALLATION1.THE MECHANICAL CONTRACTOR SHALL PROVIDE HVAC EQUIPMENT LISTED IN THE HVAC EQUIPMENT SCHEDULE AND SHALL MEET THE CAPACITIES NOTED.2.THE MECHANICAL CONTRACTOR SHALL SUBMIT MANUFACTURER SHOP DRAWINGS, CUT SHEETS AND PERFORMANCE DATA ON ALL EQUIPMENT AND OBTAIN THE ENGINEER'S APPROVAL PRIOR TO PURCHASE ANDINSTALLATION. COPIES OF ALL MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR ALL EQUIPMENT AND APPLIANCES SHALL BE AVAILABLE ON THE JOB SITE AT THE TIME OF INSPECTION.3.THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL MOTOR STARTERS, RELAYS, CONTRACTORS, SMOKE DUCT DETECTORS, ETC.4.THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL SWITCHES AND INSTALL ALL CONTROL WIRING.5.A/C UNIT SUPPLY AND RETURN AIR DUCTS SHALL BE R-6 JOHNS MANVILLE MAT-FACED MICRO-AIRE FIBERGLASS DUCT BOARD, TYPE 800 (UL APPROVED) , INSTALLED PER MANUFACTURER'S INSTRUCTIONS.6.ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED TO S.M.A.C.N.A. STANDARDS. ALL DUCTWORK SIZES ARE INSIDE DIMENSIONS.a)ALL 90 DEGREE ELBOWS SHALL BE HAVE A MINIMUM CL RADIUS OF 1.5 R/W (1.5 R/D) OR BE FURNISHED WITH TURNING VANES.b)BRANCH TAKEOFFS SHALL BE PROVIDED WITH ADJUSTABLE, ACCESSIBLE AIR SPLITTER DAMPERS.c)ROUND DUCT ELBOWS SHALL HAVE A CENTERLINE RADIUS OF NOT LESS THAN 1.5 TIMES THE DIAMETER OF THE DUCT.7.SECURE FLEXIBLE DUCTS TO BRANCH TAKE-OFF COLLAR WITH HOSE CLAMP.8.MAXIMUM LENGTH OF ALL FLEXIBLE DUCT SHALL NOT BE MORE THAN 10 FEET, UNLESS OTHERWISE NOTED.9.ALL EXHAUST AND OUTSIDE AIR DUCT SHALL BE MIN. 24GA GALVANIZED SHEET METAL. KITCHEN HOOD AND BBQ HOOD EXHAUST DUCTS SHALL HAVE SMOOTH INNER WALLS, SHALL BE AIR TIGHT, SHALL BE EQUIPPEDWITH A BACKDRAFT DAMPER, AND SHALL BE INDEPENDENT OF ALL OTHER EXHASUT SYSTEMS. T-FIN SHALL BE ACCEPTABLE FOR BATHROOM EXHAUST.10.ALL DUCT ABOVE THE ROOF TO BE MIN. 16GA SHEET METAL, INSULATED W/ 2” THK RIGID HULL BOARD AND SHEATHED WITH GALV. STEEL. EXTERIOR STEEL TO BE SEALED/WEATHERPROOFED, PRIMED AND PAINTEDPER ARCHITECTURAL PAINT SCHEDULE.11.THE MECHANICAL CONTRACTOR SHALL INSTALL SMOKE DUCT DETECTORS IN THE SUPPLY DUCT OF ALL A/C UNITS EXCEEDING 2000 CFM. SMOKE DETECTOR SHALL BE INTERLOCKED W/ AHU CONTROLS.12.AIR DISTRIBUTION ACCESSORIES SHALL BE AS NOTED ON THE PLANS.13.REFRIGERANT PIPING SHALL BE TYPE "K" COPPER WITH SOLDER FITTINGS.a)ALL REFRIGERATION PIPE INSULATION SHALL BE MIN. ½” ARMAFLEX OR EQUAL APPROVED BY THE ENGINEER.b)ALL EXTERIOR LIQUID/SUCTION LINES SHALL BE INSULATED AND WEATHER PROOFED. ALL SUCTION LINES INSIDE THE BUILDING SHALL BE INSULATED.c)LIQUID/SUCTION LINES SHALL BE ROUTED INSIDE THE STRUCTURE TO THE EXTENT PRACTICABLE.d)THE MECHANICAL CONTRACTOR SHALL SIZE ALL PIPING FOR THE SPECIFIC APPLICATION AND ROUTE OF PIPE.14.THE MECHANICAL CONTRACTOR SHALL ROUTE CONDENSATE PIPING FOR A LENGTH OF 10 FEET TO A DRAIN SUPPLIED BY THE PLUMBING CONTRACTOR. THE MECHANICAL CONTRACTOR'S CONDENSATE PIPE SHALLINCLUDE A TRAP SIZED FOR AHU FAN STATIC.15.THE MECHANICAL CONTRACTOR SHALL SET AIR HANDLER UNIT AND CONDENSING UNIT AS SHOWN ON THE DRAWINGS. EQUIPMENT SHALL BE PROVIDED DIM PAD ISOLATORS.16.ALL OUTDOOR AIR INTAKES SHALL BE PROVIDED WITH BIRD AND INSECT SCREEN OF A CORROSION-RESISTANT MATERIAL. BIRD SCREEN SHALL NOT BE LARGER THAN 1/2" MESH AND INSECT SCREEN SHALL NOT BELARGER THAN 18X14.17.THERMOSTATS SHALL BE SUPPLIED AND INSTALLED BY THE MECHANICAL CONTRACTOR:a)SHALL BE MOUNTED 5'-6' ABOVE FINISHED FLOOR, UNLESS NOTED OTHERWISE.b)SHALL BE HEAT/OFF/COOL AND FAN/AUTO/ON SWITCHED AND SHALL BE APPROVED BY AC EQUIPMENT MANUFACTURER.c)FURNISH AND INSTALL ALL TEMPERATURE CONTROLS, INCLUDING PROGRAMMABLE THERMOSTAT AND HUMIDISTAT CONTROLS.18.FIRE DAMPERS SHALL BE INSTALLED IN ALL DUCTS PENETRATING FIRE RATED ROOFS, CEILINGS AND BULKHEADS AS BY CODE. ACCESS DOORS FOR INSPECTION AND RESET SHALL BE PROVIDED AT EACH LOCATION.a)FIRE DAMPERS PROVIDED IN KITCHEN EXHAUST DUCT SHALL BE EQUIPPED WITH 212F FUSIBLE LINK.19.ALL ELEMENTS OF INSTALLATION SHALL COMPLY WITH LOCAL AND STAE BUILDING REQUIREMENTS, INCLUDING BUT NOT LIMITED TO FBC-R M1411.6 LOCKING ACCESS PORT CAPS.C)WARRANTIES1.CORRECTION OF ANY ENGINEERING DEFECT SHALL BE RECTIFIED WITHOUT ADDITIONAL CHARGE AND SHALL NOT INCLUDE REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION, WHICH MAYHAVE BEEN DAMAGED THEREBY.2.CONTRACTOR SHALL ADJUST, TEST AND BALANCE ALL SYSTEMS.a) BALANCING OF THE SYSTEM SHALL BE BY A CERIFIED THIRD PARTY.MECHANICAL GENERAL NOTESNO.DESCRIPTION1.THE PURPOSE OF THIS DRAWING IS TO PROVIDE HVAC ROUTING AND CONSTRUCTION DETAILS. THESE PLANSDETAIL THE FINAL ARRANGEMENT OF EQUIPMENT AND THEIR ASSOCIATED APPENDAGES.2.ANY AND ALL QUESTIONS AS TO THE INTENT OF, OR PROCEDURES SET FORTH IN THESE DRAWINGS MUST BEBROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO THE SUBMISSION OF A BID. LACK OF KNOWLEDGEOR UNDERSTANDING OF PLANS SHALL NOT JUSTIFY ANY CLAIMS OR EXTRA COMPENSATION.3.THE HVAC CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCT, & DIFFUSER LOCATIONS ANDCLEARANCES WITH ALL OTHER TRADES ON PROJECT, IN PRE-CONSTRUCTION MEETING, PRIOR TO ANYORDER, FABRICATION, OR INSTALLATION.4.ALL SYMBOLS MAY NOT BE USED FOR THIS PROJECT.5.PRIOR TO CONSTRUCTION, THE MECHANICAL CONTRACTOR SHALL:a. VERIFY ALL EXISTING CONDITIONS IN THE FIELD PRIOR TO CONSTRUCTION.b. NOTIFY THE ENGINEER OF ANY CHANGES REQUIRED TO COMPLETE NEW CONSTRUCTION.6.ALL 90 DEGREE ELBOWS SHALL BE HAVE A MINIMUM CL RADIUS OF 1.5 R/W (1.5 R/D) OR BE FURNISHED WITHTURNING VANES.7.ALL HANGER SPACING SHALL BE IN ACCORDANCE WITH S.M.A.C.N.A.8.DUCT SIZES ARE CLEAR, INSIDE DIMENSIONS. VERIFY ALL DIMENSIONS AND LOCATIONS PRIOR TOFABRICATION OR INSTALLATION. ALL DUCTWORK SHALL BE FIBERBOARD.9.ALL EXHAUST DUCT SHALL BE SHEET METAL CONSTRUCTION. T-FIN SHALL BE ACCEPTABLE FOR BATHROOMEXHAUST.10.KITCHEN HOOD EXHAUST IN EXCESS OF 400 CFM SHALL BE PROVIDE DEDICATED O/A FOR KITCHEN HOODMAKE-UP AIR OPERATION. PROVIDE GREENHECK VCD CONTROL DAMPER AND INTERLOCK WITH HOOD FAN.CONTROL DAMPER SHALL BE ACCESSIBLE FOLLOWING CONSTRUCTION.11.GENERATOR EXHAUST SHALL COMPLY WITH FBCM 501.3.1 2020, INCLUDING BUT NOT LIMITED TO BEINGLOCATED WITH THE FOLLOWING MINIMUM REQUIREMENTS.A. 10 FEET FROM THE PROPERTY LINE.B. 3 FEET FROM EXTERIOR WALLS AND ROOFS.C. 10 FEET FROM OPERABLE OPENINGS INTO BUILDINGS.D. 10 FEET ABOVE ADJOINING GRADE.12.HORIZONTAL DUCT SHALL BE SUPPORTED AT INTERVALS NO GREATER THAN 5 FEET AND DUCT SAG SHALLNOT EXCEED ½ INCH PER FOOT OF LENGTH. SUPPORTS SHALL BE PROVIDED WITHIN 1 ½ FEET OFINTERMEDIATE FITTINGS AND BETWEEN INTERMEDIATE FITTINGS AND BENDS. CEILING JOISTS AND RIGIDDUCT OR EQUIPMENT MAY BE CONSIDERED TO BE SUPPORTS.13.AHU APPLIANCES SHALL BE ACCESSIBLE FBCR SECTION M-1305.1 2020 (COMMERCIAL PROJECTS REF. FBCMSECTION 306 2020): APPLIANCES FOR INSPECTION, SERVICE, REPAIR AND REPLACEMENT REQUIRED.14.CONDENSING UNITS AND OTHER EXTERIOR EQUIPMENT SHALL BE MOUNTED ABOVE THE FLOOD DESIGNELEVATION IAW FBC.15.FOR ALL NEW DUCTWORK, INSTALL A 2" 3PCF DENSITY R=6, 2 RIGID DUCT BOARD INSULATION. SEAL ALLJOINTS WITH HARD CAST MASTIC AND DUCT TAPE. R=4 DUCT IS ACCEPTABLE WITHIN CONDITIONED SPACE.TYPICAL.16.NO VICTAULIC FITTINGS AT PIPE OFFSETS INSIDE APARTMENTS OR COMMON AREAS. WELDED FITTINGS ONLY.17.ALL EXHAUST PENETRATIONS SHALL BE PROTECTED FROM INFILTRATION THROUGH THE USE OFNON-RETURN DAMPER INSTALLED IN-LINE AT THE INSIDE OF THE WEATHER BOUNDARY. THE FIRST 5 FEET OFDAMPER AND DUCT SHALL BE INSULATED WITH MIN. R4 DUCT WRAP. DAMPER SHALL BE NON-METALLIC'REVERSOMATIC IPBD /PBD' OR EQUAL OR LOUVER STYLE WITH INTEGRATED NON-RETURN DAMPER.D U C T S Y M B O L SLEGENDA B B R E V I A T I O N SSUPPLY/EXHAUST SUPPLY AIR DIFFUSER W/ AIRDIRECTIONRETURN/ EXHAUST AIR GRILLETEMPERATURE & HUMIDITYCONTROL & SENSORAFFABOVE FINISHED FLOORAHUAIR HANDLER UNITBODBOTTOM OF DUCTCODCENTER OF DUCTCUCONDENSING UNITDNDOWNF6FLEXIBLE DUCT/SIZE (INCHES)GRLGRILLELSLIQUID & SUCTION LINENRDNON-RETURN DAMPEROAOUTDOOR AIRR6RIGID SHT. MTL. DUCT/SIZE (INCHES)RARETURN AIRRADRETURN AIR DUCTRCROOF CAPSADSUPPLY AIR DUCTSTLSTEELTEDTOILET EXHAUST DUCTTODTOP OF DUCTVCD(MANUAL) VOLUME CONTROL DAMPERWCWALL CAPWLWEATHER LOUVERT3LDOOR LOUVERUCUNDER CUTSUPPLY AIR SIDEWALL DIFFUSERSUPPLY AIR LINEAR DIFFUSERPLANNORTH10KEY NOTEXX1000DIFFUSER TAG (SEE SCHEDULE)AIRFLOW (CFM)COFVCARBON MONOXIDE SENSORFLAMMABLE VAPOR SENSORFINAL DUCT ARRANGEMENTS RESERVEDPENDING STRUCTURAL COORDINATIONM1010100INITIAL ISSUEJWLE09.24.21PERMIT SET 09.24.21
JOHN LANGFORD, FL#69962HVACNOTES, EQUIPMENT& CALCS
TITUS / 250 SCHEDULESIZECFM RANGESIZECFM RANGE4"x4"6"x6"0 - 80 CFM6"x4"0 - 70 CFM10"x10"81 - 250 CFM8"x6"71 - 125 CFM12"x12"251 - 350 CFM10"x8"126 - 200 CFM14"x14"351 - 550 CFM12"x8"201 - 275 CFM16"x16"551 - 690 CFMAIR DISTRIBUTION SCHEDULEDWG TAGMAKE / MODELSERVICEFACE SIZENECK SIZEMATERIALFRAMEFINISHDAMPERNOTESATITUS / 250SUPPLYSEE SCHEDULEPER FLEXALUMINUMSURFACEWHITEOBD1,2,3,4,5,6BTITUS / FLSUPPLYSEE SCHEDULEPER FLEXALUMINUMSURFACEWHITE-1,2,3,4,5,6CTITUS / FJSUPPLYSEE SCHEDULEPER FLEXALUMINUMSURFACEWHITE-1,2,3,4,5,6AATITUS / 350FLRETURNSEE SCHEDULEPER FLEXALUMINUMSURFACEWHITE-3,4,6,10BBTITUS / FJRETURNSEE SCHEDULEPER FLEXALUMINUMSURFACEWHITE-1,2,3,4,5,6NOTES:1) PROVIDE SPIN IN COLLWER W/ VOLUME DMAPER AT TRUNK TO FLEX DUCT CONNECTION (SEE DETAIL).2) PROVIDE TYPICAL 4-WAY DIFFUSION, 2 -WAY, 3-WAY OR VERTAL ONLY WHERE INDICATED ON PLANS.3) REFER TO ARCHITECT PLANS FOR CEILING TYPE.4) FINAL COLAR SELECTION SUBJECT TO ARCHTIECT APPROVAL.5) FLEX DUCT SIZE TO BE SAME AS DIFFUESR NECK SIZE.6) CONTRACTOR TO COORDINATE FINAL SELECTION WITH ARCHITECT AND OWNER.7) DOUBLE DEFLECTION, FRONT BLADES PARALLEL TO SHORT (VERTICAL) DIMENSION.8) BLADES PARALLEL TO LONG (HORIZONTAL) DIMENSION.9) 0 DEG DEFLECTION10) ALL TRANSFER AIR GRILLES SHALL BE SIZED TO COMPLY WITH FMC 601.6 - BALANCED RETURN AIR OR FBC - RESIDENTIAL 1602.3 - BALANCED RETURN AIR.11) SINGLE BLADES PARALLEL TO SHORT (VERTICAL) DIMENSION.12) ALL SUPPLY, RETURN, AND TRANSFER DIFFUSERS ARE SELECTED AND DESIGNED TO NOT EXCEED A NOISE CRITERIA (NC) VALUE OF 20.FLEX RUN-OUT TABLESIZEAIR FLOW4"0 - 25 CFM6"26 - 80 CFM8"81 - 175 CFM10"176 - 300 CFM12"301 - 450 CFM14"451 - 700 CFM16"701 - 1000 CFMTITUS / FLOWBAR (HIGH THROW)SIZECFM RANGESIZECFM RANGE(1) 1"x2'0 - 110 CFM(1) 2"x2'0 - 140 CFM(1) 1"x4'111 - 200 CFM(1) 2"x4'141 - 325 CFM(1) 1"x5'201 - 250 CFM(1) 2"x5'326 - 370 CFMTITUS / 350FL SCHEDULESIZECFM RANGESIZECFM RANGE4"x4"6"x6"0 - 80 CFM6"x4"8"x8"81 - 175 CFM8"x6"10"x10"176 - 300 CFM10"x8"12"x12"301 - 500 CFM12"x8"14"x14"501 - 725 CFM16"x16"726 - 1025 CFM18"x18"1026 - 1200 CFM24"x24"TITUS / FLOWBAR (JET THROW)SIZECFM RANGESIZECFM RANGE(1) 1"x2'0 - 185 CFM(1) 1.5"x2'0 - 300 CFM(1) 1"x4'186 - 325 CFM(1) 1.5"x4'301 - 500 CFM(1) 1"x5'326 - 365 CFM(1) 1.5"x5'501 - 600 CFM1 1/2'' MIN1/2"MAX SPACING NOT TO EXCEED5' WITH SAG NOT TO EXCEED1/2'' OVER 5' INTERVALSPIN COLLARTYPICAL TOFLEXMASTERCB OR CBDGAUGE242220THK..028.034.0401'' STRAPCAPABILITY84010701298MAXIMUMLOAD168216259* ELASTIC LIMIT ASSUMED30ksi; RECOMMEND MAX LOAD(20% OF YIELD STRENGTH).NOTES:1. FLEX DUCT WITH EXTERNAL INSULATION AND VAPORBARRIER JACKETING TYPICAL TO ''FABRIFLEX''2.'' INSPECTOR SERIES'' SPIN DOORS2SUPPORT REQUIREMENTS FOR DUCT A7SCALE: N.T.S.MAINSUPPLY TRUNKRETURN A
IR
F
LOWSUPLY
A
IR
F
LOW
TYPICAL TRANSITIONMAX. 20° ANGLEBRANCH DUCTVOLUME DAMPER W/LOCK DIVICESTEEL HANGERS ORTRAP TO STRUCTURESTRUCTURAL CHANNEL45° TAKEOFFBRANCH DUCT TAKEOFF DETAILA3SCALE: N.T.S.3. PROVIDE HANGER SPACING IAW FBCM AND SMASNASTEEL HANGERSTO STRUCTUREC4SCALE: N.T.S.FLEXIBLE DUCT HANGER DETAILSLAB MOUNT CONDENSING UNITB5SCALE: N.T.S.TYPICAL VENT LOUVERTERMINATION AT WEATHERSCALE: N.T.S.NOTES:1.PROVIDE XVENT OR EQUAL NON-COORROSIVE WALL LOUVER W/ INTEGRAL NON-RETURN DAMPERRATED FOR MIAMI-DADE SERVICE.2.MOUNT FLUSH WITH STRUCTURE AND SECURE W/ MASONARY ANCORS.3.APPLY FINISHED WALL SURFACE TO LOUVER FLANGE.4.PAINT TO SUIT ARCHITECTURAL FINISH.SECTION A-AB1CONDENSING UNITCONCRETE SLABMIN. 6" THKBY OTHERS (HEIGHT TO SUIT FLOODPLANE REQUIREMENTS)MIN. 2' SPACINGBETWEEN CU (VERIFYW/ MANUFACTURER)TIE DOWN CLIP(TYP OF 4). SEE DETAIL.L/S LINES ROUTED IN4"Ø PVC SLEEVE &CAULKED ATEXTERIOR INLETSUCTION LINE TO BESHEATHED IN MIN. 1/2"ARMAFLEX INSULATIONREEFER LINES ROUTEDUNDER SLAB TO AHU/ FCU(SEE PLANS FOR ROUTE)6" MIN. OFFSETFROM SLAB (TYP)NOTES:1.CU SHALL BE LOCATED ONE (1) FOOT ABOVE THE BASE FLOOD ELEVATION OR THEELEVATION REQUIRED BY THE FLORIDA BUILDING CODE, WHICHEVER IS HIGHER. SEEARCHITECTURAL PLANS.2.CU SHALL BE LOCATED ON 6" THICK SLAB OR EQUIVALENT.3.EQUIPMENT TIE DOWN SHALL BE CARRIER LARGE BASE CUBE (OR ALTERNATE MNFREQUAL) ENGINEERED TIE DOWN STRAPS FOR CONCRETE FOUNDATION ATTACHMENT USE: (2) 14"ØX 214" LG HEX HEAD STAINLESS STEEL BUILDEX TAPCON STEEL SCREWS (SHW4-214) AND 516"Ø STAINLESS STEEL WASHERS OR(2)14"ØX 214" LG HEX HEAD BLUE COATED BUILDEX TAPCON SCREWS (HW4-214) AND 516"Ø STAINLESS STEEL WASHERS OR(2)14"Ø X 3" LG POWER WEDGE BOLT HEAVY DUTY CONCRETEANCHORS.(2)#12-14 x 1" LG (HWH#3) HILTI KWIK-FLEXSELF DRILLING STEEL SCREW W/WASHERS12"12"CONCRETE PADBASE PAN21" MIN
25" MAX1318"12"2"TIE DOWN CLIP DETAILA1SCALE: N.T.S.TIE DOWN CLIPNOTE: CONTRACTOR TO VERIFY MANUFACTURER SPECIFIC REQUIREMENTSA5CEILING SLOTTERMINAL (SEE PLAN)HARD CEILING(H3) CLIP (TYP)CONNECT TO MNF DISTPLENUMFINISHED SURFACE(SEE ARCH DWGS)DIFFUSER FRAMING (TYP)FINISHED SURFACE(SEE ARCH DWGS)CEILING SLOT DIFFUSERFRAME/MNT DETAILSCALE: N.T.S.D1MAX 22x4 SHT MTL TRANSFER AIRDUCT (SEE PLAN)FLEXIBLE TRANSFERAIR DUCT ABV CEILING(SEE PLAN)TRANSFER GRILLE 1'-0"AFF/BELOW CEILINGFIELD FABRICATED TRANSFER BOXSCALE: N.T.S.SUPPLY AIR DUCTFRONT VIEWPRIMARY CONDENSATEW/ 6" VENT & TRAPAIR FILTERLIQUID & SUCTIONLINESSECONDARY CONDENSATEW/ FLOAT SWITCHAIR HANDLERUNITRETUR AIR DUCTFROM ABOVE (SEE PLANFOR ROUTE & LOCATIONIN FAN ROOM)SIDE VIEWSUPPLY AIR DUCTPRIMARY CONDENSATEW/ 6" VENT & TRAPSECONDARY CONDENSATEW/ FLOAT SWITCHREFIRGERANT LINESRETURN AIR DUCT2"x2"x1/4" ANGLEIRON SUPPORTNEOPRENE PAD(TYP OF 4)VERTICAL MNT AHU W/ RA TOOVERHEADB3SCALE: N.T.S.DEHUMIDIFIER OPERATION SCHEMATIC &NOTES (BASIC)C1SCALE: N.T.S.6"Ø12"Ø6"Ø12"Ø 12"ØDEHUMIDIFIERCONTROL DAMPER(100% OPEN UPON OPERATION/0% OPEN UPON DEACTIVATION)R/A MANUAL CONTROL DAMPER(BALANCE TO 430 CFM & FIX W/ SCREW)12"ØFROM R/A SYSTEMFROM O/A LOUVERTO R/A SYSTEM AT AHUACCESS SCUTTLEM1020200INITIAL ISSUEJWLE09.24.21PERMIT SET 09.24.21
JOHN LANGFORD, FL#69962HVAC PLAN,DETAILS
OPEN TOABOVESLOPESLOPEELEVATORUP
UP 9'-0" C.H.HEADER @ 8'-0"10'-0" C.H.9'-0" C.H.10'-0" C.H.10'-0" C.H.10'-0" C.H.10'-0" C.H.6 CAR GARAGEMUD ROOMFOYERCOVERED ENTRYSTORAGESD/CMMAINT ACCESS AREAPIPE / PWR CONNECTMAINT ACCESS AREAPIPE / PWR CONNECTMAINT ACCESS AREAPIPE / PWR CONNECTMAINT ACCESS AREAPIPE / PWR CONNECTAHU 1-011 TON200 CFMCU 2-025 TONCU 2-015 TONCU 3-015 TONCU 3-024 TONWALL LOUVERGWH O/ALOW ON WALL MIN. 3' BELOWE/A LOUVER AND 1' ABV.GRADEWALL LOUVERGWH E/AR4"Ø COMMON O/AVENT PIPER4"Ø COMMON E/AVENT PIPEB(1)1"x2'94 CFM2xA6"x4"12 CFMBB(1)1"x4'200 CFMF4"ØF6"ØF6"Ø10"x6"F9"ØCU 1-011 TONWALL LOUVERCOMBUSTION AIR FOR POOLEQUIPMENT.MVDR24"ØFINAL DUCT ARRANGEMENTS RESERVEDPENDING STRUCTURAL COORDINATIONM20103HVAC FLOOR PLAN - 1ST LEVELSCALE: 1/4" = 1'-0"PLANNORTH00INITIAL ISSUEJWLE09.24.21PERMIT SET 09.24.21
JOHN LANGFORD, FL#69962HVAC PLAN, FIRSTFLOOR
48" RANGE
SLOPE ELEV.REF.FR.SLOPE
SPAPOOLSUNSHELFDN WETBARSLOPEDNUP
LINEAR FIRE PITNATURAL GASVENTLESS FPNATURAL GASVENTLESS FPGLASS WINE CELLARROLL DOWN SCREENROLL DOWN SCREENNATURAL GASVENTLESSFIREPLACE2-DWRBEV.ABV. COUNTERSTORAGEROLL DOWN SCREENUTILITYCOVERED TERRACECOVERED TERRACEPANTRYBEDROOM #2WICPWDRBATHCABANACLUBROOMGREAT ROOMKITCHENDININGOUTDOOR LIVINGPOOL TERRACESTOR.SD/CMSD/CMAHU 2-015 TON2000 CFMAHU 2-025 TON2000 CFMEF0150 CFMEF0150 CFMEF0150 CFMRANGE HOODEST 399 CFMWL 12"x12"RANGE E/A6"x6" WALL LOUVERTOILET E/AR4"DRYERE/A UP6"x6" WALL LOUVERDRYER E/A6"x6" WALL LOUVERTOILET E/A6"x6" WALL LOUVERTOILET E/AB(1)1"x4'150 CFM2xB(1)1"x4'200 CFMA8"x6"75 CFMB(1)1"x4'195 CFMB(1)1"x4'185 CFM4xB(1)1.5"x5'210 CFM2xA6"x4"20 CFMA6"x4"50 CFMF8"ØF8"ØF8"ØF8"ØF8"ØF8"ØF8"ØF5"ØF4"ØF8"ØF8"ØF8"ØF6"Ø18"x10"18"x10"
12"x10"28"x12"BB(1)1.5"x5'550 CFM2xBB(1)1.5"x5'450 CFM2xF12"ØF12"Ø(x2)F10"Ø(x2)F10"Ø34"x12"CD 1-01VDR12"ØR6" OUTSIDE AIR INTAKE FROMROOF JACK (V.I.F.) MAINTAIN10'-0" FROM EXH. OPGS/PLMBG.VENTSR12"ØUCUCUCUCUCUCF8"ØA10"x8"190 CFMA14"x10"330 CFM2xB(1)1"x5'240 CFM4xB(1)1"x2'108 CFMA8"x6"67 CFMA6"x4"15 CFMAA14"x10"432 CFM2xBB(1)2"x4'568 CFM2xF10"ØF10"ØF4"ØF7"ØF6"ØF9"ØF9"ØF9"ØF9"ØF12"ØF12"Ø(x2)F10"Ø(x2)F10"Ø28"x12"22"x10"28"x12"26"x10"R4"ØR10"ØR4"ØR4"ØR4"ØCOMBUSTION AIRTRANSFER GRILLESEE DETAILF12"COMBUSTIONAIR DUCTR6"Ø34"x12"DH 1-1VENTLESS FIREPLACE. BRANDAND MODEL #TBD.R8"Ø UP TO ROOF JACKBBQ E/ABBQ HOODWL 10"x10"BBQ E/AR8"ØFINAL DUCT ARRANGEMENTS RESERVEDPENDING STRUCTURAL COORDINATIONM20204HVAC FLOOR PLAN - 2ND LEVELSCALE: 1/4" = 1'-0"PLANNORTH00INITIAL ISSUEJWLE09.24.21PERMIT SET 09.24.21
JOHN LANGFORD, FL#69962HVAC PLAN,SECOND FLOOR
HBBUILT INOPEN TOBELOWDNSLOPE
LINENSLOPE
SLOPE
LINEN CL.MECH.COFFEE BAR
CL9'-0" CLG10'-0" CLG10'-0" CLG10'-0" CLG10'-0" CLG10'-0" CLG9'-0" CLG9'-0" CLG9'-0" CLG9'-0" CLG10'-0" CLG9'-0" CLG10'-0" CLG9'-0" CLG
10'-0" CLG10'-0" CLG9'-8" CLG10'-0" CLG9'-0" CLG9'-0" CLG10'-0" CLG10'-0" CLGSLOPE
SLOPESLOPEMECH.MASTER CLOSETBEDROOM #3BATHWICMASTER BEDROOMLOUNGESUN TERRACECOVERED TERRACEBATHOFFICE/WORKOUTMASTER BATHSUN TERRACECOVERED TERRACECOVERED TERRACESUN TERRACELAUNDRYSUN TERRACESD/CMSD/CMSD/CMSD/CMSD/CMSD/CMSD/CMAHU 3-015 TON2000 CFMAHU 3-024 TON1600 CFMEF02110 CFM/VTREF0150 CFM/VTREF02110 CFM/VTREF02110 CFMR4"DRYER E/A UPTO ROOF JACKB(1)1"x5'250 CFM2xB(1)1"x5'215 CFM4xA10"x8"145 CFMA6"x4"47 CFMA6"x4"18 CFMB(1)1"x4'195 CFM2xA6"x4"40 CFMF7"ØF8"ØF8"ØF8"ØF8"ØF5"ØF9"ØF9"ØF4"ØF8"ØF8"ØF5"ØBB(1)1.5"x5'523 CFM2xBB(1)1.5"x5'524 CFMBB(1)1"x4'215 CFM2x(x2)F10"Ø(x2)F10"Ø(x2)F10"ØF9"ØF9"Ø22"x12"16"x12"10"x10"12"x10"
26"x12"A10"x8"150 CFMA10"x8"144 CFM2xA6"x4"18 CFMB(1)1"x4'150 CFMB(1)1"x4'200 CFM2xB(1)1.5"x4'112 CFMB(1)1.5"x4'133 CFM4xF8"ØF7"ØF7"ØF4"ØF8"ØF8"ØF8"ØF7"ØF7"ØF7"ØF7"ØF7"Ø16"x10"16"x10"24"x12"AA10"x8"228 CFM2xBB(1)1.5"x4'TRANSFERF10"ØF10"ØBB(1)1.5"x4'400 CFM4xF12"ØF12"ØF12"ØF12"Ø28"x12"UCUCUCUCUCUCUCUCDOOR TO REMAIN OPENUNLESS IN USE TO ENSUREPROPER AIR FLOWDOOR TO REMAIN OPENUNLESS IN USE TO ENSUREPROPER AIR FLOWCOMBUSTION AIRTRANSFER GRILLESEE DETAILF12"COMBUSTIONAIR DUCTVENTLESS FIREPLACE. BRANDAND MODEL #TBD.R6" OUTSIDE AIR INTAKE FROMROOF JACK (V.I.F.) MAINTAIN10'-0" FROM EXH. OPGS/PLMBG.VENTSFINAL DUCT ARRANGEMENTS RESERVEDPENDING STRUCTURAL COORDINATIONM20305HVAC FLOOR PLAN - 3RD LEVELSCALE: 1/4" = 1'-0"PLANNORTH00INITIAL ISSUEJWLE09.24.21PERMIT SET 09.24.21
JOHN LANGFORD, FL#69962HVAC PLAN, THIRDFLOOR
48" RANGE
SLOPE ELEV.REF.FR.SLOPE
SPAPOOLSUNSHELFDN WETBARSLOPEDNUP
LINEAR FIRE PITSD/CMSD/CMAHU 2-025 TONAHU 2-015 TON2344CONDENSATE FROM ABV.AND DN. IN WALL TOLOWER LVL. OVERHEADCONDENSATE DN. TOBELOW GRADECONDENSATE FROM ABV.AND DN. IN WALL TOLOWER LVL. OVERHEADCONDENSATE DN. IN WALL TOLOWER LVL. OVERHEADCONDENSATE DN. TOBELOW GRADESLOPESLOPEELEVATORUP
UP SD/CMMAINT ACCESS AREAPIPE / PWR CONNECTMAINT ACCESS AREAPIPE / PWR CONNECTMAINT ACCESS AREAPIPE / PWR CONNECTMAINT ACCESS AREAPIPE / PWR CONNECTAHU 1-011 TONCU 2-025 TONCU 2-015 TONCU 3-015 TONCU 3-024 TONCU 1-011 TON1212342CONDENSATE DN. TOBELOW GRADECONDENSATE FROM ABV. AND DN. INWALL TO LOWER LVL. OVERHEADCONDENSATE DN. TOBELOW GRADECONDENSATE GOOSENECKHBDNSLOPE
SLOPE
SLOPE
MECH.CLSLOPE
SLOPESLOPEAHU 3-024 TONAHU 3-015 TON42423CONDENSATE DN. TOBELOW GRADECONDENSATE DN. TOMAIN LVL. OVERHEADCONDENSATE DN.TO BELOW GRADESHEET M301 KEY NOTESNO.DESCRIPTION1.REFRIGERANT PIPING ABOVE GRADE TO BUILDING ENTRY.2.REFRIGERANT PIPING UP/DN BEHIND WALL TO OVERHEAD.3.REFRIGERANT PIPING OVERHEAD.4.REFRIGERANT PIPING UP/DN TO AHU.M30106PLANNORTH00INITIAL ISSUEJWLE09.24.21PERMIT SET 09.24.21
JOHN LANGFORD, FL#69962REFRIGERANT AND CONDENSATEPIPING PLAN - 2ND LEVELSCALE: 1/8" = 1'-0"REFRIGERANT AND CONDENSATEPIPING PLAN - 1ST LEVELSCALE: 1/8" = 1'-0"REFRIGERANT AND CONDENSATEPIPING PLAN - 3RD LEVELSCALE: 1/8" = 1'-0"HVAC PLAN, REFRG.& CONDENSATEPIPING PLAN