In-Place Density Test Report
Client:Panelli Fort Pierce, LLC UES Technician:Juan Hernandez
16460 SW 137th Avenue
Miami, FL 33177
Date Tested:01/06/2022
Project:CMT Wolflube Warehouse-Manufacturing Building Phase I
4774 South Jenkins Road, Fort Pierce, St. Lucie County, FL 34981
Type of Test:
Area Tested:North Retaining Wall Footing & North
Exterior Stair Pad
Field:ASTM D-6938 Nuclear Gauge Method
Material:Native Laboratory:AASHTO T180 Modified Proctor
Reference Datum:0 = Top of Footing
The tests below meet the 98% minimum compaction requirement.
Test
No.Location of Test Range
Maximum
Density
(pcf)
Optimum
Moisture
(%)
Field Dry
Density
(pcf)
Field
Moisture
(%)
Soil
Compaction
(%)
Pass
or
Fail
1 North west side of north retaining
wall footer
0-1 ft 105.2 11.5 103.8 11.3 99 Pass
2 North east side of north retaining wall
footer
0-1 ft 105.2 11.5 103.5 11.7 98 Pass
3 2' north from north exit door north
exterior pad
0-1 ft 114.2 13.8 112.8 11.1 99 Pass
Remarks: Permit: 2112-0081
Reviewed By
GFA International, Inc
FBPE Registry No.4930
Thomas Dominic Montano
Branch Manager
STATE OF FLORIDA
Professional Engineer No. 84146
This item has been digitally signed and sealed by Thomas Dominic
Montano on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.