GASPARILLA REVISION- MANUAL J
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-05 17:18:39 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...ts\Wrightsoft HVAC\HUDSON 4- GASPARILLA AVE.rup Calc = MJ8 Front Door faces: NW GARAGE LEFTJob:Project Summary JAN. 5, 2022Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information HUDSON 4 MODEL, SYNERGY BUILDERSFor: 430 SE GASPARILLA AVENUE, PORT ST LUCIE, FL 34983 Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh18300 Struc ture Btuh18501 Ducts Btuh5249 Ducts Btuh7632 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh23549 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh24826 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh3391 Ducts Btuh2048 Central vent (0 cfm)Btuh0 CoolingHeating (none) 18331833Area (ft²)Equipment latent load Btuh5439 1716817168Volume (ft³) Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh30265 Equiv. AVF (cfm)57109 Req. total capacity at 0.70 SHR ton3.0 Heating Equipment Summary Cooling Equipment Summary Make Make Rheem Trade Trade RHEEM Model Cond RA1436AJ1 AHRI ref Coil RH1P3617STAN AHRI ref 201184296 Efficiency 100 EFF Efficiency 11.5 EER, 14 SEER Heating input kW10.0 Sensible cooling Btuh23800 Heating output Btuh34121 Latent cooling Btuh10200 Temperature rise °F27 Total cooling Btuh34000 Actual air flow cfm1133 Actual air flow cfm1133 Air flow factor cfm/Btuh0.048 Air flow factor cfm/Btuh0.043 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.83 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-05 17:18:39 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...ts\Wrightsoft HVAC\HUDSON 4- GASPARILLA AVE.rup Calc = MJ8 Front Door faces: NW GARAGE LEFTJob:Right-J® Worksheet JAN. 5, 2022Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House M BATH 2 Exposed wall 166.9 ft 20.0 ft 3 Room height 9.4 ft 8.0 heat/coolft 4 Room dimensions ft14.0x6.0 5 Room area 1833.0 ft²84.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 372 322 1290 705 48 48 192 105 .GG 2 glazing, clr low-e 0.5502 glazing, clr low-e 0.550 nn 15.4015.40 13.4913.49 41 0 628 550 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 9.959.95 9 0 76 90 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 572 542 2170 1186 0 0 0 0 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 29.4829.48 30 0 252 885 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 160 125 499 273 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 9.959.95 15 15 126 149 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 20 20 223 211 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 392 362 1449 792 112 112 448 245 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.4829.48 30 0 252 885 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 1833 1833 1642 2933 84 84 75 134 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 1833 167 6347 0 84 20 760 0 6 c) AED excursion 0 -23 Envelope loss/gain 14954 8657 1476 462 12 a) Infiltration 3346 943 358 101 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 8900 300 Subtotal (lines 6 to 13)18300 18501 1834 863 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 18300 18501 1834 863 15 Duct loads 29%41%5249 7632 29%41%526 356 Total room load 23549 26133 2360 1219 Air required (cfm)Air required (cfm)1133 1133 114 53 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-05 17:18:39 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 ...ts\Wrightsoft HVAC\HUDSON 4- GASPARILLA AVE.rup Calc = MJ8 Front Door faces: NW GARAGE LEFTJob:Right-J® Worksheet JAN. 5, 2022Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC MASTER BEDROOM 2 Exposed wall 9.0 ft 29.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft14.0x9.0 ft14.0x15.0 5 Room area 126.0 ft²210.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 72 72 288 158 120 111 444 243 .GG 2 glazing, clr low-e 0.5502 glazing, clr low-e 0.550 nn 15.4015.40 13.4913.49 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 9.959.95 0 0 0 0 9 0 76 90 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 112 97 388 212 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 29.4829.48 0 0 0 0 15 0 126 442 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 9.959.95 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.4829.48 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 126 126 113 202 210 210 188 336 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 126 9 342 0 210 29 1103 0 6 c) AED excursion -10 -50 Envelope loss/gain 743 349 2325 1273 12 a) Infiltration 161 45 519 146 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 1200 Subtotal (lines 6 to 13)904 394 2844 2619 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 1 2 0 0 14 Subtotal 906 397 2844 2619 15 Duct loads 29%41%260 164 29%41%816 1080 Total room load 1166 560 3660 3699 Air required (cfm)Air required (cfm)56 24 176 160 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-05 17:18:39 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 3 ...ts\Wrightsoft HVAC\HUDSON 4- GASPARILLA AVE.rup Calc = MJ8 Front Door faces: NW GARAGE LEFTJob:Right-J® Worksheet JAN. 5, 2022Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 3 CLST 3 2 Exposed wall 11.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft149.0x1.0 ft8.0x2.0 5 Room area 149.0 ft²16.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5502 glazing, clr low-e 0.550 nn 15.4015.40 13.4913.49 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 9.959.95 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 29.4829.48 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 9.959.95 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 88 73 292 160 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.4829.48 15 0 126 442 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 149 149 134 238 16 16 14 26 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 149 11 418 0 16 0 0 0 6 c) AED excursion 184 -1 Envelope loss/gain 970 1024 14 25 12 a) Infiltration 197 55 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)1167 1580 14 25 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 12 20 -14 -25 14 Subtotal 1178 1600 0 0 15 Duct loads 29%41%338 660 29%41%0 0 Total room load 1516 2260 0 0 Air required (cfm)Air required (cfm)73 98 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-05 17:18:39 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 4 ...ts\Wrightsoft HVAC\HUDSON 4- GASPARILLA AVE.rup Calc = MJ8 Front Door faces: NW GARAGE LEFTJob:Right-J® Worksheet JAN. 5, 2022Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name KITCHEN/DINING BATH 2 2 Exposed wall 26.0 ft 6.0 ft 3 Room height 12.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft376.0x1.0 ft6.0x12.0 5 Room area 376.0 ft²72.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 132 91 365 200 0 0 0 0 .GG 2 glazing, clr low-e 0.5502 glazing, clr low-e 0.550 nn 15.4015.40 13.4913.49 41 0 628 550 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 9.959.95 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 180 165 661 361 0 0 0 0 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 29.4829.48 15 0 126 442 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 9.959.95 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 48 48 192 105 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.4829.48 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 376 376 337 602 72 72 65 115 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 376 26 989 0 72 6 228 0 6 c) AED excursion -147 -19 Envelope loss/gain 3106 2008 485 201 12 a) Infiltration 698 197 107 30 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 3400 500 Subtotal (lines 6 to 13)3803 5605 592 731 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 16 27 9 15 14 Subtotal 3819 5632 601 747 15 Duct loads 29%41%1095 2323 29%41%172 308 Total room load 4914 7955 773 1054 Air required (cfm)Air required (cfm)236 345 37 46 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-05 17:18:39 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 5 ...ts\Wrightsoft HVAC\HUDSON 4- GASPARILLA AVE.rup Calc = MJ8 Front Door faces: NW GARAGE LEFTJob:Right-J® Worksheet JAN. 5, 2022Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 2 HALL 2 Exposed wall 12.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft12.0x12.0 ft39.0x1.0 5 Room area 144.0 ft²39.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5502 glazing, clr low-e 0.550 nn 15.4015.40 13.4913.49 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 9.959.95 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 29.4829.48 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 9.959.95 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 96 81 324 177 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.4829.48 15 0 126 442 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 144 144 129 230 39 39 35 62 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 144 12 456 0 39 0 0 0 6 c) AED excursion 183 -2 Envelope loss/gain 1036 1033 35 61 12 a) Infiltration 215 61 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)1250 1594 35 61 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 13 23 -35 -61 14 Subtotal 1263 1616 0 0 15 Duct loads 29%41%362 667 29%41%0 0 Total room load 1626 2283 0 0 Air required (cfm)Air required (cfm)78 99 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-05 17:18:39 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 6 ...ts\Wrightsoft HVAC\HUDSON 4- GASPARILLA AVE.rup Calc = MJ8 Front Door faces: NW GARAGE LEFTJob:Right-J® Worksheet JAN. 5, 2022Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 2 LAUNDRY 2 Exposed wall 0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft8.0x2.0 ft8.0x7.0 5 Room area 16.0 ft²56.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5502 glazing, clr low-e 0.550 nn 15.4015.40 13.4913.49 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 9.959.95 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 29.4829.48 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 9.959.95 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.4829.48 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 16 16 14 26 56 56 50 90 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 16 0 0 0 56 0 0 0 6 c) AED excursion -1 -18 Envelope loss/gain 14 25 50 72 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 600 Subtotal (lines 6 to 13)14 25 50 672 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -14 -25 200 130 14 Subtotal 0 0 250 802 15 Duct loads 29%41%0 0 29%41%72 331 Total room load 0 0 322 1132 Air required (cfm)Air required (cfm)0 0 15 49 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-05 17:18:39 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 7 ...ts\Wrightsoft HVAC\HUDSON 4- GASPARILLA AVE.rup Calc = MJ8 Front Door faces: NW GARAGE LEFTJob:Right-J® Worksheet JAN. 5, 2022Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name AHU CLST GREAT ROOM 2 Exposed wall 0 ft 14.0 ft 3 Room height 8.0 heat/coolft 12.0 heat/coolft 4 Room dimensions ft3.0x3.0 ft250.0x1.0 5 Room area 9.0 ft²250.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5502 glazing, clr low-e 0.550 nn 15.4015.40 13.4913.49 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 9.959.95 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 168 168 673 368 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 29.4829.48 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 9.959.95 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.4829.48 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 9 9 8 14 250 250 224 400 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 9 0 0 0 250 14 532 0 6 c) AED excursion 0 -58 Envelope loss/gain 8 14 1429 710 12 a) Infiltration 0 0 376 106 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 1400 Subtotal (lines 6 to 13)8 14 1805 2215 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -8 -14 544 302 14 Subtotal 0 0 2348 2517 15 Duct loads 29%41%0 0 29%41%674 1038 Total room load 0 0 3022 3556 Air required (cfm)Air required (cfm)0 0 145 154 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-05 17:18:39 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 8 ...ts\Wrightsoft HVAC\HUDSON 4- GASPARILLA AVE.rup Calc = MJ8 Front Door faces: NW GARAGE LEFTJob:Right-J® Worksheet JAN. 5, 2022Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name FOYER CLST 4 2 Exposed wall 7.0 ft 2.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft112.0x1.0 ft16.0x1.0 5 Room area 112.0 ft²16.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5502 glazing, clr low-e 0.550 nn 15.4015.40 13.4913.49 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 9.959.95 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 16 16 64 35 11 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ee 8.408.40 29.4829.48 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 56 36 143 78 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 9.959.95 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 20 20 223 211 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.4829.48 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 112 112 100 179 16 16 14 26 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 112 7 266 0 16 2 76 0 6 c) AED excursion -13 -2 Envelope loss/gain 732 455 154 59 12 a) Infiltration 125 35 36 10 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)857 490 190 69 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -857 -490 -190 -69 14 Subtotal 0 0 0 0 15 Duct loads 29%41%0 0 29%41%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2022-Jan-05 17:18:39 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 9 ...ts\Wrightsoft HVAC\HUDSON 4- GASPARILLA AVE.rup Calc = MJ8 Front Door faces: NW GARAGE LEFTJob:Right-J® Worksheet JAN. 5, 2022Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 4/DEN 2 Exposed wall 30.9 ft 3 Room height 8.0 heat/coolft 4 Room dimensions ft158.0x1.0 5 Room area 158.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 .G 2 glazing, clr low-e 0.550 n 15.40 13.49 0 0 0 0 .G 2 glazing, clr low-e 0.300 n 8.40 9.95 0 0 0 0 .W 13A-4ocs 0.143 e 4.00 2.19 96 96 384 210 11 G 2 glazing, clr low-e 0.300 e 8.40 29.48 0 0 0 0 W 13A-4ocs 0.143 s 4.00 2.19 104 89 356 195 G 2 glazing, clr low-e 0.300 s 8.40 9.95 15 15 126 149 D 11D0 0.390 s 10.92 10.34 0 0 0 0 W 13A-4ocs 0.143 w 4.00 2.19 48 48 192 105 G 2 glazing, clr low-e 0.300 w 8.40 29.48 0 0 0 0 C 16B-30ad 0.032 -0.90 1.60 158 158 142 253 F 22A-tph 1.358 -38.02 0.00 158 31 1176 0 6 c) AED excursion -24 Envelope loss/gain 2376 888 12 a) Infiltration 555 156 b) Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 500 Subtotal (lines 6 to 13)2931 1544 Less external load 0 0 Less transfer 0 0 Redistribution 325 165 14 Subtotal 3256 1709 15 Duct loads 29%41%934 705 Total room load 4190 2414 Air required (cfm)202 105 2022-Jan-05 17:18:43 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...ts\Wrightsoft HVAC\HUDSON 4- GASPARILLA AVE.rup Calc = MJ8 Front Door faces: NW GARAGE LEFTJob:Duct System Summary JAN. 5, 2022Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information HUDSON 4 MODEL, SYNERGY BUILDERSFor: 430 SE GASPARILLA AVENUE, PORT ST LUCIE, FL 34983 CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm1133cfm1133 Total effective length (TEL)ft142 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk 95.05.0VlFx0x06.01.00046371054cBATH 2 95.010.0VlFx0x07.01.00099782283cBEDROOM 2 st1115.022.0VlFx0x07.01.00098732260cBEDROOM 3 95.023.4VlFx0x07.01.0001052024190hBEDROOM 4/DEN st2115.025.5VlFx0x08.01.0001541453556cGREAT ROOM st2115.025.5VlFx0x07.01.000115792652cKITCHEN/DINING st2115.020.1VlFx0x07.01.000115792652cKITCHEN/DINING-A st1115.020.4VlFx0x07.01.000115792652cKITCHEN/DINING-B 95.04.5VlFx0x06.01.00049151132cLAUNDRY st1115.026.8VlFx0x06.01.000531142360hM BATH st1115.023.3VlFx0x05.01.00024561166hM WIC st1115.023.0VlFx0x08.01.0001601763660hMASTER BEDROOM Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st2 Peak AVF 303 384 1.000 704 10.0 0x0 VinlFlx st1 Peak AVF 498 450 1.000 633 12.0 0x0 VinlFlx 2022-Jan-05 17:18:43 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 ...ts\Wrightsoft HVAC\HUDSON 4- GASPARILLA AVE.rup Calc = MJ8 Front Door faces: NW Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 11330 1133 0 0 0 0 x0 0 VlFx ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������