HomeMy WebLinkAboutPHOTOVOLTAIC SYSTEMVICINITY MAPSITE MAP (N.T.S)SITE DETAILS33°CASHRAE EXTREME LOWASHRAE 2% HIGHGROUND SNOW LOADWIND SPEEDRISK CATEGORYWIND EXPOSURE CATEGORY0°C0 PSF160 MPH (ASCE 7-16)IICDC RATING OF SYSTEMAC RATING OF SYSTEMMAX. AC OUT. CURRENTNO. OF MODULESNO. OF INVERTERSNO. OF BATTERYARRAY STRINGINGDESCRIPTIONNEW GRID-INTERACTIVE PHOTOVOLTAIC SYSTEM WITH BATTERY STORAGESYSTEM DETAILSGOVERNING CODESFLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 (FRC)FLORIDA BUILDING CODE, 7TH EDITION 2020 (FBC)FLORIDA FIRE PREVENTION CODE, 7TH EDITION 2020 (FFPC)WIND FLOW MAPNATIONAL ELECTRIC CODE, NEC 2017 CODE BOOKGENERAL NOTESSCOPE OF WORK1.THE PROJECT IS NEW PHOTOVOLTAIC SYSTEM CONSISTING OF SOLARARRAY(S) AND ASSOCIATED POWER CONDITIONING EQUIPMENT WITH BATTERYBACKUPSYSTEM.2.ALL CONSTRUCTION SHALL COMPLY WITH THE ADOPTED EDITION OF THEINTERNATIONAL BUILDING CODE AND ELECTRIC CODE AS SPECIFIED IN THE PROJECTSPECIFIC NOTES.3.IT SHALL ALSO COMPLY WITH ALL APPLICABLE CITY, COUNTY, STATE ANDLOCAL ELECTRICAL UTILITY CODES, RULES AND REGULATIONS.4.THE SYSTEM WILL BE INTERCONNECTED TO THE ELECTRICAL UTILITYGRID IN ACCORDANCE WITH THE REQUIREMENTS OF THE ADOPTED ELECTRIC AND THEELECTRICAL UTILITY COMPANY.5.THE CONTRACTOR SHALL PROVIDE LABOR FOR CONSTRUCTION OF THEARRAY AND INSTALLATION OF ALL ELECTRICAL EQUIPMENT. THE CONTRACTOR WILLPROVIDE COMPETENT SUPERVISION FOR THE WORK TO BE ACCOMPLISHED.CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR APPROVAL BY OWNER ASREQUESTED.6.THERE WILL BE NO SUBMISSION FOR ANY EQUIPMENT WITH THE VENDORPART NUMBER ON THE DRAWING WITHOUT WRITTEN APPROVAL OF THE PROFESSIONALENGINEER. COMMON ITEMS SUCH AS CONDUITS, WIRE, FITTINGS, ETC. ARE NOTSPECIFIED BY VENDOR BUT THE SIZES CANNOT BE REDUCED.7.THE CONSTRUCTION CONTRACTOR AND HIS SUBCONTRACTORS AGREETHAT IN ACCORDANCE WITH THE GENERALLY ACCEPTED CONSTRUCTION PRACTICESCONSTRUCTION CONTRACTOR AND HIS SUBCONTRACTORS WILL BE REQUIRED TOASSUME SOLE AND COMPLETE RESPONSIBILITY FOR THE SAFETY OF ALL PERSON ANDPROPERTY, AND THAT THIS REQUIREMENT SHALL BE MADE TO APPLY CONTINUOUSLYAND IS NOT LIMITED TO NORMAL WORKING HOURS.8.CONSTRUCTION CONTRACTOR AND HIS SUBCONTRACTORS FURTHERAGREE TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE DESIGN PROFESSIONALFROM ANY AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION WITH THEPERFORMANCE OF WORK ON THIS PROJECT, EXCEPT LIABILITY ARISING FROM THESOLE NEGLIGENCE OF THE DESIGN PERSONNEL.9.CONSTRUCTION CONTRACTOR AND HIS SUBCONTRACTORS WILL BEREQUIRE TO REPAIR ANY DAMAGE DONE TO BUILDINGS, GROUNDS OR UTILITIES AT NOADDITIONAL COST TO THE CUSTOMER. DEFECTIVE MATERIAL OR WORKMANSHIP WILLNOT BE ALLOWED ON THIS PROJECT.RESONABLE HOUSEKEEPING AND CLEAN UPSHALL BE CONDUCTED BOTH DURING THE EXECUTION OF AND AT THE CONCLUSION OFTHE PROJECT.GENERAL1.THE ACTUAL SYSTEM EQUIPMENT SPECIFICATIONS FOR THEPHOTOVOLTAIC SYSTEM ARE INCLUDED IN THE PV SYSTEM SPECIFICATION ON THETITLE PAGE AND THROUGHOUT THE DRAWING AS NECESSARY FOR CLARITY.INADDITION THE ACTUAL VENDOR SPECIFICATION DATA SHEETS WILL BE INCLUDED ASPART OF THE PERMIT SUBMITTAL.2.ONLY NEW MATERIAL WILL BE INSTALLED AS PART OF THE PROJECT.ALL NEW INSTALLED EQUIPMENT WILL BE APPROPRIATELY LISTED AND NEMA RATED.ALL NEW EQUIPMENT SHALL HAVE PERMANENT PLASTIC ENGRAVED IDENTIFICATIONTAGS INSTALLED.3.ALL CUTTING AND PATCHING REQUIRED FOR INSTALLATION OF NEWRACEWAYS AND EQUIPMENT SHALL BE RESPONSIBILITY OF THE ELECTRICALCONTRACTOR. ALL WORK SHALL BE PERFORMED BY TRADESMANEXPERIENCED IN WORK REQUIRED. ALL FINISHES SHALL MATCH THE EXISTINGADJACENT FINISHES. OPENING IN FIRE RATED WALLS WILL BE PATCHED IN AMANNER MAINTAINING THE ORIGINAL FIRE AND SMOKE RATING.4.DRAWINGS ARE DIAGRAMMATIC IN NATURE AND CANNOT SHOW EVERYCONNECTION, JUNCTION BOX, WIRE,CONDUIT,ETC. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE ANDFUNCTIONAL ELECTRICAL SYSTEM.5.CONTRACTOR SHALL COORDINATE ALL POWER OUTAGES WITH THEOWNER'S REPRESENTATIVE IN ADVANCE.6.PANEL DESIGNATIONS SHOWN ON THESE DRAWINGS ARE GIVEN FORCLARIFICATION OF THE CIRCUITING ONLY AND MAYNOT CORRESPOND TO THE DESIGNATIONS FOUND IN THE FIELD.7.ELECTRICAL TESTING SHALL BE IN COMPLIANCE WITH NFPA 70ECONDUIT AND WIRE1.ALL EXISTING CONDUIT RUNS ARE NOT SHOWN. CONTRACTOR SHALLVERIFY EXISTING CONDUIT LOCATIONS IN FIELD.2.ALL CONDUCTORS SHALL BE INSTALLED IN A RACEWAY AS SPECIFIEDIN THE DRAWINGS. THE EXCEPTION IS PV SOURCE CIRCUIT CONDUCTORS MADEOF PV WIRE CABLE. THESE CONDUCTORS MAY BE EXPOSED WITHIN THE PV ARRAY.3.INDOOR EMT FITTINGS MAY BE COMPRESSION TYPE OR STEEL SETSCREW TYPE. OUTDOOR EMT FITTINGS MUST BE COMPRESSION RAINTIGHT TYPE.4.A PULL ROPE SHALL BE INSTALLED IN ALL EMPTY CONDUITS.5.CONDUCTORS MATERIAL, EITHER COPPER OR ALUMINUM INSPECIFIED IN THE DRAWINGS. CONDUCTOR INSULATION TYPE SHALL BE THWN - 2UNLESS OTHERWISE NOTED.EQUIPMENT1.ALL ELECTRICAL COMPONENTS INSTALLED OUTDOORS, EXPOSED TOWEATHER OR IN DAMP LOCATIONS SHALL BE RATED FOR NEMA 3R OR GREATER.INSTALLATION OF THESE COMPONENTS MUST COMPLY WITH THEMANUFACTURER'S INSTALLATION INSTRUCTIONS.2.ALL RACEWAYS, CABINETS, BOXES, FIXTURES SHALL BE SUPPORTEDFROM THE BUILDING STRUCTURE IN AN APPROVED MANNER.3.AT THE COMPLETION OF THE PROJECT NEATLY TYPED ACCURATEPANEL BOARD DIRECTORIES INDICATING ALL BRANCH CIRCUITS AND SPARES WILLBE PROVIDED. ALL SPARES SHALL BE LEFT IN THE OFF POSITION.4.ALL SAFETY SWITCHES SHALL BE HEAVY DUTY TYPE WITH COVERINTERLOCK AND HANDLE LOCK OFF PROVISIONS. SWITCHES SHALL BEMANUFACTURED BY A COMPANY CONSISTENT WITH OTHER INSTALLED EQUIPMENTWHENEVER POSSIBLE. PART NUMBERS, RATING AND FUSING SHALL BE AS SHOWNON THE DRAWINGS.5.CONTRACTOR SHALL ENSURE ALL CEC AND MAINTENANCECLEARANCE REQUIREMENTS ARE MET FOR NEW EQUIPMENT AND MAINTAINED FOREXISTING EQUIPMENT.6.CONTRACTOR SHALL FIELD VERIFY EQUIPMENT CLEARANCE ANDPLACEMENTS WHILE COORDINATING LOCATORS WITHOTHER TRADES, CONSTRUCTION MANAGERS, AND SITE SUPERVISORS PRIOR TOPURCHASING AND INSTALLING EQUIPMENT.7.EVERY STRUCTURE AND PORTION THEREOF, INCLUDINGNONSTRUCTURAL COMPONENTS THAT ARE PERMANENTLY ATTACHED TOSTRUCTURES AND THEIR SUPPORTS AND ATTACHMENTS, SHALL BE DESIGNED ANDCONSTRUCTED TO RESIST THE EFFECTS OF EARTHQUAKE MOTIONS INACCORDANCE WITH ASCE 7, EXCLUDING CHAPTER 14 AND APPENDIX11A. THE SEISMIC DESIGN CATEGORY FOR A STRUCTURE IS PERMITTED TO BEDETERMINED IN ACCORDANCE WITH SECTION 1613 OR ASCE 7.8.ALL CONTROLS AND SWITCHES INTENDED TO BE USED BY THEOCCUPANT OF THE ROOM OR AREA TO CONTROLLIGHTING AND RECEPTACLE OUTLETS, APPLIANCE AND COOLING, HEATING AN DVENTILATING EQUIPMENT, SHALL BE LOCATEDNO MORE THAN 48 INCHES MEASURED FROM THE TOP OF THE JUNCTION OR DEVICEBOX NOR LESS THAN 15 INCHESMEASURED TO THE BOTTOM OF THE JUNCTION OR DEVICE BOX ABOVE THEFINISHED FLOOR.9.ALL RECEPTACLE OUTLETS ON BRANCH CIRCUITS OF 30 - AMPERES ORLESS AND COMMUNICATION SYSTEM RECEPTACLESSHALL BE LOCATED NO MORE THAN 48 INCHES MEASURED FROM THE TOP OF THERECEPTACLE OUTLET BOX OR RECEPTACLEHOUSING NOR LESS THAN 15 INCHES MEASURED TO THE BOTTOM OF THERECEPTACLE OUTLET BOX OR RECEPTACLE HOUSING ABOVE FINISHED FLOOR.GROUNDING1.THE GROUNDING SYSTEM SHALL MEET THE REQUIREMENTS OF THENEC AND THE LOCAL ADOPTED CODE. ALL ELECTRICAL EQUIPMENT AND RACEWAYSSHALL BE PROPERLY GROUNDED.2.AN INSULATED EQUIPMENT GROUNDING CONDUCTOR, INACCORDANCE WITH NEC CODE , SHALL BE PROVIDED IN ALL CONDUITS WITHCURRENT CARRYING CONDUCTORS. ALL LUGS AND CONNECTORS SHALL BE RATEDFOR THE CONDUCTOR MATERIAL AND THE CONDITIONS OF USE.3.THE GROUNDING RESISTIVITY WILL BE TESTED AFTER INSTALLATIONTO CONFIRM 5 OHM OR LESS RESISTANCE FROM RACKING TO GROUND. IF GROUNDRESISTANCE IS GREATER THAN 5 OHMS ADDITIONAL GROUNDING WILL BEINSTALLED UNTIL RESISTANCE IS LESS THAN 5 OHMS.WIRING DEVICES1.RECEPTACLES SHALL BE AS DESIGNED ON THE DRAWINGS ANDSHOULD BE A BRAND CONSISTENT WITH OTHERS IN THE VICINITY WHENEVERPOSSIBLE.2.ALL WIRING DEVICES SHALL BE PROVIDED WITH APPROPRIATECOVER-PLATES. ANY EMPTY BOXES SHALL HAVE BLANKCOVER PLATES. COVER-PLATES SHALL BE LEXAN, PLASTIC OR STAINLESS STEEL INFINISHED AREA. GALVANIZED COVER-PLATES MAY BE USED IN EQUIPMENT ROOMS.LABELING AND PHASING1.FOR LABELING USE NUMBERED UV RATED LABELS TO INDICATESTRING NUMBER.2.AS A SUBSTITUTE FOR LABELS YELLOW TAPE MAY BE USED FORPHASING3.EACH METHOD DESCRIBED ABOVE WILL NEED TO BE PERFORMED ONBOTH POSITIVE AND NEGATIVE AT POINTS WHERECONDUCTORS ARE TERMINATEDCOVER PAGEPV-19.57 KWSYSTEM SIZE : 13.365 KW DC STC(33) JKM 405M-72HL-V (405W) JINKO SOLAR 39.93 A(33) ENPHASE IQ7PLUS-72-M-USMICROINVERTERS(1)ENPHASE ENCHARGE 10T(2) BRANCHES OF 07 MODULES (1) BRANCH OF 09 MODULES(1) BRANCH OF 10 MODULESSIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021NICHOLSON, CHARLOTTENEW GRID-INTERACTIVE PHOTOVOLTAIC SYSTEMWITH ENCHARGE BATTERY BACKUP SYSTEMDC SYSTEM SIZE (13.365 KW)THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BYKIMANDY LAWRENCE, PE ON THE DATE ADJACENT TOTHE SEAL. PRINTED COPIES OF THIS DOCUMENT ARE NOTCONSIDERED SIGNED AND SEALED AND THE SIGNATUREMUST BE VERIFIED ON ANY ELECTRONIC COPIES. CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948COVER PAGEPV-1ELECTRICAL LINE DIAGRAMELECTRICAL CALCULATIONSLABELSMODULE DATASHEETSTRUCTURAL DETAILSINVERTER DATASHEETCOMBINER PANEL DATASHEETRACKING DATASHEETSHEET INDEXSHEET NO.SHEET NAMEPV-2PV-3PV-4PV-6PV-7PV-8PV-9PV-10FIRE SAFETY PLANPV-11RACKING LAYOUTPV-5PV-12PV-13PV-14SMART SWITCH DATASHEETENCHARGE10 DATASHEETPV-15ATTACHMENT DATASHEETSEALANT DATASHEETGROUNDING & BONDING DATASHEETPV-16ELECTRICAL LOAD CALCULATIONSPV-17LABELS CONTINUEDPV-6.1
FIRE SAFETY PLANPV-2LEGENDSSIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021NOTES:1. LOCATION OF JUNCTION BOX(ES), ACDISCONNECTS(S), AC COMBINER PANEL(S),AND OTHER ELECTRICAL EQUIPMENT(S)RELEVANT TO PV INSTALLATION SUBJECT TOCHANGE BASED ON SITE CONDITIONS.2. SETBACKS AT RIDGES CAN BE REDUCED TO18 INCHES IN COMPLIANCE WITH FBC R 324.6.2:TOTAL PLAN VIEW AREA = 3899 SQFTTOTAL PV AREA = 33(79.06 IN)(39.45 IN)/(144IN^2) = 714.75 SQFT(714.75 SQFT/3899 SQFT)100 = 18.33 %TOTAL PV AREA POPULATES 18.33 % OF TOTALPLAN VIEW AREA AND IS WITHIN THE 33%REQUIREMENT. CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948DC SYSTEM SIZEAC SYSTEM SIZESYSTEM INFORMATION13.365 KW9.57 KWROOF SPECIFICATIONSGOODW-TILE2"X4"@24" O.C.ROOF MATERIALROOF CONDITIONRAFTERSROOF INFORMATIONROOFQUANTITYAZIMUTHROOF 11245°26.57°(6/12)ROOF 302225°26.57°(6/12)ROOF 203135°26.57°(6/12)ROOF 416225°26.57°(6/12)SLOPE- AC DISCONNECT- ROOF OBSTRUCTION- JUNCTION BOX- COMBINER PANELJBACDCP- CONDUIT RUN- STRING TAG1- FIRE SETBACK- METER MAIN COMBOM- ROOF ACCESS POINTRAP- BATTERYB- SMART SWITCHSSSSP- MAIN SERVICE PANELEQUIPMENT SPECIFICATIONSDESCRIPTIONQUANTITYEQUIPMENTMODULEINVERTERJUNCTION BOXCOMBINER PANELAC DISCONNECTATTACHMENTRACKING SYSTEM111JKM 405M-72HL-V (405W) JINKO SOLARENPHASE IQ7PLUS-72-M-USMICROINVERTERS333372-IRONRIDGE KO TILEIRONRIDGE (XR100) RAILS600 V,NEMA 3R UL LISTED AC DISCONNECT 240V, 30 AMP,NON-FUSED, NEMA 3R, UL LISTED80A ENPHASE IQ COMBINER 3COMBINER PANEL160A COMBINER PANEL(N)80A COMBINER PANEL(N)AC DISCONNECT(NON-FUSIBLE)(E)METER MAIN COMBO(OUTSIDE HOUSE)ACDCPMRAP
SSPBESSRAP84'-9"JB5
6
'
-
2
"(N)BACKUP LOAD PANEL(INSIDE HOUSE)BLPROOF 1ROOF 2ROOF 3ROOF 418" SETBACKPV ARRAYROOF ACCESS POINTROOF ACCESS POINTCONDUIT RUN(N)60A COMBINER PANELCP111111111222222222233333334444444(E)SUB SERVICE PANEL(INSIDE HOUSE)(N)ENPHASE ENCHARGE 10T BATTERY(INSIDE HOUSE)(N)ENPHASE SMART SWITCH(INSIDE HOUSE)
ELECTRICAL LINE DIAGRAMPV-3SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021PER FL. STATUE 377.705 (REVISED 7/1/2017) I, KIMANDYLAWRENCE PE#83317, AN ENGINEER LICENSEDPURSUANT TO CHAPTER 471, CERTIFY THAT THE PVELECTRICAL SYSTEM AND ELECTRICAL COMPONENTSARE DESIGNED AND APPROVED USING THE STANDARDSCONTAINED IN THE MOST RECENT VERSION OF THEFLORIDA BUILDING CODE.NOTE:1.CONDUIT RUN - EMT, PVC, IMC, RMC, FMC, LFMC OR EQUIVALENT AS PER NEC.2. ALL EQUIPMENT GROUNDING CONDUCTORS SMALLER THAN #6 AWG SHALL RUN BENEATH THE ARRAY(S) OR IN ACONDUIT RUN TO PROTECT FROM PHYSICAL DAMAGE PER NEC 690.46 AND NEC 250.120(C).IQ7PLUS-72-M-US290VA240V1.21AENPHASEINVERTER SPECIFICATIONMANUFACTURERMODEL NO.MAX. CONT. OUTPUT POWERNOMINAL AC OUTPUT VOLTAGEMAX. CONT. OUTPUT CURRENTARRAY DETAILSDC SYSTEM SIZEAC SYSTEM SIZETOTAL NO. OF MODULESNO. OF MODULE PER STRINGNO. OF STRING60VMAX. DC INPUT VOLTAGE9.57 KW3313.365 KW41@10, 1@9, 2@7 CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948CONDUCTOR AND CONDUIT SCHEDULE(3) #10 AWG THWN-2 (L1,L2,N) , (1) #10 AWG THWN-2 (G)SR. NO.12CONDUIT SIZEIN 1" CONDUIT RUNDESCRIPTIONIN 3/4" CONDUIT RUNENPHASE Q CABLES, (1) #10 AWG THWN-2 (G)A(4) #10 AWG THWN-2 (L1) ,(4) #10 AWG THWN-2 (L2) , (1) #10 AWG THWN-2 (G)(3) #10 AWG THWN-2 (L1,L2,N), (1) #10 AWG THWN-2 (G)3IN 3/4" CONDUIT RUNMODULE SPECIFICATIONMODEL NO.PEAK POWER (Pmpp)PEAK VOLTAGE (Vmpp)PEAK CURRENT (Impp)OPEN CIRCUIT VOLTAGE (Voc)405W40.42V10.02A49.4VJKM 405M-72HL-VMANUFACTURERJINKO SOLARSHORT CIRCUIT CURRENT (Isc)10.69AGNG3200 A(E) SUB SERVICEPANEL 120/240V(MLO)NG200 A RATED BUSBAR(E) METER MAIN COMBOSERVICE PANEL(N)175 AUM2G(N)30A(N)20AGENERATOROPTIONAL(N)100 AENCHARGE 10T(N) BATTERY BACKUP SYSTEM(N)30A AC DISCONNECT240V,UNFUSEDNEMA 3R, UL LISTED4INTEGRATEDMICROGRIDINTERCONNECTDEVICE PERNEC 705.170(N) SMART SWITCHG1A1 STRING OF10 MODULES WITHMICROINVERTERS1 STRING OF9 MODULES WITHMICROINVERTERS1 STRING OF7 MODULES WITHMICROINVERTERS1 STRING OF7 MODULES WITHMICROINVERTERS20A/2P20A/2PGENVOY IQ15A/2P(N) 80A ENPHASEIQ AC COMBINER120/240VNEMA 3RNOTE:THE CIRCUIT BREAKER SHOWN FEEDINGTHE ENPHASE ENVOY IS FACTORYINSTALLED. THE SIZE OF THIS CIRCUITBREAKER IS SUBJECT TO CHANGE BASEDON MANUFACTURER PREFERENCE INACCORDANCE WITH THE UL LISTING.(N)100 A(N)30 AG(N)20A(N)20A(3) #10 AWG THWN-2 (L1,L2,N), (1) #10 AWG THWN-2 (G)4IN 3/4" CONDUIT RUNENCHARGE-10T-1P-NA3.84 KVA16 A240 VENPHASEBATTERY SPECIFICATIONMANUFACTURERMODEL NO.MAX. CONT. POWER OUTPUTMAXIMUM OUTPUT CURRENTNOMINAL OPERATING VOLTAGE10.08 KWHCAPACITY(N)JUNCTION BOX,600V, NEMA 3R UL LISTED(N)BACKUP LOAD PANELEP200G101-M240US00200 ANEMA 3RENPHASESMART SWITCH SPECIFICATIONMANUFACTURERMODEL NO.BUSBAR RATINGENVIRONMENTAL RATING120/240V, SINGLE PHASEVOLTAGE RATINGNOTE:ALL CIRCUIT BREAKERS BACKFEED FROMBATTERIES SHALL BE FASTENED INACCORDANCE WITH NEC 408.36(D).(N) 60 A COMBINER PANEL5(3) #10 AWG THWN-2 (L1,L2,N), (1) #10 AWG THWN-2 (G)5IN 3/4" CONDUIT RUNINTERCONNECTION120% RULE - NEC 705.12(B)(2)(3)(b)UTILITY FEED + SOLAR BACKFEED175A + 30A + 30A = 235ABUS BAR RATING x 120%200A x 120% = 240A676(3)(3) #3 AWG THWN-2 (L1,L2,N) , (1) #8 AWG THWN-2 (G)IN 1-1/4" CONDUIT RUN7(3)(3) 3/0 AWG THWN-2 (L1,L2,N), (1) #6 AWG THWN-2 IN 2" CONDUIT RUNENERGY STORAGE SYSTEM NOTES:1.THE RATINGS OF ANY INDIVIDUAL LOAD/CIRCUIT BREAKER THAT WILL BE FED BY THE ENERGY STORAGE SYSTEM MAY NOT EXCEED 20A AND/OR 3.84 KW.2.IF THE UTILITY IS DOWN, THE ENPHASE EMPOWER SMART SWITCH ISOLATES THE PV ENERGY STORAGE AND UNINTERRUPTIBLE LOADS.3.IF THE UTILITY IS DOWN, THE BACKUP SYSTEM OPERATES AS A STAND-ALONE SYSTEM UNDER THE CONDITIONS OF NEC ARTICLES 706 AND 7104.ALL METAL ENCLOSURES, RACEWAYS, CABLES AND EXPOSED NON CURRENT-CARRYING METAL EQUIPMENTS SHALL BE GROUNDED TO EARTH AS REQUIRED BY NEC 250.4(B) AND PART III OF NEC ARTICLE 250 AND EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC 690.45.5.PV SYSTEM INTERCONNECED ON THE LOAD SIDE OF MAIN DISCONNECTING MEANS PER NEC 705.12(B).6.BATTERIES INSTALLED IN GARAGE SHALL BE PROTECTED FROM VEHICLE DAMAGE BY MEANS OF APPROVED BARRIERS INSTALLED BYCONTRACTOR DURING BATTERY INSTALLATION IN ACCORDANCE WITH NFPA 855.7.BATTERIES INSTALLED IN ATTACHED GARAGE SHALL HAVE AN INTERCONNECTED LISTED HEAT ALARM INSTALLED BY THE CONTRACTOR DURING BATTERY INSTALLATION THAT SHALL ALSO BE CONNECTED TO THE SMOKE ALARM SYSTEM REQUIRED BY THE LOCAL BUILDING CODE IN ACCORDANCE WITH NFPA 855.
ELECTRICAL CALCULATIONSPV-4SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021GENERAL ELECTRICAL NOTES:1. THE DC AND AC CONNECTORS OF THE ENPHASE IQ7PLUS-72-M-US MICROINVERTERS ARE LISTED TO MEETREQUIREMENTS AS A DISCONNECT MEANS AS ALLOWED BY NEC 690.15(A).2.MICROINVERTER BRANCH CIRCUIT CONDUCTORS ARE MANUFACTURED ENPHASE Q CABLES LISTED FOR USEIN 20A OR LESS CIRCUITS OF ENPHASE IQ MICROINVERTERS. THEY ARE ROHS, OIL RESISTANT, AND UVRESISTANT. THEY CONTAIN AWG CONDUCTORS OF TYPE THHN/THWN-2 DRY/WET AND CERTIFIED TO UL3003AND UL 9703. THE CABLE'S DOUBLE INSULATED RATING REQUIRES NO NEUTRAL OR GROUNDED CONDUCTOR.3. ALL METAL ENCLOSURES, RACEWAYS, CABLES AND EXPOSED NONCURRENT-CARRYING METAL PARTS OFEQUIPMENT SHALL BE GROUNDED TO EARTH AS REQUIRED BY NEC 250.4(B) AND PART III OF NEC ARTICLE 250AND EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC 690.45. THE GROUNDINGELECTRODE SYSTEM SHALL ADHERE TO 690.47(A).4. PV SYSTEM DISCONNECT SHALL BE READILY ACCESSIBLE.5. POINT-OF-CONNECTION SHALL BE MADE IN COMPLIANCE WITH NEC 705.126. UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PHOTOVOLTAIC SYSTEM COMPONENTS LOCATED ATTHE SERVICE ENTRANCE.7. MODULES CONFORM TO AND ARE LISTED UNDER UL 1703. MICROINVERTERS CONFORM TO AND ARE LISTEDUNDER UL 1741 AND IEEE 1547.8. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PERNEC ARTICLE 300.6(C)(1) AND ARTICLE 310.10 (D).9. CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET LOCATIONS PER NECARTICLE 310.10 (C).10. ALL DC WIRING RUNNING THROUGH THE BUILDING SHALL BE ENCLOSED IN METALLIC CONDUIT INCOMPLIANCE WITH NEC 690.31(G). THIS REQUIREMENT SHALL APPLY TO OPTIMIZER-BASED SYSTEMS, BUTSHALL NOT APPLY TO MICROINVERTER-BASED SYSTEMS.11.A 10 AWG CU EQUIPMENT GROUNDING CONDUCTOR SHALL BE USED TO BOND RAILS AND OTHER ROOFTOPEQUIPMENT. THIS CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BY RUNNING UNDERNEATHTHE ARRAY. IF THIS CONDUCTOR IS UNPROTECTED FROM PHYSICAL DAMAGE, THE CONDUCTOR SHALL BEINCREASED TO 6 AWG CU.GROUNDING NOTES:PV MODULE AND RACKING GROUNDING AS PER APPROVED INSTALLATION PRACTICE AND IN LINE WITHMANUFACTURE'S GUIDELINES. CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948ELECTRICAL CALCULATIONS:1.CURRENT CARRYING CONDUCTOR(A)BEFORE IQ COMBINER PANEL :AMBIENT TEMPERATURE = 33°CCONDUIT INSTALLED AT MINIMUM DISTANCE OF 7/8 INCHES ABOVE ROOF .....NEC 310.15(B)(3)(c)TEMPERATURE DERATE FACTOR - (0.96) ..............NEC 310.15(B)(2)(a)GROUPING FACTOR - (0.8) .................................NEC 310.15(B)(3)(a)CONDUCTOR AMPACITY:= (INV O/P CURRENT ) x 1.25 / A.T.F / G.F ...NEC 690.8(B)= [(10 x 1.21) x 1.25] / 0.96 / 0.8= 19.69 ASELECTED CONDUCTOR - #10 THWN-2 ...NEC 310.15(B)(16)(B)AFTER IQ COMBINER PANEL: TEMPERATURE DERATE FACTOR - (0.96) GROUPING FACTOR - (1) CONDUCTOR AMPACITY= (TOTAL INV O/P CURRENT) x 1.25 / 0.96 / 1 ...NEC 690.8(B)= [19 x 1.21) x 1.25] / 0.96 / 1= 29.93 ASELECTED CONDUCTOR - #10 THWN-2 ...NEC 310.15(B)(16)2.PV OVER CURRENT PROTECTION FOR MODULES ON BATTERY BACKUP SYSTEM ...NEC 690.9(B)= TOTAL INVERTER O/P CURRENT x 1.25= (19 x 1.21) x 1.25 = 28.73 A SELECTED OCPD IS 30ASELECTED EQUIPMENT GROUNDING CONDUCTOR (EGC) = #10 THWN-2 ...NEC 250.122(A)3.PV OVER CURRENT PROTECTION FOR MODULES NOT ON BATTERY BACKUP SYSTEM= TOTAL INVERTER O/P CURRENT x 1.25=(14 x 1.21) x 1.25 = 21.18 A SELECTED OCPD IS 30 A.4. TOTAL BATTERY BACKUP SYSTEM OVER CURRENT PROTECTION ... NEC 690.9(B)= TOTAL BATTERY BACKUP SYSTEM O/P CURRENT x NUMBER OF ENCHARGE 10T BATTERY x 1.25= (16 x 1) x 1.25 = 20 ASELECTED OCPD IS 20 A.SELECTED CONDUCTOR - #10 THWN-2 ...NEC 310.15(B)(16)SELECTED EQUIPMENT GROUNDING CONDUCTOR (EGC) = #10 THWN-2 ...NEC 250.122(A) ...NEC 690.9(B)
ELECTRICAL LOAD CALCULATIONSPV-5SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021ELECTRICAL LOAD CALCULATION CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948
LABELSPV-6EQUIPMENT ELEVATION VIEWSIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021WARNINGSOLAR AC DISCONNECTSOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWNAC COMBINER AND DATA AQUISITION.DO NOT ADD LOADS.NOTICESOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN80A COMBINER PANELEMERGENCY CONTACT561-609-2664RAPID SHUTDOWN SWITCHFOR SOLAR PV SYSTEMNOTICEAC VOLTAGE : 240VMAX OCPD 30 A MAX. CURRENT: 22.99 ANOTES:1.THE MATERIAL USED FOR THE PHOTOVOLTAIC SYSTEM LABELSSHALL BE REFLECTIVE, WEATHER RESISTANT, AND CONSTRUCTEDOF DURABLE ADHESIVE MATERIAL OR ANOTHER APPROVEDMATERIAL SUITABLE FOR THE ENVIRONMENT IN COMPLIANCEWITH NFPA 1-11.12.2. FONT, TEXT HEIGHT , CAPITALIZATION AND CONTEXT OFPHOTOVOLTAIC SYSTEMS LABELS SHALL COMPLY WITH NFPA 1-11.12AS APPLICABLE FOR THE PHOTOVOLTAIC SYSTEM TO BE INSTALLED CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948METER MAIN COMBOMETER MAIN COMBO(OUTSIDE HOUSE)80A AC COMBINER PANEL (OUTSIDE HOUSE)SUB SERVICE PANEL(INSIDE HOUSE)ENPHASE SMART SWITCH(INSIDE HOUSE)ENPHASE ENCHARGE 10T BATTERY (INSIDE HOUSE)AC DISCONNECT(NON-FUSIBLE)(OUTSIDE HOUSE)ONOFFBACKUP LOAD PANEL (INSIDE HOUSE)60 COMBINER PANEL (OUTSIDE HOUSE) INVERTER OUTPUT CONNECTIONDO NOT RELOCATE THISOVERCURRENT DEVICEWARNINGSUB SERVICE PANEL
LABELS CONT.PV-6.1EQUIPMENT ELEVATION VIEWSIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021WARNING60A COMINER PANELSOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWNSOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWNEMERGENCY CONTACT561-609-2664RAPID SHUTDOWN SWITCHFOR SOLAR PV SYSTEMNOTICEAC VOLTAGE : 240VMAX OCPD : 30 A MAX. CURRENT: 16.94 ANOTES:1.THE MATERIAL USED FOR THE PHOTOVOLTAIC SYSTEM LABELSSHALL BE REFLECTIVE, WEATHER RESISTANT, AND CONSTRUCTEDOF DURABLE ADHESIVE MATERIAL OR ANOTHER APPROVEDMATERIAL SUITABLE FOR THE ENVIRONMENT IN COMPLIANCEWITH NFPA 1-11.12.2. FONT, TEXT HEIGHT , CAPITALIZATION AND CONTEXT OFPHOTOVOLTAIC SYSTEMS LABELS SHALL COMPLY WITH NFPA 1-11.12AS APPLICABLE FOR THE PHOTOVOLTAIC SYSTEM TO BE INSTALLED CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948METER MAIN COMBO(OUTSIDE HOUSE)80A AC COMBINER PANEL (OUTSIDE HOUSE)SUB SERVICE PANEL(INSIDE HOUSE)ENPHASE SMART SWITCH(INSIDE HOUSE)ENPHASE ENCHARGE 10T BATTERY (INSIDE HOUSE)AC DISCONNECT(NON-FUSIBLE)(OUTSIDE HOUSE)ONOFFBACKUP LOAD PANEL (INSIDE HOUSE)60 COMBINER PANEL (OUTSIDE HOUSE)60A COMBINER PANELAC COMBINER AND DATA AQUISITION.DO NOT ADD LOADS.NOTICE
RACKING LAYOUTPV-7SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021LEGENDS- ROOF OBSTRUCTION- FIRE SETBACK- JUNCTION BOX- WIND ZONE 1- WIND ZONE 1'WIND ZONE 2- WIND ZONE (2)-WIND ZONE (2r)- WIND ZONE (2e)- WIND ZONE (2n)WIND ZONE 3- WIND ZONE (3)-WIND ZONE (3r)- WIND ZONE (3e)LEGENDSNOTES:1. LOCATION OF JUNCTION BOX(ES), ACDISCONNECTS(S), AC COMBINER PANEL(S), ANDOTHER ELECTRICAL EQUIPMENT(S) RELEVANT TOPV INSTALLATION SUBJECT TO CHANGE BASEDON SITE CONDITIONS.2. TRUSS LOCATIONS ARE APPROXIMATE. ACTUALLOCATIONS MAY DIFFER AND CONTRACTOR MAYNEED TO ADJUST MOUNT LOCATIONS. IN NOCASE SHALL THE MOUNT SPACING EXCEED "MAX.MOUNT SPACING"3. PROPOSED PHOTOVOLTAIC LAYOUT INCOMPLIANCE WITH NFPA 1,2018 EDITION- RAFTERS/TRUSSES- RAILS- PV ROOF ATTACHMENTWIND LOAD INFORMATION:THIS SYSTEM HAS BEEN DESIGN TO MEETTHE REQUIREMENTS OF THE 7TH EDITION OFTHE FLORIDA BUILDING CODE AND USED THE FOLLOWING DESIGN PARAMETERS: ULTIMATE WIND SPEED: 160 MPHEXPOSURE CATEGORY: CRISK CATEGORY: IIMEAN ROOF HEIGHT: 15 FTROOF SLOPE: 20°-27° CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948DC SYSTEM SIZEAC SYSTEM SIZESYSTEM INFORMATION13.365 KW9.57 KWROOF SPECIFICATIONSGOODW-TILE2"X4"@24" O.C.ROOF MATERIALROOF CONDITIONRAFTERSROOF INFORMATIONROOFQUANTITYAZIMUTHROOF 11245°26.57°(6/12)ROOF 302225°26.57°(6/12)ROOF 203135°26.57°(6/12)ROOF 416225°26.57°(6/12)SLOPEEQUIPMENT SPECIFICATIONSDESCRIPTIONQUANTITYEQUIPMENTMODULEINVERTERJUNCTION BOXCOMBINER PANELAC DISCONNECTATTACHMENTRACKING SYSTEM111JKM 405M-72HL-V (405W) JINKO SOLARENPHASE IQ7PLUS-72-M-USMICROINVERTERS333372-IRONRIDGE KO TILEIRONRIDGE (XR100) RAILS600 V,NEMA 3R UL LISTED AC DISCONNECT 240V, 30 AMP,NON-FUSED, NEMA 3R, UL LISTED80A ENPHASE IQ COMBINER 3COMBINER PANEL160A COMBINER PANEL58'-9"19'-8"11'-11"19'-5"5'-4.8"5'-4.8"
24'-1"20'-2"36'-9"11'-11"9'
9'10'10'-2"15'-5"29'-6"3'-3"5'-11"13'-5"5'-11"14'-2"
17'-7"34'-8"6'-8"12'-4"9'-6"3'-3"5'-11"50'-11"30'-3"9'-1"17'-10"
2'
24'-7"5'-4.8"5'-4.8"5'-4.8"5'-4.8"3'-3"5'-11"4'2'
2'3'-3"5'-11"ROOF 1ROOF 2ROOF 3ROOF 45'-4.8"5'-4.8"JUNCTION BOXSOLAR MODULE18" SETBACK9'-3"
STRUCTURAL DETAILSPV-8SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021STRUCTURAL DETAILS CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948I CERTIFY THAT THE EXISTING ROOF AND BUILDINGSTRUCTURE CAN WITHSTAND ALL DEAD LOADSIMPOSED BY THE PHOTOVOLTAIC SYSTEM AND ALLWIND LOADS OF SPECIFIED INTENSITY IN ACCORDANCEWITH THE FLORIDA BUILDING CODE.RAFTERSSOLAR MODULEIRONRIDGE TILE REPLACEMENTFLASHING (W TILE)5/16"x4" STAINLESSSTEEL LAG SCREWIRONRIDGE KO L-FOOTIRONRIDGE (XR100) RAILSSOLAR MODULEIRONRIDGE KO L-FOOTIRONRIDGE (XR100) RAILSRAFTERSIRONRIDGE TILE REPLACEMENTFLASHING (W TILE)WOOD SHEATHINGWOOD SHEATHINGNOTE:RAIL SPAN LIMITS SHOWN RESPECTIVE TO WIND ZONE.VALUE IN PARENTHESES TO RIGHT OF RAIL SPAN LIMITIS ALLOWABLE MODULE CANTILEVER.NOTE:USE TWO ALTERNATING LAYERS OF PG500 ASPHALTICSEALANT AND ROOFING FABRIC EXTENDNG A MINIMUMOF 2 INCHES FROM EACH ATTACHMENT.
MODULE DATASHEETPV-9SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021 CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948
INVERTER DATASHEETPV-10SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021 CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948
SMART SWITCH DATASHEETPV-11SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021 CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948
ENCHARGE 10T DATASHEETPV-12SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021 CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948
COMBINER PANELDATASHEETPV-13SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021 CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948
RACKING DATASHEETPV-14SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021 CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948
ATTACHMENT DATASHEETPV-15SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021 CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948
SEALANT DATASHEETPV-16SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021 CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948
GROUNDING & BONDINGDATASHEETPV-17SIGNATURE WITH SEAL CONTACT: (561) 444 8192 5700 LAKE WORTH ROAD SUITE 211 GREENACRES, FL 33463,USAFLORIDA REGISTRY# 33809PERMIT DEVELOPERDESIGNERREVIEWERDATE10205 CROSBY PL.
PORT SAINT LUCIE, FL 34986
27.318691, -80.429477
NICHOLSON, CHARLOTTE
OKT11/06/2021 CONTACT: 561-609-2664 990 SOUTH ROGERS CIRCLE SUITE 4BOCA RATON, FL 33487SOLAR CONTRACTOR LICENSE: CVC56948