January 6, 2022 KSM JOB # :2200139-1d/BS/jam
CONTRACTOR:South Florida Land Clearing, Inc.
15701 Orange Avenue
Fort Pierce, Florida 34945
JOB LOCATION:20017 Southern Star Drive
Lot 6
Fort Pierce, Florida
PERMIT #:
Respectfully,
PE # 68366 01/06/22
Proudly Serving Florida since 1990
Test report shall not be reproduced, except in full, without the written approval of KSM Engineering & Testing
Email: sflcgw@gmail.com
Certified Women Owned Business - WBE
To Whom it may concern,
As requested, we tested the compacted fill for the House Pad.
To determine if the fill was properly compacted on the pad to a depth of 4 feet, we performed nuclear density
tests on the top two feet. To estimate the soil density below a depth of 2 feet we used a Static Cone
Penetrometer. During the tests, a shaft with a conical point is pushed through soil and the soil resistance
measured on a calibrated gauge. After the soil resistance is measured, the hole is advanced with a hand-auger in
1-foot increments to permit a continuation of measurement of density versus depth. Test Results:
Nuclear density tests performed on the top 2 feet indicates the compaction exceeds the project specifications of
95% (ASTM 1557). Static Cone Penetrometer readings indicate the compacted backfill
below 2 feet are generally well compacted to a depth of 4 feet.
Based on the nuclear density tests and Static Cone Penetrometer readings, it appears the fill on the house pad
was properly compacted.
Should you have any questions, please feel free to contact our office.
Julie E. Keller, P.E. President
Geotechnical Engineering - Construction Materials Testing - Special Inspections - Civil and Structural Consulting
Headquarters
11345 U.S. Highway 1
Sebastian, FL. 32958
Orlando
723 Progress Way
Sanford, FL. 32771
Mailing
PO Box 78-1377
Sebastian, FL. 32978
Phone: 772-589-0712
C.A.# 5693
KSMengineering.net
KSM JOB #:2200139-1d/BS/jam
NUC #456
Nuc Model:MC-1 Elite
Nuc Serial #:31456
20017 Southern Star Drive
Lot 6
Fort Pierce, Florida
House Pad
DEPTH PEN
READ
DRY
DENSITY
MAX. DRY
PROCTOR VALUE (P.C.F)
PERCENT
COMPACTION
1 N.E.0" - 12"45 111.6 113.3 98.5%
2 Center ""112.1 "98.9%
3 S.W.""112.5 "99.3%
4 S.E.12" - 24""112.3 "99.1%
5 N.W.""111.8 "98.7%
Proctor Optimum Moisture:
Proctor Max. Dry Density: P.C.F.
@ Test Locations the Density &
Penetrometer readings indicate the
Degree of Compaction Meets
Minimum Requirement
1/6/2022
Email: sflcgw@gmail.com
10.0%
Julie E. Keller, P.E. President
SOIL COMPACTION REPORT
ASTM D 1557 and ASTM D 6938
DATE TESTED:January 5, 2022
In Place Moisture:
PERMIT #:
JOB LOCATION:
Brown Sand with Traces of Shell and Rock
CONTRACTOR:South Florida Land Clearing, Inc.
Proudly Serving Florida since 1990
Certified Women Owned Business - WBE
8.5%
PE # 68366
for Unstaked Foundation
113.3
Disclaimer:Contractor is responsible to maintain the tested
area in the condition that KSM completed the indicated
passed compaction test.KSM is not responsible if the tested
area has been altered from the approved inspected condition.
Test report shall not be reproduced, except in full, without the written approval of KSM Engineering & Testing
Geotechnical Engineering - Construction Materials Testing - Special Inspections - Civil and Structural Consulting
ITEM TESTED:
Soil Description:
TEST LOCATION
OF SAMPLE
Headquarters
11345 U.S. Highway 1
Sebastian, FL. 32958
Orlando
723 Progress Way
Sanford, FL. 32771
Mailing
PO Box 78-1377
Sebastian, FL. 32978
Phone: 772-589-0712
C.A.# 5693
KSMengineering.net
DATE TESTED:KSM JOB # :2200139-1d/BS/jam
PERMIT #:
CONTRACTOR:South Florida Land Clearing, Inc.
JOB LOCATION:20017 Southern Star Drive
Lot 6
Fort Pierce, Florida
Soil Description:
Brown Sand with Traces of Shell and Rock
Proctor Optimum Moisture:
10.0%
Proctor Max. Dry Density: P.C.F.
113.3
Julie E. Keller, P.E. President
PE # 68366 1/6/2022
SOIL COMPACTION REPORT
ASTM D 1557
Test report shall not be reproduced, except in full, without the written approval of KSM Engineering & Testing
Certified Women Owned Business - WBE
Proudly Serving Florida since 1990
Geotechnical Engineering - Construction Materials Testing - Special Inspections - Civil and Structural Consulting
January 5, 2022
108.0
109.0
110.0
111.0
112.0
113.0
114.0
115.0
5 6 7 8 9 10 11 12 13
W
E
I
G
H
T
P
.
C
.
F
.
D
R
Y
Moisture -% of Dry Weight