HomeMy WebLinkAboutBuilding PlansAm
�* LBJ Architecture
TREATMENT
OFFICE
r----------------------
I
OFFICE
U
C
L
L
FLOOR PLAN
SCALE: 1/4" - 1'-0"
WALL LEGEND
EXISTING WALLS TO REMAIN
NEW INTERIOR FRAMING
CBS WALL INFILL
�..�. r) IJnI IP7 MATCr11A/AI I 1 11 n(lr-
SOUND
6020
4" TUBE STEEL COLUMN
SEE DETAIL FOR MORE
INFO
6068 STOREFRONT DOOR
C.C. TO SPRAY FOAM UNDERSIDE OF ROOF DECK
WITH R-20 OPEN CELL WITH FIRESHELL COATING
i■ Gilt) i /�A ( /a�' il� A, iii'
RAMP UP
PLATFORM
6020TRANSOM WINDOW 6020TRANSOM WINDOW
6ENERAL. NOTES
1. CONSTRUCT ALL WORK IN ACCORDANCE W/ ALL APPLICABLE BUILDING CODES & ASTM STANDARDS.
2. CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND NOTIFY THE ARCHITECT OF
ANY OBSERVED DISCREPANCIES PRIOR TO CONSTRUCTION.
3. DO NOT SCALE DRAWINGS.
4. THE DRAWINGS AND DETAILS INCLUDED IN THIS SET ARE REPRESENTATIVE OF THE DESIGN INTENT FOR ANTICIPATED FIELD
CONDITIONS AND DO NOT IN ALL CASES REFLECT SPECIFIC MANUFACTURER'S DETAILS AND SPECIFICATIONS REQUIREMENTS. EACH
SHEET IS PART OF A COMPLETE SET OF DOCUMENTS COMPLETED FOR THIS PROJECT AND IS TO BE USED ONLY IN CONJUNCTION
WITH THE COMPLETE SET OF CONSTRUCTION DOCUMENTS.
5. CONTRACTOR SHALL REVIEW CONTRACT DOCUMENTS FOR THE PROJECT AND NOTIFY THE ARCHITECT OF ANY OBSERVED
DISCREPANCIES PRIOR TO THE START OF CONSTRUCTION.
6. THE CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES IN ACCORDANCE WITH THE SPECIFICATIONS AND MAKE
ADJUSTMENTS IN LAYOUT AS REQUIRED, WITH ARCHITECT/ENGINEER APPROVAL ONLY, TO AVOID CONFLICT BETWEEN TRADES
FOR PROPER EXECUTION OF THE WORK.
7, THE CONTRACTOR SHALL PROVIDE PROTECTION EQUIPMENT FOR SURROUNDING MATERIAL AND SITE DURING CONSTRUCTION.
8. THE CONTRACTOR SHALL, AT HIS OR HER EXPENSE, RESTORE TO "LIKE NEW" CONDITION ANY DAMAGE TO SURROUNDING
MATERIALS DURING CONSTRUCTION.
9. CUTTING OF STEEL, WOOD, OR OTHER MAIN STRUCTURAL MEMBERS IS NOT ALLOWED WITHOUT WRITTEN APPROVAL FROM THE
ARCHITECT/ENGINEER PRIOR TO CUTTING.
h 0. MAINTAIN PREMISES AND PUBLIC AREAS FREE FROM ACCUMULATED WASTE AND RUBBISH CAUSED BY NORMAL CONSTRUCTION
ON A DAILY BASIS, UPON COMPLETION OF WORK, REMOVE WASTE MATERIALS, RUBBISH, TOOLS, AND EQUIPMENT, AND LEAVE
PROJECT AREA CLEAN AND READY FOR OCCUPANCY.
11. PROVIDE REQUIRED COORDINATION AND SUPERVISION WHERE WORK CONNECTS TO OR IS AFFECTED BY OTHER WORK.
12. WHERE WORK OF ONE TRADE WILL BE INSTALLED IN CLOSE PROXIMITY TO WORK OF OTHER TRADES OR WHERE ONE TRADE WILL
INTERFERE WITH WORK OF OTHER TRADES, CONTRACTOR SHALL ASSIST IN WORKING OUT CONDITIONS TO COORDINATE
INSTALLATION AND PROVIDE COORDINATION DRAWINGS IN 1 /8" = 1'-O" SCALE (MINIMUM].
3. WHERE TWO OR MORE DETAILS, MATERIALS, OR CONDITIONS OCCUR IN APPARENT CONFLICT, THE CONTRACTOR SHALL USE THE
MOST EXPENSIVE SOLUTION IN HIS BID. NOTIFY THE ARCHITECT OF ANY APPARENT DISCREPANCIES PRIOR TO COMMENCING WITH
THE WORK.
4. PERMITS: THE GENERAL BUILDING PERMIT FOR THE PROJECT SHALL BE OBTAINED PRIOR TO CONSTRUCTION BY THE CONTRACTOR.
HE SHALL SECURE THE PERMITS REQUIRED FROM THE APPROPRIATE AUTHORITIES HAVING JURISDICTION.
5. CONSTRUCTION COMPLETION PROCEDURES: OBTAIN CERTIFICATES OF OCCUPANCY OR USE, FROM ALL PERMITTING AGENCIES
REQUIRED FOR THIS PROJECT, PRIOR TO SUBSTANTIAL COMPLETION. PRESENT ALL CERTIFICATES OF OCCUPANCY OR USE TO THE
OWNER AS A CONDITION OF SUBSTANTIAL COMPLETION.
6'-2"
A4 l um. STA1 R G.C. TO R0
SHOP DIES
I
F,A5�ICATION ,AND APPROV
2ND FLOOR PLAN -
SCALE: 1/4" = 1'-0"
NON -BEARING INTERIOR PARTITIONS
ALL INTERIOR NON BEARING PARTITIONS SHALL BE 3 5/8" METAL STUDS 26
GA AT 24" D.C. MAX. SPACING W/ 5/8" MIN. GYPSUM DRYWALL EACH SIDE.
UILDING IDE TIFICATION
APPROVED NUMBERS OR ADDRESSES BE PLACED
ON ALL NEW AND EXISTING BUILDINGS IN SUCH POSITION AS TO BE PLAINLY
VISIBLE AND LEGIBLE FROM THE STREET OR ROAD FRONTING THE PROPERTY.
SAID NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
�:
MIRRORS SHALL BE ANCHORED TO STUDS WHEN IN EXCESS OF 9 S.F.
BATHROOM FLOORS AND BASE SHALL BE IMPERVIOUS MATERIALS PER FLORIDA
BUILDING CODE, 2017 6TH EDITION. TILE FINISH SELECTED BY OWNER
BATHROOMS
BATHROOM FLOORS AND BASE SHALL BE IMPERVIOUS MATERIALS PER FLORIDA
BUILDING CODE, 2017 6TH EDITION. TILE FINISH SELECTED BY OWNER
AA20003774
T SW nALNILL AVIM
POPT SAPT LUC r rL. )4V
772-800-N00
www. b](jrchiteaure,com
OF FL
Y
�ER E � AEG
L�
uJ
<
0
J
�
�o
<U-
u.-
0
pG
J
�
UJ
Ll_.J
Jl
>�0
U—j
v
O
d
DOCU AMT DATE::
PEVISI017S:
rl% TOUR PROOMS SUDNT DATE
9UILDIMI DIPARTAMT COAAMTS 08232021
SMUT TITLE:
FLOOR
PLAN
S
V 4 4
5'-9" 6'-W 1 EY-0"
OFFICE
TREATMENT C?
TREATMENT Cl?
.4 C
TA 1 6" 6'-4"
CU A
SOUND
A
CONTROL
A
n C=Q .3 LJ
4.
FS OCCUPANCY CLASSIFICATION
I W"
TREATMENT I I OFFICE
6D N-
10'-2"
Im
Ol%
17'-9"
FIXED SEATING ASSEMBLY AREA
PLATFORM
12'-0" 1 E3'-O"
DIMENSION PLAN
�* LB) Architecture
AA20005774
T SW MULL WnUr
PORT SA PT LUG r rL, 34V
772-800-W00
wwwlbidr(hkdurc.(om
<
U-
0
10
an
<
U-
0
LL-j
<
<
LV
U-j
00
GEC
0
>-
U-j
F-
0
DOW/All"IT DATE::
DATE:
RIVIslorls:
Fl% YOUR PROORISS SMAIT
DATC
bUILDIM DIPARTIAMT (OMMTS
08232024
St111T TITLE:
DIMENSION
PLAN
SHUT rlu/Ab[R:
A �2
BOTTOM OF EXISTING
STRUCTURE
5/8" GYPSUM WALLBOARD
3-5/8" " METAL STUD 16"oc
31 1 /2" SOUND ATTEN. BLANKET
(SEMI-RIGID/NON-COMBUSTIBLE)
CAULKED JOINT
FINISH FLOOR
TYP. WALL ASSEMBLY
SCALE; 3/4" = 1'-0"
10" METAL STUDS 12" O.C.
14 GAI IGE 12" O.C.
•-------------------- -- -
I I
I I
I i
I i
I I
I i
I I
NOMINAL 3/4" RED OAK WOOD
FLOORMCs OVER In" CDX PLYWOOD
ON NOMINAL 2"x3"PT. WOOD SLEEPERS
ON PVC RESILIANT PADS OVER
6 MIL. POLYETHELENE.
2"D. RED OAK HALF ROUND
CCNT. 2"xl 1/2" (ACTUAL. WOOD
NAILER WITH 1/49/4" SLOTS
* C. 2"O.FOR VENTING WOOD FLOOR
1 1/4"x 6 3/8" RED OAK
CROWN MOULDING
GONT. I"x4" WOOD NAILER
WITH 1/4"A/4" SLOTS i 2"O C.
FOR VENTING WOOD FLOOR
3/4" PLYWOOD
SAW CORRUGATED STEEL DECK
8" STRUCTURAL STEEL
STUDS (HORIZONTAL)
8" STRUCTURAL STEEL
14 GA. STUDS 12" O.C. (VERTICAL)
NOMINAL 3/4" RED OAK
PLANKING (VERTICAL) ON 1"x4"
P.T. WOOD FURRING.
O Altar Apron (Front Detgjl�,
PLATFORM FLOOR
RED OAK BULLNOSE WITH
1" RADIUS AND 3/4" RETURN
10" METAL STUDS 12 °' O.G.
14 GAUGE 12" O.C.
------------------
A
4
j I—
i
i-
Alter !;tmr
FLOOR MOUNTED
WATER CLOSET
WALL HUNG
URINAL
STEEL STUDS
1 /2" TILE BACKER BOARD
CERAMIC TILE FINISH - REFER
CLEAR TO FINISH SCHEDULE
1 1 /2" DIA. STAINLESS STEEL GRAB
BARS, REFER TO FLOOR PLANS
FOR LENGTH AND LOCATIONS
CONCEALED MOUNTING
W/2-SCREWS PER FLANGE
12 GAUGE x 3" WIDE ANCHOR PLATE IN
LENGTHS TO ACCOMMODATE DIFFERENT
LENGTHS OF GRAB BARS. ANCHOR PLATES
SHOULD HAVE DIEFORMED AND TAPPED
MOUNTING HOLES THAT MATCH CONCEALED
MOUNTING PLATES OF GRAB BARS. INSTALL
PER MANUFACTURER'S SPECIFICATIONS
CUTOUT FOR ANCHOR PLATE -
INSTALL PER MANUFACTURER'S
SPECIFICATIONS
01 %Lw YAM
NOTE: SINKS SHALL COMPLY
WITH ADA REQUIREMENTS
E�
LAVATORY
4 MIRROR
TOILET
ACCESSORIES
LAVATORY 8 MIRROR
HANDICAPPED
O
FEM, PROD.
DISPENSER PARR TOWEL
0 o DISPENSER
DRINKING
FOUNTAIN
TOILET
ACCESSORIES
TYPICAL MOUNTING HEIGHTS
MIRROR
PLASTIC LAMINATE ON 3/4"
THICK EXTERIOR GRADE
CONT. SEALANT
PLYWOOD AT VANITY
BACKSPLASH RETURN
COPE OUT HORIZ. LEG OF
WHERE INDICATED
STEEL ANGLE AT LAV'S
J
GYPSUM WALLBOARD
ON MTL STUDS
REFER TO FINISH SCH.
FOR WALL AND FLOOR FINISHES
Cr7
LA?
RETURN PLASTIC
LAMINATE AT
SPLAYED 3/4" TH'K
EXT. GRADE PLYWOD
FACE PANEL
FASTEN SPLAYED FACE
TO METAL CLIPS W/LAG
SCREWS FROM REAR
SIDE PROVIDE 2'O"L.
REMOVABLE ACCESS
PANEL AT LAWS ATTACH
W/CHROME OVAL HEAD
CREWS AND CHROME
INISH WASHERS 3
MOUNTING PLATES PER
STEEL FRAME)
SLOPE SPLAYED FACE
AS FAR AS PRACTICAL
TO PIPING FOR ADEQUATE
CLEARANCE FOR HANDICAP.
ACCESS
HANDICAP LAV DETAIL
m
Cu
TOILET TISSUE
DISPENSER
0
TOILET
ACCESSORIES
PAPER TOWEL SOAP
DISPENSER DISPENSER
OVER COUNTER
SINK
ACCESSORIES
TOILET
ACCESSORIES
SANITARY
NAPKIN
DISPOSAL/
T.P. HOLDER
j-
X
UA
(L
t--
FIRE EXTINGUISHER
1/811 TH'K 6TAAINLE56 STEEL
ATTACHING PLATES AT
EACH STEEL FRAME
O
' TH'K 5TAINLE55
:EL ATTACHING
ATES AT EACH
-.EL FRAME
REFER TO SECTION
LEFT FOR LAMINAT;
PLASTIC PANEL
INFORMATION
s
PROVIDE 2"x2"xI/4" STEEL ANGLE
FRAMES WITH WELDED CONNECTIONS,
BOLT TO HORIZONTAL ANCHOR PLATES
REFER TO INTERIOR ELEVATIONS FOR
STEEL FRAME LOCATIONS AND LOCATIONS
OF REMOVABLE ACCESS PANELS
LBJ Architecture
AA20005774
T SW MULL AVrRUr
PUT SAINT LUC r LL. )4V
772-800-N00
www1pir(hiteauruom
v
/-V
11 )
%.n
LI—
Q
Q
OJ
�G
0
Co
Q
U-
0
,.%,
U-1
�
�
J
�L
J
�
00
f-v
O
>
U—)
r,-.
0
DOW/AEnT DATE::
DATE:
REVISIOris:
17% TOUR PROOR155 SUMIT DATE
6UILDIM WARTADIT COrAMTS 08232024
SHICT TITLE. -
DETAILS
SHEET f1UM6ER:
AIIIIIIIIIIII 3
EXIS
41 '4 . I .
4a
.4,dd 4
A
NEW 24"x24" CONCRETE FOOTING
'd. WITH #5 RBR 6" O.C. EA WAY
UChlropm
SECTION/ELEVATION OF STEEL BEANA
L I
NOTE:
THE INSTALLATION OF GLAZING PROTECTION
DEVICES HAS BEEN CONSIDERED IN THE
DESIGN OF THE SUPPORT STRUCTURE
CONCRETE LINTEL
'CAST-CRETE'
SEE LINTEL SCHEDULE
FOR REINFORCING &
FILLING, IF REQUIRED
#5 STEEL RB
PER PLAN
CONCRETE
BLOCK WALL
BOTTOM OF
FOOTER
w
Ir
N
FUdFvr.-lFl-T@Tlv"TTffWvj
POUR SOLID 8" DEEP (MIN)
AT EACH WINDOW SILL
NOTE:
SEE FOUNDATION PLAN
FOR COLUMN LOCATIONS
& REINFORCING
4 /nll mm
T VWALL
% WOOD FRAMING
STUCCO FINISH
OVER 8 X 16 C,M.0
Will I k' 4 1 No
'y 11 16 X 3"' TAPCON
FILL ALL FACTORY
PROVIDED HOLES
THRU FRAME TO BLOCK
1 X (FRAME WIDTH) PT BUCK
APPLIED TO CONCRETE FILLED
MASONRY VVI POWER ACTIVATED
BROAD HEAD COIL NAIL La 6" O.C.
112' DRYWALL
INTE.'RIORWOOL) FRAMING
6 PANEL WOOD DOOR
STUCCO FINISH
OVER 8 X 16 C.M.U.
CAULKING
X" X 5" TAPGON
(3) PER SIDE
THRU FRAME
TO BLOCK
Architecture
AA20005774
T SW rALULL MMUC
PORT SAINT LUa rL. M))
772-800-N00
wwwbi,jrhte'(tur�.(om
OF FL
cJ
E D
r"Ll
LL—j
<
U-
9
U-
0
nz
0
<
U-
Ow,
L
0
Cv
DOUAMT DATE::
DATE:
RIVIslorls:
r1% TOUR WOMBS Subrw DATC
NUILDIFla WARTACTIT (ONAMTS 082=24
SHUT FlUnb[P:
EXISTING FRONT ELEVATIONS
1
KEY NOTES
OPREVIOUS LOCATION OF EXISTING
200A PANEL; NEW FEEDERS TO BE
PULLED TO NEW LOCATION OF NEW
200A PANEL.
CIRCUIT THROUGH PHOTOCELL /
TIMECLOCK.
LIGHTING CONTROL SYSTEM
LINE RISER
r-a
ILC APPRENTICE II
RELAY PANEL
line G2 LV Switch
load
(typical of up to 4)
EXISTING
120/24OV,
10
SERVICE
G2 LV Switch G2 LV Switch
O CAT5 CABLE WITH RJ45 CONNECTORS
00=A EYE ITT mna N11011� n' 00 ct'[RI1710M.
Fo at ft
ow ir IM A.
ddoMr. °dJl"h""'b and .oM or opall
Mleida�alt6n Weo at 1me.
UM ti* tq of 911"74-p1111W *M tee&
EXTERIOR
3#3/0 & 1#213 - 2"
NEW
200A
20 AA 2P
NEMA 3R
EXISTING METER
AND MAIN FOR
EX. METER ADJACENT TENANT.
NOT IN SCOPE
QEX. METER
Q
EX. RACEWAY
LEGEND
INTERIOR NEW
EXISTING
200 AMP
PANEL
A
EXISTING ELECTRICAL RISER DIAGRAM
• • NEVINISTIMINUM
LightSyncTm G2 Dataline Switch Detail
E) Ow"
15 posm- 6 !. 2 od- t
0 0
BACK
A
` p .
0
0611" 1�-1m 8'RRadT HOLE FOR FOR /6-M
RJ-!5/OAT-5 JACK (2) 52
THREADED
A. ALL EQUIPMENT TO BE BY INTELLIGENT LIGHTING CONTROLS, INC.
ON -SITE SYSTEM COMMISSIONING SHALL BE REQUIRED.
COMMISSIONING OF SYSTEMS VIA MODEM WITHOUT ON -SITE SUPPORT
SHALL NOT BE ACCEPTED.
B. ELECTRICAL CONTRACTOR TO PROVIDE CAT-5 DATA CABLE.
SEE CAT-5 REQUIREMENTS SHEET & RJ45 CONNECTOR DETAIL.
TEST ALL CABLE LENGTHS AND TERMINATION'S W/CAT-5 TESTER.
C. ALL LOW VOLTAGE COMMUNICATION CABLE & HARDWIRE LOW
VOLTAGE CONTROL WIRING TO BE INSTALLED PER NATIONAL
ELECTRICAL CODE FOR CLASS-2 LOW VOLTAGE WIRING.
D. CLASS-2 LOW VOLTAGE WIRING SHALL NOT BE MIXED WITH OR
RUN IN LINE VOLTAGE RACEWAYS. SEPARATE LOW VOLTAGE RUNS
FROM LINE VOLTAGE BY A MINIMUM DISTANCE OF 1-FOOT.
E. CAT-5 DATA CABLE RUNS TO BE INSTALLED IN A DAISY CHAIN
FROM ONE PANEL. OR DEVICE TO THE NEXT. NO "STAR" OR "T"
CONFIGURATIONS ALLOWED WITHOUT POWER SUPPLY REPEATERS.
F. ALL CLASS-2 & CAT-5 DATA CABLE RUNS TO BE PROVIDED AND
INSTALLED WITH THE APPROPRIATE JACKET TYPE OR CONDUIT
FOR THE INSTALLA11ON ENVIRONMENT OR CONDITIONS ON SITE.
G. EACH LIGHTING RELAY PANEL REQUIRES A DEDICATED 120V.
OR 277V, CIRCUIT' FOR CONTROL POWER TRANSFORMERS.
H. ADDITIONAL ILC POWER OR DATA REPEATING DEVICES MAY BE REQUIRED
FOR PROPER SYSTEM OPERATION, BASED ON THE ACTUAL NUMBER
AND DISTANCE OF UghtSync DEVICES TO BE INSTALLED ON CAT-5
DATA LINE- CONTACT AMY LEE 0 SESCO LIGHTING 954-474-9888.
COIN'TROLi
NrU
ELECTRICAL SPECIFICATIONS
PERT 1 - GENERAL
A. THE CONTRACTOR SHALL SUPPLY AND INSTALL ALL NEW ELECTRICAL WORK INDICATED.
CONSTRUCTION SHALL BE IN ACCORDANCE WITH DRAWINGS AND APPLICABLE SPECIFICATIONS.
IF A PROBLEM IS ENCOUNTERED IN COMPLYING WITH THIS REQUIREMENT, CONTRACTOR SHALL NOTIFY
THE ARCHITECT/ENGINEER AS SOON AS POSSIBLE AFTER DISCOVERY OF THE PROBLEM AND
SHALL NOT PROCEED WITH THAT PORTION OF THE WORK UNTIL ARCHITECT/ENGINEER HAS DIRECTED
CORRECTIVE ACTION TO BE TAKEN,
B. THE CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO BID AND FAMILIARIZE HIMSELF WITH ALL
CONDITIONS AFFECTING ELECTRICAL AND COMMUNICATIONS INSTALLATION AND MAKE PROVISIONS AS TO
THE COST THEREOF.
C. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC
CODE (AS ADOPTED BY THE AUTHORITY HAVING JURISDICTION) AND ALL CODES AND ORDINANCES OF THE
AUTHORITY HAVING JURISDICTION. THE SPECIFICATION, CODES AND STANDARDS LISTED BELOW ARE
UTILIZED IN THIS PROJECT.
1. NATIONAL ELECTRICAL CODE (NFPA-70)
2. CODE FOR SAFETY TO LIFE (NFPA-101)
3. STANDARD FOR THE INSTALLATION, MAINTENANCE AND USE OF LOCAL PROTECTIVE SIGNALING
SYSTEMS (NFPA-72)
4. UNDERWRITERS' LABORATORIES (UL)
5. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
6. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
7. FEDERAL SPECIFICATION (FED. SPEC.)
8. INSULATED POWER CABLE ENGINEERS ASSOCIATION (IPCEA)
9. FLORIDA BUILDING CODE. FBC 2017 EDITION
10. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)
11, CITY OF PORT SAINT LUCIE BUILDING CODE. (AMENDMENTS TO FLORIDA BUILDING CODE FBC 2017)
12. ADDITIONALLY, DESIGNS, WORK PRACTICES AND CONDITIONS MUST CONFORM WITH THE
OCCUPATIONAL SAFETY AND HEALTH ACT OF 1970 (OSHA)
D. DO NOT SCALE THE ELECTRICAL DRAWINGS. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS
FOR EXACT LOCATION OF ALL EQUIPMENT. CONFIRM NTH OWNER'S REPRESENTATIVE.
E. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE
CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM
AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER.
F. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FROM A
PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE.
G. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE
REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED
THERE BY.
H. ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY AND
PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS AND TESTING. CONTRACTOR
TO OBTAIN PERMIT AND APPROVED SUBMITTALS PRIOR TO BEGINNING WORK OR ORDERING EQUIPMENT.
THE TERM "PROVIDE" USED IN THE CONSTRUCTION DOCUMENTS AND SPECIFICATIONS SHALL MEAN THAT
THE CONTRACTOR IS TO FURNISH, INSTALL AND CONNECT COMPLETE.
PART 2 - PRODUCTS
A. MINIMUM WIRE SIZE SHALL BE #12 A.W.G. (EXCEPT AS NOTED OTHERWISE FOR CONTROL WIRING). ALL
CONDUCTORS SHALL BE 98% CONDUCTIVITY, COPPER WITH "THHN-THWN" INSULATION UNLESS OTHERWISE
NOTED.
B. ELECTRICAL METALLIC TUBING (EMT) SHALL BE OF BEST QUALITY STEEL, SMOOTH INSIDE AND OUT
AND SHALL BE HOT -DIPPED GALVANIZED.
C. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS
L IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES FOR OTHER CLASSIFIED AREAS.
D. RIGID NONMETAUC CONDUIT SHALL BE SCHEDULE 40 PVC.
6. ALL MATERIALS SHALL BE NEW AND BEAR UNDERWRITERS' LABELS WHERE APPLICABLE.
F. PANELBOARDS:
1. CURRENT CARRYING BUSES SHALL BE COPPER. GROUND BUS BARS SHALL BE COPPER.
2. ALL CIRCUIT BREAKERS SHALL BE BOLT ON. PLUG-IN BREAKERS ARE NOT ACCEPTABLE.
3. CIRCUIT BREAKERS USED AS SWITCHES IN FLUORESCENT OR HID LIGHTING CIRCUITS SHALL
BE LISTED AND MARKED "SWD"
4. ALL CIRCUIT BREAKERS FEEDING MECHANICAL EQUIPMENT SHALL BE HACR TYPE.
5, A.I.C. RATINGS SHALL BE AS INDICATED ON PANELBOARD SCHEDULES.
6. ALL PANELBOARDS SHALL BE FURNISHED WITH PLASTIC LAMINATE NAMEPLATES WITH 1/4"
ENGRAVED LETTERING FOR PANEL IDENTIFICATION.
7. ALL PANELBOARDS SHALL BE PROVIDED WITH TYPE -WRITTEN DIRECTORY OF BRANCH CIRCUIT
DESIGNATIONS.
G. DISCONNECT SWITCHES SHALL BE H.P. RATED, HEAVY DUTY, QUICK -MAKE, QUICK -BREAK. ENCLOSURES
SHALL BE NEMA-1 FOR INDOOR LOCATIONS, NEMA 3R FOR OUTDOOR LOCATTONSOR AS OTHERWISE NOTED.
H. MOTOR STARTERS SHAD_ BE MANUAL OR MAGNETIC AS INDICATED ON THE ELECTRICAL DRAWINGS, WITH
OVERLOAD RELAYS IN EACH PHASE.
WIRING DEVICES (GENERAL PURPOSE RECEPTACLES AND WALL SWITCHES) COLOR SHALL BE COORDINATED
WITH CLIENT.
PART 3 - EXECUTION
A. COLOR CODING OF CONDUCTORS SHALL BE AS FOLLOWS:
1. 208/120 VOLTS, 3 PHASE, 4-WIRE SYSTEM: UNGROUNDED CONDUCTORS: 1 BLACK, 1 RED AND 1
BLUE. GROUNDED (NEUTRAL) CONDUCTOR; WHITE. GROUNDING CONDUCTORS SHALL BE GREEN.
2. 480/277 VOLT, 3-PHASE, 4-WIRE SYSTEM: UNGROUNDED CONDUCTORS: 1 BROWN, 1 YELLOW, AND
1 PURPLE. GROUNDED (NEUTRAL) CONDUCTORS; GREY. GROUNDING CONDUCTORS SHALL BE GREEN.
3. BRANCH CIRCUIT WIRING (#6 AND SMALLER) SHALL BE COLOR CODED BY CONTINUOUS INSULATION
COLOR AND FEEDERS AND SERVICES (#4 AND LARGER) SHALL BE CODED AT ALL JUNCTION OR
PULL POINTS (EXCEPT LB'S OR LBD'S) USING COLOR MARKERS OR PLASTIC TAPE MANUFACTURED
I FOR THE PURPOSE.
B. WIRING METHODS
1. ALL CONDUCTORS SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING (EMT) UNLESS
OTHERWISE NOTED, SPECIFIED OR AS SPECIFICALLY PROHIBITED BY THE AUTHORITY HAVING
JURISDICTION. ALL FITTINGS AND COUPLINGS FOR EMT CONDUIT SHALL BE ALL STEEL
RAIN TIGHT COMPRESSION TYPE OR ALL STEEL CONCRETE TIGHT SET SCREW TYPE.
2. SCHEDULE 40 PVC CONDUIT, WITH FITTINGS AND COUPUNGS APPROPRIATE FOR THE USE, SHALL
BE INSTALLED UNDERGROUND OR BELOW SLABS ON GRADE,
3. TYPE MC CABLE WITH ALUMINUM ARMOR AND INTERNAL GROUND IS ACCEPTABLE FOR
USE AS GENERAL BRANCH CIRCUIT WIRING FOR CIRCUITS 20 AMPERES OR LESS AND CONCEALED
IN WALLS OR ABOVE SUSPENDED CEILING AND AS APPROVED BY THE AUTHORITY HAVING
JURISDICTION.
C. ELECTRICAL SYSTEM SHALL BE COMPLETE AND EFFECTIVELY GROUNDED AS REQUIRED BY THE LATEST
EDITION OF THE N.E.C. AND LOCAL CODES.
D. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS
WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTED BY
ENGINEER/ARCHITECT.
E. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS
OF CONSTRUCTION.
F. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF POWER AND TELEPHONE
COMPANIES, AND SHALL BE FULLY COORDINATED WITH THEM PRIOR TO COMMENCEMENT OF WORK.
G. PROVIDE AND INSTALL CONDUIT, CONDUCTORS, PULL WIRES, BOXES, COVER PLATES, AND WIRING
DEVICES, FOR ALL OUTLETS AS INDICATED.
H. MATERIALS, PRODUCTS, AND EQUIPMENT, INCLUDING ALL COMPONENTS THEREOF, SHALL BE NEW
AND SUCH AS APPEAR ON THE UL LIST OF APPROVED ITEMS AND SHALL MEET OR EXCEED THE
REQUIREMENTS OF NEC, NEMA, AND IECE.
CONTRACTOR SHALL SUBMIT AT LEAST FIVE (5) SETS OF SHOP DRAWINGS OR CUT SHEETS OF LIGHTING
FIXTURES, SWITCHES, AND OTHER ELECTRICAL ITEMS FOR APPROVAL BY ENGINEER/ARCHITECT.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED OF HIS WORK,
K. ALL LAY -IN LIGHTING FIXTURES SHALL BE SECURED TO THE SUSPENDED CEILING GRID AT EACH CORNER.
L. CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS AND PROVIDE ALL NECESSARY CONTROL
WIRING.
M. ALL ELECTRICAL POWER WIRING FOR THE HVAC SYSTEM INCLUDING WIRING THRU LINE VOLTAGE CONTROL
DEVICES SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
N. THE CONTRACTOR SHALL CONFIRM WITH THE ELECTRICAL UTILITY COMPANY ANY AND ALL REQUIREMENTS
SUCH AS: METERING EQUIPMENT REQUIREMENTS AND METERING EQUIPMENT LOCATION, TRANSFORMER
SIZE AND LOCATION OR SERVICE POINT, CONDUIT ENTRY AND LUG SIZE RESTRICTIONS. THE CONTRACTOR
SHALL SCHEDULE ALL REQUIRED DOWN TIME FOR THE OWNERS CONFIRMATION.
ANY CONFLICTS AND DESCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE
0. PROCEEDING WITH ANY WORK.
PER NEC 210.8(B)(2) ALL 15- AND 20-AMPERE, 125-VOLT RECEPTACLES IN NONDWELUNG-TYPE KITCHENS
TO BE GFCI PROTECTED.
BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTS DROP OF 3% DESIGN LOAD. FBC 2017
FBC ENERGY CONSERVATION SECTION 405.7.3.
Q. FEEDER CONDUCTORS SHALL BE SIZED FOR A MAXIMUM OF 2% VOLTAGE DROP PER 405.7.3.
SCHEDULE OF BRANCH CIRCUIT PANEL "A"
MAIN: 200 AMP MAIN LUG ONLY VOLTAGE: 120/240V, 10, 3 WIRE
SPEC: SQUARE D LOAD CENTER OR EQUAL
K40UNTING: FLUSH AIC SYMM: 22.000
DESCRIPTION
WIRE
GND.
COND.
TRIP
CKT.
A PHASE
KVA
C PHASE
KVA
CKT.
TRIP
COND.
GND.
WIRE
DESCRIPTION
RECEPTACLES
#12
#12
1 2
20
1
0.8 0.8
2
20
1 2
#12
#12
INTERIOR LIGHTING
RECEPTACLES
#12
#12
1 2
20
3
0.8 1 0.8
4
20
1 2
#12
#12
EXTERIOR LIGHTING
RECEPTACLES
RECEPTACLES
#12
#12
#12
#12
1 2
1 2"
20
20
5
7
1.0 0.8
0.6 1 -
6
8
20
20
1 2
-
#12
-
#12
-
EXTERIOR RECEPTACLE
SPARE
RECEPTACLES
#12
#12
1 2
20
9
1 0.6 1 3.3
101
4
2
3/4"
1 #10
WATER HEATER
RECEPTACLES
#12
#12
1 2
20
11
0.6 3.3
12
RECEPTACLES
#12
#12
1 2
20
13
0.6-1 3.3
14
4
2
3 4
1#10
2#6
AC-1a
DRINKING FOUNTAIN
#12
#12
1 2
20
15
0.6 3.3
16
RECEPTACLES
RECEPTACLES
RECEPTACLES
RECEPTACLES
SPARE
#12
#12
#12
#12
-
#12
#12
#12
#12
-
1 2
1 2
1 2
1 2
-
20
20
20
20
20
17
19
21
23
25
0.6 1 0.8
1 0,6 1 0.8
- 2.8
0.6 0.a
0.6 1 0.8
18
20
22
24
26
20
20
20
20
3
2
1 2
1 2
1 2
1 2
3/4"
#12
#12
#12
#12
1 #10
#12
#12
#12
#12
INTERIOR LIGHTING
INTERIOR LIGHTING
INTERIOR LIGHTING
INTERIOR LIGHTING
AC-2 FUTURE MINI -SPLIT
SPARE
-
-
-
20
27
- 2.8
28
SPARE
-
-
-
20
29
- 2.8
30
307
2
3/4"
1#10
_
AC-3 FUTURE MINI -SPLIT
SPARE
-
-
-
20
31
- 2.8
32
SPARE
-
-
-
20
33
- 6.5
34
6
-
,-2
3 4
1 #10
2#6
AC-1 b
SPARE
-
-
-
20
35
- 6.5
36
SPARE
-
-
-
20
37
- -
38
20
-
-
-
SPARE
SPARE
-
-
-
20
39
- -
40
20
-
-
-
SPARE
SPARE
-
-
-
20
41
- -
42
20
-
-
-
SPARE
20.5 19.3 KVA PER PHASE
170.8 160.8 1 AMPS PER PHASE
39.8 TOTAL KVA
EVANGELICAL UNION OF FISHERMAN CHURCH
LIGHTING FIXTURE SCHEDULE
TYPE
MANUFACTURER
CATALOG NUMBER
DESCRIPTION
LAMPS
DIMMING
VOLTS
-
MOUNTING
----
REMARKS
Qty
Type
Total Wattage
A
TRULYGREEN
SOLUTIONS
CHB-SE-97W-40K-U-D-B-HM
CRCLUAR LED HIGHBAY
INCL
LED
9&6
0-10V
UNV
PENDANT
1,2
AEM
TRULYGREEN
SOLUTIONS
CH8-SE-97W40K-U-D-B-EM-HM
CIRCLUAR LED HIGHBAYWITH EM
INCL
LED
96.6
0-10V
UNV
PENDANT
1,2
B
TRULYGREEN
SOLUTIONS
CHB-SE-67W-40K-U-D-B-HM
CIRCLUAR LED HIGHBAY
INCL
LED
69.1
0-10V
UNV
PENDANT
1,2
BEM
TRULYGREEN
SOLUTIONS
CHB SE-67W 40K -UD BEMHM ---
CIRCLUAR LED HIGHBAYWETH EM
INCL
LED
69.1
0-10V
UNV
PENDANT
1,2
C
TRULYGREEN
SOLUTIONS
EA-2240-35-tTD-8822-SK
2X2 LED FLAT PANEL WITH SURFACE MOUNT KIT
INCL
LED
40
0-10V
UNV
SURFACE
1
CEM
TRULYGREEN
SOLUTIONS
EA-22-40-35-U-D-EM-8822SK
2X2 LED FLAT PANEL WITH SURFACE MOUNT KIT & EM
INCL
LED
40
0-10V
UNV
SURFACE
1
D
TRULYGREEN
SOLUTIONS
FLU-L C-U-D
COLOR AND WATTAGE SELECTABLE G' LED DOWNLIGHT, SET AT "H"
INCL
LED
19
0-10V
UNV
RECESSED
1
DEM
TRULYGREEN SOLUTIONS
FL-6-L-C-U-D-ELLS10CDF
COLOR AND WATTAGE SELECTABLE 6" LED DOWNLIGHT WITH EM
INCL
LED
19
0-10V
UNV
RECESSED
1
E
TRULYGREEN
SOLUTIONS
FL-6-L-C-U-D-ELIS10CDF
COLOR AND WATTAGE SELECTABLE 6" LED DOWNLIGHT, SET AT"M"
INCL
LED
13
0-10V
UNV
RECESSED
1
F
BEGHELLI
MEZ-LED-ACEM-DB-120277
AC&EML.EDWALLPACK
NVCL
LED
13
0-10V
UNV
WALL
1
GEM
H.E. WILLIAMS
WPCS-L441840-EW6W-BZ
CUTOFF WALL PACK WITH EM
INCL
LED
42
0-10V
UNV
WALL
1
EX
BEGHELLI
PX-RSA
EXIT WITH EM
INCL
LED
3
N/A
UNV
SURFACE
1
--` -LED
LIGHTING SCHEDULE NOTES:
-
----
1. PROVIDE SUBMITTALS FOR ARCHITECT/ENGINEER REVIEW PRIOR TO ORDERING. NO SUBSTITUTIONS At -LOWED. -
2. PROVIDE 3/4" RGC STEM TO ACHIEVE 18'AFF MOUNTING HEIGHT - -
SCALE: 1/4" = V-0"
On A-8
a
FUTURE ME ,'ZANINE
AA20005774
W SW nALKLL AKU
POPT SA PT LUC � I �4V
772-800-N00
WWW.Ib]ar(hkdurP,(om
L�
Q
).i_
U_
00
LgL
U_
0
•�
u�
LV
LL_J
�
�G
°®
0
U U-1
O
nc
a.
DOV\Uff DATE:
DATC:
PrVISIOfns:
1 6UIU)IfIG DCPARTAMT (OSAMTS 10-29-21
17,
SHEET TIRO:
ELECTRICAL
PLAN
SMCCT nts/'A61R.
Eml
WALL LEGEND
UNIT ADDRESS 78-1 PiR1M,4- VfSTA BLVD
OCGUPANG`� CL ASS IF f G,4T f ON:
CROUP S BUSINESS
TABLE 1006.2.1
SPA[FS WI-M ONE OR EXIT ACCESS DOORWAY
OCCUPANCY
MAXIMUM
OCCUPANT
LOAD OF SPACE
MAXIMUM COMMON PATH OF EGRES'z
TRAVEL DISTANCE (feet)
Without Sprinkler
System
(feet)
With Sprinkler
Sy5teM
(feet)
Occupant Load
OLE30
OL>30
A,t E, M
49
9
49
100
75
100a
49
-_
75
100a
t,-1, H-2. H-3
3
Ir
25b
li 4. tl-5
10
1 F'
I F'
75�'
I-1. 1-2.d1-4
5=,
1 3
10
NP
R-1
10
R-2
49
R-3t
49
125'
R 4e
20
75
75
125=
5f
29
100
75
100a
U
49
100
75
75c'
r—Cf. i Lnnr — 7C9.4 O rvs.`-.
TOTAL FLU ING ' IXTURE5 REP.:
BUSINESS OC!-UPANCY SPACES REQUIRE:
I WG PER 25
1 LAVATORY PER 40
I DRINKING FOIAITAN PER 100 MALE/FEMALE
1 SERVICE 81NK MINIT`RJM
LIFE SAFETY PLAN_
SCALE: 1/4" = I'-0"
APPLICA5LE GODS:
2020 ITH EDITION OF FLORIDA BUILDING CODE
2020 ITH EDITION OF FLORIDA MECHANICAL CODE
2020 "ITH EDITION OF FLORIDA PLUMBING CODE
2020 ITH EDITION OF FLORIDA ELECTRICAL CODE
2020 ITH EDITION OF FLORIDA ENERGY CONSERVATION CODE
2020 -TTH EDITION OF FLORIDA FIRE PREVENTION CODE
r----------------- --------
I
1
LEVEL 3 ALTEiR,4TION MORE THEN 50ro OF
CROSS SQUARE FOOTAGE AFFECTED 5�'
RENOV,4TION
SGALE: 3/16" = 1'-0"
OCCPANVY ::�,S �IGAfiIOh:dE51CNE� EO<55 COWONENE75: I `5RO55 saUARe Focrac-r cAacs:
GROUP A-3- A55EM5L� OCCUPANCY
W/ GROUF B TENANT
T OF �,ON5 R�Co, - ION
TYPE Ilia' UNPROTECTED E LINSPRINKLE'RED
FOR UNSPRINKLERED BUILDING
MAX. TRAVEL D15TANCE ALLOWED: 200'
COMMON PATH OF TRAVEL: 100,
EXIT AND MEANS OF EGRESS WIDTH
DOORS 02" PER PERSON SERVED - 32" MIN CLEAR WIDTH
PER TABLE 10202
CORRIDOR OCCUPANT LOAD LESS THEN 50 : 36" MIN. WIDTH
2 ;STORY BU11-DING :
FIRST FLOOR; 4,200.5Q. FT
SECOND FLOOR : 840 SQFT
TOTAL: 5,040 SQ FT
OCCUPANT L0A '_
FIXED SEATING ASSEMBLY:
64 PPL.
ASSEMBLY:
51 PPL.
OFFICE:
I PPL.
STORAGE:
3 PPL
TOTAL:
PROVIDE PANIC
HARDWARE
--------------
�c
TOTAL OCCUFANCY:
FIXED SEATING ASSEMBLY: r64 PPL.
ASSEMBLY: 57 PPL
OFFICE: 1 PPL.
STORAGE: 3 PPL.
TOTAL: 125 PPL.
[� EXISTING WALLS TO REMAIN
NEW INTERIOR FRAMING
CBS WALL INFILL
2 HOUR RATED WALL UI.- 905
UNIT ADDfiRESS i89 PRIMA VISTA BLUD
903.2.1.3 C3ROUf= A-3. AN AUTOMATIC SPRINKLER
SYSTEM SHALL BE PROVIDED FOR GROUP A-3
OCCUPANCIES WHERE ONE OF THE FOLLOWING
CONDITIONS EXISTS:
1. THE FIRE AREA EXCEEDS 12,000 SQUARE FEET
(1115 1" 12 ).
2. THE FIRE AREA HAS AN OCCUPANT LOAD OF
300 OR MORE.
3, THE FIRE AREA IS LOCATED ON A FLOOR OTHER
THAN THE LEVEL OF EXIT DISCHARGE -
NO CONDITIONS EXISTS FOR THIS APPLICATION
a ■
11 RISK CATEGORY I I
ULTIMATE DESIGN WIND SPEED 170
2) EXPOSURE G
SURFACE ROUGHNE-SS G
3) COMPONENTS & CLADDING (WORSE CASE)
NOiR5E ROOF +1 &.3 _5258
GASE WALLS +503 _55.0
TOTAL FLW51NO F1XTJR10!5 REO
SMALL ASSEMBLY USE SPACES REQUIRE:
I WC PER 125 MALE-65 FEM: a-E
I LAVATORY PER 200 MAL r FEMALE
I DRINKING FOUNTAIN PER YrnO MALE/FEMALE
1 SERVICE SINK MMIMUMAee-mbly Occupancy Recommend®: Potty Parlty In A Ratio
Of 3 To 2. Ferrate VS. Male
ASSEMBLY: 164 PERSONS: z,-' MALE 82 FEMALE
TOTAL FIXTURES REQUIRED:, MALE I WC I LAV FEMALE 2 = I LAV
I ' -q=. i SERVICE SINK
TOTAL FIXTURES PROVIDED_
t;' LE 2 0C 2 LAV FEMALE 2 U1C 2 LAV
2 D.F. I SERVICE SINK
LB) Architecture
AAMOM774
W SW HALULL MMUC
POPT SAPT LU(Ic rL. )4V
772-800-5700
www.lbjarchitc(turc.com
OF FL 0�
Idum=0248
E D PARl'
v
U-)
U-
p
p
Q
>
�
0
4
0
<
J
_Q�_�
J
�
U��
Lai
00
DOCU/1EI7T DATE
PIVISIOrls:
r1% TOl1R PROGRESS SWIT DATC
DWLDIM DEPARTIMT (O AMtTS 06232021
COUNTY
M,
S1`1[[T TITLE:
LIFE SAFETY
PLAN
SHIFT M('1 M
1�--\L'S-1
A.,
:Ak, W""d1v Architecture
PACKAGE A/C EOUIP. SCHEDULE
A/C UNIT TAG
AC-10 5.0 TON
AC -lb 3.0 TON
MANUFACTURER
CARRIER
CARRIER
MODEL
50VL-A60
5OVL-C36
TOTAL SENSIBLE CAP. MBH.
44.5
25.6
TOTAL COOUNG CAP. MBH.
57.9
34.8
ENT. AIR TEMP D.B./W.B. "F
80'/67'
80-/67-
LEAV. AIR TEMP D.B./W.B. %
-
-
SUPPLY AIR CFM
2000
1150
OUTSIDE AIR CFM
200 - 200
120 - 120
VOLTAGE
208/10/60
240/10/60
MCA/MOCP
35.5/40.0
34/35
SEER/EER
14,2/_
14.0/-
OPERATING WEIGHT LBS.
487
349
DIMENSIONS L x W x H (IN.)
48X43X54
49X33X52
NOTES
-
1-17
REF./LBS.
R-41 OA/-
R-41 OA/-
NOMINAL TONNAGE/STAGES
5,0/2
3/1
NO. OF COMPRESSORS
1
1
COMP. R.LA. EACH
16.0
10.4
NO. OF OUTDOOR FANS
1
1
FAN FLA. EACH
1.2
1.0
INDOOR FAN TYPE
FC
FC
FAN E.S.P. (IN. W.G.)
1-
0,5"
FAN H.P./B.H.P.
1.0 BHP
0.75 BHP
FAN F.LA.
7.6
6.0
COL ROWS/FPI
-
--
HEATER TYPE
ELECTRIC
ELECTRIC
HEATER K.W. O RATED VOLTAGE
5 O 240V/10
5 O 24OV/10
NO. OF STEPS
j
1
FILTER TYPE/EFF.
�97�L
1. UNITS SHALL BE "ARI" RATED. APPROVED EQUIVALENT: AAON,
c r►wnV u_,v,•V • An V
1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY
FOR THE INSTALLATION OF A COMPLETE SYSTEM IN ACCORDANCE WITH THESE
DRAWINGS, THE FLORIDA BUILDING CODE 2017 AND ALL OTHER APPLICABLE STATE,
COUNTY AND LOCAL ORDINANCES AND THE LATEST ADDITION OF THE FOLLOWING
PUBLICATIONS; SMACNA-85, 92, 95; ASHRAE 15-01, 34-01, 62-04, NFPA 70-02, 72-02,
9OA-02, 90B-02, 91-99, 96-01; ANSI Z10.1-98, Z10.3-98, Z21.8-94, Z21.83-98.
2. THE CONTRACTOR SHALL PAY ALL COSTS OF PERMIT, INSPECTIONS AND ALL OTHER
COSTS INCIDENTAL TO THE COMPLETION AND TESTING OF THIS WORK.
3. THE CONTRACTOR SHALL VISIT THE SITE AND COORDINATE WORK WITH OTHER TRADES.
4. THE CONTRACTOR SHALL SUPPLY THE ARCHITECT WITH "AS -BUILT' DRAWINGS.
5. CONTRACTOR SHALL SUBMIT, FOR APPROVAL FIVE [51 COPIES OF MANUFACTURER'S
DRAWINGS FOR EACH PIECE OF EQUIPMENT AND CONTROLS INCLUDED IN CONTRACT,
6. ALL MATERIAL SHAD- BE NEW OF U.S. MANUFACTURER OF GOOD QUALITY. ALL WORK SHALL
BE PERFORMED AT INDUSTRY STANDARD QUALITY LEVEL BY CERTIFIED PROFESSIONALS.
ALL EQUIPMENT SHALL BE UL OR ETL LISTED.
ALL INSTALLATIONS SHALL COMPLY WITH FMC 2017. CH. 3, GENERAL REGULATIONS. BUILDINGS
LOCATED WITHIN 3,000 FT FROM THE OCEAN SHALL UTILIZE NON-FERROUS MATERIALS FOR
ALL OUTDOOR EXPOSED SUPPORTS, STANDS, FASTENERS, ETC.
7. DUCTWORK:
& ALL AIR CONDITIONING DUCT WORK SHALL BE OF 1-1/2" (R-6) HEAVY DUTY FOIL
REINFORCED FIBERGLASS WITH MANUFACTURER'S LOGO PRINTED ON VAPOR BARRIER
& ALL FLEX DUCT SHALL BE RATED CLASS 1, UL-181 LISTED WITH METALLIZED INNER AND OUTER FOIL
UNERS, MIN. R-6 WITH A MAX. TOTAL LENGTH NOT TO EXCEED 15 FT.
FLEX113LE DUCTWORK ELBOW SUPPORTS AT EACH DIFFUSER, GRILLE, AND REGISTER EQUAL TO "FLEXFLOW
ELBOW" AS MANUFACTURED BY 'THERMAFLEX'.
C. ALL EXHAUST DUCTS AND OUTSIDE AIR DUCTS SHALL BE GALVANIZED SHEET METAL
WITH SEALED SEAMS AND JOINTS. ALL OUTSIDE AIR DUCT SHALL BE INSULATED WITH
EXTERNAL BLANKET INSULATION R-6 MIN.
ALL METAL EXHAUST, MAKE-UP OR OTHERWISE DUCTS INSTALLED IN LOCATIONS WHERE DEWPOINT
CONDITIONS CAN OCCUR INSIDE THE DUCT SHALL BE EXTERNALLY INSULATED WITH R-6 MIN.
THE CONTRACTOR SHALL PROVIDE ALL SHEETMETAL DUCTWORK, HANGERS, AUX. SUPPORT STEEL, ETC.
ALL METAL DUCTS SHALL BE FABRICATED IN ACCORDANCE NTH LATEST EDITION OF S.M.A.C.N.A.
AMAL
SMAC14A DUCT PRESSURE CLASSES BASED ON OPERATING PRESSURE ARE: 1/2-, 1", 2-, 3-, 4'.
6", AIND 10". EACH DUCT SYSTEM SHALL BE CONSTRUCTED FOR THE SPECIFIC DUCT PRESSURE
CLASS SHOWN ON PLANS.
WHERE NO PRESSURE CLASS IS SPECIFIED FOR CONSTANT VOLUME SYSTEMS, 1" W.G. PRESSURE
CLASS IS THE BASIS OF COMPUANCE WITH THE SMACNA STANDARDS REGARDLESS OF VELOCITY.
WHERE NO PRESSURE CLASS IS SPECIFIED FOR VARIABLE VOLUME SYSTEMS, 2" W.G. PRESSURE
CLASS IS THE BASIS OF COMPLIANCE WITH THE SMACNA STANDARDS FOR DUCTWORK UPSTREAM
OF VAV BOXES.
ALL DUCTWORK SHALL BE SEALED TO SMACNA "HVAC DUCT CONSTRUCTION STANDARDS' FOR
ITS PRESSURE CLASS SEALING METHODS.
9. OUTSIDE AIR INTAKES SHALL BE SCREENED WITH A CORROSION RESISTANT MATERIAL NOT LARGER
THAN 1/2" MESH. O/A INTAKES SHALL NOT BE TAKEN FROM A LOCATION CLOSER THAN 10 FT.
FROM ANY CHIMNEY, VENT OUTLET OR SANITARY SEWER VENT OUTLET, UNLESS SUCH VENT
IS NOT LESS THAN 24 INCHES ABOVE THE OUTSIDE AIR VENT.
OUTSIDE AIR INTAKE VENTS LOCATED ON ROOFS WILL BE PROPERLY MARKED WITH A UNIVERSAL
MARKIING "INTAKE', PERMANENTLY ATTACHED PER FMC 2017, SEC. 401.5
10. DUCT SIZES SHOWN ARE INSIDE DIMENSIONS.
11. ALL AJR DEVICES (DIFFUSERS, REGISTERS AND GRILLES) SHALL BE ALL ALUMINUM
CONSTRUCTION WITH EXPOSED SURFACE OFF WHITE BAKED ENAMEL FINISH OR AS
SPECIFIED BY ARCHITECT. DEVICES SHALL BE AS SPECIFIED OR EQUAL TO TITUS OR METALAZRE.
PROVIDE OPPOSED BLADE DAMPERS AT ALL DIFFUSERS AND REGISTERS AS INDICATED ON
PLANS. PROVIDE BALANCING DAMPERS FOR ALL SUPPLY AND RETURN DIFFUSERS AND REGISTERS
TO ERASURE COMPLAINCE WITH FMC 2017, PAR. 601.5 AND PAR. 603.18 FOR BALANCED AIR FLOW.
12. TEMPERATURE CONTROLS/THERMOSTAT-
A. SHALL BE COMBINATION COOUNG/HEATING, WITH SYSTEM "COOL -AUTO -
HEAT --OFF' AND FAN "ON -AUTO" SELECTOR SWITCHES. PROVIDE PROGRAMMABLE TYPE AS
RECOMMENDED BY MANUFACTURER, HONEYWELL OR EQUAL PROVIDE TAMPER PROOF COVERS.
13. THERMOSTAT LOCATION SHALL BE APPROVED BY OWNER AND ENGINEER BEFORE INSTALLATION.
INSTALL THERMOSTAT 48' TO 54" A.F.F. PER A.D.A REQUIREMENTS WHERE APPLICABLE.
MECHANICAL CONTRACTOR SHALL COORDINATE WITH ELECTRICAL CONTRACTOR ALL REQUIREMENTS
FOR JUNCTION BOXES, CONDUITS, CONTROL. WIRING, POWER, ETC. AND DEFINE RESPONSIBIUTIES
AND SCOPE OF WORK FOR EACH TRADE PRIOR TO ANY PURCHASING OR INSTALLATION.
WHENEVER THERE ARE MORE THAN ONE SENSOR OR THERMOSTAT, SIDE BY SIDE, THEY SHALL BE
GANGED TOGETHER WITHIN THE SAME COVER PLATE WHEREVER POSSIBLE.
CONTRACTOR SHALL COORDINATE THIS ISSUE WITH ARCHITECT/OWNER PRIOR TO INSTALLATION AND
SHALL BRING ANY DISCREPANCY TO THE ENGINEER'S ATTENTION.
14. REFRIGERANT UNES SHALL BE COPPER, TYPE -L" HARD DRAWN WITH WROUGHT COPPER
BRAZING -JOINT TYPE FITTINGS, USE BRAZING MATERIALS FOR HIGH PRESSURE PIPING
PER AWS A5.8: BCuP SERIES COPPER -PHOSPHORUS ALLOY OR BAg1 SILVER ALLOY.
REFRIGERANT UNES SHALL BE SIZED PER MANUFACTURER'S RECOMMENDATIONS.
SOFT COPPER TYPE 'M' SHALL BE ALLOWED FOR RISER PIPING INSIDE CHASE TO OMIT
NUMBER OF JOINTS. COORDINATE WITH ENGINEER FOR PRIOR APPROVAL
ALL EXPOSED INSULATION SHALL BE PROTECTED WITH UV RESISTANT PAINT OR ALUMIN. SHIELD.
15. ARMAFLEX INSULATION SHALL BE USED FOR SUCTION UNES (1/2- FOR ABOVE 40- F AND
1- FOR BELOW 40- F) PER FLORIDA ENERGY CODE TABLE 4-11 FOR PIPING INSULATION.
FILTER/DRYER AND SIGHT GLASS SHALL BE PROVIDED AT UQUID UNES.
O SIDE AIR CALCULATIONS
(PER TABLE 6-1, ASHRAE 62.1-2010)
AREA SERVED
AREA SQ.FTNET ABLL
AREA
R RATE T(R)
CFIM/FT"2
TOTAL NO,
OF
AIR RATE (RP) OUTDOOR
CFM/PERSON
DEFAULT
DEFAULT VALUES
TOTAL. NO. OF
PEOPLE FROM
DEFAULT VALUES
COMBINED OUTDOOR
AIR RATE
0 TOTAL
/O/A
TOTAL
PROVIDED
NOTES
OCC. DENS. P/
I000FT"2 FL AR.
CFM/PERSON
AC-la
ASSEMBLY
820
0.06
25
5
-
-
49.2+125
174.2
175
SEE NOTES
AC -lb
LOBBY/ASSEMBLY
155206
10.
25
5
-
-
93.12+125
218.12
220
SEE NOTES
TOTAL
_
_
392.3
395.0
NOTES-
1. CALCULATIONS ARE BASED ON ESTIMATED MAX. OCCUPANCY RATES PER ARCHITECTURAL PLANS AND
ASHRAE 62.1. VENTILATION RATES PER ASHRAE 62.1
2. FOR OFFICE AND OTHER SIMILAR AREAS CALCULATIONS ARE BASED ON CONTINUOUS OCCUPANCY
FAN SCHEDULE
MEMODATA
FAN DATA
M011umn DATA
DATA
TAG
SERVICE AREA
MANUF.(i)
MODEL
CONFIG.
CFM
ESP ("WG)
SONES
HP
RPM
DRIVE
VOLTAGEIMENSION
L"xWxH'
OPENING
L"xW"
CONTROL
ACCESSORIES
EF-1-6
BATHROOMS
GREENHECK
SP-AP0511W
CEILING
80
.2
0.7
10.5 WATT
831
DIRECT
120/1/6014X12X8
•
LIGHT INTERLOCK
1-7
(') APPROVED EQUAL MANUFACTURER: COOK, TWIN -CITY, ACME, PENN
ACCESSORIES NOTES:
1.
PROVIDE GRILLE COLOR PER ARCH. SPECS
S;EdEBAI FAN NOTES:
2.
PROVIDE BACK DRAFT DAMPER
®.
MOTOR STARTERS, DISCONNECTS (IF NOT FACTORY PROVIDED) AND ALL EQUIPMENT
3.
LOCATE BACK DRAFT DAMPER AT DISCHARGE
NORMAL POWER AND EMERGENCY POWER WIRING BY ELEC. CONTRACTOR
4.
PROVIDE FACTORY MOUNTED DISCONNECT SWITCH AND INTEGRAL THERMAL OVERLOAD PROTECTION,
b.
ALL CONTINUOUS -DUTY MOTORS SHALL BE PROVIDED WITH OVERLOAD PROTECTION
COORDINATE WITH ELECTRICAL CONTRACTOR PRIOR TO ANY PURCHASING.
ACCORDING TO NATIONAL ELECTRICAL CODE PAR. 430-32.
5.
PROVIDE BIRD SCREEN
6.
SUPPORT FROM STRUCTURE COMPLETE WITH VIBRATION ISOLATORS
C.
FIELD ADJUST OPENINGS WITH STRUCTURE.
7.
PROVIDE WEATHERHOOD DRAIN AND CORROSION COATING.
d.
ALL OUTDOOR EQUIPMENT SHALL COMPLY WITH LOCAL ZONING NOISE
8.
PROVIDE WITH MOTORIZE DAMPER.
ORDINANCE OR NOT EXCEED A NOISE LEVEL OF 65dB AS MEASURED
9.
PROVIDE MOTOR SIDE GUARD
RADIALLY 30 FT. FROM THE EQUIPMENT IN ALL DIRECTIONS.
10.
PROVIDE SPARK RESISTANCE CONSTRUCTION FAN
e.
COORDINATE WITH ELECTRICAL CONTRACTOR BEFORE BIDDING OR
ORDERING ANY EQUIPMENT.
f.
SEE PROJECT PLANS AND SPECIFICATIONS FOR OTHER FIELD SUPPLIED ITEMS
AND ADDITIONAL INFORMATION.
g.
ALL FANS ON ROOF SHALL BE PAINTED AS PER ARCHITECTURAL SPECS.
16. ALL BRANCH TAKE -OFFS TO BE PROVIDED W/ MANUAL VOLUME DAMPERS. PROVIDE RADIUS ELBOWS
WHERE FEASIBLE, SQUARE ELBOWS AND TEE'S SHALL BE FURNISHED W/SINGLE FOIL TURNING VANES.
PROVIDE MANUAL VOLUME DAMPERS WITH EXTRACTOR AT ALL FLEX TAKE -OFFS.
PROVIDE REMOTE, CABLE OPERATED VOLUME DAMPERS IN INACCESIBLE AND HARD CEILING AREAS,
'YOUNG REGULATOR" OR EQUAL
17. PROVIDE NEW FILTERS FOR ALL AIR CONDITIONING EQUIPMENT BEFORE START-UP,
REPLACE PRIOR TO FINAL ACCEPTANCE BY OWNER.
18. PROVIDE SMOKE DETECTORS WITH SERVICE ACCESS DOORS IN ALL SUPPLY AIR DUCTS
FOR FANS AND AHU'S SERVING A COMMON PLENUM OF 2000 CFM OR ABOVE.
FOR SMOKE DETECTORS NOT VISIBLE, IN CONCEALED SPACES, PROVIDE REMOTE ANNUNCIATION/TEST
STATION AS REQUIRED BY AUTHORITY HAVING JURISDICTION, COORDINATE PRIOR TO INSTALLATION.
DETECTORS MALL BE BY ONE MANUFACTURER, COORDINATE VOLTAGE ETC. WITH
ELECTRICAL CONTRACTOR AND FIRE ALARM SYSTEM BEFORE ORDERING. UPON
DETECTION, SMOKE DETECTORS SHUT DOWN ASSOCIATED AIR MOVING EQUIPMENT AND
ALL AIR MOVING EQUIPMENT SERVING THAT COMMON PLENUM.
19. PROVIDE TYPE "B' DYNAMIC FIRE DAMPERS WITH SERVICE ACCESS DOORS IN AEI. DUCTS AND
OPENINGS PENETRATING FIRE RATED WALLS, MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS,
TENANT SEPARATION, PARTITIONS. FLOOR OR ROOF SLABS AND AT OUTSIDE AIR INTAKES AS
REQUIRED. PROVIDE RADIATION DAMPERS IN RATED CEILINGS FOR ALL CEIUNG OPENINGS, CEILING
FANS, DIFFUSERS OR GRILLES RATED FOR USE IN THE CEIUNG ASSEMBLY.
PROVIDE LOW -LEAKAGE CLASS DAMPERS FOR ALL SITUATIONS WHERE THE AIRFLOW CFM
HAS TO BE CONTROLLED. VERIFY AND REPLACE AS REQUIRED FOR EXISTING SYSTEMS.
20. HVAC CONTRACTOR SHALL PROVIDE A T & B REPORT PER F.B.C. 2017. CH. C40B.2.2
(THE T & B REPORT SHALL BE INDEPENDENT FOR SYSTEMS OVER 15 TONS)
FOR ALL MECHANICAL EQUIPMENT, AIR DEVICES, DAMPERS, AHU'S AND FANS.
THE TEST AND BALANCE REPORT SHALL BE IN ACCORDANCE WITH THE AIR BALANCE COUNCIL
STANDARDS AND SHALL INCLUDE AIR QUANTITIES FOR ALL SUPPLY GRILLES, RE11JRN GRILLES
AND EXHAUST GRILLES AND THE LEAVING AND ENTERING AIR TEMPERATURE (T=) FROM
SUPPLY GRILLES AND EVAPORATORS.
FOR (EXISTING) SMOKE EVACUATION SYSTEMS HVAC CONTRACTOR SHALL PROVIDE: A T & B
REPORT PRIOR TO ANY NEW WORK, PROVING THAT THE SMOKE EVACUATION SYSTEM PERFORMS
PER ORIGINAL DESIGN DOCUMENTS AND IS COMPUANT WITH LOCAL CODE REQUIREMENTS.
21. RUN INSULATED FIRE RATED CONDENSATE DRAINS AS REQUIRED.
22. ALL INSULATION WILL HAVE FIRE/SMOKE RATING LESS THAN 25/50.
23. MECHANICAL EQUIPMENT ON ROOF OR ELEVATED STRUCTURES SHALL COMPLY WITH FBC 2017
PAR. 306.5 IF INSTALLED HIGHER THAN 16 FEET A.F.F.
MECHANICAL EQUIPMENT INSTALLED IN ATTICS SHALL MEET THE REQUIREMENTS OF FBC-ENERGY 2017
PAR. C403.2.7.6 IF THE EQUIPMENT CAN NOT BE SERVICED/REMOVED THROUGH REQUIRED OPENING.
MECHANICAL EQUIPMENT SHALL BE PROTECTED WITH MECHANICAL BARRIERS IF EXPOSED TO
MECH. DAMAGE. ALL EQUIPMENT SHALL BE INSTALLED ON 6" CONCRETE PAD AT GRADE LEVEL .
NOTE: AIR HANDUNG UNITS ARE NOT ALLOWED IN COMMERCIAL ATTICS.
fifloalm
ALL WIND LOAD AND OTHER COMPLIANCE CALCULATIONS AND/OR INSTALLATION DETAILS
FOR ROOF MOUNTED EQUIPMENT AS REQUIRED BY FBC 2017, SEC. 1509, 1522 AIND CHAPTER 16,
SHALL BE PROVIDED BY STRUCTURAL ENGINEER/ARCHITECT.
24. PROVIDE A MIN. OF 36' CLEARANCE IN FRONT OF ALL 120-208 VOLT PANELS AIND MIN. 42"
CLEARANCE IN FRONT OF ANY 240-480 VOLT PANEL PROVIDE ADEQUATE SIDE CLEARANCE
PER NEC.
25. MECHANICAL PLANS IN GENERAL, ARE DIAGRAMMATIC IN NATURE, AND ARE TO BE READ
IN CONJUNCTION WITH ARCHITECTURAL, PLUMBING, ELECTRICAL, FIRE SPRINKLER, AND
STRUCTURAL PLANS AND SHALL BE CONSIDERED AS ONE SET OF DOCUMENTS.
DUCT AND PIPING OFFSETS, BENDS AND TRANSITIONS SHALL BE REQUIRED TO PROVIDE AND
INSTALL A COMPLETE FUNCTIONAL SYSTEM AND SHALL BE PROVIDED BY THE CONTRACTOR
AT NO ADDITIONAL COST TO THE OWNER. CHANGES IN DUCTWORK SIZE AND ROUTE
WILL BE REQUIRED TO AVOID STRUCTURAL, PLUMBING, FIRE SPRINKLER AND ARCHITECTURAL
BUILDING FEATURES. DUCTWORK CHANGES MAY BE MADE BY CONTRACTOR USING
EQUIVALENT SIZED DUCT. CONTACT ENGINEER IF DUCT AREA WILL NOT FIT.
26. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO BIDDING, ORDERING.
FABRICATION OR INSTALLATION OF MATERIALS OR EQUIPMENT, IN ORDER TO PROVIDE
A FULLY INTEGRATED MECHANICAL AND CONTROLS SYSTEMS WITH THE EXISTING ONES.
ANY DISCREPANCY BETWEEN EXISTING CONDITIONS AND PLANS, OR ADDITIONAL CLARIFICATION REQ'D
SHALL BE BROUGHT TO THE ATTENTION OF ENGINEER PRIOR TO FINAL BIDDING AND WORK.
27. NO COMBUSTIBLE MATERIALS ARE ALLOWED IN RETURN AIR PLENUMS OR ABOVE
CEILINGS USED AS RETURN AIR PLENUM. IF SPACE WITH RETURN AIR PLENUM
HAS ANY DECK TO DECK PARTITIONS, AIR TRANSFER DUCTS MUST BE INSTALLED.
WHEN CPVC PIPING IS USED FOR FIRE SPRINKLER SYSTEMS, THE R/A GRILLES LAYOUT SHALL
BE (FIELD) COORDINATED WITH SUCH PIPING SO THAT NO PORTION OF THE GRILLES WILL BE
DIRECTLY BELOW THE CPVC PIPING.
28. CONDENSATE DRAIN PIPING TO BE AS SPECIFIED PER PLUMBING PLANS, IF NOT SPECIFIED
TO BE TYPE "L" COPPER OR PVC WHERE ALLOWED BY CODE WITH 1/2' ARMAFLEX INSULATION.
PROVIDE APPROVED WATER LEVEL DETECTOR OR FLOAT SWITCH TO AUTOMATICALLY SHUT DOWN
THE AIR COND. UNIT, AS A SECONDARY DRAIN SYSTEM TO COMPLY WITH FMC 20117, SEC. 307
SUPPLY CONDENSATE PUMP WHERE NECESSARY AS IMPOSED BY FIELD CONDITIONS OR INSTALLATION
CHANGES AND PIPE TO CONDENSATE DRAIN PER PLUMBING PLANS.
29. MANUFACTURER'S WARRANTY: CONTRACTOR SHALL PROVIDE WARRANTY FOR A PERIOD OF
(1) ONE YEAR AFTER BUILDING C.O. FOR ALL MECHANICAL SYSTEMS, DUCTWORK, CONTROLS
ACCESSORIES AND ALL OTHER EQUIPMENT, PARTS AND LABOR UNDER THESE DRAWINGS AND
AND SPECIFICATIONS. CONTRACTOR SHALL PROVIDE WARRANTY FOR COMPRESSORS FOR
(5) FIVE YEARS. ANY REPAIRS REQUIRING SYSTEM SHUTDOWN WILL BE DONE DURING
NON -OPERATIONAL PERIODS OR AS AGREED WITH OWNER.
30. ON PROJECT SPECIFIED WITH EQUIPMENT UTIUZING HOT GAS REHEAT AND/OR DEHUMIDIFICATION;
CONTRACTOR SHALL PROVIDE FACTORY STARTUP OF EQUIPMENT WITHIN THEIR BID. STARTUP
REPORT DOCUMENT TO BE PROVIDED TO ENGINEER FOR REVIEW.
I
O1 COORDINATE FINAL LOCATION IN
FIELD WITH EXISTING CONDITIONS.
O1OX10 DUCT CHASE UP' TO FLOOR
ABOVE.
OFUTURE 1.5 TON MINI -SPLIT UNITS.
0 r UP TO ROOF
SUPPLY AIR CaLLE SCHEDULE
TAG
MANUR & MODEL
FACE SIZE
NECK SIZE
MATERIAL
FRAME
FINISH
DAMPER
THROW
NC
RANGE
NOTES
A
METALMRE
PHENOMENdATOR
24X24
SEE SCH.
ALUM.
NOTE #3
OFF WHITE
OBD
4-WAY
MAX. NCI
SEE SOH.
1-5
C
TITUS/ FL-10
LINEAR
SEE SON.
AUIM.
NOTE /3
OFF WHITE
OBO
4-WAY
MAX. 25
SEE SCH.
1-5
®1
PHENOMENATOR
12X12
I SEE SCH.
I ALUM.
NOTE #3
OFF WHITE
OBD
4-WAY
MAX. 30
SEE SCH.
1-5
(*) EQUIVALENT MANUFACTURER: METALAIRE, PRICE, CARNES, T & B. NAILOR
1. PROVIDE SPIN -IN COLLAR AT TRUNK TO FLEX DUCT CONNECTION.
2. PROVIDE TYPICAL 4-WAY DIFFUSION, 2-WAY OR 3-WAY ONLY WHERE INDICATED ON PLAN
�� BCME
3. REFER TO ARCHITECT PLANS FOR CEILING TYPE.
4. CONTRACTOR TO COORDINATE FINAL SELECTION WITH AF041TECT AND OWNER
BP 50-125 (FM
5. FLEX DUCT SIZE TO BE SAME AS DIFFUSER NECK SIZE
8/' 130-200 CFM
100" 205-330 CFM
CONTRACTOR SHALL VERIFY WITH ARCHITECT AND TENANT/OWNER,
12e' 335-450 CFM
PRIOR TO ANY PURCHASING OR INSTALLATION, IF A BOLDING
STANDARD HAS TO BE FOLLOWED REGARDING A SPECIFIC MODEL
94M' 45, 5-800 CFM
OR MANUFACTURER AND SHALL BRING ANY DISCREPANCY TO
THE ATTENTION OF IENGINEER.
191^' 805-700 CFM
TV RETURN AIR GFILLE SCHEDULE -�
TAG
MANUF. & MODEL
FACE SIZE
NECK SIZE
MATERIAL
FRAME
FINISH
DAMPER
THROW
NC
CFM RANGE
NOTES
AA
PHENOMENATOR METALAIRE
24X24
SEE SOH.
ALUM.
NOTE #1
OFF WHITE
-
-
MAX. 30
SEE SCH.
1-3
CC
TITUS/ MLR-39
UNEAR
SEE SCH.
ALUM.
NOTE /1
OFF WHITE
-
-
MAX. 25
SEE SCH.
1-3
BB
PHENOTALAIRE MENATad
12x12
SEE SOH.
ALUM.
NOTE {j1
OFF WHITE
_
-
MAX. 30
SEE SC.H.
1-3
(0) EQUIVALENT MANUFACTURER: METALAIRE. PRICE, CARNE% T & B. NAILOR
CONTRACTOR SHALL VERIFY WITH ARCHITECT AND TENANT
OR OWNER, PRIOR TO ANY PURCHASING OR INSTALLATION,
AN MGM IF A BUILDING STANDARD HAS TO BE FOLLOWED REGARDING
A SPECIFIC MODEL OR MANUFACTURER AND SHALL BRING
1. REFER TO ARCHITECT PLANS FOR CEILING TYPE ANY DISCREPANCY TO THE ATTENTION 01' ENGINEER.
2. FINAL COLOR SELECTION SUBJECT TO ARCHITECT APPROVAL -
3. PROVIDE INSULATION ON THE BACK OF DIFFUSER IF IN N111Clt: em CFM EAWE NWX M CFM RANW
UNCONDITIONED FACE -
6X6 0-150 CFM 15x1!i 0-900 CFM
8X8 0-250 CFM 18X18 0-1350 CFM
toxlo 0-400 CFM 22x22 0-2000 CFM
12x12 D-600 cFM -
IN ISOLATION, SEE SPECS M6.1
HIGH CONCRETE PAD
MECHANICAL PLAN-
? --ALE;
-WATERPROOF SEAMS
AND JOINTS (TYP)
WATERPROOF CAULK -
ALL AROUND (TYP.)
GALV. METAL DUCTWORK
WITH MIN. R-8
DOUBLE WALL DUCT
EQUAL TO "K-27"
1-1/2"x1-1/2x1/4"TH
ANGLE IRON SUPPORT
ALL AROUND DUCT.
TYP. SHEET METAL SCREWS -J
OR TAPCONS AS APPLICABLE
OUTDOOR
GALV. METAL DUCTWORK
WITH MIN, R-6 EXTERIOR
INSULATION
:1 I __---FLANGE--_.----
DUCT THROUGH
WAIL (SEE ARCH.)
WALL (SEE ARCH.)
INDOOR
FUTURE MEZZANINE
AA26003774
517 SW nALULL AVrnUr
POPT SAIM LUCIr rL. 54955
'772-800-5700
www1blar(hiteaure.(om
�C S Mc r
44r d
14248
�J
�L
LL-
>_
CAL
O
0
lam_
OJ1
LLJ
y
J
OL
LLJ
II J
%/'N
t-
00
OL
0
F-
v
O
II l
(�m
a.
DO(MI11T DATA:
DATE:
PIVISIOM:
f1� YOUP PROWSS SUbAIT DAR
Srl[[T TITLE:
MECHANICAL
PLAN
SM(T MAW:
mml
SHOCK ARRESTOR SCHEMILE
P.D.I. DESIGNATION
MANUF. & MODEL
FIXTURE UNITS
CONNECTION
A
SIOUX CHIEF 652-A
1-11
1/2"
B
SIOUX CHIEF 653-B
12-32
3/4-
C
SIOUX CHIEF 654-C
33-60
1.
SIOUX CHIEF SHOCK ARRESTORS APPROVED FOR INSTALLATION WITH NO
ACCESS DOOR REQUIRED. CONFORMS TO ANSI/ASSE 1010 STANDARDS.
SLOPE OF ±2M. UHANA99 PIPE
SIZE (inches)
MINIMUM SLOPE (Inch per foot)
2-1/2 or less
1/4
3 to
1/8
8 or larger
1/16
TABLE 704.1 OF THE FLORIDA PLUMBING CODE 2017
CONDENSATE DRAIN
PIPE SIZING
HVAC EQUIPMENT CAPACITY
MINIMUM CONDENSATE PIPE DIAMETER
UP TO 20 TONS OF REFRIGERATION
1"
OVER 21 TONS TO 40 TONS OF REFRIGERATION
1-1/4-
OVER 41 TONS TO 60 TONS OF REFRIGERATION
1-1/2-
OVER 61 TONS TO 100 TONS OF REFRIGERATION
2-
OVER 101 TONS TO 250 TONS OF REFRIGERATION
3-
OVER 251 TONS & LARGER OF REFRIGERATION
4"
PLUMBING FIXTURE SCHEDULE
F
DICAP LAVATORY, AMERICAN STANDARD, LUCERNE WALL HUNG LAVATORY MODEL #0356.028.
E, WITH T&S BRASS FAUCET BS-2701-VF05. CONTRACTOR TO SUPPLY CONCEALED ARM SUPPOR
PORT CARRIER FOR MOUNTING OF LAV. WADE MODEL If 520-M36. SUPPLY PLUMBEREX MODEL
/4333 INSULATION KIT. MUST MEET A.D.A. CODE.
WC
WATER CLOSET, AMERICAN STANDARD 2333.100 FLOOR MOUNTED, WHITE
CENTOCO SEAT # 50OCC, OPEN FRONT WITH COVER. A.D.A EL 1.28 ELONGATED OR EQUAL
HANDICAP WATER CLOSET, AMERICAN STANDARD #215AA.004 FLOOR MOUNTED, WHITE, CENTOCO SEAT
HWC
#500CC, OPEN FRONT WITH COVER.
A.D.A EL 1.28 ELONGATED 18" HIGH OR EQUAL
HDF
ELKAY LZS8WSLP ENHANCED EZH2O BOTTLE FILLING STATIONA ND SINGLE ADA COOLER,
FILTERED, 8 GPH, LIGHT GRAY
FIAT MSB MODEL # 2424 MOLDED TERRAZZO BASIN WITH DRAIN BODY AND STRAINER.
MOP
FIAT SERVICE SINK FAUCET MODEL #530-AA, WITH FIAT 832-AA HOSE AND HOSE BRACKET
SK
DISCHARGE; PAIL HOOK AND TOP BRACE; VACUUM BREAKER, FIAT #889-CC MOP HANGER AND
BP !SPLASH CATCHER ALL GUARD.
RECIRC
TACO RECIRC. PUMP. MODEL 111 BRONZE CASTING , 115V, 1/8 HP, 2.0 AMP WITH
PUMPLWA-TnER
TIMER AQUSTAT.
EWH
HEATER SHALL BE 30 GAL ELECTRIC 208V, 1 PHASE, 4.5 KW.
HINVAR TALL MODEL ETT-OW-KD.
GENERAL NO ,5
(1) - FIXTURES SHALL BE AS SHOWN OR EQUAL
- ALL FIXTURES SHALL COMPLY WITH TABLE 604.4 OF FBC 2017
((2)
3)- ALL FIXTURE TRIM PACKAGES INCLUDING BUT NOT LIMITED TO TRAP, ANGLE STOP, FLUSH VALVE"
SUPPLY TUBES, AND CLEANOUT COVER PLATES SHALL BE OF THE SAME FINISH AS THE ABOVE
SPECIFIED FAUCET AND PER ARCHITECTURAL FINISH SCHEDULE.
(4) - ALLFIXTURES SHALL BE ROUGHED IN PER MANUFACTURER CUT SHEET TO MAINTAIN UNIFORMITY.
PROVIDE TEST TEE
WITH SCREWED COUNTER-
SUNK ABS PLASTIC PLUG:
TAPERED -THREAD WITH
TFE JOINT COMPOUND. -
MERE CLEANOUT TEE
IS CONCEALED IN A
CHASE OR PARTITION,
PROVIDE A ROUND 18
GAUGE STAINLESS STEEL
COVER WITH BEVELED
EDGES AND FLATHEAD
MACHINE SCREW.
. d
CONCRETE CC_
FLOOR
SLAB
COLUMN OR PARTITION
AS SHOWN ON FLOOR PLAN
CLEANOUT FACE SHALL
BE WITHIN 4" OF WALL
SURFACE. PROVIDE
PIPE EXTENSION IF REQUIRED.
NOTE:
PROVIDE WCO WHERE SHOWN ON PLAN, AND ON SANITARY WASTE BRANCHES
NOT SERVED WITH A (FLOOR CLEANOUT: LOCATE ABOVE FIXTURE FLOOD RIM
WITHIN 4' OF FLOOR. CONSULT LOCAL CODES FOR 07HER WCO REQUIREMENTS.
WALL CLEANOUT DETAIL
NOT TO SCALE
PROVIDE 3/8" DIAMETER THREADED ROD WITH WASHERS AND DOUBLE NUTS AT
EACH END. ROUTE ROD FROM CHANNEL BELOW WATER HEATER UP TO FASTENERS
ABOVE. (TYPICAL OF 4) ___7
3/6" HILTY INSERT HDI-3/8". (TYPICAL OF 4)
BAR JOIST STRUCTURAL SUPPORT SYSTEM.--a�
COLD WATER SUPPLY
TO WATER HEATER
HEAT TRAP
(OMIT IF HEAT TRAP IS AN
INTEGRAL PART OF HEATER).
HOT WATER TO FIXTURES
AS SHOWN ON PLANS.
PROVIDE FULL PORT BALL
SHUT-OFF VALVES.
PROVIDE PIPE
UNIONS, DIELECTRIC
IF REQUIRED FOR
DISSIMILAR METALS.
DRAIN VALVE BY
HEATER MAUFACT.
THERMOSTAT AND
PRESSURE REGU-
LATOR FURNISHED
WITH WATER HEATER.-
3/4' PLYWOOD BELOW
WATER HEATER DRAIN
PAN AS PLATFORM.
2" DEEP SAFEPAN.
PROVIDE A DRAIN /
PAN, RUN OVERFLOW
UNE TO EXTERIOR
OF BUILDING AT 6"
ABOVE GRADE OR
NEAREST APPROVED WATER HEATER - MAXIMUM
INDIRECT WASTE. OF 30 GALLON CAPACITY.
PIPING ARRANGEMENT SHOWN IS SCHEMATIC:. ADJUST TO SUIT
FIELD CONDITIONS. REFER TO ISOMETRIC RISER FOR PIPE SIZES.
SET HEATER THERMOSTAT AT 120' F. PROVIDE MIXING VALVES
AS REQUIRED AT LAVATORIES TO COMPLY WITH FBC ENERGY 504.3.
PUMP
HOT WATER
RECIRCULATION 7UNE
PROVIDE A 210T
TEMPERATURE AND
150 PSI PRESSURE
RELIEF VALVE
WITH TEST LEVER
SIZED WITH AGA/CGA
TEMPERATURE STEAM
RATING 10X OVER
HEATING INPUT.
PROVIDE A HARD
COPPER RELIEF
VALVE DISCHARGE
LINE FULL SIZE OF
VALVE OUTLET RUN
TO INDIRECT WASTE
IN SAME ROOM OR
TO OUTSIDE BUILDING
6" ABOVE GRADE WITH
A VISIBLE AIR GAP IN
SAME ROOM PER FLORIDA
BUILDING CODE 2017 SEC.
504.6.1
PROVIDE 2" CHANNELS
WITH MINIMUM 2 COATS
OF RUSTPROOF PRIMER
SPANNONG BETWEEN
THREADED RODS TO
SUPPORT WATER HEATER
SAFEPAN.
1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, AND EQUIPMENT ESSARY FOR THE
INSTALLATION OF A COMPLETE SCOPE OF WORK. ALL WORKMANSHIP AND g, RIALS SHALL BE IN
STRICT ACCORDANCE WITH THE FLORIDA BUILDING CODE 6TH EDITION (2017'. PLUMBING,
APPLICABLE LOCAL CODES, RULES, AND ORDINANCES.
2. PLUMBING CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAM RIZE HIMSELF WITH ALL
EXISTING CONDITIONS.
3. ALL MATERIALS SHALL BE NEW AND OF GOOD QUALITY.
4. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR; FIRST CLASS
WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY -OPERA XL ALL EXCAVATION
AND BACKFILL AS REQUIRED FOR THIS PHASE OF CONSTRUCTION SHALL BE ART OF THIS
CONTRACT.
5. REQUIRED INSURANCE SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR F PROTECTION
AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF TI WORK.
6. PLUMBING CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, IN ECTIONS AND TESTS.
PLUMBING CONTRACTOR SHALL OBTAIN PERMIT AND APPROVED SUBMITTALS P )R TO BEGINNING
WORK OR ORDERING EQUIPMENT. PLUMBING CONTRACTOR MUST BE PRESENT 7R ALL INSPECTIONS
OF HIS WORK BY REGULATORY AUTHORITIES.
7. CONTRACTOR SHALL SUBMIT TO ARCHITECT/ENGINEER, FOR REVIEW & APPROVk FIVE (5) SETS OF
MANUFACTURER'S CUT SHEETS FOR EACH FIXTURE, PIPING/FITTING MATERIAL At, rQUIPMENT ITEM
WITH ASSOCIATED CONTROLS, THAT ARE INCLUDED IN THE CONTRACT.
8. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FOR THE EXACT LOCATION OF F' :S, PIPING,
EQUIPMENT, ETC.
9. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERE:NCU I THE
PROGRESS OF CONSTRUCTION. REPORT ANY DISCREPANCY TO ARCHITECT/ENIGINI RIOR TO
BEGINNING CONSTRUCTION.
10. VERIFY LOCATION, SIZE, DIRECTION OF FLOW AND INVERT ELEVATIONS OF ALL EXI UTILITIES
PRIOR TO BEGINNING OF CONSTRUCTION. ADVISE ARCHITECT/ENGINEER OR ANY I ?ANCIES.
11. WATER DISTRIBUTION PIPING ABOVE AND BELOW GROUND SHALL BE TYPE -L" COP ALTERNATE
PIPING & FITTING MATERIALS MAY BE USED IN ACCORDANCE WITH FLORIDA BIUILDI )DE 6TH
EDITION (2017) - PLUMBING, TABLES 605.3, 605.4 & 605.5, WHEN APPROVED BY AEER OF
RECORD AND LOCAL AUTHORITY HAVING JURISDICTION. PROVIDE ALTERNATE FOR PIPING &
FITTINGS EQUAL TO LUBRIZOL CORZAN OR FLOW -GUARD GOLD. PROVIDE ALTERNr OR PEX TYPE
'A' PIPING & FITTINGS EQUAL TO UPONOR. ALTERNATES ARE PERTINENT FOR' WAl ERVICES
KNOWN OR DETERMINED TO HAVE ACIDIC CHARACTERISTICS OR OTHER PARTICULAR :;UMSTANCES
AS DEEMED APPROPRIATE BY DIRECTIVE FROM THE OWNER. CONTRACTOR SHALL I ORM A WATER
TEST TO DETERMINE WATER CHEMISTRY PRIOR TO ANY WORK OR PIPING INSTALLA7 AND SHALL
SUBMIT TEST RESULTS TO THE ARCHITECT/ENGINEER FOR REVIEW AND APPROVAL 9NFECTION OF
POTABLE WATER SYSTEM SHALL COMPLY WITH FLORIDA BUILDING CODE 6TH ED17101 '017) -
PLUMBING, SECTION 610. ALL WATER PIPING & FITTINGS SHALL BE OF DOk' ST1C I UFACTURE;
SPECIFICALLY IN THE UNITED STATES OF AMERICA.
12. SOIL, WASTE, VENT, AND RAINWATER (DWV) PIPING & FITTINGS SHALL BE CAST IF PVC, WHERE
CODE ALLOWS. PVC MAY NOT BE USED THRU RATED ASSEMBLIES OR IN PLENUM PIPING
SHALL BE SOLID -CORE ONLY, FOAM -CORE PIPING SHALL NOT BE ACCEPTED. CAE N PIPING &
FITTINGS SHALL BEAR THE CISPI-301 MARK. ALL DWV PIPING & FITTINGS SHALL B. DOMESTIC
MANUFACTURE; SPECIFICALLY IN THE UNITED STATES OF AMERICA.
13. ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE ANGLE STOPS AND APF PRIATELY
MARKED ACCESS PANELS (WHERE REQUIRED). COORDINATE LOCATIONS WITH :`_NEr'1k 'ONTRACTOR
PRIOR TO INSTALLATION.
14. PROVIDE APPROVED WATER HAMMER ARRESTORS FOR ALL (GROUP) PLUMBING FIXT SIZED &
LOCATED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS & PDI-WH2O1.
15. PROVIDE DIELECTRIC COUPLINGS OR FLANGES BETWEEN ALL DISSIMILAR METALS IN P: G AND
EQUIPMENT CONNECTIONS.
16. ISOLATE COPPER PIPING FROM METALLIC HANGERS OR SUPPORTS WITH ISOLATOR P 2
NON-CONDUCTIVE MATERIAL,
17. ALL FIRE RATED FLOOR AND WALL PENETRATIONS SHALL BE PROPERLY PROTECTED F FIRE,
SMOKE AND WATER PENETRATION BY FILLING ANNULAR SPACE BETWEEN PIPING AND VES WITH
INTUMESCENT CAULK, TO ACHIEVE THE SAME RATING AS WALLS OR FLOORS, AS PAR THE
PLUMBING CONTRACTOR'S WORK,
18. PLUMBING CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE F DEFECTS
FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE BY OV
CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE A ALL
INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION Wilt. Y HAVE
BEEN DAMAGED.
19. PROVIDE ACCESS PANELS FOR ALL CONCEALED VALVES. ACCESS PANELS IN RATED V SHALL
MAINTAIN THE SAME RATING AND SHALL MATCH THE FINISH OF THE WALL IN WHICH 11 ISTALLED.
20. PROVIDE COMBINATION CLEANOUT PLUG AND COVER PLATE OR ACCESS PANEL, FOR ALL
CLEANOUTS. FINISH TO MATCH NEARBY FIXTURE TRIM.
21. NO COMBUSTIBLE MATERIAL SHALL BE INSTALLED IN MECHANICAL ROOMS NOR IN C SPACES
WHERE USED AS RETURN AIR PLENUMS.
22. NO WATER, SANITARY OR DRAINAGE PIPING SHALL BE INSTALLED IN ELECTRICAL OF EVATOR
EQUIPMENT ROOMS.
23. ALL CONTROL VALVES SHALL BE TAGGED AND MARKED. A REPRODUCIBLE DIAGRr 1CATING ALL
VALVES SHALL BE FURNISHED FOR OWNER/OPERATOR.
24. CONDENSATE DRAIN PIPING SHALL BE TYPE -L- COPPER NTH ARMAFLEX INSULATION AND A
VAPOR -BARRIER JACKET PER FLORIDA BUILDING CODE 6TH EDITION (2017) - ENERGY
CONSERVATION, TABLE C403.2.8. PVC WITHOUT INSULATION IS ACCEPTABLE FOR RISERS AND BELOW
GRADE PIPING. WHEN USED IN A RETURN AIR PLENUM, PVC PIPING WITH INSULATION IS ACCEPTABLE
IN LOCATIONS WHERE ALLOWED BY LOCAL CODES. CONDENSATE PIPING SHALL NOT DRAIN ONTO THE
ROOFING SYSTEM NOR ANY OF ITS COMPONENTS. CONDENSATE PIPING ARRANGEMENT IS EXEMPT
FROM MINIMUM EQUIPMENT CLEARANCE REQUIREMENTS PER FLORIDA BUILDING CODE 6TH EDITION
(2017), SECTION 1522.3.5. ALL HORIZONTAL RAINWATER PIPING RUN ABOVE FINISHED FLOOR THAT
RECEIVES CONDENSATE DISCHARGE SHALL BE INSULATED WITH ARMAFLEX AND A VAPOR -BARRIER
JACKET.
25. HOT WATER PIPING INSULATION SHALL BE PROVIDED IN ACCORDANCE WITH FLORIDA BUILDING CODE
6TH EDITION (2017) - PLUMBING, TABLE 607.5 & FLORIDA BUILDING CODE 6714 EDITION (2017) -
ENERGY CONSERVATION, TABLE C403.2.8. CONTRACTOR SHALL USE ARMAFLEX OR EQUAL WHERE
APPLICABLE. WHERE DOMESTIC WATER TEMPERATURES CAN CAUSE SWEATING, ALL COLD WATER
PIPING SHALL BE INSULATED WITH ARMAFLEX INSULATION AND A VAPOR -BARRIER JACKET, PER
FLORIDA BUILDING CODE 6TH EDITION (2017) - ENERGY CONSERVATION, TABLE: C403.2.8.
26. AIR ADMITTANCE VALVES MAY BE USED AS AN ALTERNATE TO VENT PIPING THRU ROOF WHERE
pACCCEEPPTTEgD� BY THE
{ LOCAL
F AUTHORITY �HEA�VING JU�RIISDIIC�TIIOgNp.�� IN�SSTTAULLLATTION METHODS SHALL BE IN
27.PROVIDE AN STOPS ONAALL WATER %WUNIS TO FIXTURES(FOR' DIMDUAL
SHUT-OFF.
28• STUDOR MINI/MAXI AIR ADMITTANCE VALVES MAY BE USED AS AN ALTERNATE TO
VENT PIPING THRU ROOF WHERE ACCEPTABLE BY THE PLUMBING OFFICIAL AND LOCAL
CODES. INSTALLATION SHALL BE AS PER MANUFACTURER'S RECOMMENDATIONS„
29. ALL HORIZONTAL RAINWATER PIPING THE RECEIVES CONDENSATE DISCHARGE FROM AIR
CONDITIONING EQUIPMENT SHALL BE INSULATED WITH 1" THK. ARMAFLEX.
30. PLUMBING PLANS IN GENERAL, ARE DIAGRAMMATIC IN NATURE, AND ARE TO BE READ IN CONJUNCTION
WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, FIRE SPRINKLER, STRUCTURAL, AND CIVIL PLANS AND
SHALL BE CONSIDERED AS ONE SET OF DOCUMENTS. PIPING MODIFICATIONS SUCH AS OFFSETS, BENDS,
TRANSITIONS, AND SIZES SHALL BE REQUIRED TO PROVIDE AND INSTALL A COMPLETE FUNCTIONAL
SYSTEM AND SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
CHANGES IN PIPE SIZES AND ROUTING SHALL BE REQUIRED BY THE CONTRACTOR TO AVOID CONFLICTS
AND TO ADAPT TO EXISTING FIELD CONDITIONS PROVIDED THAT INSTALLATION MEETS ALL
APPLICABLE CODES.
31. SUPPLY TRAP PRIMER FOR ALL FLOOR DRAINS, FLOOR SINKS, HUB DRAINS, ETC. SHOWN ON PLANS.
32. CONTRACTOR TO FIELD VERIFY ALL SUPPLY PRESSURE REQUIREMENTS AND LIMITATIONS. PROVIDE
PRESSURE REDUCING VALVE IF REQUIRED.
O1 EXISTING 3' SANITARY LINE, FIELD VERITY EXACT LOCATION, INVERT, AND CONNECTION
POINT PRIOR TO ROUGH IN.
O3" SANITARY RISER TO FLOOR ABOVE, PROVIDE ACCESSIBLE CLEANOUT AT BASE OF
RISER.
O3/4" DOMESTIC WATER LINES TO FLOOR ABOVE, PROVIDE ISOLATION VALVES FOR
EACH RXTURE.
OEXISTING DOMESTIC WATER CONNECTION; FIELD VERIFY EXACT SIZE, LOCATION AND
CONNECTION POINT.
0
e
.JIB
�I
I
A +
`\+ \
LL riu%
izz
ezoIle , l
l I
1
e
DOM. WATER ISOMETRIC
N.T.S.
������*L#MBING PLAN
SC,A-�E: 1/4" r V-0"
f UTURE MEZZANINE
AA20003774
517 SW MULL AVEW
PORT SAM LUCK rL. 54955
772-800-5700
www1jar(h i te(turexom
OF PL0
S. Meg, jd
14248 U
�w
ti
�.J
Ei
®
®_
u-
nz
0�0
<�
0
,./'\
u.-.J
�L
LLJ
LL-J
~ Q
OG
u�
0
0
O LLJ
r- ,
0_
d
DOCU/AE17T DATE::
DATE:
REVISIOnS:
fly TOUR PROWSS S&AIT DATE
SHUT TITLE:
PLUMBING
PLAN
SKEET nUfWP:
95