Loading...
HomeMy WebLinkAboutResponse to Comments4,00-4mv.-LBJ Architecture AA26003774 October 29 2021 To: Saint Lucie County Building Department. Re: 2103-0616 To whom it may concern, We offer the following responses to the plan review comments Comment: all electrical, mains need to be grouped together. Existing A panel has no main disconnect ahead of it. Main disconnect needed outside with all other meters and mains. The 2 AC units need the disconnects mounted on the building, not on the units. EM lighting wall packs need to show locations in building. Response: Please see revised sheet E-1, riser diagram updated, new main disconnect added and grouped with other main. AC unit disconnects shown mounted to building. New light fixtures designated with the "AEM, BEM, CEM, DEM, GEM labels indicate emergency battery backup ballast are included in the fixture. Thank you for your consideration in this matter. Mark McCree Architect, NCARB, OVID tit 00- ve4 sty gel 10� q �e Goy 517 SW Halkell Ave Port Saint Lucie Florida 34953 772.800.5700 jb@kbjarchitecture.com