We offer the following responses to the plan review comments
Comment: all electrical, mains need to be grouped together. Existing A panel has no main disconnect ahead of it.
Main disconnect needed outside with all other meters and mains. The 2 AC units need the disconnects mounted on the
building, not on the units. EM lighting wall packs need to show locations in building.
Response: Please see revised sheet E-1, riser diagram updated, new main disconnect added and grouped with other
main. AC unit disconnects shown mounted to building. New light fixtures designated with the "AEM, BEM, CEM, DEM,
GEM labels indicate emergency battery backup ballast are included in the fixture.